fischer Test Report Fixing Tests for Wienerberger Porotherm blocks



Similar documents
Injection System VMU. Injection System for non-cracked concrete and brickwork. Threaded Stud VMU-A for concrete and brickwork

HUS-A 6 / HUS-H 6 / HUS-I 6 / HUS-P 6 Screw anchor in precast prestressed hollow core slabs

HORIZONTAL INSTALLATION

HUS-HR, CR Screw anchor, stainless steel

SMART PLUG TYPE BP AND LBP

PART 1 GENERAL 1.1 SECTION INCLUDES

Rockwool Flexi Insulation Application Guide

HUS-HR Stainless steel Concrete Screw A CE conformity. Corrosion resistance. European Technical Approval

Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors

The right solutions. However, it is inevitable that with the introduction of any new construction system the question arises How does it compare?

Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

The Stabilizer TM. Benefits. Supplemental support system for sagging beams and floor joists within a crawl space

Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: No.: SE-...

PRESENTATION ON REPAIR AND REHABILITATION OF BUILDINGS DAMAGED IN EARTHQUAKE. By H P Gupta & D K Gupta

TZ WEDGE ANCHOR FOR CRACKED AND UNCRACKED CONCRETE

Permanent Stainless Steel Anchorage Point for Concrete, Solid Masonry and Steel Constructions

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

12.1 Schlüter -KERDI-BOARD

Removable Aluminium posts

Connection Solutions

7Čå.e.279(1Ì HEAVY DUTY ANCHOR

Bonded Anchors & Mechanical Anchors

March 14, Installation of Bay, Bow and Garden Windows


PART E SPECIFICATIONS

PC-Concrete Injectable Concrete Anchoring and Repair System

SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS

HUS-HR, CR Screw anchor, stainless steel

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

(English language translation, the original version is in French language) SPIT HIT M. Société SPIT Route de Lyon F BOURG-LES-VALENCE France

HUS-V Screw anchor. HUS-V Screw anchor. Basic loading data (for a single anchor) Mean ultimate resistance

Flamco Stainless steel mountings

Window Installation Instructions

Samuel Shorty Bunk Bed

Hilti, Inc South 122 nd East Avenue Tulsa, OK

Ermächtigt u n d n o t i f i z i e r t gemäß Artikel 10 der Richtlinie des Rates vom 21. Dezember 1988 zur Angleichung

172 Holesaws Overview Bosch Accessories for Power Tools 09/ Diamond holesaw. with Power-Change adapter. 190 Diamond drill bits

High-performance, 2-part epoxy anchoring adhesive

Hilti HIT-HY 200 with rebar

Policy on Water Heater Installations Policy No. UPC Effective: September 1, 1995 Revised: February 10, 1996

HVU with HAS/HAS-E rod adhesive anchor

European Technical Approval ETA-13/0235

CONCEALED BEARING HINGES. StANLEy ARCHItECtuRAL HARDwARE

Poro Lintel System Range Unique to the Porotherm & thin joint masonary systems

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S

Panel Track Installation Guide

Europeiskt Tekniskt Godkännande European Technical Approval

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength.

Batibox TM flush-mounting boxes for dry partitions

Tundra Series Windows January 2016

Introduction...COMB-2 Design Considerations and Examples...COMB-3

GENERAL SHIELDING REQUIREMENTS FOR DIAGNOSTIC X-RAY FACILITIES. Major Medical (Radio/Fluoro/CT/Cardiac/Chiropractic)

first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel

Installation Manuals Version n. 01 of 14/06/2013

LK Wallbox UNI Push. Assembly. Only intended for LK PE-X Universal Pipe X.

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Guidelines for Earthquake Bracing of Residential Water Heaters

2.18 INTERIOR & EXTERIOR FINISHES VAPOR & AIR BARRIERS

Eurocode 4: Design of composite steel and concrete structures

Report on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

AMF112 Instruction Manual

Hilti HIT-HY 150 MAX with rebar

Discussion on Products under the Scope of EN and proposed CEN/TR to clarify the scope

SECTION COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

Timber Frame Construction

Rollers. from the UK s largest roller manufacturer. Quality Performance Reliability

Chapter 36 - STRAW BALE CONSTRUCTION SECTION PURPOSE. SECTION SCOPE. SECTION DEFINITIONS.

Structural Bolting. Notice the Grade 5 has a much smaller head configuration and a shorter shank then the A325 structural bolt. Rev.

