VMR. Safety solenoid valves for air and gas Fast opening and fast closing type DN10 DN150.



Similar documents
ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

System 8. ü ( System 8

PRESSURE REDUCING CONTROL VALVE

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Stainless Steel Single and Dual Circulation Kits

820 NOVA mv THERMOPILE POWER SUPPLY THERMOELECTRIC SAFETY DEVICE SERVO-CONTROLLED PRESSURE REGULATOR SHUT-OFF SOLENOID VALVE.

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

3/2-way Solenoid Valve, direct-acting, NC or NO

WE-350 Series ¼ Turn Electric Actuator

Volkswagen Jetta, Golf, GTI 1999, Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)

Installation Instructions S

TECHNICAL DATA. Dry 122a. November 12, 2013

STORAGE, INSTALLATION AND MAINTENANCE PROCEDURES

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17)

Assisted lift operated 2/2-way solenoid valves Type EV250B

DeZURIK 3-20" BAW AWWA BUTTERFLY VALVES WITH TRANSFER MOLDED SEAT

Round Housing with Side Ports

S GATE KNIFE GATE VALVE WITH PNEUMATIC ACTUATOR

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

Toroidal Conductivity Sensor

Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description

TYPE E Main Valve Sizes 3 /8 through 12

STABITHERM INSTALLATION & SERVICE BOOKLET

Cooling system components, removing and installing

Volkswagen Jetta, Golf, GTI 1999, 2000 Brake System 47 Brakes - Hydraulic Components (Page GR-47)

REPAIR AND MAINTENANCE MANUAL

series Materials Body: 1/2, 3/4 and 1 : dezincification resistant alloy brass EN CW617N

Rear wheel brakes, servicing. Стр. 1 из 45. Note:

POSEIDON 2-29, 2-25 & 2-22 POSEIDON 2-29, 2-25 & 2-22 XT

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

PBX Series Quick Fit Connector Bimetallic Steam Traps

3/2- and 2/2-way cartridge valve type BVE

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Overview PARTS LIST. B. Lever mounting base C. Flush handle assembly D. Grey/Blue float stop E. Grey float (Full Flush) F. Flush valve washer

Valve series MN-06 acc. to NAMUR, 3/2-way G1/4 750 Nl/min (0.762 Cv)

STC 3S A Series Solenoid Valves

This instruction is valid for all ACD pump models shown on page 2

Drive shaft, servicing

Vacuum Gate Valve DN 100 and DN 150


Operating Instructions

SLAM-SHUT VALVE. Type OSE. Europe, Middle East, Africa and Asia Pacific Documents Only. Process Management TM

DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual

Pilot Operated Pressure Reducing Valve PRV 47 (Steel) PRV47I (St.Steel)

5800 Temperature Sensor Cable Assembly

Float and Thermostatic Traps Series H, C and X

Your safety and the safety of others are very important.

11. COOLING SYSTEM 11-0 COOLING SYSTEM BET & WIN 50

Installation Instructions

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF)

2/2 and 3/2 Way Size 6 Seat Valves

Materials : Cast iron body

RUBBER SLEEVE KNIFE GATE VALVE

GAS VALVE USER MANUAL

BACKPACK SPRAYERS. MODEL NOS: KSP16 & KSP20 Part Nos: & OPERATING & MAINTENANCE INSTRUCTIONS GC04/12

1805 Series Relief Valves

SELECTION, APPLICATION AND MAINTENANCE

M A N U A L

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

DIAMOND Retractable Rodding Robot Model SPRAYROD-R

Duct Humidity Transmitter

INSTALLATION & OPERATING INSTRUCTIONS

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap

Machine needle shut-off nozzle type HP

INSTALLATION, OPERATION & MAINTENANCE MANUAL

Ball valve C 16 valve ball completely moulded in place, extremely low clearance volume, high k v value

VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES

2 WAY (2/2) AND 3 WAY (3/2) BRASS AND STAINLESS STEEL SOLENOID VALVES

MFP14, MFP14S and MFP14SS Automatic Pumps

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

Size : Ends : Min Temperature : Max Temperature : Materials : Cast iron body

AIR-AIR PRESSURE MULTIPLIER (BOOSTER)

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

USE &CARE GUIDE. Remote Faucet Pump System. See Important Safeguards on page 2

Tech. Services: (800) Fax: (800) Order Entry: (800) Fax: (800) Internet Address:

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

Maintenance and Service Instruction

Types 66R and 66RR Low-Pressure Relief Valves

HERZ-Thermal Actuators

DIAMOND Gear Company, LTD. an ERIKS Company. Installation, Maintenance, & Operation Manual Declutchable Worm Gear

Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II

Back Pack Sprayer. Operator's Manual MODELS MS - 40 MS - 50

Manual piston sampler...m 11

Stainless Steel Valves For the Sanitary Industries

Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC)

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: No.: SE-...

