Technical Instructions Document No. 155-021P25 ET 141-5 September 28, 2004. ET 141 High Limit Control Thermostat. Description.



Similar documents
PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

Powers Controls TH 192 S Single Temperature Room Thermostat

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

POWERS CONTROL RC 195 Single Input Receiver-Controller

RC 195 Multiple Input Receiver-Controller

POWERS Controls No. 4 Pneumatic Damper Actuator

Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations

Cooktop Low-Profile Ventilation Hoods

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SET-UP AND INSTALLATION FOR LEAD SCREW CARTRIDGE ASSEMBLY

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Installer Guide smart connect

DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual

INSTALLER S & OWNER S MANUAL

, User s Manual

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

P70, P72, and P170 Series Controls for Dual Pressure Applications

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

T25 Two-Stage Room Thermostat

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

WARNING CANADIAN D.O.C. WARNING

WARNING: Important: Keep these instructions for future reference. Gate Instructions (1) Assembly and Installation Instructions

Easy Tool Retracting System CMC-SR2159ER36

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

System 350 A350R Electronic Temperature Reset Control (with Relay)

Model 43AP Pneumatic Controller, Style B

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

GeniJet Pipeless Motor Spa Installation

Duct Temperature Sensors

Table of Contents. What to Expect with. Preparation. Tools Needed. Wiring. Hanging the Fan. Blades. Motor Housing.

TR21, TR22, TR23, and TR24 Wall Modules

Small Flat Panel Lift Arm FSA-1004 and KSA-1004

Operation and Installation Manual. Max Series

Solid State Timers Type F

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

PACKAGED TERMINAL AIR CONDITIONER (PTAC) / PACKAGED TERMINAL HEAT PUMP (PTHP) AND ACCESSORY INSTALLATION INSTRUCTIONS

Model. Roof-Top Air Conditioner CARAVAN MODEL B3200 TYPE INSTALLATION & OPERATING INSTRUCTIONS B3200

PS6500 Storage Arrays Rack Mount Instructions

Installation Instructions S

Roof Top Unit. Description Model Type Use With Air Distribution Box. Heat Pump B Integral Mechanical

Accessory Manual Ventilation Section Model Comfort Circle

T7079A,B Solid State Remote Temperature Controllers

UV100A Ultraviolet Air Treatment System

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:

JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator

SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND

TorqPlus TM Electric Valve Actuators and Controls

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

Ceiling Mount Air Handler Manual

Installation Instructions WARNING: WARNING: WARNING: WARNING: WARNING:

T-4000 Series Room Thermostat Adjusting Instructions*

Owners & Installation Manual for the Sheridan, Mountainair, Pine Valley and Old Forge Ceiling Fan Family

T5000 T000 LCD Digital Fan Coil Thermostat

ATS Overhead Table Shelf System INSTRUCTION MANUAL

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER

Commercial Gas Furnace Upflow

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Operation Manual. 150 Watt Halogen Light Source for Endoscopy Model # s ESS-150, ESS-150A ESS-220, ESS-220A

Toroidal Conductivity Sensor

M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators

Operator: Save these instructions for future use!

E-PDD Duct Smoke Detector Installation Sheet

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS

A. Air-Conditioning and Refrigeration Institute: 1. ARI Commercial and Industrial Air Filter Equipment.

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

G670 Intermittent Pilot Ignition Controls

Air Conditioner B B

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

Fuel Injection Pump, Rotary ( )

Application Engineering

DUCT SMOKE DETECTOR D4120

Installation Instructions

DBF 4XL Dryer Booster Fans

T822, TS822 Heating/Cooling Thermostats

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

SIMPLEX UNICAN LOCKS CHANGING THE CODE / COMBINATION 900 Series 1000 Series L1000 Series LP1000 Series EE1000 Series 2000 Series 2015 Series

SECTION HEAT PUMPS

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

SECTION AIR CONDITIONING UNIT

AIR CONDITIONER & HEAT PUMP DIGITAL CONTROL FOR DUCTED SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES.

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

SETTING UP YOUR 6000 SERIES TIME RECORDER

Pressure Switch for gas and air

Router. A. Identify the major parts of the router. B. Complete a written test on safety and operating procedures of the router with 100% accuracy.

