VU53S; VU54S; VU443A; VU444A; VU843A; VU844A Fan Coil Valves and Actuators



Similar documents
Q309A,B; Q335C; Q340A; Q390A Thermocouples and Q313A,B,C,F Thermopile Generators

T7079A,B Solid State Remote Temperature Controllers

VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES

XE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY

UV100A Ultraviolet Air Treatment System

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types

Installation Instructions S

Automatic control equipment for HVAC systems

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Select Radiators Installation Guide

Oil and Coolant Circulating Heating System. Model - OCSM

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

VC series BALANCED HYDRONIC VALVES 2 -WAY AND 3 -WAY

V47 Series Temperature Actuated Modulating Water Valves

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

Installation Instructions

Fleck Service Manual INSTALLATION AND START-UP PROCEDURE TABLE OF CONTENTS JOB SPECIFICATION SHEET

Float and Thermostatic Traps Series H, C and X

PRESSURE REDUCING CONTROL VALVE

Many Products...One Source

G670 Intermittent Pilot Ignition Controls

Y7230A CO 2 Alarm System

Butterfly Valves PN 6/10/16 for flanged connection

THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER

AMX300 DirectConnect Mixing Valve Kits

RayClic Connection System Installation Instructions

Introduction. Angle/Flared/Sequence/Changeover Service Valves. Valves D

T822, TS822 Heating/Cooling Thermostats

Your safety and the safety of others are very important.

A99B Series Temperature Sensors

Portable Air Conditioner

3/2-way Solenoid Valve, direct-acting, NC or NO

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

RADIATOR VALVES / MANIFOLD ASSEMBLIES AND DIVERTERS

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

SunMaxx Solar Filling Station Operating Instructions

HE220A,B and HE260A,B Bypass Flow-Through Humidifier

2-Port Self-acting Temperature Control Valve Selection for Heating and Cooling Applications

Stainless Steel Single and Dual Circulation Kits

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types

3 Port Solenoid Valve

TAC Erie VT/VS PopTop Series Two Position Spring Return Valves

BERMAD Fire Protection

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

OBSOLETE. VS8420 Millivolt Gas Valve

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions

Installation Guide. Programmable Thermostat TH6220D

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

TA-FUS1ON. Fully adjustable Kvs control and balancing valves. That s just two good.

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Cartridge Valves. Solenoid Valves. Vickers. Screw-in Cartridge Valves. Maximum Pressure 210 bar (3000 psi) Maximum Flow 227 l/min (60 USgpm)

! WARNING. Before using product, read and understand instructions.

OHIO MEDICAL CORPORATION. Medical Gas Outlets. Installation and Maintenance Manual

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

Installation Instructions

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

IMPORTANT DOCUMENTATION DO NOT DISCARD!

OBSOLETE. VS8510,VS8520 Millivolt Gas Valve

RayClic Connection System Installation Instructions

Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U Technical characteristics types D and E

INSTRUCTION MANUAL IM042. Slide Rail Systems - Series A10 INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Step 1. Item 6. Item 1

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

Why and How we Use Capacity Control

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

PBX Series Quick Fit Connector Bimetallic Steam Traps

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS

JOB or CUSTOMER: ENGINEER: CONTRACTOR: SUBMITTED BY: SPECIFICATION REF: QUANTITY TAG NO. MODEL NO. GPM FEET LEAD LENGTH COMMENTS.

stainless steel pre-assembled manifolds

5800 Temperature Sensor Cable Assembly

Operator: Save these instructions for future use!

