Flare Pilot System Safety



Similar documents
Flares are used extensively in the hydrocarbon and

Process burners (1) operate in heaters and furnaces in

FLARE MONITORS FLARE MONITOR (FM) PILOT MONITOR (PM) FLAME INTENSITY (FI)

POROUS BURNER - A New Approach to Infrared

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

This article provides a basic primer on an

PROCEDURES PREVENTION OF ACCIDENTAL IGNITION

G670 Intermittent Pilot Ignition Controls

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Early Fire Detection & Condition Monitoring

Combustion Pulsation and Noise by Dan Banks, P.E., Banks Engineering Inc.

Syngas Furnace Tubeskin Temperature Measurement

SULFUR RECOVERY UNIT. Thermal Oxidizer

Natural Gas Emergencies

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009

Basis and Purpose Document on Specifications For Hydrogen-Fueled Flares

Control Device Requirements Charts For Oil and Gas Handling and Production Facilities

LANDFILL GAS ENCLOSED FLARE SYSTEM

Chapter. Flares and Stacks. Flares (FLR) Stacks (STK) G2 ICARUS Corporation, 1998.

HOW MUCH FUEL DOES A GAS STOVE CONSUME AND HOW MUCH DOES IT COST TO OPERATE?

Compressed Gas Cylinder Safety

Callidus Flares FLARES FOR THE PETROCHEMICAL AND PETROLEUM INDUSTRY. A world leader in flare and flare system applications

Natural Gas Information Contents

Certain specific properties of compressed gases make them highly useful in various research activities.

Flame Conductivity VS Flame Rectification Systems

INSTALLATION INSTRUCTIONS

Electronic Flow Switches

Low Emission - Low Maintenance Burner Design

Calculate Available Heat for Natural Gas Fuel For Industrial Heating Equipment and Boilers

FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH

Boiler Preparation, Start-Up and Shutdown

Munchkin Heat Exchanger Maintenance

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

The Behaviour Of Vertical Jet Fires Under Sonic And Subsonic Regimes

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

Hydrogen Detection in Oil Refineries

Fiscal Measurement Natural Gas

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve


Select the Right Relief Valve - Part 1 Saeid Rahimi

COMBUSTION. In order to operate a heat engine we need a hot source together with a cold sink

Process Heater Burners, Flare Systems, Thermal Oxidizers and Catalyst Systems. Combustion Technology

ASK THE EXPERT: Burner Troubleshooting Information & Maintenance

GAS LEAKAGE DETECTION & AUTO ON-OFF GAS SYSTEM

Proven Utility Solutions from John Zink Hamworthy Combustion.

Grounding and Bonding Against Static Electricity. Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute

TODAY S THERMAL OXIDIZER SOLUTIONS TO MEET TOMORROW S CHALLENGES

Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service

Gas-Fired, Residential Storage Type Water Heaters

Sustainable Energy Sources By: Sue Peterson

SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND

Making sense of Intrinsic Safety and Intrinsically Safe Tools

Emergency Response Guide

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

In-Line Electronic Flow Switches

White Paper. Best Practices for Gas Monitoring in the Commercial Kitchen

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

Compressed Gas Cylinders Safety Policy

Preventing Overheated Boiler Incidents

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems

CSB Public Meeting February 7, 2010, Natural Gas Explosion Kleen Energy Middletown, Connecticut

The photoionization detector (PID) utilizes ultraviolet

Compressed Gas Cylinder Safety

Explosion-Proof Electric Unit Heaters

CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute

RGC-IR Remote Gas Calibrator for IR400

Improving Steam Methane Reformer Performance with the ZoloSCAN-SMR

Thermal Mass Flow Meters

Oxy-Fuel Gas Welding. Given a functional oxy-fuel gas unit, instruction and demonstration of use, each student will be able to:

COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.

