Supercritical boiler technology for future market conditions

Similar documents
Best Choice BENSON BOILER. Excellent performance features make the Benson boiler the most widely used type of once-through boiler

BENSON Boilers for Maximum Cost-Effectiveness in Power Plants

Design and Operating Experience of the Latest 1,000-MW Coal-Fired Boiler

Power Plants. BENSON Once-Through Heat Recovery Steam Generator. Power Generation

CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2

912 MW Supercritical Boiler for the next Coal Fired Plant Generation

Boiler Calculations. Helsinki University of Technology Department of Mechanical Engineering. Sebastian Teir, Antto Kulla

RELIABLE AND EFFICIENT STEAM GENERATION SYSTEMS FOR MODERN UTILITY SERVICE

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES

NAWTEC CONCEPTS AND EXPERIENCES FOR HIGHER PLANT EFFICIENCY WITH MODERN ADVANCED BOILER AND INCINERATION TECHNOLOGY

Progress on High Efficiency Coal Power Plants

Heat Exchangers in Boilers

Efficiency on a large scale CFB Steam Boilers

1. A belt pulley is 3 ft. in diameter and rotates at 250 rpm. The belt which is 5 ins. wide makes an angle of contact of 190 over the pulley.

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS

PERFORMANCE EVALUATION OF NGCC AND COAL-FIRED STEAM POWER PLANTS WITH INTEGRATED CCS AND ORC SYSTEMS

HYBRID COMBINED CYCLE POWER PLANT

Operational Flexibility Enhancements of Combined Cycle Power Plants. Dr. Norbert Henkel, Erich Schmid and Edwin Gobrecht

MODERN STEAM GENERATORS

Steam Power Plants as Partners for Renewable Energy Systems

Design and Test Operation Performance of 1,500 C Class Gas Turbine Combined-Cycle Power Plant:

HYBRID WAY EAF OFF GAS HEAT RECOVERY -ECORECS- MASANARI YAMAZAKI*1, YASUHIRO SATO*2, RYUTARO SEKI*3

Thermodynamical aspects of the passage to hybrid nuclear power plants

5. State the function of pulveriser. The pulverisers are the equipments which are used to powdered coal.

High-performance steam boiler and hot water boiler plants for industry

OROT RABIN POWER STATION UNITS x 350 MW

OPPORTUNITIES FOR HEAT RATE REDUCTIONS IN EXISTING COAL- FIRED POWER PLANTS: A STRATEGY TO REDUCE CARBON CAPTURE COSTS

SRS: THE STANDARDIZED REPOWERING SOLUTION FOR 300MW STEAM POWER PLANTS IN RUSSIA. Matthias Fränkle Siemens Power Generation (PG), Germany

I. STEAM GENERATION, BOILER TYPES

Natural Gas Conversions of Existing Coal-Fired Boilers

BIOMASS LOOKING FOR EFFICIENT UTILIZATION THE REHEAT CONCEPT. Jaroslav Lahoda Olaf Arndt Walter Hanstein. Siemens Power Generation (PG)

Committed to make a better world

Basics of Steam Generation

INTEC Engineering GmbH Heating Solutions for the Marine Industry

Webpage: Volume 3, Issue IV, April 2015 ISSN

Overview of Integrated Coal Gasification Combined-cycle Technology Using Low-rank Coal

GAS COOLING SYSTEMS FOR STEAM REFORMING PLANTS

Drying of Woody Biomass. Process Engineering / GEA Barr-Rosin

Advanced Steam Parameters in a Large Scale CFB Application Operating on REF and Biofuels background and experiences

Babcock & Wilcox Company Supercritical (Once Through) Boiler Technology

A MAJOR STEP FORWARD---THE SUPERCRITICAL CFB BOILER

Modern boiler design. by Flemming Skovgaard Nielsen, BWE Paolo Danesi, BWE M.V.Radhakrishnan, BWE Energy India

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

Pulverized Coal Pipe Testing and Balancing

Syngas Furnace Tubeskin Temperature Measurement

International Journal of Engineering Research and Development

A Review on Power Generation in Thermal Power Plant for Maximum Efficiency

The soot and scale problems

North American Stainless

POLYCITY. Technical measures and experiences at a 6 MW cogeneration plant with wood chip furnace POLYCITY

Boiler Preparation, Start-Up and Shutdown

AIR CONDITIONING TECHNOLOGY

Tutkimuksen merkitys menestyvässä liiketoiminnassa- Innovaatiosta tuotteeksi

Tips for burner modulation, air/fuel cross-limiting, excess-air regulation, oxygen trim and total heat control

5.2. Vaporizers - Types and Usage

COGENERATION. This section briefly describes the main features of the cogeneration system or a Combined Heat & Power (CHP) system. 36 Units.