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

Operators manual Basic water heater

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

F50F Duct Mounted Electronic Air Cleaner

% ^ ) 0.55 W Low Power Solenoid Valves Aluminum, Brass, or Stainless Steel Bodies 1/4" to 1" NPT. 2/2 3/2 4/2 5/2 5/3 SERIES Low Power

Morrison Bros. Co. General Product Specifications

Direct steam injection humidifiers

Explosion-Proof Electric Unit Heaters

STATFlow. Direct-to-Drain System. For use with STATIM 2000 and STATIM 5000 Autoclaves. Installation Guide and Operator s Manual

PLATE HEAT EXCHANGER. Installation Manual. Customer Name: Serial number: Purchase order number: Project:

RUBBER SLEEVE KNIFE GATE VALVE

3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide

Transcription:

VU53S; VU54S; VU443A; VU444A; VU843A; VU844A Fan Coil Valves and Actuators APPLICATION VU Fan Coil Actuator and Valves The VU443, VU444, VU843 and VU844 Fan Coil Valve Actuators are used in conjunction with the VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors. These valves are humidity resistant and are suitable for use in condensing, noncorrosive environments. IMPORTANT These valves are not for use in systems containing dissolved oxygen. FEATURES Compact construction for easy installation. PRODUCT DATA Fits under the cover of most baseboard convectors with actuator fitted. ACTUATOR One-button, quick release. Secure 3-point, metal latch to valve body. Spring return operation. Stainless steel case and aluminum cover. Line or low voltage, rust-resistant motors. Slotted conduit hole for faster wiring. Connecting leads available up to 8 feet (2.4m) long. Manual opener for valve operation on power failure. Valve returns to automatic position when power is restored. Actuator may be reinstalled or serviced without draining the system or dissassembling the valve. VU443, VU843 actuators fit all 2-way VU53 valve bodies from /2" to 3/4". VU444, VU844 actuators fit all 3-way VU54 valve bodies from /2" to 3/4". VALVE VU53 provides 2-way, straight-through control of water. Available in normally closed or normally open configurations. VU54 provides 3-way diverting control of water. 300 psi (2,000 kpa, PN20) operating pressure rating. Patented ball seal provides long service life, soft close off. Triple O-ring seal provides three lines of defence against corrosion and water leakage around driveshaft. Quick opening flow curve. Choice of sweat brass end connections. Contents Application... Features... Specifications... 2 Ordering Information... 2 Installation... 5 Operation... 6 Checkout... 7 Copyright 0-999 Honeywell Ltd. All Rights Reserved

SPECIFICATION ACTUATOR Models: VU443, VU843: for use with VU53 2-way valves. VU444, VU844: for use with VU54 3-way valves. VALVE Models: VU53: 2-way, normally closed valves. VU54: 3-way diverting valves. Actuator Electrical Rating & Connection: 0 VA Maximum Model Control Circuit Current Draw (A) Connection/Leads VU443A VU444A 20V, 60Hz 0.07 VU843A VU844A 24V, 50-60 Hz 0.32 6" motor leads standard. 8", 36" or 96" Leadwires optional. Note: Motors for all the above models are Class A, Plated. Type 2-WAY, Normally Closed; or Open; (VU443A,VU843A) 3-WAY, Diverting; or Mixing; (VU444A,VU844A) Valve Styles, Sizes, Flow Capacity Rating (C v )& Maximum Close-off Pressure Rating (psi): Pipe Connections Flow Capacity Rating Maximum Closeoff Pressure* Model Type End Fittings Size C v k v psi kpa VU53S VU54S 2-WAY Normally Closed 3-WAY Diverting SWEAT SWEAT /2" 3.5 3.0 20 38 3/4" 3.5 3.0 20 38 3/4" 8.0 7.0 0 69 /2" 4.0 3.4 20 38 3/4" 7.0 6.0 2 83 Maximum Ambient @ Fluid Temperature Rating: Standard models (with class A motor): 04 F(40 C) ambient @ 200 F(94 C) fluid. Minimum Ambient Temperature: 34 F( C) Shipping and Storage Temperature: -40 C to 65 C (-40 F to 50 F). Atmosphere: Non-corrosive, non explosive, condensing. Noise Rating: Low Noise - non obtrusive. Materials: Case: stainless steel. Cover: aluminum. Sector gear: reinforced with KEVLAR brand fiber. KEVLAR is a Dupont registered trademark. Dimensions: See Fig.. ORDERING INFORMATION Max. Fluid Temperature: Standard Models (with Class A motor): 200 F(94 C) fluid @ 04 F(40 C) ambient. Min. Fluid Temperature: 34 F( C) for all models. Max. Operating Pressure Rating: 300 psi (2000 kpa), PN20. Flow Characteristics: Quick opening for on-off application. Material: Valve body: forged brass. Drive shaft stem: brass. Ball plug: Buna-N rubber. O-ring seals: EPDM rubber. Service Medium: Suitable for hot and chilled water with up to 50% glycol. Dimensions: See Fig.. Approvals: CSA C/US Certified. For ordering information when purchasing replacement and modernization products from your TRADELINE wholesaler or your distributor, refer to the TRADELINE Catalog or price sheets for complete ordering number, or specify:. Order number. 2. Voltage and frequency. 3. Size and type of end connections. 4. Cv (kv) rating. 5. Lead length if different from standard. 6. Replacement parts, if needed. If you have additional questions, need further information, or want to comment on our products or services, please write or phone:. Your local Honeywell Home and Building Control sales office (check white pages of phone directory). 2. Home and Building Control Customer Logistics Honeywell Inc., 885 Douglas Drive North Minneapolis, Minnesota 55422-4386 (62) 95-000 In Canada Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario MV 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A. 2