Application Note 12: TrendView Recorders Continuous Emissions Monitoring

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners

MICROPACK Visual Flame Detection Application Note

PSAC/SAIT Well Testing Training Program Learning Outcomes/Objectives Level D

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL

Routine and Emergency Boiler Operation

TB-A A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION

High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR

15GAL STEEL OIL DRAIN WITH 110V PUMP

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

San josé OWNER S MANUAL

7.1 Introduction Flare Types Steam-Assisted Flares Air-Assisted Flares

Air Conditioning Sign-Off Sheet

Calculation of Liquefied Natural Gas (LNG) Burning Rates

Chemical Fume Hoods. Environmental Health and Safety

FLARE SELECTION AND SIZING (ENGINEERING DESIGN GUIDELINE)

Unsteady State Relief Valve Evaluation. External Pool Fire Scenario

The Basics of Natural Gas

CLEAN COMBUSTION. CLEAR SOLUTIONS. John Zink Vapor Combustion System

Flame detection across the spectrum. Range Brochure

Heating Water by Direct Steam Injection

Evaluating Thermal & Catalytic Oxidation Technology for VOC, HAP & Odor Abatement. John Strey

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

How to Select a Flame Detector

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

Vehicle Maintenance Facilities Requirements for CNG and LNG Vehicles

Presented by: Rich Perry Marsh Risk Consulting

Stack Sampling Stack sampling or source sampling

PART 1 - INTRODUCTION...

Transcription:

Flare Pilot System Safety John Bellovich, Jim Franklin, and Bob Schwartz John Zink Company, LLC, 11920 East Apache, Tulsa, OK 74116; john.bellovich@johnzink.com (for correspondence) Published online 30 August 2006 in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/prs.10154 One of the worst nightmares a plant manager can experience is a complete flare system outage. The flare system is the last line of defense for many refining and petrochemical facilities and, when out of commission, can cause the shutdown of the entire facility. Flare ignition failure may lead to unburned venting of dangerous gases, and may develop into an explosive hazard leading to the loss of property and equipment, or worse, injury to personnel or loss of life. The safety and effectiveness of flaring are dependent upon one or more continuously burning pilots for immediate and sustained ignition of gases exiting a flare burner. Because pilot failure can compromise safety and effectiveness, it should be detected quickly and accurately to allow prompt automatic and/or operator response. Proper disposal of process and waste gases during routine and/or emergency conditions is crucial to help operating facilities protect plant employees and the surrounding community, and to avoid hundreds of thousands of dollars in fines. These reasons alone make the pilot monitoring and ignition system the most important component of any flare system. The advanced flare pilot systems explained in this article offer increased protection from harsh environmental conditions and rapid notice of pilot flame failure. Recently published industry standards for flare pilot design and performance are also discussed. 2006 American Institute of Chemical Engineers Process Saf Prog 26: 10 14, 2007 Keywords: flare pilots, flare ignition, flare monitoring, SoundProof, flame ionization 2006 American Institute of Chemical Engineers Prepared for Presentation at American Institute of Chemical Engineers 2006 Spring National Meeting, Orlando, FL, April 23 27, 2006. INTRODUCTION A flare can only achieve its objective of safe, effective disposal if the exiting gases are ignited and the ignition is sustained. Ignition is sustained through the use of a design concept that includes several elements: the pilot, the pilot ignitor, and a pilot flame monitor. While each is important, the critical element in this system is the pilot; flare pilots are typically premix type burners designed for operation at a fixed heat release. In application, the pilot is positioned adjacent to the exit of the flare tip. When the flare is in service, the flare tip and its pilot(s) are remote, inaccessible, and exposed to external influences. Therefore, the pilot must be capable of operating for long periods of time without adjustment or maintenance. API STANDARD 537 The recently released API Standard 537 is a good reference to have concerning flare systems. API STD 537 states that the pilot should continue to burn and ignite the flare at wind speeds of 100 mph under dry conditions and 85 mph when combined with a rainfall of 2 in/hr. These guidelines should be viewed as the minimum level for performance. When the height of most flares is taken into consideration, an effective wind stability of 125 mph or more is desirable. In this same section, API STD 537 recommends a minimum pilot heat release of 13.2 MW (45,000BTU/hr) (LHV) when flaring hydrocarbon gases, with a lower heating value of 11,175 kj/nm 3 (300 BTU/scf) or greater. Pilots must be able to provide sufficient energy to initiate burning of the waste products as they exit the flare tip. The energy level required is dependent on a number of factors, including: the composition of the waste gas being burned, the gas exit velocity of the flare burner, the design of the flare burner, and the atmospheric conditions under which the pilot is operating. Good practice recommends a minimum pilot heat release of 45,000 Btu/hr for favorable conditions. The use of lower-heat-release pilots can compromise the initiation of burning. Most flare manufacturers use a premixed pilot of some design. Premix pilots offer greater stability over raw gas burners. PILOT ANATOMY A pilot will usually consist of a pilot tip, a windshield, a venturi mixer, and a metering orifice, as shown in Figure 1. PILOT ENVIRONMENT During the course of a pilot s service life on a flare, the pilot can be exposed to a number of external influences, including: wind, rain, envelopment in flare flame or inert gas, smoke suppression media, and caustic or acidic gases. Recent Computational Fluid Dynamics (CFD) modeling and testing has shown that wind can cause variations in the local static pressure, which will affect the ability of the pilot mixer to supply a 10 March 2007 Process Safety Progress (Vol.26, No.1)