Steam/Water Circulation Design

Steam Turbine Concepts for the Future Volatile Power Market

Care and Maintenance of Circulating Fluidized Bed Boilers Refractory Failure

Performance of the Boiler and To Improving the Boiler Efficiency Using Cfd Modeling

North American Stainless

Steam turbines for solar thermal power plants. Industrial steam turbines. Answers for energy.

Fast cycling and rapid start-up: new generation of plants achieves impressive results

Investigating the Impact of Boiler Aging In Replacement Decisions

ASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

GENERAL PROPERTIES //////////////////////////////////////////////////////

Study of a Supercritical CO2 Power Cycle Application in a Cogeneration Power Plant

Torino Nord. Cogeneration Plant. The gas turbine. The steam generator. The Torino Nord cogeneration plant produces electricity and heat for district

GE Oil & Gas. Air Cooled Heat Exchangers. Robust and reliable for all loads and applications

High Efficiency Low Emissions: The first way forward for clean coal technology. Dr Andrew Minchener OBE General Manager IEA Clean Coal Centre

HOW TO SELECT A LOW VOLUME (L.V ) BOILER

Operating Performance and Latest Technology of DeNOx Plants for Coal-Fired Boilers

Review of Potential Efficiency Improvements at Coal-Fired Power Plants

HEAT TREATMENT OF STEEL

ENERGY EFFICIENCY IN POWER PLANTS

Condensing Boiler Efficiency

High-efficient gas boiler CompactGas

R&D on Oil-Burning, Environment-Friendly, High-Efficiency Boiler

Steam Generator Boilers Compact Steam Boilers. Rapid Start-Up Safe in Operation

Building Energy Systems. - HVAC: Heating, Distribution -

Originators of the Flexible Water Tube design

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE

New-generation Integrated Monitoring and Control System

INSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9

Optimization Design for Sulfur Dioxide Flow Monitoring Apparatus in Thermal Power Plants Hao-wei Hu 1, a, Xue Yang 1, b and Xiao-wei Song 1, c

Vogt Power Emission Control Solutions

ANCILLARY SERVICES SUPPLIED TO THE GRID: THE CASE OF THISVI CCGT POWER PLANT (GREECE)

UNIT 2 REFRIGERATION CYCLE

VAD Variable Area Desuperheaters

ODS Alloys in Coal-Fired Heat Exchangers Prototypes and Testing

North American Stainless

ADVANCED BOILER DESIGN

Waste Heat Recovery through Air Conditioning System

Condensing Economizers Workshop Enbridge Gas, Toronto. MENEX Boiler Plant Heat Recovery Technologies. Prepared by: Jozo Martinovic, M A Sc, P Eng

Hybrid Modeling and Control of a Power Plant using State Flow Technique with Application

The Technology and Business of Power Andrew Valencia, P.E. Lower Colorado River Authority

BOILER OPERATORS HANDBOOK

EFFICIENT ENERGY SUPPLY (ELECTRICITY AND DISTRICT HEAT) FOR THE CITY OF LINZ

Transcription:

Supercritical boiler technology for future market conditions Joachim Franke and Rudolf Kral Siemens Power Generation Presented at Parsons Conference 2003 Oct. 2003 H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 1 of 13

