Blower Door. Testing. Get ready: Airtightness requirements are part of the 2012 building and energy code BY LARRY ARMANDA

Similar documents
Blower Door Testing by David Keefe

Minneapolis Blower Door. Operation Manual for Model 3 and Model 4 Systems

Duct Leakage Testing 101 Frank Spevak The Energy Conservatory Minneapolis, MN

Good ventilation is important

DRYER VENTING SPECIFICATIONS DRYER SAFETY

Center for Energy Education Laboratory

Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen

Home Energy Evaluation Report

Heating, Ventilation and Air-Conditioning (HVAC)

air conditioners how to choose a cooling system

Home Performance with ENERGY STAR. Evaluation Report

Key energy-efficient features of your new home

Crawford Inspection Services C.C.B. #

Troubleshooting Draft Problems in Chimneys

HOW MUCH FUEL DOES A GAS STOVE CONSUME AND HOW MUCH DOES IT COST TO OPERATE?

Chapter 8. Duct Design and Sealing

2014 British Columbia Building Code Changes

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

Energy Efficiency Evaluation Reportii House file number: 9900D00001ii

ECHO System for Basements

The Only GUY To Call. Why are my utility bills so high? What can I do to lower my energy expenses?

Minneapolis Duct Blaster

BUILDING PERFORMANCE INSTITUTE TECHNICAL STANDARDS

Your Personal Home Energy Action Plan

THREE. Heating and Cooling

Residential Pressure and Air Leakage

READ AND SAVE THESE INSTRUCTIONS

heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved.

CARING FOR YOUR WATER HEATER

Thermal Imaging for Home Inspectors

EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money

Chapter Eight RESNET Standards

Inspection Report Atlanta Strip Mall Commercial Building Property Address:

CITY OF FAIRFAX CODE ADMINISTRATION / FAX

Attic condensation during winter can

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.

BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER

WHOLE-HOUSE VENTILATION SYSTEMS

HVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings

HVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades

Residential Duct Systems for New and Retrofit Homes

Does Wall Township require an inspection by the building department on resale of a home?

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

Proposed Amendment: Revisions to Chapter 8 Sections Proponent: RESNET Technical Committee

First Time Home Buyers Energy Efficiency Workshop Guide

Home Energy Auditing Standard

1 DESCRIPTION OF THE APPLIANCE

Heating, Ventilation, and Air Conditioning

Amendment: Combustion Appliance Testing Standards Removal. Proponent: Brett Dillon, Chair Standards Development Committee

Your safety and the safety of others are very important.

New Home Walk-Through Package

Single Family Residential Basement Finish

Inspection Tech. (330) Inspected By: Aaron Westerburg

Sample DTE Energy Rebate Programs Follow:

FREQUENTLY ASKED QUESTIONS about HERS and CHEERS Provided by the California Energy Commission Consumer Energy Center

about your house How to Get the Ventilation That You Need in Your House Figure 1 Infiltration and exfiltration of air in a house

With colder weather approaching and heating costs continuing to skyrocket, ASHRAE is offering some simple ways to save energy and keep you and your

Standardized Terminology for Combustion Appliances and. Combustion Safety Testing

BPI Air Conditioning & Heat Pump Professional Training Sample Slides ( ) Agenda

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

Category Measure Minimum Efficiency / Certification Requirements

GENERAL WIRING RULES FOR HOUSES

October 5, 2015 Dear Client,

Home Maintenance Checklist

SL280UHV SERIES GAS FURNACE WARNING

Installation Instructions

Building and Grounds Maintenance Checklist

Gas-Fired, Residential Storage Type Water Heaters

Before You Start an Energy Efficiency Retrofit The Building Envelope

HV AC CODE CHECKLISTS

Diagnostics for Mobile Homes: HVAC

Name Of Occupancy Date. Yes No Describe

energy-saving checklist a guide for rental property owners

Arapahoe County Residential Water Heater Installation and Inspection Guide

Evaluate, Clean, and Tune Guidance

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012

The growing popularity of Gas Fireplaces has created a demand for an ever increasing array of styles and sizes to fit every decor and budget.

Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10

Report for. Dick and Jane Homeowner Lovers Lane, Houston, Texas 77000

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

Pre-Drywall Inspection Report

Home inspectors are not mold inspectors, however they do inspect for defects that

Underwriters Laboratories Testing Information

Home Management Checklist: Spring

Home Inspection Report

Applications for building permits will not be reviewed until all of the required information has been submitted.

Inspection Report. Dream Home Inspections Second Ave. Frisco CO (970)

ANSI/BPI-1200-S-2015:

Basement Development Construction requirements for the development of basements in residential dwellings.