PILOT FUELS According to API STD 537 section 5.2.4[1], In order to maximize pilot reliability, the most consistent and reliable fuel source should be used. Where possible, natural gas should be used. The pilot should be designed to handle a reasonable range of fuels. These fuels typically consist of natural gas, methane, ethane, propane, and refinery fuel gases. Fuels with moderate to high amounts of hydrogen, ethylene, and acetylene should be avoided, as these fuels have such a high flame speed that burning can occur in the mixer and not at the tip as intended. Figure 1. A typical pilot assembly. combustible mixture to the tip. Surprisingly, the upwind pilot is the least affected by winds and is the most stable. The pilots in the cross wind and down wind positions are more unstable because of the low pressure zones created by the wind. It is important that the cross wind and down wind pilots remain lit, as they are in the best position to light the flare gas. PILOT LIFE Extending the service life of a pilot has become more important in recent years as facilities have increased the amount of time between major turnarounds. The average service life of a pilot is about 7 years, but it is not uncommon for a pilot to last 30 years depending upon the situation. The number one cause of pilot failure is flame envelopment from the main flare flame. Temperatures caused by direct flame impingement are far greater than the maximum continuous temperature that alloys can take in a reducing atmosphere. PILOT MATERIAL As stated in API STD 537 section 5.2.3[1], The pilot tip should be constructed of a heat resistant material, such as 309SS, 310SS, CK 20, or a nickel-based alloy such as 800H. For applications with any amount of H2S in the fuel or flare gas, 800 alloys are not recommended. It is possible that the piping between the pilot tip and mixer may be exposed to the flare flame. For this portion of the pilot, an austenitic stainless steel, such as 304SS or 316SS, is adequate. [1] PILOT IGNITION There are two primary methods of pilot ignition in the refining and petrochemical industry. The oldest and most common method uses the Flame Front Generator (FFG), shown schematically in Figure 2. The FFG combines ignition fuel and compressed air at a mixing tee with the ignition air and gas mixture flowing through an ignition line to the pilot tip. After filling the ignition line with the air-fuel mixture, an electrical spark is initiated at the mixing tee. The resulting fire ball, or flame front, travels through the ignition line up to the pilot and ignites the pilot. Each pilot is ignited in sequence. FFG ignition can be quite reliable if maintained properly. Proper maintenance includes frequent draining of the ignition lines and routine practice attempts to create a fire ball by each operator responsible for the FFG system. The second method of pilot ignition uses a high energy or high voltage spark at or near the pilot tip, as shown in Figure 3. This may be done with a spark probe or electrode in direct contact with the pilot gas or in a slip stream tube. The design must protect the probe from the high temperatures at the pilot tip. Electronic Spark Ignition (ESI) pilots are easy to use compared to the FFG system and require little training or maintenance. The downside to ESI is that shutdown of the flare system is required for maintenance. Often confused with the ESI system, Direct Spark Ignition (DSI) uses a spark probe in place of a pilot. In order to reduce maintenance costs, DSI has been used in lieu of a continuous pilot to ignite the flare. This is not recommended as it is not in compliance with EPA regulations and cannot ensure that a destruction efficiency is occurring in the flame zone. As stated in section 5.2.2 of API STD 537[1], Such designs are not considered to be a suitable alternative to a continuous pilot because, without an independent fuel supply, it is impossible to ensure that a flammable mixture will always exist at the location of the spark. Other methods, such as flare guns, flaming arrows, oily rags, and magnesium or phosphate pellets, are generally unacceptable in the petrochemical and refining industry as they are potential safety hazards. PILOT DETECTION Flare performance is closely linked to reliability of the flare pilots and the verification that they are burning. Good operating practice and, in many locations, governmental regulation require that the presence of a flame at each pilot be verified on an ongoing basis. Process Safety Progress (Vol.26, No.1) Published on behalf of the AIChE DOI 10.1002/prs March 2007 11

