1. Description Sanicom is a lifting pump for wastewater used in commercial applications (restaurants, hairdressing salons, the catering industry etc.). The unit operates automatically, has a high performance level, and is safe and reliable, provided all the rules for installation and maintenance in this notice are strictly followed. Especially those indicated by: Failure to comply with this instruction could endanger the safety of persons Indication that a risk of electrical origin exists Electrical installation must be carried out by a professional electrician. Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk Attention Failure to comply with this instruction could endanger the safe functioning of the apparatus. For any additional information, please contact our customer service department. 2. List of Accessories included x2 x1 x2 x2 A B C D 25 x 40 32 x 50 50 x 70 Flexible inlet connector Hose clip Hose clip Hose clip x1 x1 x2 x2 E F G H 40 x 60 Inlet Cover Hose clip Screw Plug I x1 Elbow
3. Dimensions and overall measurements 420mm 230mm 330mm ø 60 490mm 4. How it works The Sanicom contains 1 pump. The tank is equipped with a sensor tube which controls the automatic activation of the motor when waste enters the unit. As soon as the waste enters the tank, the pump starts. 5. Performance Curve & Height and Length of the discharge pipe Vertical Height - Metres 12 11 10 9 8 7 6 5 4 3 2 1 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 Flow Rate - litre/min Max 8m max 10m 7m max 20m 1% 6m max 30m 3 7 5m 4m 3m 2m 1m max 40m max 50m max 60m max 70m max 80m
6. Technical Data & Application Application Type Maximum vertical pumping height Voltage Frequency Maximum power consumption Maximum current consumption Electrical class Protection index Commercial sink, washing machine, dishwasher or shower* or bath* FF03-P95 8m 220 240 V 50 Hz 750 W 3.3 A I IP44 Max temp with intermittent functioning 80 Net weight 10 kg * In the case of bath or shower tray, make sure the waste traps are raised 15cm above floor level. CAUTION: 1. All applications other than those described in this notice are prohibited. 2. Do not exceed an incoming flow rate greater than 80% of the flow rate stated on the design curve in any of the apparatus. 7. Installation FITTING The Sanicom can be fixed to the floor, preventing it from turning or moving. I G 1. Warning: The space in which the Sanicom is installed must be large enough to leave at least 600mm around the unit for easy maintenance. This space must be well lit, ventilated, and must never be immersed in water and must be protected from frost. H G H 2. Isolation valves should be fitted to the inlet pipework and discharge pipework to isolate the unit in case of the need for service. 8. Connection to side inlets Use the flexible inlet connector (A) for side inlet connections. Using a metalwork saw, saw off the desired inlet point, remove any burrs and then fix the flexible inlet connector with the hose clip (D). C A D We recommend the installation of a grease trap for installations with a high grease inflow. Connection to the inlet can be made using a 40mm or 50mm pipe. To make a 50mm connection, cut off the end of sleeve (A) beforehand.
9. Connection to sanitary ware To connect a bathtub (or shower), make sure the waste trap height is raised by at least 15cm above floor level. Connection must be made using 40mm or 50mm diameter pipework, with minimum slope of 1%. 2.5% 2.5% 150mm min 10. Connection to soil and vent pipe or drain 1% 40mm 32mm The disposal of waste from the Sanicom can discharged through a 32mm diameter copper or plastic pipes (or PVC, ABS, etc.). This discharge pipe must be designed so as to prevent back-flow from the sewers. See diagram above. Horizontal discharge pipework should maintain a 1% fall (1cm/M) to the soil and vent pipe. If a vertical rise is required, this must be installed at the start of the run, before the horizontal section. The horizontal section should then have a minimum 1% fall to the final drain point. Take care that the discharge valve flap faces the direction of flow. If the end of the discharge pipework is much lower than the unit, install a riser pipe about 80mm long from the highest point of the discharge run and fit an air admittance pipe on top (capable of withstanding at least 15psi pressure.) to break the syphon. The discharge should be connected to a 100mm discharge stack via a strap boss connector.
11. In case a service is needed Allow for a drain-off point at the bottom of the rising discharge pipe. Ensure that the unit is easily accessible for possible maintenance. 12. Electrical connection The electrical installation should be carried out by a qualified person. All wiring must conform to BS7671, 1992 requirements for electrical installations. The Sanicom requires a 220/240V single phase AC 50 Hz supply (UK specification). Do not connect the Sanicom to a conventional plug and socket. It must be wired into a fused, unswitched, fixed wiring connector fitted with a 5 amp fuse. The Sanicom has an earth wire. The wires in the mains lead are coloured in accordance with the following code: Brown Live Blue Neutral Green/Yellow Earth Warning: Ensure the electricity is turned OFF at the main switchboard before wiring to connector. All work on cable, pressure chamber and motor should only be carried out by a qualified Saniflo servicing agent, as special tools are required. UK 230/240V 50Hz. The unit should be installed so it is easily accessible/removable for possible maintenance. The unit should not be exposed to splashing in normal use. CANADA USA EUR CH GB 13. Standard Sanicom conforms to Standard EN 12050-2. Lifting station for waste products not containing faecal matter. SANICOM Société Française d Assainissement EN 12050-2/03 FF03-P95 220-240 V - 50 Hz - 750 W - IP44 14. Alarm There is the option of connecting an alarm (light, bell) on to the electronic circuit board (2 terminals fed with 220V). If the motor is run continuously (more than 5 minutes), the contact will be made. This enables the user to carry out a check if he wishes. Connection of the alarm Two 6.35 push on connection points are available on the electronic circuit board (arrowed) for creating an alarm circuit. (These connectors have a 220V, 0.5A maximum current passing through them). To access them after turning the power off, remove the cover then unscrew and unclip the upper casing of the electronic box, to expose the electronic circuit board. On this card use the point marked E.V. and the unused neutral connection point marked N. Use a round 2 x 0.75mm 2 wire, which must pass across the lid of the upper casing, through the cable gland, before being connected to the chosen alarm system.
15. Commissioning Once the hydraulic and electrical connections have been made, check that the connections are tight by allowing water to flow through each entry point used. Ensure that the pump is working properly. 16. Use Sanicom is designed for disposing of wastewater originating from a commercial sink, washing machine, dishwasher, shower or bath and basin. Sanicom can pump out hot water upto 85 C for short periods only (eg. glass washer cycle etc.) CAUTION: 1. Do not dispose of chemical products (acids, solvents, oils, etc.) into the items connected to the Sanicom. 2. In the event of power failure, stop all water flow to the appliances connected to the Sanicom. 17. Troubleshooting FIRST LEVEL TROUBLESHOOTING ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY A PROFESSIONAL ELECTRICIAN SYMPTOMS PROBABLE CAUSES REMEDIES Motor does not start The appliance is not switched on The cable is defective Check the electrical installation The alarm sounds Pump is blocked Pump Jammed To much water flowing through Reduce water inflow SECONDARY LEVEL TROUBLESHOOTING ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY A PROFESSIONAL ELECTRICIAN Before carrying out any service work always disconnect power supply. SYMPTOMS PROBABLE CAUSES REMEDIES Motor does not start Pressure reader tube kinked or out of position Electronic card defective Check the electrical installation Pumps working constantly Alarm Sounding Vertical discharge too high Electronic card defective Pump blocked Pump jammed Electrical problems with motor Too much water flowing through Electronic card defective Check Installation If the pump revolves but does not pump, call a service engineer Intermittent start-up of pumps The non-return valve broken or leaking Clean or change the valve or call a service engineer 18. Warranty Sanicom SFA is guaranteed for 2 years for labour and parts, subject to correct installation and use of the apparatus.