Dynamic Pile Analysis Using CAPWAP and Multiple Sensors Camilo Alvarez 1, Brian Zuckerman 2, and John Lemke 3



Similar documents
METHOD STATEMENT HIGH STRIAN DYNAMIC TESTING OF PILE. Prepared by

PROVA DINAMICA SU PALI IN ALTERNATIVA ALLA PROVA STATICA. Pile Dynamic Load test as alternative to Static Load test

Dynamic Load Testing of Helical Piles

Proceedings of the ASME 28 TH International Conference on Ocean, Offshore and Arctic Engineering OMAE2009 May 31 June 5, 2009, Honolulu, Hawaii, USA

The advantages and disadvantages of dynamic load testing and statnamic load testing

Driven Concrete Pile Foundation Monitoring With Embedded Data Collector System

DYNAMIC TESTING OF MICROPILES. COMPARISON OF STATIC AND DYNAMIC TEST RESULTS

High Strain Dynamic Load Testing of Drilled Shafts

Design, Testing and Automated Monitoring of ACIP Piles in Residual Soils

ADVANCEMENTS IN STATNAMIC DATA REGRESSION TECHNIQUES

PDCA Driven-Pile Terms and Definitions

Instrumented Becker Penetration Test for Liquefaction Assessment in Gravelly Soils

Lymon C. Reese & Associates LCR&A Consulting Services Tests of Piles Under Axial Load

MICROPILE FOUNDATIONS IN KARST: STATIC AND DYNAMIC TESTING VARIABILITY

METHOD OF STATEMENT FOR STATIC LOADING TEST

Practice of rapid load testing in Japan

CHAPTER 9 LONG TERM MONITORING AT THE ROUTE 351 BRIDGE

Offshore Pile Testing Campaign Wikinger

Pile Driving Contractors Association & Pile Dynamics, Inc.

Comparison Between Dynamic and Static Pile Load Testing

vulcanhammer.net This document downloaded from

Pile Driving Analysis Via Dynamic Loading Test

STATNAMIC : Pile Load Testing Equipment

ALLOWABLE LOADS ON A SINGLE PILE

DRIVEN PILE COST COMPARISON FOR TWO LARGE WISCONSIN DOT BRIDGE PROJECTS

4 SENSORS. Example. A force of 1 N is exerted on a PZT5A disc of diameter 10 mm and thickness 1 mm. The resulting mechanical stress is:

Analysis of statnamic load test data using a load shed distribution model

Offshore Dynamic Pile Load Testing & Pile Driving Monitoring Services

DROP WEIGHT DYNAMIC TESTING OF DRILLED DEEP FOUNDATIONS

Step 11 Static Load Testing

SAMPLE GUIDE SPECIFICATIONS FOR OSTERBERG CELL LOAD TESTING OF DEEP FOUNDATIONS

Local Authority Building Control Technical Information Note 3 Driven and In-situ Piled Foundations

Design of pile foundations following Eurocode 7-Section 7

Statnamic Load Testing Overview

DEM modelling of the dynamic penetration process on Mars as a part of the NASA InSight Mission

Chapter 3 DESIGN AND CONSTRUCTION FEATURES IMPORTANT TO SEISMIC PERFORMANCE

System. Stability. Security. Integrity. 150 Helical Anchor

SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS

Introduction to Data Acquisition

Seismic Analysis and Design of Steel Liquid Storage Tanks

Pro-Lift Steel Pile Foundation Repair

Cone Penetration Test (CPT)

Design and installation of steel open end piles in weathered basalt. Luc Maertens*

Centrifugal Fans and Pumps are sized to meet the maximum

Rock Bolt Condition Monitoring Using Ultrasonic Guided Waves

vulcanhammer.net Visit our companion site

Dead load (kentledge) A structure over the test pile. Ground anchorage either by tension piles or ground anchors. Bi-directional (Osterberg-cell)

PILE FOUNDATIONS FM 5-134

New construction Repairing failed or old foundations Retrofit foundations Permanent battered piers Machinery/equipment foundations

Measuring Temperature withthermistors a Tutorial David Potter

Geotechnical Measurements and Explorations Prof. Nihar Ranjan Patra Department of Civil Engineering Indian Institute of Technology, Kanpur

Laterally Loaded Piles

Measuring the Condition of Prestressed Concrete Cylinder Pipe

Acceleration levels of dropped objects

Electronic Soil Test Logging. Strategic Advantage or Unnecessary Headache?