RESNET Interim Guidelines for Combustion Appliance Testing and Writing Work Scope September 1, 2010

STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE:

CHAPTER 10: APPLIANCES AND LIGHTING

Boiler and Burner Cleaning and Servicing Specifications

HVAC Code Requirements

Ventilation Solutions Kitchens. fantech

Below are detailed instructions for using the EMS load calculator.

Boiler Preparation, Start-Up and Shutdown

- 2 - IMPORTANT SAFETY REMINDERS

Housing Quality Standards Inspection Checklist

Transcription:

Blower Door Testing Get ready: Airtightness requirements are part of the 2012 building and energy code BY LARRY ARMANDA 48 FINE HOmEBuILDING

Air leaks in houses are a big problem. Leaks make homes uncomfortable and expensive to heat and cool. They create condensing cold spots that attract mold and rot. They lead to frozen pipes and make homes less resilient during prolonged power outages. Dealing with air leaks starts with locating them. There are many ways to find air leaks; the easiest and most common is to use a blower door. Blower-door tests used to be the exclusive domain of weatherization workers and building-science geeks, but that s not the case anymore. Everyone involved in residential building needs to become more familiar with blower-door testing because universal testing for all new homes is coming. Section N1102.4.1 of the 2012 International Residential Code (IRC) includes a requirement for blower-door testing with airtightness standards spelled out for the country s various climate zones. New houses will need to meet or exceed these airtightness numbers to meet the current building code (see climate-zone map, p. 53). It s not clear who will do the testing, however. Some codeenforcement offices let contractors do their own blower-door tests. Others require thirdparty testing. It seems likely that some will have their inspectors do the testing. How does a blower door work? A blower door has a powerful variable-speed fan and a two-channel digital manometer, or air-pressure gauge. After being temporarily installed in an exterior door opening and turned on, it draws air from the house and blows it outside. The manometer measures both inside and outside air pressure. For most of the tests, the idea is to register a 50-pascal (Pa) difference between the inside and outside air pressure using the blower door s 3 4-hp fan. The amount of air and fan power that it takes to register the 50-Pa difference corresponds to how tight or how leaky the house is. You can adjust the fan speed with the sensitive electronic speed controller and match the fan size to the expected leakiness of the building with a series of flow rings that adjust the size of the fan inlet. What the numbers mean The results of most blower-door tests are expressed in cfm50 (cubic feet per minute at 50 Pa) or in ACH50 (air changes per hour at 50 Pa). A 50-Pa difference is roughly the Prep the house Safety first. To prevent the blower door from sucking exhaust gases down the chimney and into the house, turn off all combustion appliances before testing. For appliances without an on/off switch, such as gas water heaters, turn the gas valve to the pilot setting. TIP: After shutting everything off, leave your keys on one of the appliances so that you remember to turn everything back on after testing. Don t forget ventilation fans. Turn off bath fans, clothes dryers, and range hoods before testing. Timer-controlled ventilation equipment such as ERVs and HRVs also should be turned off. Close windows, and open interior doors. Shut and lock exterior doors and windows, and open interior doors to allow air movement. Close flue dampers and pet doors also. www.finehomebuilding.com february/march 2014 49

install the door Size and cover the frame. Assemble and adjust the aluminum frame so that it s slightly loose in the opening but so that the cam locks will tighten the fit and lock the door in place when they re rotated. Remove the frame for installing the fabric cover. Route the hose. The air hose that measures outside air pressure is routed through a small hole. Putting the open end at least 5 ft. from the fan and inside the unzipped manometer storage bag prevents strong winds from distorting the measurement. Install the fan. Insert the blowerdoor fan through the elastic hole in the fabric cover. Once it s in place, secure it to the intermediate frame rail with the Velcro strap, and attach the red hose to the air fitting on top of the housing. equivalent of a 20-mph wind on all sides of the house. The intense pressure from the blower door exaggerates the natural conditions to make air leaks appear more obvious. The cfm50 measurement refers to how much air is rushing back into the building as the blower door is forcing air out, depressurizing the house. A good number here would be about 800 cfm50 or 900 cfm50 for a 2000-sq.-ft. house. ACH50 measures how many times the air in the house is completely replaced in one hour under the blower door s artificial 50-Pa pressure difference. Most building-science and weatherization professionals consider about 3 ACH50 to be the sweet spot between a house that s too tight and one that s too leaky. Leakier homes should have airsealing work to make them more energy efficient, while tighter homes may need mechanical ventilation to control indoor-air pollutants. Blower-door tests are useful for both new and existing homes. Old homes are often tested to direct weatherization efforts and to gauge the effectiveness of those efforts. New homes are often tested as part of Energy Star and other home-performance certifications. Preparing for the test The most important step in preparing for a blower-door test is to turn off all combustion appliances (furnaces, boilers, and water heaters). If you don t, the blower door s powerful fan could suck flue gases, including carbon monoxide, down the chimney and into the house, creating a dangerous condition called backdrafting. For appliances equipped with a switch, I simply turn them off. If an appliance doesn t have a switch for example, most gas water heaters I turn the gas valve to the pilot setting. 50 FINE HOMEBUILDING