Mini USB and USB 2.0-IP67 Connector System

AIR LINE VALVES AND GAUGES

STC 2P050 Series Solenoid Valves NSF Compliant Materials, 2 Way, Direct Acting

Cooling system components, removing and installing

Hydraulic multidisc Brake H420

Electric Rotary Actuator - On/Off or programmable control actuator

Compact pressure switch Flameproof enclosure Ex d Model PCA

Transcription:

VMR Safety solenoid valves for air and gas Fast opening and fast closing type DN0 DN50 www.pandid.nl VMR6 - VMR9 Certified Quality System Printed in Italy - EE6/0705

VMR Fast safety solenoid valves Class A Group The VMR type valve is a fast opening single-stage solenoid valve, normally closed. This type of device is suitable for air or gas blocking and releasing controls, required in gas power burners, atmospheric gas boilers, furnaces and others gas consuming appliances. The VMR type valves are made in accordance with EN6 standard. (EC type examination certificate no. 006AQ50). - Features Wide range for inlet/outlet connections, from /8 to 6 pipes sizing. Provided with G/ pressure gauge on two sides in the inlet pressure chamber (except brass model). Others gauge points on request. Optional G/8 connection for closed position indicator micro switch (on request from /" to 6"). Fine mesh filter incorporated prevents dirty contamination of the seal seat. Maximum operating pressure 00 mbar or 60 mbar. Suitable for air and non-aggressive gases (EN 7,, and families). Easy adjustable flow rate, provided of locking screw (except ", 5", 6" and brass models). Qualified for continuous service (00% ED) and endless ON/OFF cycles. Coil insulation is class H (80 C). Terminal box with PG connector or ISO 00 plug on /". The large models are provided with a power saving electronic device, to reduce power consumption and working temperature. Valves are 00% tested by computerized testing machineries and are fully warranted. For valve identification see the following charts. This control must be installed in compliance with the laws in force. Read instructions before use. Elettromeccanica Delta S.p.a. reserves the right to update or make technical changes without prior notice. - Technical specifications Fig. Connections. Gas threaded ISO 7/ from Rp/8 to Rp Flanged PN6 - ISO 5 from DN0 to DN50 Voltage rating.. 0 VAC 50/60 Hz (other voltages on request) Voltage tolerance. -5% / +0% Power consumption. see charts Environment temperature.. -5 C / +60 C Max. working pressure 00 / 60 mbar Flow capacity see charts Disc sealing NBR Opening/Closing time.. < sec. Protection class IP 5 (EN 6059) Cable gland... PG09 Overall dimensions.. see charts Printed in Italy - EE6/0705

- Operation The VMR type valve is a safety shutting device using auxiliary power supply. When it is de-energized, the spring pushes on the seal disc, keeping the gas passage closed. Now, the inlet chamber is under the gas line pressure, and it forces on the disc too, improving the seal. When the coil is powered the valve opens rapidly, against the strength of the spring and gas pressure. The flow may be adjusted using the regulating screw on the top (see the Service Instruction Section). If the power supply is shut off, the valve rapidly closes, interrupting the gas flow. - Accessories A fine mesh filter is provided, to prevent dirty contamination of the seal seat. However, an external strainer must be installed upstream of the valve. Brass models are available without internal filter only. Inlet pressure area is provided with bilateral G/" gauges, to connect min/max adjustable pressure switches, leakage tester or other gas equipments. Flanged models are provided with gauges in the outlet chamber too. Brass models are available without gauges only. On request, valves are supplied with a G/8 connection on the bottom, to installed a closed position indicator micro switch (from /" to 6"). An adapting rod is provided too. 5- Coil features The continuous service (00% ED) causes inevitable coil heating, depending of working environment. This situation is absolutely normal and has not to worry. To improve the coil cooling, install the valve allowing free air circulation. The models from "¼ up to 6" are provided with a power saving electronic device. It has two stages of operation: full power is supplied to the coil while the valve is opening; low power is supplied while the valve is opened. Coil and terminal box are provided with suitable gaskets, to avoid water and dirty contamination (see the Service Instruction Section). 6- General information Testing pressure must not exceed,5 bar. Fig. Backpressure sealing is compliant with the Class A: the maximum backpressure admitted, with leakage within the EN6 requirements, is 50mbar. Maximum torsional stresses admitted are compliant with the Group of the EN6 standard. All components are design to withstand any mechanical, chemical and thermal condition occurring during typical service. Effective impregnation and surface treatments has been used to improve mechanical sturdiness, sealing and resistance to corrosion of the components. Valves are suitable for use with air and nonaggressive gases included in the, and families (EN 7). Materials in contact with gas: Aluminium Brass Stainless steel Plated steel Anaerobic adhesive Nitrile rubber (NBR) Polytetrafluoroethylene (PTFE) Printed in Italy - EE6/0705

