THE MINARET INCIDENTS AT PUTRAJAYA

Similar documents
ADVENTURE ISLAND LIGHTNING INCIDENT AN IN-DEPTH REPORT ON THE DEADLY FAILURE OF AN EARLY STREAMER EMISSION LIGHTNING ROD

SEAWORLD ORLANDO LIGHTNING INCIDENT FAILURE OF THE SECOND GENERATION EARLY STREAMER EMISSION LIGHTNING ROD

ADVENTURE ISLAND LIGHTNING INCIDENT. REPORT ON THE DEADLY FAILURE OF AN EARLY STREAMER EMISSION LIGHTNING ROD [Revision 1)

Lightning Protection Introduction

THE LIGHTNING PROTECTION INTERNATIONAL STANDARD

Lesson 26: Reflection & Mirror Diagrams

GCSE Exam Questions on Volume Question 1. (AQA June 2003 Intermediate Paper 2 Calculator OK) A large carton contains 4 litres of orange juice.

INTERNATIONAL STANDARD

Acceleration of Gravity Lab Basic Version

Consultants Handbook

EXPERIMENT 6 OPTICS: FOCAL LENGTH OF A LENS

TUESDAY, 6 MAY 9.00 AM 9.45 AM. 2 Full credit will be given only where the solution contains appropriate working.

Chapter 22: Mirrors and Lenses

How to build a Pizza Oven in 4 days

CHAPTER 29 VOLUMES AND SURFACE AREAS OF COMMON SOLIDS

ME 111: Engineering Drawing

Geometric Optics Converging Lenses and Mirrors Physics Lab IV

MECHANICS OF SOLIDS - BEAMS TUTORIAL 1 STRESSES IN BEAMS DUE TO BENDING. On completion of this tutorial you should be able to do the following.

Intermediate 2 NATIONAL QUALIFICATIONS. Mathematics Specimen Question Paper 1 (Units 1, 2, 3) Non-calculator Paper [C056/SQP105] Time: 45 minutes

SECTION 22 LIGHTNING PROTECTION SYSTEM

HOW DOES A LIGHTNING ROD WORK? by MARTIN A. UMAN ORIGINALLY PUBLISHED IN

Thin Lenses Drawing Ray Diagrams

CALCULATING THE AREA OF A FLOWER BED AND CALCULATING NUMBER OF PLANTS NEEDED

Calculating Area, Perimeter and Volume

PRESENTATION ON REPAIR AND REHABILITATION OF BUILDINGS DAMAGED IN EARTHQUAKE. By H P Gupta & D K Gupta

Copyright 2011 Casa Software Ltd. Centre of Mass

Freehand Sketching. Sections

Drexel-SDP GK-12 ACTIVITY

Speed, velocity and acceleration

WEDNESDAY, 2 MAY 1.30 PM 2.25 PM. 3 Full credit will be given only where the solution contains appropriate working.

Free Inductive/Logical Test Questions

GroundRod AC Substation Earthing Tutorial

Chapter. Earthquake Damage: Types, Process, Categories

EAST LYME HIGH SCHOOL

Snap to It with CorelDRAW 12! By Steve Bain

2. More Use of the Mouse in Windows 7

GCSE Revision Notes Mathematics. Volume and Cylinders

Technical Drawing Specifications Resource A guide to support VCE Visual Communication Design study design

Traditional Drawing Tools

RENOVATION AND RESTORATION OF OLD BUILDINGS IN SRI LANKA

2) A convex lens is known as a diverging lens and a concave lens is known as a converging lens. Answer: FALSE Diff: 1 Var: 1 Page Ref: Sec.

The minimum reinforcement for the stem wall is the placement of:

Circle the right answer for each question. 1) If a shape is three-dimensional, we know we can measure how high and how wide it is, and what else?

INVISIBLE TURBULENCE IN VICINITY OF CB / CUMULUS CELL

RULES FOR INSTALLATION OF COMMUNICATION TOWERS.

Hanson Building Products. precast basement solutions

Geometry - Calculating Area and Perimeter

MATHEMATICS FOR ENGINEERING BASIC ALGEBRA

Projectile Motion 1:Horizontally Launched Projectiles

Newton s Law of Universal Gravitation

Wigan LEA Numeracy Centre. Year 3 Time Block 3 Mental Arithmetic Test Questions

TABLE OF CONTENTS. INTRODUCTION... 5 Advance Concrete... 5 Where to find information?... 6 INSTALLATION... 7 STARTING ADVANCE CONCRETE...