Set up the Gauge Establish a baseline. Outdoor temperature and air pressure along with varying indoor conditions can affect manometer measurements, so the manometer must be calibrated with each test to ensure that the results are consistent. Pick a ring. Removable flow rings allow the blower door to work with homes of all sizes and airtightness levels. Before testing, choose the ring that best matches the home s expected leakiness. Most homes will use the A ring. Tighter homes will use the B ring or C ring. The leakiest or largest homes will require the open fan setting without rings. Fan configuration Flow range (cfm) for model 3 fan Expected airtightness Open (no flow ring) 6300 to 2430 Leaky Ring A 2800 to 915 Typical Ring B 1100 to 300 Tight Ring C 330 to 85 Very tight After shutting off everything, I leave my keys on one of the appliances so that I remember to turn everything back on after I m done with the testing. Next, I shut and lock all windows and exterior doors. This includes garage doors on attached garages. I leave open interior doors, including closet doors, to allow the free movement of interior air. When the basement is included as part of the home s conditioned space, I also open the basement door. Fires in woodstoves and fireplaces must be extinguished for at least 24 hours before testing, and fireplace doors and chimney dampers should be closed. It s also important to turn off clothes dryers, ventilation fans, and air conditioners. I also look around for broken plaster and loose wall paneling. If the home has a drop ceiling, I always check above the tiles for holes. If I find any, I remove a few ceiling panels so that the blower door doesn t pull down the entire ceiling. I also take a good look at any vinyl flooring, even tile, because moving air can pull it from the floor during the test. Setting up the door The Minneapolis Blower Door (energyconservatory.com) I use is packed in three parts. The adjustable aluminum frame that supports the motor is packed in a nylon carrying bag. The manometer, air hoses, and fabric cover are in a second bag. The fan, which is protected by its plastic housing, is carried separately. The whole rig sells for about $2700. I begin setting up the blower door by assembling the metal frame on the floor. Doing this on a rug or a blanket prevents scratching the www.finehomebuilding.com february/march 2014 51

START TESTING Start slowly. Gradually increase the fan speed with the controller until the manometer reaches about 25 Pa. Walk around the house to look for problems such as blowing fireplace ash or lifting vinyl flooring. If everything s OK, increase the speed to reach 50 Pa, then record the results. floor. Once the frame is together, I fit it in the doorway where I ll be conducting the test. I choose a centrally located exterior door free of obstructions that could block airflow. I first adjust the frame width, and then I adjust the height. I tighten the adjustment knobs so that when the cam-shaped locking levers are fully tightened, they exert enough pressure to make a tight seal around the door. Once the frame is sized, I remove it from the door opening. I lay the nylon cover on the floor with the manufacturer s label on the fabric cover facing up, and then place the frame on top of the cover, securing it with the attached Velcro tabs. I now return the covered frame to the opening and press it tight to the stops on the door jamb. Then I lock the frame in place using the locking levers. Next, I hang the speed controller and the digital manometer from the frame using the provided bracket. The green air hose runs outside through the small hole provided in the fabric cover. The fan fits through the large hole in the cover. A wide Velcro strap attached to the intermediate frame rail helps to hold the heavy unit in place. After making sure that the speed controller is in the off position, I connect it to the fan and plug the other end into a house receptacle. I then connect the green air hose running outside to the Ref tap on the A-side of the manometer. The red hose runs from the airpressure tap on the top of the fan to the Input tap on the B-side of the manometer. Set up the gauge With the fan cover and all flow rings in place on the fan housing, I turn on the manometer with the On/Off button. I then press the Mode button twice to choose the PR/FL@50 mode so that the gauge will display results based on 50 Pa even if the actual pressure is greater or less. I do this for two reasons: First, some leaky homes simply won t get to 50 Pa; the fan just can t move enough air to depressurize them to this amount. More commonly, though, it s so that I don t waste time adjusting the fan speed to get to exactly 50 Pa. Instead, the gauge uses the current reading to extrapolate cfm to the 50-Pa benchmark. I shoot for between 45 Pa and 55 Pa for the most accu rate test. I now calibrate the gauge to current outdoor conditions and eliminate pressure differences caused by the stack effect inside the house. This step, described as establishing baseline, makes the test useful in all times of the year and makes the results repeatable. The process, which involves a series of keystrokes on the manometer, is explained in the blower-door manufacturer s Quick Guide. Pick a flow ring This next step requires experience or additional experimentation. You have to guess which flow ring on the fan housing best matches the expected leakiness of the house (chart, p. 51). Most modern, conventionally built houses from about 1600 sq. ft. to 2500 sq. ft. will use the A ring. Tighter homes will use a smaller ring. Especially leaky homes will use open fan, which describes the fan without any flow rings. If you choose wrong, it s no big deal, but with every guess, you need to reconfigure the gauge to match the flow ring you ve selected. For the test shown here, the A ring is in place. Before starting your own test, be sure to confirm that the gauge is set up correctly by pressing 52 FINE HOMEBUILDING Photo far right, facing page: Rodney Diaz. Drawing facing page: Dan Thornton.

