Maxi Pressurisation Units (Maxi, Maxi Plus & HP)



Similar documents
PRESSURISATION UNITS EXPANSION VESSELS ELECTRONIC FILLING DEVICE (EFD) MAXI MAXI PLUS EXPANSION VESSELS

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual

INSTALLATION & TECHNICAL MANUAL

SF15K SF05KSS, SF10KSS

Operation & Maintenance Manual

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/

Drayton Digistat +2RF/+3RF

PC1131 Electric Air Compressor

Visage. Digital. Digital diverter. Installation guide. Visage Digital diverter installation instructions Page 1

Elson Coral E. Open Vented Thermal Store providing mains pressure hot water heated by electricity. Installation, Servicing and User's Instructions

GeyserWise TSE. thermostat instruction manual. SANS 181 compliant

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

Installation and maintenance instructions. Danfoss Vent

User manual. 086U6297 Rev. 9 EN

SELECTION, APPLICATION AND MAINTENANCE

Technical data. Danfoss DHP-A

Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual

Quinta Range. Condensing Boilers REMEHA QUINTA RANGE. High efficiency wall hung condensing boiler with ultra low NOx emission

English. Symbols used to mark instructions...3. Congratulations...5 Getting the best results...5. Warnings...6 Operating Procedure...

PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator

Bench Autoclave. Standard Operating Procedure. For Installation, Use and Maintenance

PC1130 Electric Air Compressor

For installation guide see reverse of book

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

Portable Air Conditioner

LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual

Baxi Combi 130 HE. User s Operating Instructions. Gas Fired Wall Mounted Condensing Combination Boiler

Back-UPS Pro 1300/1500 Installation and Operation

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS

NÜVE SANAYİ MALZEMELERİ İMALAT VE TİCARET A.Ş. OT 020 BENCH TOP STEAM STERILIZER USER S MANUAL

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS

Designed for multi-injector endurance testing, the

Operating instructions

Electric Flow Boiler

TMS TANK MANAGEMENT SYSTEM

THE INTELLIGENT AUTOMATIC STOPCOCK

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

USER S MANUAL HSC-24A

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

Water Priming Mode Purge air from plumbing system. How do I solve ER-3 WATER PRIME: TIPS ON FILLING SPA IMPORTANT NOTE WARNING

Operating instructions

Visions become real. Temperature control and cooling systems. The innovative and reliable solution

Thermo Top - Troubleshooting Tree

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Mikrofill Ethos Condensing combination boiler

CO2 Alarm. Operation. Application

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

PORTABLE AIR CONDITIONER

ECOCIAT. Domestic hot water heat recovery unit

Pre-Fab Easy Installation For Models: 006-CT-USK, 008-CT-USK Installation and Operating Instructions for Existing Homes with Standard Piping

Nexus FS Point of Use Installation Guide

Water Tec of Tucson Water Systems

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T

THE BOILING WATER DISPENSER INSTALLATION & OPERATING INSTRUCTIONS

SHHH AIR COMPRESSOR Model Nos. SHHH2 - SHHH2/9 - SHHH3/9 - SHH3/24

Power consumption (kw)

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

THE BOILING WATER DISPENSER INSTALLATION & OPERATING INSTRUCTIONS

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

INSTRUCTION MANUAL CIRRO MK 3/TYPE 2 MIST GENERATOR

Link-Up. Solid Fuel Association Guide to Central Heating.

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

Diesel Engine Driven Generators Page 1 of 6

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)

Owners Guide and Installation Instructions

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

KEMPER Leak Detection System

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

Wireless 7 Day Programmable Room Thermostat

SET1E. Installation & User Instructions. Electronic timeswitch for heating & hot water. Certification Mark

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Single Channel Loop Detector

LK Electric Boiler - 4,5

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

PANASONIC TROUBLE SHOOTING GUIDE

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

ELECTRIC CENTRAL HEATING FLOW BOILER

Refrigeration Compressed Air Dryer Buran Ultrapulse

SUB Universal water baths SBB Boiling baths JB, PB Unstirred water baths

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Morco House Riverview Road Beverley HU17 0LD

