New-generation Integrated Monitoring and Control System



Similar documents
Completion of High-efficiency Coal-fired Power Plant

Latest Power Plant Control System

Design and Operating Experience of the Latest 1,000-MW Coal-Fired Boiler

REMOTE MONITORING AND CONTROL OF THE KAKKONDA GEOTHERMAL POWER PLANTS

OROT RABIN POWER STATION UNITS x 350 MW

Combined Cycle Control Overview

Recent Technologies in Nuclear Power Plant Supervisory and Control Systems

Tips for burner modulation, air/fuel cross-limiting, excess-air regulation, oxygen trim and total heat control

Permissible ambient temperature Operation Storage, transport

New Technologies for Electric Power Distribution Systems

Operational Flexibility Enhancements of Combined Cycle Power Plants. Dr. Norbert Henkel, Erich Schmid and Edwin Gobrecht

HC900 for Boiler Control Applications

Completion of Hitachinaka Thermal Power Station Unit No. 1

Wide-area Integrated SCADA System Designed to Improve Availability and Flexibility

ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES

Completion of SCR System for Ninghai Power Plant Unit 4 in China

Integration of Supervisory Control and Data Acquisition Systems Connected to Wide Area Networks

Dynamic Behavior of BWR

Control of Boiler Operation using PLC SCADA

SRS: THE STANDARDIZED REPOWERING SOLUTION FOR 300MW STEAM POWER PLANTS IN RUSSIA. Matthias Fränkle Siemens Power Generation (PG), Germany

Design and Test Operation Performance of 1,500 C Class Gas Turbine Combined-Cycle Power Plant:

Latest Low-NOx Combustion Technology for Pulverized-coal-fired Boilers

Railway Business Strategy and R&D in Europe

CSP-gas hybrid plants: Cost effective and fully dispatchable integration of CSP into the electricity mix

water is cooled in a secondary cooling control tasks: use of seawater. Treatment of the seawater formation of algal vegetation.

Operating Performance and Latest Technology of DeNOx Plants for Coal-Fired Boilers

Improving Steam Methane Reformer Performance with the ZoloSCAN-SMR

O&M Service for Megasolar Power Plants and Precise Monitoring Techniques for PV Modules

SPPA-T3000 Control System The Benchmark in Controls

Webpage: Volume 3, Issue IV, April 2015 ISSN

Demonstration tests of microgrid systems using renewable energy for small remote islands

Abstract. s: phone: , fax:

HC900 Boiler Control. Background. Solution. Application Brief Industry: Manufacturing

Thermodynamical aspects of the passage to hybrid nuclear power plants

Making power plants energy efficient

Assessment of Solar-Coal Hybrid Electricity Power Generating Systems 13

Natural Gas Conversions of Existing Coal-Fired Boilers

Best Choice BENSON BOILER. Excellent performance features make the Benson boiler the most widely used type of once-through boiler

Improved Passenger Services for Local Existing Railways Uchibo Line Transportation Management System (Operation Control and Passenger Services)

525-MVA Generator-motor and Thyristor Starter Put into Service at the Tokyo Electric Power Co., Inc. s Kannagawa Hydroelectric Power Station

Performance Analysis of Thermal Power Station: Case Study of Egbin Power Station, Nigeria

Steam Power Plants as Partners for Renewable Energy Systems

Industrial IT for Substation Automation & Protection

Boiler Calculations. Helsinki University of Technology Department of Mechanical Engineering. Sebastian Teir, Antto Kulla

Alain Nifenecker - General Electric Manager Controls Engineering

The Optical Submarine Repeater and Its Associated Technologies

OPPORTUNITIES FOR HEAT RATE REDUCTIONS IN EXISTING COAL- FIRED POWER PLANTS: A STRATEGY TO REDUCE CARBON CAPTURE COSTS

Features. Emerson Solutions for Abnormal Situations

Pulverized Coal Pipe Testing and Balancing

The Technology and Business of Power Andrew Valencia, P.E. Lower Colorado River Authority