Figure A-1. Figure A-2. continued on next page... HPM-1. Grout Reservoir. Neat Cement Grout (Very Flowable) Extension Displacement Plate

DESIGN OF PILES AND PILE GROUPS CONSIDERING CAPACITY, SETTLEMENT, AND NEGATIVE SKIN FRICTION

TDMS Test & Data Management Software

Address for Correspondence

GUIDELINE FOR HAND HELD SHEAR VANE TEST

Understanding Dynamic Range in Acceleration Measurement Systems. February 2013 By: Bruce Lent

Trigno/Vicon System Integration

Kentucky Lake Bridge Pile Load Testing Overview Ohio Transportation Engineering Conference Columbus, Ohio 10/28/2015

Pent Up Load and Its Effect on Load Test Evaluation

Similar benefits are also derived through modal testing of other space structures.

Objectives. Experimentally determine the yield strength, tensile strength, and modules of elasticity and ductility of given materials.

Two driven pile load tests for use in Missouri LRFD guidelines

Multiple parameters with one Cone Penetration Test. by Mark Woollard

Comparison of the Humboldt GeoGauge With In-Place Quasi-Static Plate Load Tests. Charles R. Nelson, P.E. Mike Sondag

DEVELOPMENT AND APPLICATIONS OF TUNED/HYBRID MASS DAMPERS USING MULTI-STAGE RUBBER BEARINGS FOR VIBRATION CONTROL OF STRUCTURES

Chapter 3.8 & 6 Solutions

WIND TURBINE TECHNOLOGY

PILE DRIVING ANALYSIS BY THE WAVE EQUATION

Increase System Efficiency with Condition Monitoring. Embedded Control and Monitoring Summit National Instruments

Measurement of Soil Parameters by Using Penetrometer Needle Apparatus

ON THE INTERPRETATION OF SEISMIC CONE PENETRATION TEST (SCPT) RESULTS

Abaqus Technology Brief. Automobile Roof Crush Analysis with Abaqus

Closed-Loop Motion Control Simplifies Non-Destructive Testing

Time Domain and Frequency Domain Techniques For Multi Shaker Time Waveform Replication

Precision Miniature Load Cell. Models 8431, 8432 with Overload Protection

Bending, Forming and Flexing Printed Circuits

How To Design A Foundation

Instrumentations, Pile Group Load Testing, and Data Analysis Part II: Design & Analysis of Lateral Load Test. Murad Abu-Farsakh, Ph.D., P.E.

Active Vibration Isolation of an Unbalanced Machine Spindle

SEISMIC DESIGN. Various building codes consider the following categories for the analysis and design for earthquake loading:

Comprehensive Design Example 2: Foundations for Bulk Storage Facility

Hidetsugu KURODA 1, Fumiaki ARIMA 2, Kensuke BABA 3 And Yutaka INOUE 4 SUMMARY

PILE TESTING SPECIFICATION

ACCEPTANCE CRITERIA FOR BORED PILES BY ULTRASONIC TESTING

STATIC PILE LOAD TEST MANUAL. GEOTECHNICAL CONTROL PROCEDURE GCP-18 Revision #4

PROCESS MONITORING FOR DEEP ROLLING IN THE SERIAL PRODUCTION

Numerical Analysis of Texas Cone Penetration Test

Load Testing of Drilled Shaft Foundations in Limestone, Nashville, TN Dan Brown, P.E., Ph.D.

CONTRIBUTION TO THE IAEA SOIL-STRUCTURE INTERACTION KARISMA BENCHMARK

Unsteady Pressure Measurements

HELICAL SCREW PILES (HSP) CAPACITY FOR AXIAL CYCLIC LOADINGS IN COHESIVE SOILS

FRC WPI Robotics Library Overview

B.TECH. (AEROSPACE ENGINEERING) PROGRAMME (BTAE) Term-End Examination December, 2011 BAS-010 : MACHINE DESIGN

GLOSSARY OF TERMINOLOGY

Transcription:

Dynamic Pile Analysis Using CAPWAP and Multiple Sensors Camilo Alvarez 1, Brian Zuckerman 2, and John Lemke 3 1 GRL Engineers, Inc. Los Angeles, California. (661) 259-2977 2 Berkel & Company. San Francisco, California. (415) 495-3627 3 Geodaq, Inc. Sacramento, California. (916) 93-98 Abstract A new system of multiple dynamic strain sensors and accelerometers embedded in test piles provides direct synchronous measurement of force and acceleration at various locations within a pile during high strain dynamic pile testing. This instrumentation system creates an opportunity to explore side and end bearing pile resistance distribution with a higher level of confidence and reliability than from top measurements alone. Dynamic testing results using embedded transducers are presented for a 16-inch Auger Pressure Grouted Displacement (APGD) pile. The procedure is explained to estimate static side and end bearing components by matching force and/or acceleration data at the pile top and tip using the CAPWAP program. Static load and displacement characteristics at the pile top predicted by CAPWAP are compared to static pile load test results. Introduction The need to predict and better understand the ultimate loads to which a cast-in-place pile foundation is capable is critical for pile design and optimization, as well as for quality assurance of such elements. The use of high strain dynamic testing of cast-in-place piles and drilled shafts has become a more frequent routine for bearing capacity evaluations in many countries around the world, increasing the levels of standardization and codification (Beim et al. 1998). Extensive correlation studies (Seidel and Rausche, 1984; Likins et al. 24) between static load tests of castin-place pile foundations and simulated static load tests obtained from dynamic testing utilizing the Case Pile Wave Analysis Program (CAPWAP) have proven successful. A system of multiple dynamic bended compensated sensors was embedded in a 16-inch Auger Pressure Grouted Displacement (APGD) pile installed at a jobsite in Los Angeles, California. For this particular test pile, sensors were installed near the pile s top and toe. Dynamic testing was performed while dynamic measurements were collected near the pile top as well as with the embedded dynamic sensors. Dynamic measurements were analyzed using CAPWAP to better assess the separation between side shear and end bearing. The simulated static results obtained using the dynamic measurements were then compared with a static pile load test. Measurements and Instrumentation A Pile Driving Analyzer (PDA) collected pile top strain and acceleration measurements during the high strain dynamic testing. The PDA immediately converts these strain and acceleration signals to force and velocity records which yield the dynamic compression stresses and the tension along the shaft, to determine if a higher energy drop can be performed without exceeding the recommended material stress levels. In this manner, dynamic testing was performed utilizing GRL s APPLE 15 ton drop hammer system at multiple drops heights varying between 23 inches and 36 inches, until a significant set (.25 in) was obtained. In addition to PDA instrumentation, strain and acceleration signals were captured by two digital transducer modules embedded in the test pile near the pile top and toe. Each transducer module included a microprocessor, signal conditioning circuitry, a 16-bit analog-to-digital conversion circuit, and Controller Area Network (CAN) hardware. Each analog signal was digitized by the transducer module circuitry at a rate of 7,75 samples per second. The total number of strain and acceleration points is defined by the user and can range up to 8, samples per signal. Prior to conducting the high strain dynamic test, both transducers were placed into a dynamic testing mode by issuing a command via a field laptop computer. Samples were then acquired continuously by each transducer module, and every sample was compared to a user defined trigger level. Once a sample exceeded the specified threshold value, each transducer module reserved a user specified number of pre-trigger samples in SRAM and continued sampling until the user specified total number of samples was obtained. At the completion of sampling, data from each transducer module was transferred to a central controller via the CAN data bus where it was then sent to a laptop computer and stored to disk. Figure 1 presents a picture of the high strain testing setup and instrumentation. 1

Figure 1. Dynamic Testing and Instrumentation Analytical Methods After high strain dynamic data was collected in the field, it was processed utilizing the signal matching software CAPWAP (Case Pile Wave Analysis Program). CAPWAP separates static and damping soil characteristics and also allows for an estimation of the side shear distribution and the pile s end bearing. CAPWAP is based on the wave equation model, which analyses the pile as a series of elastic segments and the soil as a series of elasto-plastic elements with damping characteristics, where the stiffness represents the static soil resistance and the damping represents the dynamic soil resistance. Typically the pile top force and velocity measurements acquired under high strain hammer impacts can be analyzed utilizing the signal matching procedure yielding forces and velocities over time and along the pile length. Initial CAPWAP analysis results utilizing only the top force and velocity records yielded an ultimate soil resistance of 58 kips, of which 24 kips were estimated to be in the shaft and 34 kips in end bearing. Figure 2 presents the initial CAPWAP results which include the force and velocity traces and obtained shaft resistance distribution and end bearing. 2