Figure 2. A simple flame front generator (FFG). the pilot flame so that the thermocouple is heated when a flame is present. The thermocouple is connected to a temperature switch with an adjustable set point. The pilot is assumed to be on when the temperature is above the set point and off when it is below the set point. The primary drawback of the thermocouple is that the response time may take anywhere from 30 seconds to 10 minutes to alert the operators that there is a problem. It is possible to operate the flare for some time without knowing the pilots are out. Because the pilot ignition system is a safety control system, it is important to adhere to a routine maintenance procedure. Maintenance performed on a thermocouple is minimal; there is little more to do than monitor its performance to ensure it has not failed. Figure 3. An Electronic Spark Ignition (ESI) pilot. More than 50 years ago, visual sighting of the flame, although difficult in the daytime, was an accepted means of flame verification. Today, visual verification is no longer accepted for most flares. Federal Regulation 40 CFR 60.18[2] states, The presence of a flame shall be monitored using a... device to monitor the presence of a flame. Fortunately, there are four different detection methods that can be used. Because of the nature of combustion, energy is emitted in three different forms: heat, light, and noise. The fourth method uses a unique phenomenon that occurs within the flame during combustion. Thermocouples The most common means of compliance with 40 CFR 60.18 is to detect the heat produced by the pilot flame by means of a thermocouple. In practice, the thermocouple junction is placed in a position in or near Optical Systems Optical systems use the light emitted by the fire to detect the presence of a flare flame. Much like a camera, these devices use a set of lenses aimed at the flare tip to direct infrared or ultraviolet light into a sensor. In principle, the presence of any flame in the viewing area is detected. Upon flame failure, the device sends a signal to the control room to alert the operators. The advantages of an optical device are that it may be maintained at grade, is easy to use, and has a fast response time. However, there are several disadvantages. Because the optical monitors are looking for the presence of any ultraviolet or infrared light, there is no way to detect if a pilot is out or not. The presence of any flame in the viewing area will satisfy the pilot proved requirements. It is quite possible that the main flare flame be lit and all pilots are out, creating a potentially dangerous situation. Another disadvantage of the optical system is that environmental conditions can hide the flare from the field of view. Snow, rain, and fog can, if dense enough, blind these sensors. Acoustic Systems The third way energy is released from a pilot flame is in the form of noise. An acoustic system operates by 12 March 2007 Published on behalf of the AIChE DOI 10.1002/prs Process Safety Progress (Vol.26, No.1)