7- Valve identification Connections type 0V AC 0V AC Threaded Flanged 60 mbar 00 mbar 60 mbar 00 mbar Rp / brass VMROTN VMROTN.B Rp /8 VMR0 VMR0A VMR0.B VMR0A.B Rp / VMR VMRA VMR.B VMRA.B Rp / VMR VMR.B Rp VMR VMR.B Rp ¼ VMR5 VMR5.B Rp ½ VMR VMR.B Rp VMR6 VMR6.B DN 0 ( ) VMRF VMRF.B DN 50 ( ) VMR6F VMR6F.B DN 65 VMR7 VMR7 VMR7.B VMR7.B DN 80 VMR8 VMR8 VMR8.B VMR8.B DN 00 VMR9 VMR9 VMR9.B VMR9.B DN 5 VMR9 VMR9 VMR9.B VMR9.B DN 50 VMR95 VMR95 VMR95.B VMR95.B Fig. Model Connections Max. Pressure Power Consump. @0VAC Overall dimensions (mm) Weight Threaded Flanged (mbar) (W) A B C D Int h (Kg) VMROTN Rp / brass 00 6 0 58 95 0 - - 0, VMR0 Rp /8 00/60 0 88 77 0 - -, VMR Rp / 00/60 0 88 77 0 - -, VMR Rp / 60 5 88 96 50 6 - -,5 VMR Rp 60 5 88 96 50 6 - -,5 VMR5 Rp ¼ 60 0/80 ( ) 0 5 88 0 - - 5,7 VMR Rp ½ 60 0/80 ( ) 0 5 88 0 - - 5,7 VMR6 Rp 60 0/80 ( ) 06 56 9 0 - - 6 VMRF DN 0 ( ) 60 0/80 ( ) 50 9 88 6 0 x8 7, VMR6F DN 50 ( ) 60 0/80 ( ) 65 96 9 7 5 x8 8 VMR7 DN 65 00/60 60/0 ( ) 00 05 66 55 5 x8 VMR8 DN 80 00/60 60/0 ( ) 00 05 66 55 60 8x8 VMR9 DN 00 00/60 80/0 ( ) 5 50 5 9 80 8x8 6 VMR9 DN 5 00/60 90/60 ( ) 0 60 0 600 0 8x8 58 VMR95 DN 50 00/60 90/60 ( ) 0 60 0 600 0 8x 60 ( ) Optional kit ( ) Working/Opening Printed in Italy - EE6/0705

8- Loss of pressure dp [mmh O] Air Natural gas Town gas DN 50 DN 5 DN 00 DN 80 DN 65 0. 0. 0. 0. 0. 0. 0. 0. 0. 5 6 7 8 0 0 0 0 50 60 70 80 00 00 0 5 6 7 8 0 0 LPG 0 50 60 70 80 00 00 00 000 000 5000 000 000 000 5000 000 000 5000 000 000 000 000 000 600 500 00 00 00 000 000 600 500 00 00 000 000 600 500 00 00 000 600 500 00 00 00 Rp Rp ½ Rp ¼ Rp Rp / 00 80 70 60 50 0 0 0 0 8 7 6 5 00 00 80 00 70 80 60 70 50 60 0 50 0 0 0 0 00 0 0 8 0 7 8 6 7 5 6 5 00 80 70 60 50 0 0 0 0 8 7 6 5 V [Nm³/h] Rp / Rp /8 Rp /-OT 0. 0. 0. dp [mbar] Formula of conversion from air to other gases Gas type Specific gravity (Kg/m³) K Air,5,00 Natural gas 0,80,5 Town gas 0,57,8 LPG,08 0,77 +5 C, 0 mbar, dry 5 Printed in Italy - EE6/0705

