Performance Analysis of Grid connected Wind Energy Conversion System with a DFIG during Fault Condition



Similar documents
WIND TURBINE TECHNOLOGY

Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique

Control Strategies of the Doubly Fed Induction Machine for Wind Energy Generation Applications

MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS

Simulation and Analysis of Parameter Identification Techniques for Induction Motor Drive

Analysis of Space Vector Pulse Width Modulation VSI Induction Motor on various conditions

Power Quality Paper #3

Simulation and Analysis of PWM Inverter Fed Induction Motor Drive

Analysis, Calculation and Reduction of Shaft Voltage in Induction Generators

Dually Fed Permanent Magnet Synchronous Generator Condition Monitoring Using Stator Current

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

Transient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink

Coordination Control of a Hybrid AC/DC Microgrid With Various Renewable Energy Sources

Pulse Width Modulated (PWM) Drives. AC Drives Using PWM Techniques

SYNCHRONOUS MACHINES

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

2012 San Francisco Colloquium

Renewable Energy Applications: Photovoltaic and Wind Energy Conversion Systems (WECS)

System Protection Schemes in Eastern Denmark

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

The design and performance of Static Var Compensators for particle accelerators

Pulse Width Modulated (PWM)

Configuration study of large wind parks

Offshore Platform Powered With New Electrical Motor Drive System

THESIS FOR THE DEGREE OF DOCTOR OF PHILOSOPHY. Modeling of Wind Turbines for Power System Studies

Principles of Adjustable Frequency Drives

An Isolated Multiport DC-DC Converter for Different Renewable Energy Sources

AC Induction Motor Slip What It Is And How To Minimize It

FREQUENCY CONTROLLED AC MOTOR DRIVE

Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives

Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems

Simulation on Micro Wind Power Generator with Battery Energy Storage for Critical Load

Design and Simulation of Soft Switched Converter Fed DC Servo Drive

Management of Low- and High-Frequency Power Components in Demand- Generation Fluctuations of a DFIG-Based Wind-Using Fuelcell

Simulation of VSI-Fed Variable Speed Drive Using PI-Fuzzy based SVM-DTC Technique

Mathematical Modelling of PMSM Vector Control System Based on SVPWM with PI Controller Using MATLAB

NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM

Hybrid Wind-Fuel Cell Renewable Energy Utilization Scheme for Village Electricity

Control Development and Modeling for Flexible DC Grids in Modelica

THIS paper reports some results of a research, which aims to investigate the

Modeling and Simulation of a Novel Switched Reluctance Motor Drive System with Power Factor Improvement

Renewable Energy Laboratory for Engineering Students

How To Improve Power Quality

LOSSELESS STARTING METHOD FOR THE WOUND ROTOR INDUCTION MOTOR

Power System review W I L L I A M V. T O R R E A P R I L 1 0,

Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting, excitation system

Closed Loop PWM Control for Induction Motor Drive Using Dual Output Three Phase Inverter

Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

HVDC-VSC: transmission technology of the future

POWER TRANSMISSION FROM OFFSHORE WIND FARMS

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

Performance Enhancement of Wound Rotor Induction Motor by VSI with Dynamic Capacitor Controlled Rotor Circuit

How To Simulate A Multilevel Inverter

Speed Control Methods of Various Types of Speed Control Motors. Kazuya SHIRAHATA

DC/DC BUCK Converter for Renewable Energy Applications Mr.C..Rajeshkumar M.E Power Electronic and Drives,

MULTI-LEVEL INVERTER WITH DC LINK SWITCHES FOR RENEWABLE ENERGY SOURCES

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors

Hybrid Power System with A Two-Input Power Converter

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Distributed Generation and Power Quality Case Study

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Low Frequency AC Transmission System

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Project description. Power Electronics for Reliable and Energy efficient Renewable Energy Systems

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

Renewable Energy Grid Integration

Droop Control Forhybrid Micro grids With Wind Energy Source

Verification of Short Circuit Test Results of Salient Poles Synchronous Generator

300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc.

