Chapter 4.5: Electric Motors, Variable Speed Drives



Similar documents
Centrifugal Fans and Pumps are sized to meet the maximum

Induction Motor Theory

IV. Three-Phase Induction Machines. Induction Machines

OJ L 191, , p. 26. OJ L 2, , p. 1.

DETERMINING ELECTRIC MOTOR LOAD AND EFFICIENCY

DEPARTMENT OF THE AIR FORCE HEADQUARTERS AIR FORCE CIVIL ENGINEER SUPPORT AGENCY

Data Sheet. AC Industrial Electric Motors

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

APPLICATIONS FOR MOTOR CURRENT SIGNATURE ANALYSIS

Neetha John 1, Mohandas R 2, Suja C Rajappan 3 1,3 PG Scholar, Sri Shakthi Institute of Engineering & Technology, L&T Bypass Road,Coimbatore-62,

Energy Savings With Adjustable Frequency Drives. for Centrifugal Fans

Introduction. Three-phase induction motors are the most common and frequently encountered machines in industry

We will discuss common industrial applications with guides for the proper use of electric motors on these.

AC Motor Speed. n s = synchronous speed (in RPM), f = frequency (in Hz), and p = the number of poles

INDUCTION REGULATOR. Objective:

Agricultural Pumping Efficiency Improvements

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

Basics of Electricity

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.

Module Title: Electrotechnology for Mech L7

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

How the efficiency of induction motor is measured?

On the Influence of Stator Slot shape on the Energy Conservation Associated with the Submersible Induction Motors

Unit 33 Three-Phase Motors

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR

AC Induction Motor Slip What It Is And How To Minimize It

INDUCTION MOTOR PERFORMANCE TESTING WITH AN INVERTER POWER SUPPLY, PART 2

Motor Specifications. Nameplate

Motors and Inverters for Environmentally Friendly Industrial Equipment

Lab 8: DC generators: shunt, series, and compounded.

Chapter 3.5: Fans and Blowers

Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection

Control of Motor Characteristics by Squirrel-Cage Rotor Design

Motor Fundamentals. DC Motor

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

8 Speed control of Induction Machines

Improving Motor and Drive System Performance:

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

Single-Phase AC Synchronous Generator

Physical Address: City: State: Zip Code:

VARIABLE FREQUENCY DRIVES THEORY, APPLICATION, AND TROUBLESHOOTING

DIRECT CURRENT GENERATORS

THREE-PHASE INDUCTION MOTOR March 2007

CRK A-W-A-BUBV

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

Lab 14: 3-phase alternator.

The Energy Independence and Security Act of The law s requirements for 1 to 500 horsepower AC motors Effective December 19, 2010

WIND TURBINE TECHNOLOGY

ENERGY-SAVINg DRIVE PACKAGE DE ES FR IT. Overview

ABB drives. Technical guide No. 4 Guide to variable speed drives

Unidrive M Energy Savings

APPLICATION GUIDELINE FOR ELECTRIC MOTOR DRIVE EQUIPMENT FOR NATURAL GAS COMPRESSORS

Baldor Electric Position on DOE Small Motor Rule

SYNCHRONOUS MACHINES

SUNON SPECIFICATION FOR APPROVAL

*ADVANCED ELECTRIC GENERATOR & CONTROL FOR HIGH SPEED MICRO/MINI TURBINE BASED POWER SYSTEMS

Guideline for Energy Efficient Electrical systems for building. Presentation by TERI

DATA COLLECTION AND PUMP ENERGY SAVING OPPORTUNITIES. Presented By: Rick Rumsey, P.E.

Technical Guide No High Performance Drives -- speed and torque regulation

Permanent Magnet Technology within Direct Drive Cooling Tower Motors Creates System Energy Savings

Understanding Energy Efficient Motors

Synchronous motor. Type. Non-excited motors

Introduction. Upon completion of Basics of AC Motors you should be able to:

SUNON SPECIFICATION FOR APPROVAL DESCRIPTION : DC BRUSHLESS FAN. DIMENSIONS : 60X60X15 mm M O D E L : KD0506PHS2

AC Kinetics Variable Frequency Drive Comparative Transient Inertial Testing. This document was prepared by Advanced Energy.

CDX. EBARA PUMPS EUROPE S.p.A. CENTRIFUGAL PUMPS. Page - CONTENTS 100

GE Industrial Systems. AC Motor Selection and Application Guide

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

Specifying a Variable Frequency Drive s

COOLING TECHNOLOGY INSTITUTE

Inverter and programmable controls in heat pump applications

Life Expectancy : Class A Class B Class C Class D 30,000hrs 10,000hrs 3,000hrs 1000hrs

FREQUENCY CONTROLLED AC MOTOR DRIVE

Multistage high-pressure multistage centrifugal pumps

How To Improve A Variable Frequency Drive

JOB or CUSTOMER: ENGINEER: CONTRACTOR: SUBMITTED BY: SPECIFICATION REF: QUANTITY TAG NO. MODEL NO. GPM FEET LEAD LENGTH COMMENTS.