DIY GUIDE 10 EASY STEPS FOR TREATMENT OF RISING DAMP

Light Steel Modular Construction

Installation Instructions

Awning Instructions. Standard Manual 1.5m to 4.5m

PERIMETER FLASHING. Table of Contents

Guidelines for Earthquake Bracing Residential Water Heaters

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona

AMF112 ( <00>) 13mm (1/2 in.)

Residential Deck Safety, Construction, and Repair

Protecting Your Home from Wind Damage

Architectural Nylon. Architectural. Nylon

SECTION 6. Glass Storefront Doors:

ELECTRIC PERISTALTIC MORTAR POINTING PUMP

Site Survey Questionnaire

Cannon T4 Modular Data Centres. For Outside Deployment & Challenging Environments

SAN25 ( <00>)

WHI 90-Minute Rated Veneered Door Frame Installation Instructions

City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures

Installation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details

The Effects of Hole Cleaning on Post-Installed Anchor Systems in Concrete

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...

SWIM N DUNK CHALLENGE RESIDENTIAL BASKETBALL GAMES And COMMERCIAL ASSEMBLY AND INSTALLATION INSTRUCTIONS

ICC-ES Evaluation Report

YTONG Product list.

Veneer Anchors. Masonry Veneer Anchors. Description. Applications

Beautifully Traditional

Diameter. Swift Lift Round Recess Plug. Note: The diameter of the narrow recess plug is the same as the diameter of the round recess plug.

HARDWARE STANLEY ARCHITECTURAL HARDWARE

Transcription:

fischer Test Report Fixing Tests for Wienerberger Porotherm blocks

CONTENTS. Test Parameters... Substrates Tested Wienerberger Porotherm 90 &. Fixings Products Tested... Fischer Nylon UX Plug... Fischer Nylon FUR Frame Fixing... Fischer Nylon SXR Frame Fixing. Fischer FIS V 0 S Hybrid Vinyl Ester Resin with FIS H x8 K Sleeve and M0 Rod.. Test Results... Fischer Nylon UX Plug (UX 8x0 R with gauge wood screw).... Fischer Nylon FUR Frame Fixing... Fischer SXR Frame Fixing. Fischer FIS V 0 S Hybrid Vinyl Ester Resin with FIS x8 K Sleeve and M8 Rod... Conclusion..

. Test Parameters The fixings were tested into both Wienerberger Porotherm 90 & Porotherm Fired clay construction Blocks. The tests were carried out by Laurence Parker fischer Technical Field Engineer on th March 009 Tests were carried out on walls constructed from Porotherm 90 and Porotherm at the Wienerberger Factory complex in the UK. Fixings were fitted in to block ends and randomly into Wall sides to simulate the unpredictability of locating fixings into a plastered surface where the structure of the block cannot be determined. All drilling operations into these blocks should be done without the Hammer action using rotary only. All tests were carried out using a calibrated Hydrajaws 000 tensile meter 0-0 kn Gauge seriel No CF S, conforming to CFA (Construction Fixings Association) guidelines each type of fixing was tested six times.

Fischer/TB th August 009 fischer fixings UK Limited Whitley Road Hithercroft Industrial Estate Wallingford Oxon OX0 9AT For the attention of Mrs Mirka Valovicova. Dear Mrs Valovicova, Testing of Fischer Fixings in Porotherm Vertically Perforated Clay Blocks We confirm that the test as detailed in your document titled Fixing Tests for Wienerberger Porotherm Blocks, were carried out on masonry walls constructed from Porotherm 90 and at our site in Surrey on th March 009. The tests were carried out using a range of fischer products, which were fixed into the block ends and randomly into wall sides. We can confirm that the results are a true record of the tests. Therefore, we can recommend that the fixings described are suitable for use in our vertically perforated clay blocks, up to the safe working loads stated. Yours faithfully, For Wienerberger UK Ltd. Tim Burgess Technical Development Manager Porotherm Wienerberger Ltd., Wienerberger House, Brooks Drive, Cheadle Royal Business Park, Cheadle, Cheshire SK8 SA T + (0) 9 800 F + (0) 9 700 office@wienerberger.com www.wienerberger.co.uk Registered Office: Wienerberger House, Brooks Drive, Cheadle Royal Business Park, Cheadle, Cheshire SK8 SA Registration No. 990