Figure 5. Flame ionization system. using the sound generated by the energy release of the flame. The acoustic monitoring system is responsive to the difference between the sound signature of a pilot burning and that of a pilot with no flame. The acoustical selectivity of this system allows it to monitor a specific pilot and ignore extraneous sounds, such as those generated by other pilots, the flare flame, or steam used for smoke suppression. John Zink s system, SoundProof, takes advantage of the fact that most flare pilots are ignited by using an FFG. The FFG pilot ignition system includes a conduit connecting the FFG panel to the pilot, as shown in Figure 4. This conduit is used only during pilot ignition, and provides a convenient means of conducting the pilot flame sound to a location remote from the pilot, usually a point at or near the base of the flare stack. Based on the characteristics of the signal received, a signal processing unit indicates that the pilot is on or off using signal lights on the face of the unit. The on or off indication is also available through a set of dry contacts. Maintenance of acoustic systems is capable of being done as required online; regular maintenance is minimal and includes checking the drains in the sound conveying piping. The primary advantage of the acoustic systems is that each monitor is dedicated to a specific pilot and has a fast response time. Current acoustic technology limits the pilot distance to approximately 350 feet from the pilot, which may be an issue for taller stacks. Figure 4. SoundProof Acoustic System. Flame Ionization The final method of flame detection takes advantage of a unique phenomenon that occurs during combustion. As the chemical reaction occurs in the pilot tip between the hydrocarbon gases and the air, a pool of ionized gas forms at the base of the combustion zone. This pool of ionized gas is conductive and can actually carry a small current. To accomplish this, a ceramic rod with a conductive core may be placed in the flame zone, as shown in Figure 5. A continuous current may be run through the flame rod into the ionized gas and into common ground. The monitoring system looks for a flow of current between the electrode and ground. If current flow is detected, a flame is present. If there is no current (open circuit), no flame is present. Flame ionization is a fast method of pilot detection and is also highly reliable. Unless the flare is taken out of service, no maintenance can be performed on a flame ionization system. Retractable Systems Critical components on the flare stack, such as pilots and thermocouples, may be installed with a retractable system. The advantage of a retractable system is that it allows the operators to maintain or change a component while the flare system is still in operation. Retractable thermocouples usually consist of a thermocouple being pushed through a tube that runs from grade to the pilot tip. Replacing the thermocouple is fairly simple. Retractable pilots are slightly more complicated and generally consist of a set of cables and possibly Table 1. Comparison of flare pilot ignition systems. Ignition System Conventional Flame Front Generator (FFG) Spark Probe Igniter Compressed air Required Not required Ignition line 1 in. diameter Not required Max distance 1 mile for FFG line 750 ft. for ignition transformer Components at grade Main Some Control Automatic or manual Automatic or manual Response time One to several minutes 1 10 sec. Process Safety Progress (Vol.26, No.1) Published on behalf of the AIChE DOI 10.1002/prs March 2007 13

Table 2. Comparison of flare pilot detection systems. Method Thermocouple Flame Ionization IR Sensor Acoustic Sensed phenomenon Heat Electrical Light Sound current Able to distinguish between individual pilot flames? Yes Yes No Yes Able to distinguish pilot flame from main flare flame? Partially Yes No Yes Average response time (sec) 100 300 5 5 5 10 Location of key system components Pilot tip Pilot tip and Grade Grade grade Installation while flare is operational? No No Yes Yes Serviceable while flare is operational? No Partial Yes Yes Resistant to: Rain No Yes No Yes Fog Yes Yes No Yes Snow Yes Yes No Yes Steam No Yes Yes Yes Sunlight (direct or reflected) Yes Yes No Yes slides. The idea is that the pilot is simply lowered to the ground by a winch or crank when maintenance is required. Although retractable systems can be somewhat costly, they can be worth the extra expenditure if a shutdown or fines can be avoided. CONCLUSION In order to protect plant employees, preserve the environment, and avoid costly fines, it is critical to operate and maintain flare systems properly. The pilot and pilot verification system are directly related to flare performance, making them essential elements of safe, effective flaring. In this article we have examined several methods of pilot ignition and monitoring that are available, as well as their advantages and disadvantages. Using redundant ignition and monitoring systems can help prevent costly shutdowns and flare outages. LITERATURE CITED 1. API Standard 537, Flare Details for General Refinery and Petrochemical Service, September 2003. 2. U.S. Code of Federal Regulations, 40 CFR 60.18. (f) (2). 14 March 2007 Published on behalf of the AIChE DOI 10.1002/prs Process Safety Progress (Vol.26, No.1)