Control Strategy for Three Phase Shunt Active Power Filter with Minimum Current Measurements

Synchronous motor. Type. Non-excited motors

INDUCTION MOTOR PERFORMANCE TESTING WITH AN INVERTER POWER SUPPLY, PART 2

Harmonic Reduction and Load Balancing of Three Phase Four Wire DSTATCOM using Three Leg VSC and a Zig Zag Transformer

SVC LIGHT: A POWERFUL MEANS FOR DYNAMIC VOLTAGE AND POWER QUALITY CONTROL IN INDUSTRY AND DISTRIBUTION.

Scholars Research Library

Advance Electronic Load Controller for Micro Hydro Power Plant

Reactive Power Generation by DFIG Based Wind Farms with AC Grid

8 Speed control of Induction Machines

13 ELECTRIC MOTORS Basic Relations

Control of a Three Phase Induction Motor using Single Phase Supply

Wind Turbine Operation in Power Systems and Grid Connection Requirements

AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Modeling and Control for Smart Grid Integration with MPPT of Solar/Wind Energy Conversion System S. Sathish Kumar 1, B.Swapna 2, Dr.C.

Modeling Grid Connection for Solar and Wind Energy

Solar Power Plant Design and Interconnection

Lecture 4 Energy Conversion in Wind Turbine

PMG vs. DFIG the big generator technology debate

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

POWER QUALITY ISSUES IN A STAND-ALONE MICROGRID BASED ON RENEWABLE ENERGY

Transformer Based Voltage Sag Generator to test Renewable Energy Systems during Grid Faults in the Laboratory

Transcription:

Performance Analysis of Grid connected Wind Energy Conversion System with a DFIG during Fault Condition Sasi.C Assistant Professor Department of Electrical Engineering Annamalai University Chidambaram, India G.Mohan, PhD. Professor Department of Electrical Engineering Annamalai University Chidambaram, India ABSTRACT Integration of wind turbine based on doubly fed induction generator (DFIG) into the electrical grid has become an important part of electrical generation in many countries and its importance is continuing to increase. A few of them are various speed generations, the decoupled control of active and reactive power and high power capacity. The current and future wind power situation is modeled as two cases and short circuit faults in the system are simulated. The simulations yield information on (i) how the faults impact on the wind turbines and (ii) how the response of the wind turbines influences the post-fault behavior of the power system. Here, we attempted to compare the impact, in terms of voltages, active and reactive power, of adding wind turbines into electrical power grid. Therefore, the analysis of wind power dynamics with the DFIG wind turbines has become a very important research issue, especially during transient faults. Keywords Doubly Fed Induction Generator, Wind Turbine, Nomenclature DFIG WECS ω B P w Ρ R V ω C p λ β u R Doubly Fed Induction Generator Wind Energy Conversion System Rotational speed of turbine Power from the wind Air density Blade radius Wind speed Power coefficient Tip speed ratio Blade pitch angle Voltage Resistance 1. INTRODUCTION Wind energy is the fastest growing and most widely utilized emerging renewable energy technologies in electrical energy conversion systems at present [1]. This high penetration of wind energy in the power system has been closely related to the advancement of the wind turbine technology and the way of how to control. There are basically three types of generators that are commonly used with commercial wind turbines. They are (1) fixed-speed system with squirrel-cage induction generator, (2) variable-speed system with Doubly- Fed Induction Generator (DFIG) (3) variable-speed system with a direct-drive synchronous generator. DFIG based variable speed wind energy conversion systems are currently the most admired one, due to its important advantages such as, high capacity with high energy efficiency, four-quadrant active and reactive power controls and the small converter size with a rating of only 20% 30% of the rated Wind turbine power [2]. The control aspect of DFIG is decided by two back to back converter placed on rotor side. In this, constant-frequency ac grids are used, whereas primary mechanical power sources such as a dc machine usually operate at variable speed [3] - [6]. Indeed, they are used in small-scale generators in windmills for instance. However, specific applications, such as aircraft, require higher level reliability and/or long-time maintenance periodicity. The power converter need only be rated to handle the rotor power [7]. To satisfy the grid code requirements of wind turbine, usually grid side converter is playing a major role. Independent control of active and reactive power from the grid or to the grid is possible by vector control of line side converter [8]. This paper considers the mutual effects of wind power in power systems under transient fault situations. It is analyzed (i) what impact the wind turbines have on the dynamic behavior of the system experiencing a fault and (ii) how the wind turbines behave in the system when it experiences a transient fault[9]- [11]. If transient faults in the system lead to considerable excursions in voltage and/or frequency the wind turbines were to disconnect and to reconnect only once the system has returned to stable operation. Increasing wind power penetration leads to the problem that considerable amount of generation might disconnect in case of a transient fault in the system, causing the system to become unstable from an otherwise harmless fault situation [12] & [13]. To prevent such situations newly installed wind turbines have to comply with new grid connection requirements that demand wind turbines to ride through transient faults. This paper presents the dynamic behavior of the power system during transient faults, when wind energy is connected to the existing power system. 2. POWER SYSTEM MODEL INTEGRATED WITH WIND FARM USING DFIG Dynamic model of a DFIG wind turbine can be represented in terms of the equations of each of the subsystems, mainly the turbine, the drive train, the induction generator and the control system. WECS considered for analysis consist of a DFIG driven by a wind turbine, rotor side converter, DC to DC intermediate circuit and grid side converter as shown in Fig.1. 31