Contactless Power Transfer : Inductive charging of EV

3. Three phase winding technology

What Do All Those Things on an AC Motor Nameplate Mean?

Lecture 6: AC machinery fundamentals

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Basic Nameplate Information

C Standard AC Motors

GE Industrial Systems. AC Motor Selection and Application Guide

How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc.

Torque motors. direct drive technology

WIND POWER GENERATION TECHNOLOGY Mrs. N.V. Vader Mrs. V.A. Joshi

E N E R G Y S AV I N G S

DLW 8. POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw

ENGINEERING BULLETIN No. EB 039 Product: Cooling Towers, Closed Circuit Coolers & Evaporative Condensers Date: June 2003

Current Transformers

AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE

Simulation and Analysis of Parameter Identification Techniques for Induction Motor Drive

Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: Date: december 03, 2015 Supersedes: new Date: new

Drives and motors. A guide to using variable-speed drives and motors in data centres

Section 10. Application Manual for NEMA Motors. Special Applications

1 Temperature Derating Guide

Vibration analysis: what does it mean?

Transcription:

Short type questions Chapter 4.5: Electric Motors, Variable Speed Drives 1. The resistance of a motor stator winding at 30 C is 0.264 ohms per phase. What will be the resistance of the stator winding per phase when the motor winding temperature is 100 C? Ans Stator resistance at 100 C = R1 x [(235 + t1] / (235 + t2)] = 0.264 x [(235 + 100) / (235 + 30)] = 0.334 ohms per phase 2. Calculate the full load power factor of a motor with following operating details: Output power = 30 kw Efficiency = 85% Voltage (V) = 415 V Full load current (Ifl) = 58 A Full load power factor = [Input power / (1.732 x V x Ifl)] x 1000 Input power = output power / efficiency = 30/0.85 = 35.3 kw Full load power factor = [35.3 / (1.732 x 415 x 58)] x 1000 = 0.847 3. Calculate the percentage loading of a motor using the following data: Synchronous speed in rpm = 1500 at 50 HZ operating frequency. Nameplate full load speed = 1440 Measured speed in rpm = 1475 Nameplate rated power = 11 kw 1500 1475 *100% = 41.6% 1500 1440 4. Calculate the rotor I 2 R losses using the following data:? Slip = 4% Stator input = 3000 W Stator I 2 R losses = 100 W Core loss = 50 W Rotor I2R losses = Slip x (Stator input stator I 2 R losses - Core loss) = 0.04 x (3000 100 50) = 114 W 5. What are the two main advantages of application of a variable frequency drive in an induction motor other than accurate speed regulation? Two of the main advantages are (i) (ii) High operating power factor Energy savings during part load operation for longer duration of time. 6. Why the accuracy of the slip method is limited? The largest uncertainty relates to the accuracy with which manufacturers report the nameplate fullload speed. Manufacturers generally round their reported full-load speed values to some multiple of 5 rpm. While 5 rpm is but a small percent of the full-load speed and may be considered as insignificant, the slip method relies on the difference between full-load nameplate and synchronous speeds. Given a 40 rpm correct slip, a seemingly minor 5 rpm disparity causes a 12% change in calculated load. 4.5 - Electric motors (table format) 29

7. The nameplate details of the motor shows the motor is rated at 22 kw with efficiency 91%. The actual power measured was 13 kw. Estimate the percentage loading of the motor? Input power at full rated power in kw, Pi = 22/0.91 = 24.2 kw Percentage loading = 13/24.2 = 53.77% 8. List down important factors required for successful implementation of variable speed drives for any application The important factors required to be considered for successful implementation of VSD are: Load type Motor information Efficiency and power factor Protection and power quality 9. List down various methods available for determination of percentage loading of an induction motor? The following methods are available for determination of percentage loading of induction motors with their own advantages and disadvantages: 1. By input power measurements 2. By line current measurements 3. Slip method 10. Comment on estimation of efficiency of 3 phase induction motor at field? It must be clear that accurate determination of efficiency is very difficult. The same motor tested by different methods and by same methods by different manufacturers can give a difference of 2 %. Estimation of efficiency in the field can be done as follows: a) Measure stator resistance and correct to operating temperature. From rated current value, I 2 R losses are calculated. b) From rated speed and output, rotor R losses are calculated c) From no load test, core and F & W losses are determined for stray loss. Long type questions 1. What are the points to be considered while evaluating the efficiency of motor? It must be clear that accurate determination of efficiency is very difficult. The same motor tested by different methods and by same methods by different manufacturers can give a difference of 2 %. In view of this, for selecting high efficiency motors, the following can be done : a) When purchasing large number of small motors or a large motor, ask for a detailed test certificate. If possible, try to remain present during the tests. This will entail extra costs. b) See that efficiency values are specified without any tolerance c) Check the actual input current and kw, if replacement is done d) For new motors, keep a record of no load input power and current e) Use values of efficiency for comparison and for confirming; rely on measured inputs for all calculations. 4.5 - Electric motors (table format) 30