HERZ-Thermal Actuators

CRAC Precision climate control units for data centres

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

Gastronorm Supra Cabinet & Counter

OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12)

SunMaxx Solar Filling Station Operating Instructions

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Nirvana. Cycling Refrigerated Dryers

BoilerMate SP. benchmark. user instructions A - C L A S S

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

Transcription:

Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Installation and Maintenance Instructions

Contents 1 Dimensions 3 1.1 Installation 4 1.1 Mains/boosted cold water inlet 4 1.2 Connection to the system 5 1.3 Overflow 5 2 Electrical connections 6 2.1 Electrical diagram 6 3 Alarm conditions 7 3.1 Low water level alarm 7 3.2 System failure 7 3.3 High or low pressure alarms 7 3.4 Pump failure 7 3.5 Frequent use reset 8 3.6 Hours run facility 8 3.7 Hours run reset 8 4 Fault diagnosis 8 5 Manual override 10 6 Audible alarm override 10 7 Adjusting settings 10 8 Menu functions 11 9 Maintenance 11 2

Dimensions 320 480 540 600 390 465 View on arrow 'A' Typical installation diagram Safety valve Pump Flow Return Front view The expansion vessel is usually connected on the inlet side of the pump on the system return. For systems exceeding 90 o C contact our technical department for advice. See notes on pipework sizing on page 5. Mains cold water Overflow Alternative pump position 3

Maxi & Maxi Plus pressurisation units The Mikrofill Maxi range is a fully automatic heating / chiller system pressurisation device, and is suitable for the water management in all domestic and commercial heating and cooling systems. It is supplied as a fully commissioned unit and should require no "on site" commissioning. 1 Installation All Mikrofill products should be installed by a competent person with regard to the relevant requirements of the Health and Safety Regulations, Building Regulations, IEE Regulations, Water Supply (water fittings) Regulations, Water Bye-laws (Scotland) and any other local bye-laws or planning requirements. The Mikrofill Maxi is intended for floor mounting: the unit should be situated in such a position as to enable the liquid crystal display to be easily read. 1.1 Mains/boosted cold water supply The Mikrofill Maxi is designed to be connected directly to the mains cold water supply, or a boosted cold water supply, the unit is supplied complete with all necessary isolating valves, but an inlet water isolating valve is recommended. The water inlet is 15mm compression and should be connected to the mains cold water supply by 15mm copper tube or equivalent approved plastic pipework. If the Mikrofill Maxi is sited some distance from the mains cold water supply it may be advisable to install a single check valve adjacent to the mains cold water supply. To reduce the pressure drop on very long supply routes then 22mm supply pipework is recommended. 4

1.2 Connection to the system The Mikrofill Maxi is connected to the heating/chiller system by way of the 15mm outlet valve, the pipework from the unit should be made in 15mm copper or similarly approved plastic pipework. A suitably sized expansion vessel should be incorporated into the system at this point. Please refer to typical installation diagram on page 3. If you require any assistance regarding vessel sizing please contact our technical sales department. The final connection into the heating/chiller system should be sized accordingly, recommendations are shown below: Vessel size up to 100L Vessel size up to 300L Vessel size up to 1000L 1/2" (15mm) expansion pipework. 3/4" (22mm) expansion pipework 1" (28mm) expansion pipework. For vessel sizes in excess of 1000L capacity please contact our technical sales department. IMPORTANT NOTE The expansion vessel nitrogen/air charge must be set at the same pressure as the cold fill pressure of the system.* All Mikrofill expansion vessels are factory commissioned to the correct pressure. * When the installed height of the expansion vessel is different to that of the MAXI then please contact our service department who will advise on the nitrogen/air charge. 1.3 Overflow connection The Maxi is supplied with a 3/4" bsp plastic overflow (warning pipe) connection which should be led to a drain and be visible at point of discharge, MIKROFILL SYSTEMS LTD cannot accept any responsibility for flood damage caused by failure to connect the overflow. 5