Head(Ft.) VU53F,N,S,T; VU54F,N,S,T; VU443A; VU444A; VU843A; VU844A -3/4-3/4-3/4-3/4 7/8 DIA. 2-3/8 (44) (44) (44) (44) (22) (60) 2 3/8 (0) 3-3/4 3/8 -/2 (33) (0) (38) VU Actuator. B AB A A 7/8 (23) 2-Way B 3-Way 5/32 (2) VU53 Valve with Actuator. VU53 and VU54 Valve Dimensions with Actuator. VALVE BODY SIZE A B /2" Sweat -5/6 (33) -5/6 (33) 3/4" Sweat -3/8 (35) -/6 (43) 2 HEIGHT NEEDED TO REMOVE ACTUATOR OR COVER. OPENING FOR /2 IN. CONDUIT ON OPPOSITE SITE OF MANUAL LEVER FOR ALL MODELS. Fig. : Mounting Dimensions in in. (mm). How to Find Valve Pressure Drop ANSI units The pressure drop in psi, or feet of water can be calculated from Fig. 2 as follows:. Calculate the flow rate to cool and dehumidify. 2. Determine the Cv rating of the valve. 3. Select the graph corresponding to the Cv rating of the valve. 4. Determine the pressure drop across the valve using the following procedures for calculating pressure drop.. Locate the flow rate at the bottom of the graph. 2. Draw a line up from the flow rate to the intersection of the curve. 3. Draw a line from the intersection to the left edge of the graph to determine the pressure drop in psi, or to the right edge to determine the pressure drop in feet of Head. (Pressure drop in feet of Head = psi X 2.2.) Pressure Drop (psi) 00 50 30 0.0 5 3 0.5 0.3.0Cv 3.5Cv 4.0Cv 8.0Cv 7.0Cv 28 90 43.5 2.8 3. 8.7 4.4 2.2 0.9 0.4 0. 0.2 0.0 5.0 0.0 5.0 20.0 25.0 Flow Rate (USgpm) Fig. 2. Flow characteristics of VU53, VU54 valves, ANSI units. 3

How to Find Valve Pressure Drop SI (metric) units (Fig.3). Calculate desired flow through valve in m 3 /h or litres/ second. L/s = 3.6 X m 3 /h. 2. Determine the kv rating of the valve. 3. Select the graph corresponding to the kv rating. 4. Determine the pressure drop across the valve by:. Locate the flow rate (in m 3 /h on the left edge of the graph). 2. Draw a line from the flow rate to the intersection of the kv line. 3. Draw a line from the intersection to the bottom to determine the pressure drop in kpa or Bar. 0 36 5 kv7.0 kv6.0 2 8 3 kv3.4 kv3.0 0.8 Flow(m/h) 3 kv0.8 7. 3.6 Flow (L/s) 0.5 0.3 2.2. 0.9 0.7 kpa Bar 0. 3 5 0 30 50 00 300 0.0 0..0 Pressure Drop 0.4 Fig. 3. Flow characteristics of VU53, VU54 valves, SI units. INSTALLATION When Installing this Product. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician. 4. After installation is complete, check out product operation as provided in these instructions. CAUTION. Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage. 2. On 24V systems, never jumper the valve coil terminals even temporarily. This can burn out the heat anticipator in the thermostat. 3. Wear safety glasses to protect eyes from injury when removing or installing the large spring clip that holds the actuator mounting plate to the valve body. Use proper snap ring pliers to remove or install spring clip. Mounting The valve can be mounted in any position on a vertical line. See Fig. 5. If the valve is mounted horizontally; the actuator must be even with or above the center line of the piping. Make sure to leave enough room above the actuator to remove the cover or actuator for servicing. Mount the valve directly in the tube or pipe. Make sure that the flow through the valve is in the direction indicated by the arrow stamped on the valve body. VERTICAL PIPING HORIZONTIAL PIPING Fig. 5 Mounting positions. M062 4