1 Introduction The requirements for environmental protection and operating economy in future steam power plants make high efficiency levels and operating flexibility a matter of course not only in the EU but also in increasing measure around the world. Existing technologies have currently enabled fulfillment of these requirements by pulverized-coal-fired power plants and in part also by power plants with circulating fluidized bed (CFB) combustion systems. 2 State of the art Power plants operating at supercritical pressure and high steam temperatures were already being constructed in the 1950s (Fig.1). The 1960s saw a series of supercritical plants in the U.S. (such as those equipped with the universal pressure boiler) and in the last twenty years supercritical plants were used exclusively in Germany and Japan. The latter were designed for sliding-pressure operation and thus also fulfill the requirements for high operating flexibility and high plant efficiencies at part load. (Fig.2). Plant Comission Date Chemische Werke Hüls 1956 Philo Nr. 6 1957 Eddystone Nr. 1 1959 Higher efficiencies can be achieved only along the path of higher steam temperatures and pressures. To date, CFB power plants have been used especially for smaller power output levels, generally with drum boilers. Plants up to 350 MW are in the meantime already in operation and several plants equipped with Benson 1 boilers have also been constructed. Supercritical plants for ratings above 400 MW are planned. Electrical Output MW 85 125 Steam Flow t/h 260 306 Main Steam bar/ C 304 / 600 321 / 621 Reheater 1 bar/ C 109 / 560 82 / 565 Reheater 2 bar/ C 32 / 560 13 / 537 Figure 1: World s first supercritical Power Plants 325 907 357 / 649 76 / 565 19 / 565 Power plants operating at supercritical steam pressure have already demonstrated their operational capabilities and high availability over decades. The transition to steam temperatures of 600 C and higher is now a further major development step, which decisively affects many aspects of the design of the power plant, especially of the boiler. Whether the transition to these high steam temperatures is economical also depends not only on the choice of main steam pressure, reheat pressure and feedwater temperature, but also on the range of fuel. 1 Benson is a registered trademark of Siemens AG H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 2 of 13

To date, the focus was on material development for the superheaters and the thick-walled components for high steam temperatures. However, investigations indicate that the wall heating surfaces can become the limiting components for further increases in steam parameters. One reason for this is the increasing fraction of superheater heat to be transferred with increasing steam parameters. Power Plant Avedorevaerket 2 Boxberg Skaerbaekvaerket Lippendorf Nordjyllandsvaerket Aghios Dimitrios Schkopau Neckar 2 Rostock Hemweg Meri Pori Staudinger 5 Fynsvaerket Tachibanawan Tachibanawan 1 Haramachi 2 Matsuura 2 Nanao Ota Shinchi Noshiro Hekinan 2 Shin Miyazu Output [MW] 415 915 410 2 x 930 410 350 2 x480 340 550 660 550 550 430 1050 700 1000 1000 500 1000 600 700 450 Design Pre ssure *) [bar] 332 310 310 242 261 240 275 275 280 275 275 275 293 275 270 Steam Temperature Boiler Outlet [ C] 582 / 600 545 / 580 582 / 580 / 580 554 / 583 582 / 580 / 580 540 / 540 545 / 562 545 / 568 545 / 562 540 / 540 540 / 540 545 / 562 540 / 540 605 / 613 570 / 595 604 / 602 598 / 596 570 / 595 542 / 567 542 / 567 543 / 569 541 / 569 Year of Commisioning 2001 2000 1999 1999 1998 1998 1997 1997 1994 1994 1994 1992 1992 2001 2000 1998 1997 1995 1994 1993 1992 1991 Figure 2: Large Supercritical BENSON Boilers in Europe and Japan - References Europe Japan *) max. allow able working pressure at boiler outlet 3 Effect on design - Size of heat exchange surfaces Higher steam temperatures automatically diminish the temperature differences between the flue gas and steam, with relatively large superheater and reheater heating surfaces as a consequence. As higher tube wall temperatures also mean an increased tendency to fouling, corresponding heating surface reserves must be provided. Feedwater temperature has a large effect on the size of the heating surfaces in the cooler flue-gas path. Values of 290 C to 300 C or higher are necessary for high-efficiency plants. As on the one hand the flue-gas temperature downstream of the economizer is set in the design case at roughly 400 C the temperature window for DeNOx and on the other hand the water outlet temperature from the economizer is limited to avoid steaming, the upstream superheaters must absorb more heat with increasing feedwater temperature. At higher steam conditions, especially at increasing reheat pressures, the exhaust steam temperatures from the HP section of the turbine and thus the reheat inlet temperatures also increase. While these temperatures are still approx. 320 C at a design main steam temperature of 540 C, they already increase to over 350 C in a 600 C main steam temperature design and even up to over 420 C in a 700 C design. This considerably decreases the temperature difference to the flue gas, with the consequence of still larger heating surfaces in the reheaters. Under consideration of a cost-effective heating surface design, feedwater temperatures should not exceed 300 C, and HP exhaust steam pressures should lie in the range of 60 bar. H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 3 of 13