2 Electrical connections The Mikrofill Maxi requires a permanent 230V 50Hz 1 phase supply rated at 6 amp. The unit is internally fused at 5 amp (see electrical installation diagram). The Maxi also incorporates two BMS relays offering volt free contacts for the remote indication of high or low pressure conditions within the heating/chiller system. These relays are also independently fused at 5 amp to protect the Mikrofill Maxi from external electrical faults. A further volt free relay is included in the unit, this is to interlock the boiler or chiller control circuits. Should either of the alarm relays operate then the relay will shut down the boiler or chiller, indication of any alarm situation will be indicated on the display. The relays are suitable for use on control voltages up to 250V. Once the Mikrofill Maxi has been correctly connected the unit is ready for use. Ensure that the unit has an adequate water supply and the service valves are open. Check for water leaks. Although every Maxi unit is factory tested it is still advisable to vent the pump(s) before operation. This is achieved by slackening the brass plug (14mm A/F).situated on the pump housing, until all air is eliminated. Switch on electrical supply to the unit and the illuminated on/off switch to the lower right hand side of the unit and the unit will start to pressurise the system. When the system has achieved the set pressure, the unit will stop filling, and go to standby. Important note, "pump type" pressurisation units are not designed to fill systems from empty, they are only capable of "top up" and pressurisation. The system should be filled by other means in compliance with the water regulations. The Mikrofill Maxi is capable and approved to fill and pressurize heating/chiller systems. 2.1 Electrical diagram Electrical data Supply: 230V 1ph 6 amp Full load current: 2.5 amp Start current: 4.5 amp Fuse rating: 6 amp BMS relays and boiler/chiller relays: volt free contacts rated at 250VAC at 5 amp All relays are independently fused at 5 amp Low pressure alarm High pressure alarm Boiler/chiller common alarm 230 VAC 50Hz 6

3 Alarm conditions Please note the Maxi is a factory pre-commissioned product, should you require to change any of the preset parameters - please see "Settings". 3.1 Low water level alarm The Maxi continuously monitors the water level in the feed tank. If this falls to below an acceptable level then the unit will operate a safety shut down. When water level is reinstated the unit will automatically reset. 3.2 System failure The Maxi can differentiate between normal system fill rates and excessive water demand usually due to a flood condition. If this situation occurs the unit will shut down, and issue a flood alert warning on the LCD. This alert must be reset manually, by switching off the Maxi waiting 30 seconds and switching back on, if the leak has been rectified the unit will then operate as normal. 3.3 High or low pressure alarms If, for any reason the system water pressure reaches a high or low condition, as determined by the preset parameters the LCD will show the alarm message, the relevant BMS relay will operate and the Boiler/chiller control relay will shut down the boiler or chiller. When normal operating pressure is resumed the unit will automatically reset, 3.4 Pump failure The Maxi can also determine whether a pump has developed a fault. This is achieved by monitoring the system pressure and if an increase in pressure is not sensed in a set period of time it will stop operation of that pump and the "pump failure" message will appear on the LCD. If the Maxi Plus is used, it will automatically change to the remaining pump, and a pump failure message will be displayed. 7

3.5 Frequent use alarm This alarm is to assist in diagnosing any leaks that may be present in the heating (or cooling system). If in any 24 hr period the Maxi operates more than a preset limit i.e. 5, then a frequent use alarm will show, (the operation of the system will not be affected, this function is for information only). 3.6 Frequent use reset This is achieved by switching the power supply to the unit off and on again. 3.7 Hours run facility This is accessed by scrolling the system data button. 3.8 Hours run reset This is achieved by depressing the simultaneously. IMPORTANT NOTE The MAXI has a predetermined maximum fill rate of 12 litres per minute. Therefore, by multiplying the fill rate by the hours run the approximate water usage can be calculated. 4 Fault diagnosis System faults will be apparent from the alarm message displayed. The Maxi itself has a full self diagnostic microprocessor unit which continually self checks the operation, if an internal fault is diagnosed then the fault will be displayed on the screen, e.g. sensor disconnected. 8