angle β. The calculation of the performance coefficient requires the use of blade element theory. ω B is the rotational speed of turbine. Usually C p is approximated as, 2 3 C p (4) where α, β and γ are constructive parameters for a given turbine. The torque developed by the windmill is Fig.1: Components of DFIG Wind Turbine The turbine output power is controlled in order to follow a pre-defined power-speed characteristic, named tracking characteristic. The electrical output power at the grid terminals of the wind turbine is added to the power losses and is compared with the reference power obtained from the tracking characteristic. In rotor side converter system, AC voltage and VAR are regulated. DC to DC intermediate circuit consists of two converters: Converter 1 (DC to AC) and Converter 2 (AC to DC). The control system of DC to DC intermediate circuit consists of DC voltage and current regulation and pitch control system. The pitch angle is regulated at zero degree by pitch angle regulator until the speed reaches desired speed of the tracking characteristic. The DC voltage output from intermediate circuit is applied to grid side converter, which consists of an Insulated Gate Bipolar Transistor (IGBT) two-level inverter, generating AC voltage at 50 Hz. The IGBT inverter uses Pulse Width Modulation (PWM) at 2000 Hz carrier frequency. A 9 MW wind farm consisting of six 1.5 MW wind turbines connected to 440V distribution system through power electronic interface. The wind speed is maintained constant at 15 m/s. Half of the world s leading wind turbine manufacturers use the DFIG systems. This is due to the fact that the power electronic converter only has to handle a fraction (20% 30%) of the total power, i.e., the slip power. This means that if the speed is in the range ±30% around the synchronous speed, the converter has a rating of 30% of the rated turbine power, reducing the losses in the power electronic converter, compared to a system where the converter has to handle the total power. In addition, the cost of the converter becomes lower. The WECS considered for analysis consist of a DFIG. The mechanical power available from a wind turbine 2 3 Pw 0.5R V C p, (1) 2 2 0.17 0.022 5.6 e 1 C p (2) V (3) where P w is the extracted power from the wind, ρ is the air density, R is the blade radius and V ω is the wind speed. C p is called the power coefficient and is given as a nonlinear function of the parameters tip speed ratio λ and blade pitch B C 3 2 p V T 0.5 ur (5) t The reactive power produced by the wind turbine is regulated at 0 MVAR. This model is well suited for observing harmonics and control system dynamic performance over relatively short periods of times. Power system model [14] is used. W r + Pitch Angle Maximum W d - Pitch Angle 0 Fig.2: Pitch Angle Control System The protection system that disconnects the turbines in case of a fault is implemented in the form of under voltage, overs peed and over current protection. The protection scheme implemented in this model disconnects the generator and its compensation unit, when the voltage at the generator terminals drops below 0.75 pu for 100 ms; the speed of the generator exceeds 105% of its rated speed (when the generator cannot export as much power as is imported through the wind, it accelerates); the voltage exceeds 1.1 pu for 100 ms, the instantaneous AC over current exceeds 10 pu., the maximum AC current exceeds 1.1 pu., the maximum AC current unbalance exceeds 0.4 times maximum AC current., the maximum AC voltage unbalance exceeds 0.05 times maximum voltage. The Power Coefficient Cp v/s Curves for Various Values of Pitch Angles are shown in Fig.3. Fig.4 shows turbine output power v/s turbine speed for pitch angle 0 deg. Fig.3: Power Coefficient C p vs Lambda 32