- End of evaporation The location of the separator determines the location of the end of the evaporator on startup and at low load in recirculation mode. Usually the separator is configured such that its temperature is slightly superheated at the lowest once-through load point. Design of the boiler for high steam temperatures and pressures leads to this being already the case in lower areas of the furnace walls instead of as from the outlet first pass or in the boiler roof. The reason for this is the increasing degree of superheat and correspondingly decreasing fraction of evaporation in the heat input to the HP section with increasing steam parameters. At a load of 40%, the degree of superheat in a 540 C boiler is approx. 27%, and this increases to 39%, for example, in a design for 700 C main steam temperature (Fig. 3 and Fig. 4). As the highly Q [%] 100 90 80 70 60 50 40 30 20 10 27 58 15 0 1 2 3 Steam conditions T HP/RH 540 / 560 C 600 / 620 C 700 / 720 C p HP 250 bar 290 bar 350 bar M HP 600 kg/s 543 kg/s 476 kg/s 32 53 15 39 46 15 HP HP Superheating Preheating and Evaporation RH RH Superheating loaded heating surface area must lie upstream of the separators for reasons of evaporator cooling and the separator thus cannot be moved arbitrarily toward the burners, a significantly larger degree of superheat will result at the lowest once-through operating point (Fig.5). This considerably increases the downward step of the steam temperatures on the transition to recirculation mode. In order to extensively prevent this temperature change, the transition from once-through to recirculation mode must be placed at a very low load point, requiring recirculation mode only for startup. Whereas for boilers with spiral wound tubing the minimum load in once through operation is in the range of 30% to 40%, an evaporator based on the "Benson Low Mass Flux"[1] design with vertical rifled tubes enables loads to below 20%. Furnace Design and Size is given by Coal and Ash Quality Figure 3: Heat Flow Distribution in Variable Pressure Operation at 40% Load H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 4 of 13

3000 FEGT = IDT - 50 K FEGT = Furnace exit gas temperature IDT = Initial deformation temperature of ash kj/kg 2600 2200 1800 Furnace Design and Size is given by Coal and Ash Quality h Evaporation at 40% Load (sliding pressure) 1000 Corresponding full load steam pressure: 350 bar 290 bar 250 bar 190 bar 0 100 200 bar Zones of Evaporation (at Part Load) Full Load Steam Conditions 190 bar / 535 C / 535 C Full Load Steam Conditions 250 bar / 540 C / 560 C Full Load Steam Conditions 290 bar / 600 C / 620 C Full Load Steam Conditions 350 bar / 700 C / 720 C Figure 4: Increasing steam conditions lead to different evaporator designs H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 5 of 13

4000 T [ C] 800 3900 3800 Superheater Outlet 703 C / 358 bar 476 kg/s 750 3700 3600 3500 3400 3300 3200 3100 3000 Reheater Water Wall Outlet Roof 540 C 200 bar 544 C / 261 bar 600 kg/s 603 C / 300 bar 543 kg/s Water Wall Outlet 700 650 600 550 2900 2800 2700 2600 100% Load Nose Roof Nose 500 2500 450 2400 2300 h [kj/kg] 2200 2100 2000 1900 400 1800 1700 1600 1500 Evaporator Inlet Evaporator Inlet 350 1400 1300 300 1200 1100 1000 Economiser Inlet 100% Load 250 900 200 800 700 600 Economiser Inlet 40% Load 150 500 400 0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 p [bar] Figure 5: Water and Steam Temperatures in the h-p Diagram 100 Water walls The water walls in boilers for subcritical steam conditions are generally configured as evaporators. At increasing steam temperatures and pressures, the fraction of evaporator heating surfaces decreases, with the result that parts of the water walls must also be configured as superheaters, i.e. downstream of the separator. In the highly loaded furnace area, spiral-wound evaporator tubing is usually used with smooth tubes and high mass fluxes approx. 2000 2500 kg/m³s. As spiral-wound furnace tubing of this type is not self-supporting, it is reinforced with support straps which are welded to the tube wall with support blocks. High steam parameters also lead to higher material loading in the evaporator. The previously existing design reserves are no longer available, with the result that a detailed stress analysis is required for the design of the evaporator tubing in each case. As a result of the requisite large wall thicknesses, the design of highly loaded heating surface areas is in part no longer determined by the primary stresses due to internal pressure but rather by the secondary stresses due to re- H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 6 of 13