Test results: By the numbers Manometer results are displayed in cfm, but a more meaningful result is expressed in air changes per hour at 50 pascals (ACh50), which takes into account the size of the home. to calculate ACh50, multiply the cfm by 60 and divide by the home s total volume (length width height) as shown in the example at right. the 2012 international residential Code (irc) requires blowerdoor airtightness testing for new homes. the airtightness requirement varies with climate zone (see map, right). here s what the code says: The building or dwelling unit shall be tested and verified as having an air-leakage rate not exceeding five air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with a blower door at a pressure of 50 Pa. Where required by the code official, testing shall be conducted by an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. (irc n1102.4.1.2) Climate zones 1 2 3 4 5 6 7 Example 2200 cfm50 60 minutes...132,000 House: 2500 sq. ft. 8.5 ft. (ceiling height)... 21,250 cu. ft. 132,000 21,250... 6.2 ACH50 Climate zone 2009 iecc 2012 irc 1 2 < 7 ACh50 < 5 ACh50 3 8 < 7 ACh50 < 3 ACh50 the Device button until you get the right model. In this case, the setting is BD 3 for a minneapolis Blower Door model 3. Start the test I begin by slowly turning the speed-controller knob while watching the A channel on the manometer until the fan brings the house to 25 Pa. With the pressure holding steady at 25 Pa, I walk through the house to make sure the fan isn t blowing around fireplace ashes or damaging anything. I learned this step the hard way when years ago I filled a child s crib with fiberglass insulation by sucking it through a disconnected ceiling register. Once I m satisfied that everything is OK, I continue to increase the fan speed until I ve reached between 45 Pa to 55 Pa. As mentioned earlier, blower-door tests are based on depressurizing the house to 50 Pa, but it s time-consuming and unnecessary to adjust the fan speed to reach exactly 50 Pa. modern blower-door manometers can automatically extrapolate the results to 50 Pa, even if you can t get there exactly. The exact pressure measurement in pascals is displayed on the channel-a side of the manometer, while the corresponding cfm at 50 Pa is displayed on the channel-b side of the gauge. What the numbers mean In addition to the indoor-air pressure on the channel-a side of the manometer, the gauge also shows how leaky the house is with a cfm number on the channel-b side of the manometer. For those doing weatherization work, cfm measurements are commonly understood, but they re less clear for designers, builders, and homeowners, who are more likely to understand results expressed in ACH50. To calculate air changes, multiply the cfm number by 60. Divide that number by the house s total cubic volume (in feet). Depending on the house shape, this can be easy or complicated. A good resource for determining geometric volume for uncommon shapes can be found at calculatorsoup.com. Once you have a cfm number recorded, you can pack up your gear, or you can leave the blower door running and use a smoke puffer or infrared camera to track down the worst-offending air leaks (see Finding leaks, below). Larry Armanda is a building-science educator and professional in South Williamsport, Pa. Photos by Patrick McCombe, except where noted. Smoke puffer Finding leaks In addition to testing airtightness, blower doors can be used to track down air leaks. One common way is to use a smoke puffer (left), which shows leaks with a chemical smoke. If you want to see air leaks behind walls, you ll need to use an infrared camera. Unfortunately, you ll need a 10 F to 20 F temperature difference between inside and outside air for the leaks to show up. The IR image at right shows how the blower door is drawing hot attic air into stud cavities. IR camera www.finehomebuilding.com FEBRuARY/mARCH 2014 53