After the clearance of fault, the voltage recovers to normal position in the system. Fig.5 shows voltage at different locations during present case. The fault excites the inherently flexible drive train of the wind turbines to oscillations, which in the first instances after the clearance of the fault leads to a strongly reduced active power production. At the same time the compensation capacitors stay connected helping the voltage to recover. Fig.6 and Fig. 7 shows active and reactive power of wind turbines. Fig.3: Wind Turbine Power Characteristics 3. RESULTS AND DISCUSSIONS The simulation result shows the characteristic waveforms of the stator voltage, stator current, active power, reactive power, dc-link voltage, rotor speed under steady state condition. It is observed that the active and reactive powers supplied by the utility grid are decoupled and dc link voltage is maintained constant due to the control strategy made in the grid side converter. Different scenarios are simulated to assess the impact of wind power on integration with power grid. The faults simulated are 104 ms, zero impedance; phase to phase short circuits on 132KV line. The fault gets cleared by permanent disconnection of the faulted line. This is a fault situation described in Elkraft s grid connection requirements for wind farms connected to the transmission system. Case I: The situation which is simulated here is that the wind turbines are not connected to the transmission system. A phase to phase fault is simulated on 132KV line i.e. bus B5 at t=5 sec. for 104 ms. Fig.4 shows that the voltage at busbar B5 drops to zero, as it is closest to the fault location. Bus B6 is hardly affected by this fault as it is far away from the fault. The voltage at B5 gets suppressed in the beginning of the fault and after a few ms it recovers quickly after the clearance of the fault which means that they do not consume reactive power any more. The voltage at B4 recovers also relatively quickly because of the reduced reactive power demand in the first seconds. Fig.5: Voltage at different location in power system Fig.6: Active Power at Wind Turbines 1, 2 &3 Fig.7: Reactive Power at Wind Turbines 1, 2 &3 Fig.4: Voltage at different location in power system Case -II: Here the situation is simulated that 9 MW wind farm has been connected to power system. The fault conditions are kept same as before. There is substantial drop in voltage at wind turbines due to fault and wind turbine WT1 trips due to operation of protection system of turbines, which disconnects wind turbine WT1 due to AC under voltage at t=5.112 sec. Comparison of I and II As noted above, the voltage variations caused by the faults, simulated in the different cases, has a negligible impact on the power system. The frequency and hence the active power flow through the system gets affected though. An effective means of comparing the consequence of the different scenarios on the power system is comparing the active and reactive powers in the system. Fig.8-10 shows the comparison of active power at buses B4, B5 and B6 for -I and II. It is observed that 33

variation in active power at buses B4, B5 and B6 for Case-I which do not include wind turbines, is very less as compared to Case-II. The variation is about -0.05 to +0.05 for buses B4 and B5 and -0.3 to 0.1 for bus B6 during phase to phase fault for Case-I and hence cannot be predicted clearly while comparing with Case-II. The active power at buses in Case-II has a dip during fault, but oscillations die out quickly in approx. 2 secs. Fig.11-13 shows the comparison of reactive power at buses B4, B5 and B6 for various cases. The reactive power at bus B6 is most affected during A-B fault at t=5sec, but oscillations die out quickly after the clearance of fault. Fig. 11: Reactive Power at Bus B4 during different Fig.8: Active Power at Bus B4 during different Fig. 12: Reactive Power at Bus B6 during different Fig. 9: Active Power at Bus B5 during different Fig. 10: Active Power at Bus B6 during different Fig. 13: Reactive Power at Bus B5 during different 4. CONCLUSION The system performance analysis is done under steady state and for a sudden change in grid voltage. The generated stator voltages and currents, active power supplied to grid, VAR requirement for the DFIG are observed and it is concluded that with the implemented vector control strategy, the doubly fed induction generator system under simulation study is suitable under sudden change in grid voltage. This paper has presented the analyzed results on transients of a small wind power generation system connected to a low voltage power grid. Two different cases are considered examining the influence of adding 9 MW wind farm to the power system. A transient phase to phase fault was simulated and its impact on the system voltage, active and reactive power at different 34