On diverting valves, the three fittings or ports are labeled on the bottom of the valve body casting. Port AB is the inlet port and is open at all times. Port A is closed and port B is open when the valve is de-energized. Refer to the equipment manufacturer instructions to determine which port (A or B) should be connected to the coil bypass. Sweat Copper Models. Use new, properly reamed pipe, free from dents or corrosion. 2. Place the valve on the pipe. Rotate valve stem so that the shaft slot points at the notch in the side of the body (90 to flow directions.) See Fig. 6. This protects the plug inside the valve by removing it from the seat. 3. Sweat the joints, keeping the outer surface free from solder. DO NOT use silver solder because of the high melting temperature required. NOTCH SHAFT SLOT IN VALVE STEM POINTING TO NOTCH ON SIDE OF VALVE BODY NOTCH ACTUATOR COUPLING ENSURE SHAFT SLOT POINTS TOWARDS NOTCH ON SIDE OF BODY FOR FITTING INTO ENGAGING SHAFT Fig. 7 Installing new actuator. REMOVING ACTUATOR FROM THE VU-SERIES VALVE BODY ASSEMBLY (See Fig. 8): Fig. 6 Slot position. To Install & Remove Actuator INSTALLING ACTUATOR ON VU-SERIES VALVE BODY ASSEMBLY(See Gig. 7) :. Orient slot in shaft of VU-series valve body toward notch in side of body (i.e. 90 to water flow.) See Fig. 7. This lifts the ball off seat, prevents damage to the ball seat while soldering, and makes actuator attachment easier. 2. Install valve body into pipe. 3. Wiring connections may be made either before or after actuator installed on valve body. 4. Place manual operating lever on the actuator in the MAN. OPEN position. 5. Line up motor coupling to slot in shaft of body and fit the head onto the valve body, ensuring that the shaft seats correctly. (See Fig. 7) 6. Snap actuator onto body by pressing down. 7. Make wiring connections. Refer to wiring section for proper instructions. 2. DEPRESS AUTO OPEN. PLACE MANUAL 3. LIFT ACTUATOR Inspect the actuator installation and the valve body to ensure that all connections and adjustments have been correctly made. Adjust the thermostat or controller connected to the valve so that the valve runs through its cycle. Make sure the valve runs smoothly and positively from closed to open to closed again. Fig. 8 Removing actuator from valve 5