ALPERTON COMMUNITY SCHOOL MATHS FACULTY ACHIEVING GRADE A/A* EXAM PRACTICE BY TOPIC

Proper use of the Rebound Hammer Updated to reflect the changes to ASTM C805

Session 7 Bivariate Data and Analysis

Web review - Ch 3 motion in two dimensions practice test

Numeracy Targets. I can count at least 20 objects

Number Sense and Operations

Geometrical Optics - Grade 11

Minimum Safety Requirements for temporary Helicopter Landing Areas.

SA B 1 p where is the slant height of the pyramid. V 1 3 Bh. 3D Solids Pyramids and Cones. Surface Area and Volume of a Pyramid

Building Condition Assessment: West Lexington Street Baltimore, Maryland

Transportation and Lifting of Liquefied Gas Dewars

CONTACT NUMBER: (786) PHYSICS I

`Fall Protection Guidelines in Construction

Physics 1114: Unit 6 Homework: Answers

1. The volume of the object below is 186 cm 3. Calculate the Length of x. (a) 3.1 cm (b) 2.5 cm (c) 1.75 cm (d) 1.25 cm

As we study each type of perspective, we will look both art work and photographs that exhibit each type of perspective.

MEASUREMENT OF END FACE GEOMETRY ON FIBER OPTIC TERMINI...2

THE PARABOLA section

University Rd., Tainan, Taiwan, R.O.C.,

Mathematics (Project Maths Phase 1)

Physics Section 3.2 Free Fall

APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE

Geometry Notes PERIMETER AND AREA

7.2. Focusing devices: Unit 7.2. context. Lenses and curved mirrors. Lenses. The language of optics

Solar Heating Basics Page 1. a lot on the shape, colour, and texture of the surrounding

Calculate the circumference of a circle with radius 5 cm. Calculate the area of a circle with diameter 20 cm.

Zeltbahn tents and shelters

Anamorphic Projection Photographic Techniques for setting up 3D Chalk Paintings

SURFACE AREA AND VOLUME

40m-10m DELTA LOOP ANTENNA - GU3WHN

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing

Not for distribution

Shape Dictionary YR to Y6

Presentation. Lightning Protection practices in Bangladesh :An overview

PE AND NUMERACY LINKS - KEY STAGE 1

Up-Down Construction Utilizing Steel Sheet Piles and Drilled Shaft Foundations

Valley fold 1/4 at the left side, again creasing only at the edge, and unfold. Valley fold, connecting the tops of the angle bisectors, and unfold.

The formulae for calculating the areas of quadrilaterals, circles and triangles should already be known :- Area = 1 2 D x d CIRCLE.

Digital Photography Composition. Kent Messamore 9/8/2013

Mathematics (Project Maths)

rarecorvettes.com, (831) Pacific Time Zone

The small increase in x is. and the corresponding increase in y is. Therefore

1 of 9 2/9/2010 3:38 PM

Chapter 36 - Lenses. A PowerPoint Presentation by Paul E. Tippens, Professor of Physics Southern Polytechnic State University

Inductive Reasoning Free Sample Test 1

Chapter 17: Light and Image Formation

Parametric modeling in AutoCAD By Neil C. Katz Skidmore, Owings & Merrill LLP October 11, 2008

9/16 Optics 1 /11 GEOMETRIC OPTICS

Transcription:

THE MINARET INCIDENTS AT PUTRAJAYA The Ultimate Test Case for the Early Streamer Emission Technology & Standard By Z. A. Hartono & I Robiah October 2010 E-mail: zahartono@ieee.org

Summary Bypasses (i.e. lightning strike damages) to buildings installed with the early streamer emission (ESE) air terminals have been observed in Malaysia as far back as 1991. They mostly occurred at the corners of the buildings. Since the majority of the ESE air terminals were installed centrally on top of the buildings, these bypasses were located close to the limit of the ESE protection zone. In order to conduct the ultimate test on the validity of the ESE standard, NF C 17-102, a tall and slender structure is required where an ESE air terminal can be installed at the apex. If the ESE standard is valid, then no part of the slender structure should be struck by lightning since they are located deep within the claimed ESE protection zone. The minaret of the Putra Mosque is a slender 116 metre high structure which is located in Putrajaya, the new administrative capital of Malaysia. The structure was completed in 1998 and was installed with an ESE air terminal at the apex. The slender shape of the structure made it the ideal ultimate test case for the ESE technology and standard since every part of the minaret is located deep within the claimed protection zone of the ESE air terminal and should not (in theory) be struck by lightning. However, periodic observations conducted on the minaret since its completion reveals that it has been struck and damaged by lightning several times. These damages provide more compelling evidences that the ESE air terminal is incapable of protecting tall structures higher than 60 metres. Since the minaret is about four times higher than the Sigolsheim bell tower reported earlier and located in a very high thunder day region, the ESE air terminal and standard has been shown to be ineffective under all possible structural and climatic conditions. Cover picture: The Putra Mosque and the subject minaret located beside a lake in Putrajaya. 2