locations in power system was investigated. The local voltage depression can hardly be noticed in other parts of the transmission system. It does however upset the wind turbines in the vicinity and cause their flexible drive trains to exhibit torsional oscillations. These oscillations manifest themselves in power fluctuation. Such power fluctuations are not only local effects but propagate through the system. It has been proven that with the inclusion of wind turbines equipped with sufficient control mechanisms, the performance of power system improves. 5. ACKNOWLEDGMENTS The authors wish to thank the authorities of Annamalai University, Annamalainagar, Tamilnadu, India for the facilities provided to prepare this paper. 6. REFERENCES [1] Bhim Singh and Shailendra Sharma Stand-Alone Wind Energy Conversion System with an Asynchronous Generator Journal of Power Electronics, Vol. 10, No. 5, September 2010. [2] Sol-Bin Lee, Kyo-Beum Lee, Dong-Choon Lee and Jang-Mok Kim An Improved Control Method for a DFIG in a Wind Turbine under an Unbalanced Grid Voltage Condition, Journal of Electrical Engineering & Technology Vol. 5, No. 4, pp. 614~622, 2010. [3] H. Akagi, "Active Harmonic Filter," In: Proceedings of the IEEE, 2005, pp. 2128-2141.B. and Plate, J. 2000. [4] J. Arrillaga and N. R. Watson, Power System Harmonics, 2nd ed. NJ:Wiley, 2003. [5] Lian, K. L. Noda, T., A Time-Domain Harmonic Power-Flow Algorithm for Obtaining Nonsinusoidal Steady-State Solutions, In: IEEE Transactions on Power Delivery, Issue 99, 2010. [6] S. A. Papathanassiou, A Technical Evaluation Framework for the Connection of DG to the Distribution Network, In: Electr. Power Syst. Res., Jan. 2007, Vol. 77, No. 1, pp. 24 34. [7] D. Schulz, R. Hanitsch, K. Moutawakkil, and C. Saniter, Power Quality Behavior of Large Wind Parks with Variable Speed Wind Energy Converter, CIRED, Barcelona, Spain, 2003. [8] T. Thiringer, T. Petru, and C. Liljegren, Power Quality Impact of a Sea Located Hybrid Wind Park, In: IEEE Trans. Energy Conversion, Jun. 2001, Vol. 16, No. 2, pp. 123 127. [9] S. A. Papathanassiou and M. P. Papadopoulos, Harmonic Analysis in a Power System with Wind Generation, In: IEEE Trans. Power Del., Vol. 21, No. 4, Oct. 2006, pp. 2006 2016. [10] V.M.Moreno, M. Liserre, A. Pigazo, and A. Dell Aquila, A Comparative Analysis of Real-Time Algorithms for Power Signal Decomposition in Multiple Synchronous Reference Frames, IEEE Trans. Power Electron., Jul. 2007, Vol. 22, No. 4, pp. 1280 1289. [11] R. S. Herrera, P. Salmeron, and H. Kim, Instantaneous Reactive Power Theory Applied to Active Power Filter Compensation: Different Approaches, Assessment, and Experimental Results, In: IEEE Trans. Ind. Electron., Jan. 2008, Vol. 55, No. 1, pp. 184 196. [12] J. Rodriguez, S. Bernet, B. Wu, J. O. Pontt and S. Kouro, Multilevel Voltage-Source-Converter Topologies for Industrial Medium-Voltage Drives, In: IEEE Trans. Ind. Electron., Dec. 2007, Vol. 54, No. 6, pp. 2930 2945. [13] L. G. Franquelo, J. Rodriguez, J. I. Leon, S. Kouro, R. Portillo and M.M. Prats, The Age of Multilevel Converters Arrives, In: IEEE Ind. Electron. Magazine, June 2008, Vol. 2, No. 2, pp. 28 39. [14] Sasi.C and Dr.G.Mohan, Power Quality Improvement of Grid Connected Wind Energy Conversion System during Transient Fault, International Journal on Energy Conversion, Jan 2013, Vol. 1, No. 1, pp 28-34. 35