9- Valve installation Verify the line pressure is lower of the maximum working pressure admitted to the valve. Check correspondence of flow direction with arrow printed on valve body. Check correct alignment of connecting pipes and allow enough space from the walls to allow free air circulation. Remove the end caps and make sure no foreign body is entered into the valve during handling. Install in an area that is protected from rain and water splashes or drops. Threaded models:. Put sealing agent onto the pipe thread (avoid excessive quantities of fittings glue which could enter in the valve and damage the seal seat).. Screw the pipes using proper tools only. Do not use unit as lever because damage to the valve stem could result. Flanged models:. Position the gasket and insert the bolts.. Screw the nuts tightening them crosswise and using proper tools only. Avoid overtightening and mount tension free. Following chart shows the maximum values of bending moment (Fmax), torque (Tmax) and screws driving torque (Cmax), according to EN6. 0- Electrical connections (IEC 70-) Check correspondence between valve voltage rating and line power supply, before making any electrical connections.. Switch off power supply and remove protection cover.. Connect power cables to rectifier circuit terminal board.. Should cables pass through originally closed opening, use the rubber disc placed underneath the box plug to close any other opening.. Screw back the box cover, taking care to use all gaskets properly, because this could condition the valve life duration. Connections Fmax (Nm) t<0 s Tmax (Nm) Cmax (Nm) Rp/8 70 5 - Rp/ 05 50 - Rp/ 5 85 - Rp 0 5 - Rp¼ 75 60 - Rp½ DN0 60 00 50 Rp DN50 00 50 50 DN 65 600-50 DN 80 00-50 DN 00 5000-80 DN 5 6000-60 DN 50 7600-60 Tmax Fmax Cmax Fig. 5 To prevent product damage and dangerous situations, read the Installation and Service Instructions carefully. Turn off all power before servicing any part of the system. Perform leak and functional tests after mounting. A gas leak detection spray may be used also. Coil and terminal box must be replaced with identical spare parts only. If the coil is turned, make sure the cap is properly tightened and the coil is locked. Use all gaskets properly (void warranty). All wiring must be in compliance with local and national codes. Make sure all works are performed by qualified technicians only. Fig. Valve may be mounted with coil in horizontal or vertical position. Coil may be oriented 60 degrees in any direction. 6 Printed in Italy - EE6/0705

- Flow rate adjustment (Vmax) Flow rate may be adjusted from 0 cubic meters/h to the maximum (excepting ", 5", 6" and brass models). To perform regulation do the following:. Remove coil fastener cap.. Using a mm Allen wrench, remove the locking dowel.. Located under the locking dowel is the flow regulation screw. Use the Allen wrench to set it.. Turn wrench clockwise to decrease or counterclockwise to increase flow rate (factory setting is max. flow rate). 5. When adjustment is completed, screw back the locking dowel and cap. Make sure that capacity adjustments are made while burner is operating. Check the regulation is not changed during reassembly. Adjustments below 0% of capacity are unadvisable because they may cause turbulence. Fig. 7 - Coil replacement Before to start with coil replacement, make sure it is the cause of failure. To perform coil replacement do the following:. Make sure an identical one spare part is available.. Switch off power supply and remove the box cover.. Disconnect the wires from terminal board.. Remove coil fastener cap and replace the coil. 5. Reassemble following the inverse sequence. When reassemble, use all gaskets properly. Perform functional test after mounting. Fig. 6 All works must be executed by qualified technicians only and in compliance with local and national codes. 7 Printed in Italy - EE6/0705

- Maintenance To maintain a good performance of the system, almost once a year, an inspection of the valve is recommended. Cap O-ring External inspection Turn off all power before servicing any part of the system. Check the conditions of the terminal board gasket. If gasket is deteriorated, replace it with a new one. Check the electrical connections are clean, dry and correctly tightened. Check the conditions of pipe connections: cover them with a soap solution and check for leakages. Internal inspection To make an internal inspection of the valve, do the following:. Close ball valve upstream the system.. Remove the coil like shown in the section.. Using an Allen key, remove the screws on the upper flange, in cross way. The gas in the valve will come out during this step.. Check the main O-ring and, if it s necessary, replace it with a new one. 5. Clean the internal side of the stem with a clean cloth and compressed air. 6. Remove the spring and blow it with compressed air. Check the spring is corrosion free. Take attention to the assembly direction of the spring. 7. Check the wear conditions of the sliding rings and, if it s necessary, replace them. 8. Clean the plunger assembly with a clean cloth and compressed air. 9. Check the conditions of the sealing gasket. If gasket is deteriorated, replace it with a new one. 0. Clean the sealing lip with a clean cloth. Do not use tools, because a lip damage could result.. Remove the filter and blow it with compressed air.. Reassemble the valve following the inverse sequence. Fig. 8 Coil assembly Stem Screw Upper flange Main O-ring Spring Sliding ring Plunger Disc + gasket Filter G/ plug Valve body To assemble the sliding rings, wind them onto a lower diameter (ex. Screw driver), then insert them from the top. When reassembling, take attention to the correct position of the sliding rings and spring. When the reassembly is finished, verify the correct sealing between the upper flange and the valve body:. Open ball valve to restore pressure into the valve.. Apply a soap solution between the upper flange and the valve body and check for leakages.. Remove the soap solution with a clean cloth, before to reassemble the coil. When reassemble, use all gaskets properly. Perform functional test after mounting. All works must be executed by qualified technicians only and in compliance with local and national codes. 8 Printed in Italy - EE6/0705