2. What is the information needed to evaluate energy savings for variable speed application? 1. Method of flow control to which adjustable speed is compared: o output throttling (pump) or dampers (fan) o recirculation (pump) or unrestrained flow (fan) o adjustable-speed coupling (eddy current coupling) o inlet guide vanes or inlet dampers (fan only) o two-speed motor. 2. Pump or fan data: o head versus flow curve for every different type of liquid (pump) or gas (fan) that is handled o Pump efficiency curves. 3. Process information: o specific gravity (for pumps) or specific density of products (for fans) o system resistance head/flow curve o equipment duty cycle, i.e. flow levels and time duration. 4. Efficiency information on all relevant electrical system apparatus: o motors, constant and variable speed o variable speed drives o gears o transformers. If precise information is not available for all the above, one can make reasonable assumptions for points 2 and 4. Numerical type questions 1. Calculate the annual cost savings of a 25 HP motor operating at 90 % efficiency compared to 85 % efficiency. Consider 8000hours of operation and a tariff rate Rs 4 / kwh. At 85 % efficiency: Input electric power = 25 x 0.746 At 90 % efficiency 0.85 = 21.94 kw Input electric power = 25 x0.746 Power Input difference 0.9 = 20.72 kw = 1.22 kw For 8000 hours of operation and Rs 4/ kwh the annual cost saving is = 1.22 x 8000 x 4 = Rs. 39,040/ annum 4.5 - Electric motors (table format) 31

2. Estimate the percentage loading of the induction motor with following data using input power method, line current method and slip method. Name plate details: Rated kw of Motor = 30 kw Rated Amps = 55 A Rated voltage = 415 V Name plate efficiency = 92% Name plate speed = 1440 rpm No. of poles = 4 Frequency = 50 Hz Operating Data Measured speed Input load current Operating voltage Input power a) input Power method = 1460 rpm = 45 A = 425 V = 20 kw Input power at full rated power in kw, Pi = 30/0.92 = 32.6 kw Percentage loading = 20/32.6 = 61.3% b) Line Current Method % load = [input load current / Input rated current] x [Rated voltage/ operating voltage] x 100 = [45 / 55]x [415/425] x 100 = 79.9% c)slip Method Slip %Loading = (Ss Sr) x (Vr / V)² x 100% Synchronous speed = 120 x 50 /4= 1500 rpm Slip = Synchronous Speed Measured speed in rpm, = 1500 1460 = 40 rpm 40 x 100% = 69.9% (1500 1440) x (415 / 425)² 3. Determine the actual output power of an induction motor using the following data? No. of poles = 2 Frequency = 50 Hz Rated voltage = 415 V Name plate full speed = 2980 rpm Measured speed at 423 V = 2990 rpm Name plate rated power = 22 kw Slip %Loading = x 100% (Ss Sr) x (Vr / V)² Synchronous speed = 120 x 50 /2 = 3000 rpm Slip = Synchronous Speed Measured speed in rpm, 4.5 - Electric motors (table format) 32

= 3000 2990 = 10 rpm 10 x 100% = (3000 2980) x (415 / 423)² 51.9% Actual output power = 51.9% x 22 = 11.418 kw 4. Calculate the annual energy savings and simple payback from replacing an existing standard motor with premium efficiency Motor versus repairing a standard efficiency motor. The data given are: Motor : 15 kw, working hours: 8000 hr, η standard = 88.3, η premium = 93.5%, 75 100 Energy cost savings (Rs./year) = kw x %loading x η s tan dard η 100 premium x hrs/annum x Rs./kWh Simple Payback (years) = Price premium / Annual cost savings (in (Rs) Simple Payback Analysis for an average 15 kw, 1500 RPM, TEFC Motor Repair or Replacement: Description Parameter Efficiency after Rewound of Standard Motor 88.3% Efficiency of Premium Efficiency Motor 93.5% Operating Hours 8,000 % Loading of Motor 75% Average cost of rewinding, Rs. 5,000 Cost of new premium efficiency motor, Rs. 40,000 Utility Rate Rs. 4.0/kWh Energy Cost Savings Simple Payback = 15 kw x 0.75 x 8,000 hrs x [100/88.3-100/93.5] x Rs. 4/kWh = Rs. 22, 674.28/year = (Rs. 40000 Rs.5000) / Rs. 22,674.28 = 1.54 years 4.5 - Electric motors (table format) 33