Installation & User Instructions

9013 PUMPTROL Commercial Pressure Switches Type F and 9013 Commercial Pressure Switches Type G. January. Catalog

OPERATION & MAINTENANCE MANUAL

FIELDPOINT BUS EXTENDER CABLE

E2 Series Electric Furnaces

Part I - Installation

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS

Transcription:

Document No. 155-021P25 ET 141-5 ET 141 High Limit Control Thermostat Description Application The ET 141 high limit control thermostat is duct mounted and has a rigid bulb, bi-metal rod and tube construction. Normally, the thermostat is used as a high limit control when a "lock-out" type control is desired or required by local code. Often it is located in a return air duct and is wired to shut down air conditioning or ventilating fans when the duct air temperature becomes excessive. Product Number 141-0530 Specifications Switch Action Single-Pole, Single-Throw (SPST) manual reset Scale Range Adjustable from 25 F (-4 C) to 215 F (102 C) Maximum Bulb Temperature 300 F (149 C) Cover Finish Gray baked enamel galvanized steel Shipping Weight 1.8 Ib (0.8 kg) Thermal System Rigid bulb, bi-metal rod and tube construction Dimensions See Figure 3 Agency Certification UL Listed: File MP3487, CCN MBPR CSA Certified: File LR 948, Class 4813 02 Table 1. Electrical Ratings. Locked Rotor Motor Ratings Non-Inductive Amps Amps (LRA) (Full Load Amps) 120 Vac 240 Vac 120 Vac 240 Vac 120 Vac 240 Vac 96 48 16 8 16 16

ET 141 High Limit Control Thermostat Operation and Adjustment The setpoint adjustment knob (see Figure 2) permits adjustment of the setpoint between 25 F and 215 F (-4 C and 101 C). The temperature differential is factory set, non-adjustable, and approximately 20 F (11 C), depending on the rate of temperature change. The standard model includes a knob for setpoint adjustment. Temperature Setpoint Stop The temperature setpoint stop is an integral part of these controls, and is field adjustable. To set the stop, do the following: 1. Set dial temperature at desired stop. 2. Remove control cover. 3. Loosen the stop screw, slide the screw to the front of the control against the plastic stop behind the dial, and tighten the screw (see Figure 2). Sometimes, an exact stop setting is not possible, and the stop must be set to the closest stop corresponding to the required dial setting. Figure 1. Setpoint Stop Screw. Reset Procedure Verify that the temperature has dropped to 20 F (11 C) below setpoint. Press the reset lever to reset the unit (closing the circuit). Figure 2. Page 2

ET 141 High Limit Control Thermostat Technical Instructions Installation 1. Select a mounting location for the thermostat in the duct (or plenum). The location must allow the sensing element to measure the average temperature in the duct. 2. Drill (or cut) a 1-3/8 inch hole in the duct at the selected mounting location (see Figure 3). 3. Using the flange as a template on the duct, mark the location for two #10 1/2" long sheet metal screws. 4. Punch (or drill) both sheet metal screw holes in the duct at the marked locations. 5. Secure the flange to the duct with the two #10 1/2" long sheet metal screws provided. 6. Insert the sensing element and sleeve through the flange installed in Step 5 (and into the duct). 7. Secure the thermostat to the flange by screwing the set screw firmly against the sleeve. Do not over-tighten the set screw. Insert the sensing element as far as possible into the air stream without allowing it to contact any object inside the duct. Provide at least 5-3/4 inch (14 cm) clearance between the sensor and any other objects inside the duct. Figure 3. Installation. Page 3

ET 141 High Limit Control Thermostat Wiring Diagram When the temperature increases to above the setpoint, the circuit opens. When the reset lever is pressed after the sensed temperature decreases to approximately 20F (11C ) below the setpoint, the circuit closes. See Figures 4 and 5 for terminal identification and typical wiring connections. Only use the terminal screws furnished with the thermostat (#8-32 1/4-inch binder head). Use of other screws will void warranty, may damage switch terminals, and result in improper connections Figure 4. Terminal Identification. Figure 5. Typical Wiring Diagram. Checkout Procedure Return Air Applications After installing the thermostat, perform the following procedures. Observe at least three complete operating cycles to verify that all components are functioning properly. If the unit fails to checkout, replace it. 1. After completing the installation and wiring procedures, turn on the power to the circuit. 2. Turn the setpoint knob counterclockwise until the thermostat shuts down the system. The thermostat should lock-out. The setpoint at shutdown should equal the approximate duct air temperature. 3. Turn the setpoint knob clockwise to the desired setpoint. Nothing should happen. 4. Press the reset lever. The system should restart. Page 4

ET 141 High Limit Control Thermostat Technical Instructions Supply Air Applications 1. After completing the installation and wiring procedures, turn on the power to the circuit. 2. Raise the supply air temperature to the setpoint temperature. The supply air temperature can be raised by simulating a fan failure or restricting the return air flow. 3. When the system shuts down, determine the temperature at the thermostat sensing element. The temperature reading should closely approximate the thermostat's setpoint at which the system is shut down. 4. Return the system to normal operation by re-establishing the air flow or by restarting the fan. 5. Press the reset lever. The system should restart. Service There is no servicing of this thermostat. Replace if inoperative. Dimensions Figure 6. Dimensions in Inches (Millimeters in Parentheses). Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. 2004 Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089 + 1 847-215-1000 Your feedback is important to us. If you have comments about this document, please send them to sbt_technical.editor.us.sbt@siemens.com Document No. 155-021P25 Printed in the USA Page 5