Figure 2. Initial CAPWAP analysis Utilizing the bottom force and velocity measurements obtained with the dynamic sensors embedded in the pile, bottom force and velocity estimates from the CAPWAP program were matched to measurements by adjusting the magnitude of static resistance, quake and damping parameters for both shaft and toe. Initially the main separation between side shear and end bearing was determined utilizing both peak force and velocities at the pile tip. The side shear distribution and the damping coefficient were modified to obtain a better match utilizing the signal matching capabilities of CAPWAP. The ultimate soil resistance calculated by CAPWAP analysis for the dynamic test was 56 kips, of which 3 kips of those were estimated to be in side shear and 26 kips in end bearing. Figures 3 and 4 show a comparison between measured toe force and velocity, the latter multiplied by the pile impedance, and the equivalent readings from the embedded dynamic sensors. TOE FORCE VS TIME 6 5 Toe Force - Embedded Sensors Toe Force- CAPWAP 4 FORCE (kips) 3 2 1 1 2 3 4 5 6 7 8-1 TIME (ms) Figure 3. Toe Force 3

TOE VELOCITY*IMPEDANCE VS TIME 5 4 Toe Velocity * Impedance - Embedded Sensors Toe Velocity * Impedance - CAPWAP Analysis VELOCITY *IMPEDANCE (kips) 3 2 1 1 2 3 4 5 6 7 8-1 -2 TIME (ms) Figure 4. Toe Velocity*Impedance CAPWAP also allows for a computation of a simulated load set curve utilizing the static components of the calculated total resistance. Thus, after signal and dynamic sensor matching was achieved a simulated load-set curve was generated and compared to the results of a static load test. The static load test was conducted using a standard load schedule, and the maximum test load was maintained for about 12 hours. High strain dynamic testing models a quick load test and does not account for any additional settlements associated with the long-term static test method. Both load-set curves are given as a visual comparison with the understanding that results are not meant to be directly compared. Figure 5 presents load-set curves from both the static load test and the CAPWAP simulation. Figure 5. Static and Dynamic Load Set Curves Static Load Set Curves Load (kips) 1 2 3 4 5 6 TP 43-Static TP 43-Dynamic.2.4 Displacement (in).6.8 1 1.2 1.4 4

Table 1. Comparison of calculated with static test loads Table 1. Summary of Pile Capacity Estimates Using Standard PDA and Embedded Sensors Capacity Estimates Using Capacity Estimates Using Resistance CAPWAP with Embedded CAPWAP with Standard PDA Component Dynamic Sensor Modules Instrumentation (kips) (kips) Percent Change Total 58 56 4 Side 24 3 2 Tip 34 26 31 Conclusions A dynamic testing procedure utilizing standard PDA top transducers, an accelerometer and strain transducer embedded at the pile bottom, plus the Case Pile Wave Analysis Program (CAPWAP), was devised to calculate with an increased degree of confidence side shear and end bearing components of an augercast displacement pile than possible from top measurements alone. Results of this study indicate that estimates of side and end bearing components of the total capacity changed by 2 to 31 percent, respectively, using embedded dynamic strain and acceleration sensors, while the total capacity estimate was changed by 4 percent. Additional case histories are needed to further characterize the potential benefit of using multiple embedded dynamic sensors and to further improve the multiple signal matching techniques described in this paper. References Beim, J., Gravare, C.J., Klingmuller, O., De-Qing, L., Rausche, F. (1998). Standardization and Codification of Dynamic Pile Testing - A Worldwide Review. Seventh International Conference & Exhibition on Piling and Deep Foundations: Vienna, Austria; 1-8. Likins, G. E., Rausche, F., (24). Correlation of CAPWAP with Static Load Tests. Proceedings of the Seventh International Conference on the Application of Stresswave Theory to Piles 24: Petaling Jaya, Selangor, Malaysia; 153-165. Rausche, F., Seidel, J. (1984). Design and performance of dynamic tests of large diameter drilled shafts. Second International Conference of the Application of Stress-Wave Theory on Piles: Stockholm, Sweden; 9-16. 5