Fault conditions Fault indications Low water level Cause No water in tank Remedies Reinstate water supply to tank Sensor failure Possible sensor fault Incoming voltage instability 1. Switch unit off and back on, if sensor failure does not reappear on the display see note 2. If sensor failure does reappear check sensors are connected to the printed circuit board correctly. If the problem persists ring our service department. 2. If this occurs switch the unit off and back on, the unit should then operate as normal. If this fault appears on a regular basis then a mains electrical filter (anti surge device) is required. Ring our service department for advice. Low pressure alarm System pressure low Check system for leaks. Switch unit off and back on to reinstate. Check Low Alarm setting. High pressure alarm System pressure high Reduce pressure in system and check expansion vessel air charge/size. Check High Alarm setting. System failure Possible excess water leak on the system Check system for leaks, then switch unit off and back on to reinstate. Pump failure Possible pump fault Switch unit off and back on to reinstate, if pump does not operate when required replace pump. If pump operates, dry run setting may need to be increased. Frequent use alarm Possible persistent leak on system If the unit operates more than the set value in a 24hr period the unit will bring up the frequent use alarm, this will not stop the unit from operating but indicates that there may be a small leak on the system. Switch the unit off and back on to reinstate. Investigate possible leak. The Mikrofill Maxi and Maxi Plus have been designed such that most apparent 'faults' can be remedied on site, if in doubt ring our service department on 01527 574574. 9

5 Manual override Should the Mikrofill fail for any reason then a manual override facility can be employed. After ensuring that the heating system is charged with water, and that the Mikrofill is not indicating a system fault, rather than a unit fault i.e. flood alarm, then the BMS relays can be overridden by depressing the and service buttons simultaneously for 3 seconds, repeating the operation will return the BMS relays to normal mode. 6 Audible alarm override If the Mikrofill MAXI does indicate a fault, an audible alarm will sound, this can be overridden by depressing the service button. 7 Adjusting settings The Mikrofill MAXI is supplied pre-commissioned with the settings as shown on the commissioning report. The setting can be adjusted on site as follows: 7.1 Press and hold the system data & service mode buttons simultaneously for approx 3 seconds 7.2 The display will indicate that you are now in the service mode 7.3 Use the system data button to scroll through the settings, each setting can be adjusted by use of the buttons. Section 8 describes the function of each setting 7.4 After adjusting the setting, the unit will return to its standard operating mode approximately 30 seconds after release of the buttons 7.6 Operating links Link in MAXI operating mode Link in MAXI PLUS operating mode Display Display 10

8 Menu functions Target low - this is the pressure at which the unit will operate i.e. start to fill. This is usually set at 0.2-0.3 below the target high Target high - this is the pressure at which the unit will cease filling i.e. the cold fill pressure Alarm low - the pressure at which the low pressure alarm relay will operate. Usually set 0.4-0.5 bar below the target low Alarm high - the pressure at which the high pressure alarm relay will operate. Usually set 0.5 bar below the system safety valve setting Hours run - for information only, no setting required. Please note, to zero the hours run the to be pressed simultaneously for 3 seconds buttons need Dry run - this function affects the pump failure facility, the longer the dry run setting (which is calculated in minutes) the longer the unit will try to operate before notification of failure Please note: where being used on a very large system the unit may indicate pump failure when it is operating normally, in this instance a longer dry run period may be required Delay off - this setting allows adjustment to prevent over or under shoot of the fill pressure - increasing time prevents under shoot, decreasing time prevents over shoot Frequent use - this setting warns of frequent use which would indicate a system leak and will show a warning message if in any 24 hour period the unit operates in excess of the frequent use setting Delay on - This setting is a further flood protection setting and reducing the setting will reduce the sensitivity of the flood protection Diff delay - no setting required 9 Maintenance The inlet filter(s) which is housed in the service valve on the pump(s) inlet pipework should be checked and cleaned annually. EXPANSION VESSELS - Charge pressure should be checked annually when the system is cold (the air charge pressure must equal the cold fill pressure of the Maxi). 11

O&M MAXI 05/04 Mikrofill Systems Ltd West Court Buntsford Park Rd Bromsgrove B60 3DX T +44 (0) 1527 574574 F +44 (0) 1527 575565 W mikrofill.com E info@mikrofill.com 12