strained thermal expansion. The higher evaporator temperatures also result in increasing temperature differences between the tubes and support straps on startup and shutdown. This in turn leads to longer startup times, especially on cold start. The "Benson Low Mass Flux" design Low mass flux design with natural developed by circulation characteristic SIEMENS with design mass fluxes Simple, cost-effective manufacture and of approx. 1000 assembly of water walls kg/m²s and below and with vertical rifled evaporator Simpler maintenance e. g. for tube damage tubes requires no additional support No stresses due to thermal expansion structure and thus because welded-on support straps also does not impair are eliminated plant flexibility in spite of wall outlet temperatures of approx. Reduced auxiliary power consumption Reduced slagging 500 C and above.(fig.6). In a design for main steam temperatures Figure 6: Vertically-Tubed Furnace for BENSON Boilers Principle and Characteristics of 600 C and above, the creep strengths of the wall materials commonly used to date such as 13CrMo44 (T12) are no longer sufficient, necessitating the transition to new developments such as 7CrMoVTiB1010 (T24) or HCM2S (T23). This is already the case at steam pressures of 300 bar and above for lower design temperatures. Looking at primary stresses the creep strengths of these materials, which require no post-welding heat treatment, permit steam temperatures up to 530 C in the furnace walls depending on main steam pressure, but the corrosion resistance and secondary stresses limit these values down to 500 C. Main steam temperatures of 630 C at moderate steam pressures are thus achievable as regards the walls. At higher steam temperatures, materials such as HCM12 or T92 are required which must be heattreated after welding. In order to minimize the manufacturing expenditure in such a design, the erection welds on evaporator tubes must be reduced to the absolute minimum possible. This is currently feasible only with vertical tubing. The relatively complex welds in the corners for spiralwound furnace tubing are eliminated and the individual wall segments are welded together only at the fins. Welding of tubes may become necessary only in the horizontal plane. Solutions are also available for this which minimize expenditure on heat treatment on erection. In all cases, it can be stated that the problems in the design of the water walls increase disproportionately with increasing steam pressures. A reduction of main steam pressure from 350 bar to 250 bar reduces the efficiency of a 700 C plant by 0.7 percentage points but it also reduces the wall outlet temperature from 540 C to 500 C and makes a design with materials without post weld heat treatment possible. Main steam pressures far above 250 bar should therefore be avoided, also in plants with high steam temperatures. H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 7 of 13

- Evaporator/superheater dividing point At high steam parameters the water walls can no longer be designed entirely as an evaporator. The transition from evaporator walls to superheater walls then lies above the furnace. This transition must be designed so as to minimize the temperature differences between the evaporator and superheater sections of the walls which automatically result on water filling after shutdown, especially on water filling after an emergency shut down. Values of up to 80 K represent no cause for concern. For higher values such as can occur at very high steam conditions as well as in large furnaces, a flexible connection, not necessarily welded gas-tight, should also be taken into consideration for this transition. - Superheater heating surfaces For steam temperatures up to approx. 550 C, all heating surfaces can be constructed of ferritic or martensitic materials, while at 600 C austenitic materials are necessary for the final superheater heating surfaces for both the HP section of the boiler as well as the reheater. In addition to the strength parameters, corrosion behavior on the flue-gas and oxidation behavior on the steam sides is especially determinative for material selection. Fig.7, Superheater materials for high temperatures, shows a selection of available materials. With regard to strength parameters, construction of superheater heating surfaces for steam temperatures up to 650 C is currently already feasible with austenitic steel materials. The corrosion resistance of the available materials however reduces the design limits to about 630 C. Maximum HP Steam Temperature limited by Creep Rupture Strength* Corrosion Approved by X3CrNiMoN1713 595 580 EN AC66 605 620 VdTÜV Esshete 615 580 VdTÜV / BS TP 347 H (FG) 620 600 VdTÜV / ASME MITI Super 304H (FG) 635 600 ASME / MITI NF 709 HR 3C Save 25 645 620 630 630 655 630 MITI VdTÜV / ASME MITI under development / MITI Alloy 617 A130 685 720 under development * 100 MPa at Steam Temperature +35K Figure 7: Available Superheater Tube Materials H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 8 of 13