1. THE PUTRA MOSQUE. The Putra Mosque is located in Putrajaya, the new administrative capital of Malaysia which is located about 25 km south of Kuala Lumpur. The annual thunder day (TD) level at this location is about 200. The mosque was completed in 1998 and has a 116 metre high minaret which has been installed with a Helita Pulsar ESE air terminal (Figs 1 and 2). Figure 1: The Putra Mosque and minaret taken from the circle. Figure 2: Close-up picture of the minaret reveals a Helita Pulsar ESE lightning air terminal installed on the apex. 3

Another Helita Pulsar ESE air terminal was also installed on the apex of the spire erected on the dome of the mosque (Figs. 3 and 4). This indicates that the ESE air terminal that was installed on the minaret was designed for the protection of the minaret only. Figure 3: The dome of the Putra Mosque. Figure 4: The Helita Pulsar ESE air terminal on top of the spire of the Putra Mosque dome. 4

2. FIRST MAJOR LIGHTNING STRIKE INCIDENT AT THE MINARET In March 2005, lightning struck and damaged the tip of one of the triangular marble protrusions on the side of the minaret. The bypass was located about 30 metres below the apex (Fig. 5). The lightning stroke broke off a marble slab which fell to the base of the minaret. This incident has been described in an article that was published in the Journal of the Association of Consulting Engineers Malaysia in 2007. http://www.lightningsafety.com/nlsi_lhm/acem_journal_q1_2007.pdf Figure 5: The arrow points to the location of the lightning damage in the 2005 incident. 3. SECOND MAJOR LIGHTNING STRIKE INCIDENT AT THE MINARET In September 2010, lightning again struck and damaged one of the protrusions on the side of the minaret. This time, the bypass was located on the tip of one of the triangular concrete protrusions about 12 metres below the apex (Fig. 6). A significant portion of the concrete protrusion was broken off by the lightning stroke. Parts of the debris also knocked off a section of a marble slab from one of the lower protrusions below it. The bypass to the concrete protrusion can be seen in the pictures below (Fig. 7). This kind of bypass is similar to those that were observed at the corners of numerous lightning damaged buildings around the country. 5

Figure 6: The arrow points to the location of the bypass in the September 2010 incident. Figure 7: The location of the bypass (left) on the horizontal concrete protrusion and a close-up view of the same bypass (right). Compare this photo with that of Fig. 2 (before the strike). The Helita Pulsar ESE air terminal can be seen on the apex of the minaret about 12 metres above the bypass. 6

4. OTHER LIGHTNING STRIKE INCIDENTS AT THE MINARET In addition to the two major incidents mentioned above, there were several other incidents of lightning strikes to the minaret that left only minor damages. These minor damages were virtually undetectable to the naked eye but they can be clearly seen through a binocular or a camera equipped with a zoom lens. The horizontal concrete protrusions below the apex originally have pointed tips when the minaret was first completed in 1998. Of the original eight pointed tips which were constructed in an eight-pointed star formation, only one remains undamaged (Fig. 8). From observations made to other buildings in the country, it is very difficult to detect the effects of a second lightning strike to an existing bypass unless the second strike causes a much bigger damage which drastically alters the shape of the original bypass. This suggests that the minaret have been struck at least eight times in the past dozen years since it was installed with the ESE air terminal. Figure 8: A close-up photo showing three of the concrete protrusions taken from the base of the minaret. Two of the protrusions displayed minor damages while the only remaining undamaged protrusion is shown on the left. 7