NOTE! It is not necessary to drain the system if the valve body assembly remains in the pipeline.. Switch power supplies OFF. Disconnect electrical leads, carefully noting the position and colour of each lead. 2. Place the manual operating lever in the MAN. OPEN position. See Fig. 8. 3. Remove actuator by depressing locking button and lifting straight up. Wiring Disconnect the power supply before connecting wiring to prevent electrical shock or equipment damage. All wiring must comply with local codes and ordinances. See Fig. 9 and 0 for typical hookups. TO ATTACH FLEXIBLE CONDUIT. Strip cable jacket. 2. Fit conduit strain relief onto cable. 3. Slide strain relief nut over wires. 4. Connect cable and actuator wires. 5. Slide cable wires down through slot in the wiring hole, so that the strain relief nut is inside the actuator housing. 6. Secure nut onto strain relief. 7. Install actuator cover. L (HOT) FAN COIL THERMOSTAT (TYPICALY T4039, T6380, T6570) L ELECTRONICS H / C L2 OPERATION CAUTION ON 24V SYSTEMS, NEVER JUMPER THE VALVE COIL TERMINALS EVEN TEMPORARILY. THIS CAN BURN OUT THE HEAT ANTICIPATOR IN THE THERMOSTAT. Automatic Operation On a call for heat or cool by the fan coil thermostat, the valve motor operates, opening the valve. When the call ends, the valve closes by integral spring return. Manual Operation The 2-way normally closed and 3-way motorized valve actuators can be opened manually by lifting the manual opening lever over the stop and pushing slowly and firmly to the MAN. OPEN position. The stop permits the valve to be locked in the open position. The valve returns to automatic position when it is energized. Normally Closed Models With the manual opener set to AUTO and the actuator energized, the A port is opened as shown in Fig. A and 2A. When the actuator is de-energized, a spring-return mechanism drives the valve to the port A closed position as shown in Fig. B and 2B. The valve can also be opened with no electrical power by moving the manual opening lever over the stop and pushing slowly and firmly to the MAN. OPEN position. The stop permits the valve to be locked in an open position. The valve returns to the automatic position L2 VU448 ACTUATOR MOTOR IN OUT IN OUT OPEN POSITION (POWERED) Fig. A CLOSED POSITION (UNPOWERED) Fig. B M595 Fig. 9 Typical wiring for VU440-series actuator. Fig. Actuator operation for normally closed 2-way valve. T822 T822 T822 L (HOT) L2 A B A B 2 2 2 OUT OUT 2 VU VALVE VU VALVE VU VALVE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONNECT BLACK LEADWIRE TO THERMOSTAT. Fig. 0 T822 Thermostat, VU80-series actuator hookup. A B IN A B IN FLOW-THROUGH SERVICE PORT FLOW-THROUGH BYPASS PORT (POWERED) (UNPOWERED) Fig. 2A Fig. 2B Fig. 2 Actuator operation for normally closed 3-way valve. 6

CHECKOUT Set to heating mode. Raise the setpoint on the zone thermostat above the room temperature to initiate a call for heat. 2. Observe all control devices the valve should open. 3. Lower the setpoint on the zone thermostat below the room temperature. 4. Observe the control devices. The valve should close. Set to cooling mode. Lower the setpoint on the zone thermostat below the room temperature to initiate a call for cooling. 2. Observe all control devices the valve should open. 3. Raise the setpoint on the zone thermostat above the room temperature. 4. Observe the control devices. The valve should close. SERVICE This valve should be serviced by a trained, experienced service technician.. If the valve is leaking, drain the system and check to see if the O-ring needs replacing. 2. If the gear train is damaged, replace the entire actuator. See the Installation section. If the motor is burned out, replace the motor. NOTE: Honeywell fan coil valves are designed and tested for silent operation in properly designed and installed systems; however, water noises can occur as a result of excessive water velocity or piping noises can occur in high temperature (higher than 22 F (00 C)) systems with insufficient water pressure. Valves are designed for normal cycling operations. Product life will be shortened if energized continuously. VU53F,N,S,T; VU54F,N,S,T; VU443A; VU444A; VU843A; VU844A 7

By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys fees, arising out of, or resulting from, any modification to the literature by you. Home and Building Control Home and Building Control Honeywell Asia Pacific Inc. Honeywell Inc. Honeywell Limited-Honeywell Room 323-3225 Honeywell Plaza Limitée Sun Hung Kai Centre P.O. Box 524 35 Dynamic Drive No. 30 Harbour Road Minneapolis MN 55408-0524 Scarborough, ON MV 4Z9 Wanchai Canada Hong Kong Honeywell Latin American Division Miami Lakes Headquarters Honeywell Europe S.A. 4505 Commerce Way Suite 500 3 Avenue du Bourget Miami Lakes FL 3306 B-40 Brussels Belgium -0 MK/KT -99 Printed on recycled paper containing at least 0% post-consumer paper fibers. www.honeywell.com www.honeywell.ca/water_products