. Substrates Tested Porotherm Porotherm 90 Installation

. Fixing Products Tested. fischer Nylon UX Plug The UX plug is a Universal nylon wall plug suitable for fixing light duty applications in to, plasterboard, solid brickwork, perforated brick ( such as the Porotherm 90 & ), Aerated block & concrete (both solid and Hollow). The range extends from UX to UX for use with wood & chipboard screws from mm to mm. The UX 8 x 0 R (with Rim) for pre-installation was used for the tests into Porotherm blocks with. mm Wood screws. It combines nylon with a -way expansion zone and anti-rotation fins to perform into solid substrates, and a patent knotting system that form locks in hollow section and perforated brick. This results in higher load bearing capacity in perforated substrates where conventional plugs are unable to hold. It was developed as a universal fixing giving good performance into many different substrates. The design of the UX permits "push-through" installation, thereby saving valuable time and energy. A "knock-in" lock effectively prevents the fixing from expanding prematurely. All of these points mean that the fischer UX plug is an ideal light duty fixing for use with Porotherm blocks. Typical Installation; Light duty fixing for general fixings, ie battens, curtain rails, light weight shelving, bathroom cabinates etc. Below UX plug ready for testing

. fischer Nylon FUR Frame Fixing The FUR nylon universal frame fixing is a revolutionary design. Thanks to its asymmetrical teeth in the expansion zone the FUR is suitable for every substrate from low density blocks to concrete. Solid and hollow materials can be fixed to using this product and it is particularly suitable for perforated blocks. The 70mm expansion zone gives good penetration into most blocks ensuring excellent form locking in perforated substrates. The use of the fischer safety screw with the FUR also gives excellent bending moment figures and the smooth outer geometry and stability of the screw facilitate push through assembly. A strong collar prevents expansion of the plug when being tapped into the hole. The FUR range covers 8mm, 0mm & mm frame fixings, in lengths from 80mm 70mm with various head options. For testing purposes the FUR 0 x 80 FUS Hex head with built in washer was used. The FUR is a Medium duty mid range fixing that is available in Zinc plated and A stainless safety screw options for internal and external applications. Typical Applications; Façade fixing (wooden & metal Substructures): Anchorage of laths, wall plates, beams and frames, metal consoles. Supports & rails on inner & outer walls. Form Locking in perforated Blocks, the teeth lock in the voids preventing the fixing from being pulled out...

. fischer Frame Fixing SX R The fischer SXR frame fixing for through-fixing whereby a hole can be drilled through the assembly item and into the substrate. The embedment depth /Expansion zone is 0mm so the fixing is most suited to solid substrates and vertically perforated block with closely spaced webs. The SXR has European Technical Approval for concrete and brickwork as multiple fixing for non-load bearing systems. In addition to this the SXR has a Fire resistance Classification of R 90 for facades. The SXR comes in a range of Ø from -0mm and usable lengths (frame or plate thickness) up to 0mm. Typical Applications; The SXR is a Light - Medium duty fixing and can be used to fix door frames, battens for cladding, shelving and with the A grade screws, external fixtures & fittings Typical Installation diagram; ETA Approvals; ETA approval is available for the SXR Frame fixing in to various Porotherm Blocks. (Please refer to fischer Fixings Technical Department 09 87 90 for further details)

. FIS V 0 S Hybrid Vinyl Ester Resin with FIS H x8 K sleeve and M0 Rod The fischer Injection System FIS V 0 S contains a styrene free, quick-setting, high quality hybrid resin mortar, this combined with the Nylon sleeve gives the system the versatility to be used in perforated block such as Porotherm 90 &. The resin is pushed through the holes in the sleeve which form locks in the voids making an extremely strong fixing which is stronger than the surrounding substrate. It achieves maximum strength values in almost all building materials and anchors safely and without expansion pressure. The components are mixed together inside the static mixer. A simple exchange of the static mixer allows the renewed use of cartridges after they have been opened. Typical Applications: This is a Heavy duty Fixing for Door frames, Wall plates and any application where a recommended load of up to. kn per fixing is required. Installation Detail Suspended Ceiling Grids Building Services