- Thick-walled components In the first steam generators with very high steam temperatures, austenitic materials were used for the hot headers and connecting lines. However, the poor thermoelastic behavior low thermal conductivity, high thermal expansion render these materials unsuitable for boilers which are implemented in power plants with a large number of load changes and minimum startup times. The development of chromium steels such as P91, P92 or E911 has enabled steam temperatures up to 620 C without the use of austenitic materials for thick-walled components. More recent developments such as NF12 and Save 12 could extend the limits of implementation at moderate main steam pressures up to 650 C in the near future. With regard to the thick-walled components, especially for the main steam headers, it proves that the main steam pressures should more likely lie below 300 bar for optimum component utilization (Fig.8) [2]. Main steam pressure upstream of turbine [bar] 360 320 280 240 200 540 X 20 P 91 Ferritic E 911/ NF 616 NF 12 Austenitic TP 347H FG Ni-based material 560 580 600 620 640 660 680 700 720 Figure 8: Optimum Main Steam Conditions with given Main Steam Header Dimensions Alloy 617 Main steam temperature upstream of turbine [ C] - Effect on operation Power plants which are designed for fast load changes and short and frequent starts must necessarily be operated in sliding-pressure mode. Only then does the material loading of the turbine remain acceptable: in sliding-pressure operation usually between full load and 40% load - the temperature curve in the turbine remains nearly constant over the entire load range. These advantages for the turbine contrast with disadvantages for the boiler. For example, the temperatures in the water walls decrease from full load to part load by approx. 100 K. Due to their magnitude and the ordinarily larger wall thicknesses at the elevated steam parameters, the temperature changes during start up and load variations place increased requirements on the design of the thick-walled components such as multiple parallel passes, but also on the design of the tube walls, such as vertical tubing, in order to achieve similar startup times and load change rates to those in plants with conventional steam parameters. With increasing steam parameters, the degree of superheat at the outlet of the evaporator sections of the water walls at the lowest once-through load point also increases. A high degree of superheat H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 9 of 13

leads to a temperature reduction at the evaporator end and in the superheaters in the transition to recirculation mode. The separators are therefore moved as far as possible toward the burner zone. Operating measures to reduce the degree of superheat are increased excess air, flue-gas recirculation and use of the uppermost burner levels. The higher the steam temperatures and pressures become, the more important is the lowest possible load point in once-through operation, so that the once-through/recirculation mode transition need be traversed only on startup. The large degree of superheat in the separator at the lowest once-through operating point also results in changes in startup behavior at high steam parameters. On warm and hot startup in recirculation mode, the achievable hot steam temperatures are below the values required by the turbine. The earliest possible transition to once-through operation is necessary in order to shorten startup time, as full main steam temperatures are also already possible at low load in this operating mode. High feedwater temperatures can restrict the sliding-pressure range in plants with very high main steam pressures. In order to prevent the economizer from approaching the evaporation point at low load, the pressure must be already fixed below 50% load or still higher depending on the design. Evaporator outlet temperature Increasing steam parameters also decrease the design reserves of nearly all pressure part components, as, not least for reasons of cost, the decision for advanced materials is not made until the reserves of lower quality materials become insufficient. This also increases the requirements on control quality: temperature deviations from the design value, such as on load changes, must be kept to a minimum. The conventional cascade controller is no longer sufficient for superheat temperature control; concepts such as two-loop feedback control or observer Previous feedwater 470 control concept features provide New feedwater significantly better 460 control concept control quality. with allowance for 450 - inlet enthalpy Special attention - storage of thermal must be given to energy feedwater control. 440 Conventional systems which employ 430 only simple delay modules to account for the dynamic 420 differences between heat release 410 by the fuel and heat absorption by the evaporator 400 tubes usually lead 0 250 500 750 1000 1250 s 1500 to large temperature fluctuations at Time Figure 9: Comparison of Feedwater Control Concepts the evaporator outlet on load Load reduction from 100% to 50% changes. New control concepts which account for effects such as those of changes in the evaporator inlet tempera- H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 10 of 13