5. LIGHTNING INTERCEPTION MECHANISM AT THE PUTRA MOSQUE MINARET AND METHOD TO PREVENT FURTHER DAMAGES The lightning strike incidents to the minaret are not unusual since the interception positions can be predetermined by a method first developed by Professor Horvath of Hungary more than half a century ago. This method, which is known as the rolling sphere method (RSM), have been included in most national and international lightning protection standards published since 1970 (eg. NFPA780, BS6651, IEC62305). In this method, an imaginary sphere is rolled over and around the structure (eg. minaret) to be protected (Fig. 9). The surfaces of the minaret that are at risk of being struck by lightning, and hence require protection, are those that come into contact with the imaginary sphere, such as the apex and the tips of protrusions along the sides of the minaret. Figure 9: The rolling sphere method applied to the minaret. The method predicts that the sides of the minaret can be struck by lightning. The RSM predicts that the majority of the lightning strikes in the vicinity of the minaret will occur at the apex. The RSM also predicts that lightning can strike the minaret below the apex and the observed bypasses to the protrusions validated this method. 8

Hence, in order to protect the minaret from further damages, conventional air terminals (i.e. lightning rods) should be installed at the tips of all protrusions on the sides of the minaret. To effectively receive the lightning stroke, the air terminals on the protrusions should be pointing outwards and slanted slightly upwards at an angle. This is shown in the diagram below (Fig. 10). These air terminals can be bonded to the structural reinforcement steel bars for continuity to ground. Air terminals Figure 10: Vertical cross-section of the upper minaret showing the recommended position of conventional air terminals on the protrusions. 9

6. VALIDITY OF THE ESE STANDARD, NF C 17-102 According to the ESE standard, the protection zone starts at the tip of the ESE air terminal and takes the shape of an umbrella as it drops below the tip (Fig. 11). The radius of the protection zone at a particular height below the tip is determined by a specified mathematical formula found in the standard. At a height of about 30 metres below the tip of the ESE air terminal, the radius of the claimed protection zone should be at least 25 metres (protection level 1). The average radius of the minaret at 30 metres below the apex is less than 5 metres, hence all the protrusions are deep within the claimed ESE protection zone. Therefore, the minaret is the ideal ultimate test case to validate the ESE standard, NF C 17-102. However, the repeated failure of the ESE air terminal to prevent bypasses to the protrusions clearly suggests that the claimed ESE protection zone is non-existent and that the ESE air terminal positioning method described in the ESE standard is invalid and dangerous to apply on real buildings. Figure 11: The dashed line indicates the claimed protection zone, according to the ESE standard NF C 17-102, of the ESE air terminal which was installed at the apex of the minaret. 10

7. DISCUSSION The bypasses that occurred on the minaret of the Putra Mosque are not unique events since dozens of other similar bypasses have been observed and photographed on other buildings. They occurred well within the claimed protection zones of the ESE air terminals. A few examples of these bypasses and the nearby ESE air terminals are shown below (Figs. 12a to 12d): Figure 12a Figure 12b 11

Figure 12c The example below shows an ESE air terminal whose positioning method follows a different design method called the Collection Volume Method (CVM). The application of the CVM has also resulted in numerous bypasses on tall buildings in Malaysia. Some of these bypasses were found to be very close to the air terminals as shown in the example. Figure 12d 12

8. CONCLUSION In our earlier article The Bell Tower Incident at Sigolsheim (September 2010), the ESE air terminal was found to be incapable of protecting an ancient stone cross from being struck by lightning even though the cross was installed only 6 metres away from it. The bypass occurred in spite of the fact that the tip of the ESE air terminal was higher than the stone cross, the height of the bell tower was only about 30 metres and the tower was located in a very low thunder day region (about 20 thunder days per year). http://www.mikeholt.com/newsletters.php?action=display&letterid=930 The lightning incidents at the minaret of the Putra Mosque provide more compelling evidences that the ESE standard, NF C 17-102, is invalid. Since the ESE air terminal is incapable of protecting a tall and slender structure from direct lightning strikes, it is quite reasonable to conclude that it cannot protect real buildings too since they are much wider and their corners and edges are much closer to the limit of the claimed ESE protection zone. This conclusion is supported by the hundreds of bypasses observed and photographed on ESE installed buildings in Malaysia over the last two decades. Some of these bypasses were found to be well within the claimed protection zone of the ESE air terminal and some were known to have caused fires on the affected roof. http://www.mikeholt.com/newsletters.php?action=display&letterid=823 Both the Sigolsheim bell tower and the Putrajaya minaret incidents provide compelling evidences that the ESE standard, NF C 17-102, is invalid and should not be applied as an air terminal positioning method by all safety minded professionals. To do so will intentionally expose the building to direct lightning strikes and endanger the occupants and systems inside the buildings. 13