. Test Results Porotherm 90 &. fischer Nylon UX into PTH 90 & PTH using Ø8mm drill hole, embedment depth of 0mm fixed for this plug, screw length will depend on fixture thickness..a fischer Nylon UX 8x0 R with mm wood screw into PTH 90.0 0.9 0. 0.7 0. 0. Block End st Tensile Slip Block end st Tensile Slip Mid Block st Tensile slip Mid Block st Tensile Slip Mid Block st Tensile Slip Mid Block st tensile Slip Average Ultimate Tensile Load = 0.8kN Using a global safety factor of 7, safe working load in tension = 0.0kN.b fischer Nylon UX 8x0 R with mm woodscrew into PHT.0 0.7. 0.7.0 0. Block End st Tensile Slip Block end st Tensile Slip Mid Block st Tensile slip Mid Block st Tensile Slip Mid Block st Tensile Slip Mid Block st tensile Slip Average Ultimate Tensile Load = 0.9kN Using a global safety factor of 7, safe working load in tension = 0.kN

. fischer Nylon FUR Frame fixing in PTH 90 & PTH using Ø0mm drill hole..a fisher FUR 0 x 80 FUS into PTH 90. 0..8...0 Block End st Tensile Slip Average Ultimate Tensile Load =.kn Using a global safety factor of 7, safe working load in tension = 0.7kN.b fischer FUR 0 x 80 FUS into PTH.. 0.8... Block End st Tensile Slip Average Ultimate Tensile Load =.kn Using a global safety factor of 7, safe working load in tension = 0.kN Choice of FUR frame fixing length will depend on the fixture thickness, but all FUR s both 8mm & 0mm require a full 70mm embedment to perform correctly.

fischer SXR Fame Fixing into PTH 90 & PTH with Ø0mm drill hole..a fischer SXR 0 x 00 T into PTH 90.0. 0.8.0 0.9. Block End Substrate Failure Mid Block Substrate Failure Mid Block Substrate Failure Mid Block Substrate Failure Mid Block Substrate Failure Mid Block Substrate Failure Average Ultimate Tensile Load =.0 kn Using a global safety factor of 7, safe working load in tension = 0. kn.b fischer SXR 0 x 00 T into PTH 0.9.0.... Block End Substrate Failure Block End Substrate Failure Block Side Substrate Failure Block Side Substrate Failure Block Side Substrate Failure Block Side Substrate Failure Average Ultimate Tensile Load =. kn Using a global safety factor of 7, safe working load in tension = 0.7 kn Choice of SXR frame fixing length will depend on the fixture thickness, but all SXR s both 8mm & 0mm require a full 0mm embedment to perform correctly.

. fischer FIS V 0 S Resin + Sleeve and M8 Stud in to PTH 90 & PTH.a FIS V 0 S with FIS H x 8 Sleeve + M 8 Stud in to PTH 90.0.. 7.0 9.9.0 Average Ultimate Tensile Load =.7 kn Using a global safety factor of, safe working load in tension =.7 kn.b FIS V 0 S Resin + Sleeve & M 8 Stud into PTH..0 7.0.0.0. Average Ultimate Tensile Load =.7 kn Using a global safety factor of, safe working load in tension =. kn

. Conclusion fischer has a range of fixings suitable for both the Wienerberger Porotherm 90 & perforated fired clay building blocks. From heavy duty fixing requirements to light duty applications, the correct solution can be found. For the most demanding Heavy Duty applications, in both blocks, the Resin anchor FIS V 0 S with FIS H Nylon Sleeve and threaded rod gives the best results with recommended loads of up to.7kn in Porotherm 90 &.kn in Porotherm. For Medium Duty applications up to 0.7kN the FUR and SXR frame fixings are the most suitable. The FUR with an embedment depth of 70mm is generally a more efficient fixing and easier to install where web spacing is 0mm apart, being particularly useful in block ends. The SXR however is a powerful fixing in blocks with web spacing s of between mm and 0mm as in the Porotherm. The UX plug offers a first class light duty fixing for general applications in both blocks. It friction locks in blocks with close spaced webs and knot locks behind st web or outer skin in blocks with larger web spacing s and block ends. Recommended loads in the region of 0.0kN were achieved in both blocks. N.B All drilling operations in these Blocks should be done without Hammer action. Summary Product tested Average Ultimate Load (kn) Porotherm 90 Average Recommended Load (kn) Average Failure Mode UX 8 Plug 0.8 0.0 st Tensile Slip FUR 0. 0. st Tensile Slip SXR 0.0 0. Substrate Failure FISV 0 S + FIS H K.7.7 Product tested Average Ultimate Load (kn) Porotherm Average Recommended Load (kn) Average Failure Mode UX 8 Plug 0.9 0. st Tensile Slip FUR 0. 0. st Tensile Slip SXR 0. 0.7 Substrate Failure FIS V 0 S + FIS H K.7.