ture or the thermal storage capacity of the tube wall in the form feed forward control (Fig.9) increase control quality decisively and thus minimize the use of more expensive, higher-quality materials. For high degrees of superheat at the lowest once-through load point, the transition from recirculation mode to once-through operation and back can no longer take place without delay due to the relatively large temperature change; the control must be adapted accordingly for a sliding transition. 4 Other effects Design of the tube walls in particular is impeded by the high steam temperatures and pressures. The design parameters should be selected as best as possible so as not to necessitate the use of materials for which heat treatment must be performed after welding. A significant aspect for this is selection of the fuel. Coals with low ash deformation temperatures require large furnaces, associated with high heat input to the walls. A 100K lower ash deformation temperature leads in a comparable boiler concept to a temperature increase at the wall outlet of about 25K. Because of this for the currently available wall ma- Wall exit temperature C terials without post-welding heat treatment, the ash deformation temperature for a 600 C boiler may not be much lower than 1200 (Fig.10). The implementation of flue-gas recirculation extraction of the flue gases if possible upstream of the air heater in order to reduce the negative effect on exhaust-gas temperature can shift the limits to higher steam parameters. 600 500 400 A617 P92 7CrMoVTiB1010 13CrMo44 1100 1200 1300 Ash deformation temperature C Figure 10: Design Limits for Water Wall Materials T FD = 700 C p FD = 350 bar T FD = 600 C p FD = 300 bar T FD = 540 C p FD = 250 bar Steam generators for power plants with high steam parameters and hence high plant efficiencies are consequently also designed for high boiler efficiencies. The lowest possible exhaust-gas temperatures 115 C to 110 C can be achieved depending on the coal and lower excess air are prerequisites for this. Both of these factors lead to an increased heat input to the evaporator and thus impede the design of the wall heating surfaces. H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 11 of 13

The high tube wall temperatures of the superheater heating surfaces as well as lower excess air and low-nox firing systems increase the corrosion problem. For the selection of supeheater materials the resistance to scale formation from the flue-gas atmosphere and steam is therefore just as important as creep resistance. 4.1 Special aspects for CFB The advantages of CFB technology are uncontested for low-grade fuels or for fuels with widely fluctuating quality as well as for low exhaust-gas emissions without post-combustion control measures. CFB plants up to capacities of 350 MWe are currently in operation. However, only oncethrough operation with high steam conditions render CFB technology serious competition for pulverized-coal firing. A plant for approx. 460 MWe with steam parameters of 560 C/580 C and 265 bar was developed in an EU research program. The BENSON "Low Mass Flux" design was selected as the evaporator concept. It fulfills the requirements of a fluidized bed to a special degree: the tube orientation parallel to the flue gas/ash flow ensures low susceptibility to erosion, and temperature variations between the evaporator tubes are extensively prevented, as non-uniform heat inputs are evened out by the natural circulation flow characteristic of the low mass flux design. It also features an especially simple construction, as flow through all of the tubes in a single pass is parallel, thus eliminating the need for elaborate water/steam distribution. The suitability of this evaporator system for sliding-pressure operation also fulfills all requirements for a power plant with regard to operating flexibility. 4.2 Combined-cycle plants Heat-recovery steam generators downstream of gas turbines are usually designed as drum boilers. Increasing exhaust-gas temperatures downstream of gas turbines as well as the increasing requirements on flexibility of a combined-cycle plant with frequent starts also make the use of once-through systems interesting here. Elimination of the drum on the one hand increases operating flexibility and on the other hand is a noticeable cost aspect. In the Cottam combined-cycle plant, a heat-recovery steam generator with a once-through evaporator based on the Benson "Low Mass Flux" design was constructed for the first time and runs successfully in commercial operation since Sept.1999. This evaporator concept is characterized by extremely low mass fluxes which still lie far below those of fired boilers. H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 12 of 13

5 Summary and outlook Steam temperatures of 600 C to 620 C are currently possible as a result of efforts in materials development. However, not only are new materials necessary for higher temperature ranges, but further development was also necessary for the wall materials. On further temperature increases, previous design concepts can no longer be adopted without modifications. New designs are necessary for the evaporator in particular in order to give boilers for high-temperature plants similar flexibility to that of previous once-through boilers. The Low Mass Flux Design provides an evaporator concept which meets the new requirements and which permits further development to higher steam parameters for pulverized-coal-fired boilers and for boilers with circulating fluidized bed firing as well as for heat-recovery steam generators downstream of gas turbines. A further increase in steam temperatures appears possible in the next years with continuous materials development, but without using nickel based materials not more than 10K to 20K. From the current standpoint, the jump to 700 C will not take place until the next decade. However, from an economic perspective, the high steam temperatures will only be selected given correspondingly competitive materials prices and if, among other things, the appropriate main steam and reheat pressures are selected and the fuel ranges are limited. References [1] J. Franke and R. Kral Innovative Boiler Design to Reduce Capital Cost and Construction Time Power-Gen 2002 [2] J. Franke, R. Kral and E. Wittchow Steam Generators for the Next Generation of Power Plants VGB Power Tech 12/99 H30-K0018-X-X-7600 Textseite, engl. 2001-09 D97 H:\BENSON\Homepage\Parsons_2003.doc Page 13 of 13