Making power plants energy efficient ABB, integrated power and automation solutions

DeltaV SIS for Burner Management Systems

Hybrid Modeling and Control of a Power Plant using State Flow Technique with Application

SOLARPACES: Development of an integrated solar thermal power plant training simulator

ENERGY EFFICIENCY IN POWER PLANTS

SuperIOr Controller. Digital Dynamics, Inc., 2014 All Rights Reserved. Patent Pending. Rev:

PROCESS DATA VISUALIZATION AND MONITORING USING INTERNET

ABB PSPS Erich Steinmann; Generator control-2013

Hybrid Solar and Fossil Power Generation

Overview of Integrated Coal Gasification Combined-cycle Technology Using Low-rank Coal

OilonChooser Operating Instructions

Design Feature and Prototype Testing Methodology of DHIC s Nuclear I&C System

Automation Technology Helps Precast Producer Reduce Energy Consumption and Lower Costs

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES


Accelerating your engineering workflow. Engineering solutions for industry

OZW30. Central Unit SYNERGYR

PIPELINE ENGINEERING - Pipeline System Automation and Control - C. Bruce Warren and Mike S. Yoon PIPELINE SYSTEM AUTOMATION AND CONTROL

Ship Propulsion/Electric Power Hybrid System Recovering Waste Heat of Marine Diesel Engine

ON-LINE MONITORING OF POWER PLANTS

EVALUATION OF GEOTHERMAL ENERGY AS HEAT SOURCE OF DISTRICT HEATING SYSTEMS IN TIANJIN, CHINA

M&V of Hot Water Boiler Plant. Boban Ratkovich, P. Eng, CEM, BESA, LEED AP President CES Engineering Ltd

Power Plants. BENSON Once-Through Heat Recovery Steam Generator. Power Generation

DESIGN CHALLENGES AND OPERATIONAL EXPERIENCE OF A MEGA MED SEAWATER DESALINATION PLANT IN TIANJIN

Soft PLC Research And Development System Based On PC ZHOU Wenjun 1, a

INFORMATION UNIFICATION BE- TWEEN ENTERPRISE RESOURCE PLANNING SYSTEM AND PRODUC- TION CONTROL SYSTEM

Project description. Power Electronics for Reliable and Energy efficient Renewable Energy Systems

The Use of Hybrid Regulator in Design of Control Systems

The product segments Heating, ventilation, air conditioning. Control Products & Systems OEM. Answers for infrastructure.

This paper describes an instrumentation system concept which should be capable of early detection of a leak-before* break in main steam lines.

FOR IMMEDIATE RELEASE

CHAPTER 1 INTRODUCTION

Process Heater Burners, Flare Systems, Thermal Oxidizers and Catalyst Systems. Combustion Technology

Development of Coal Gasification System for Producing Chemical Synthesis Source Gas

RELIABLE AND EFFICIENT STEAM GENERATION SYSTEMS FOR MODERN UTILITY SERVICE

NRG Energy Center Minneapolis

Process Alarm Solutions

5. State the function of pulveriser. The pulverisers are the equipments which are used to powdered coal.

Disturbance Recoder SPCR 8C27. Product Guide

Traffic Management Solutions for Social Innovation Business

A CASE STUDY: PERFORMANCE AND ACCEPTANCE TEST OF A POWER AND DESALINATION PLANT. Keywords : Power Plant, Boiler Capacity, Electrical Power

Skoda Supercritical Steam Turbine 660 MW

Big Data Collection and Utilization for Operational Support of Smarter Social Infrastructure

Short-term Forecast for Photovoltaic Power Generation with Correlation of Solar Power Irradiance of Multi Points

How To Reduce Coal Power Plant Emissions

Siemens Steam Turbine SST-600

NAWTEC CONCEPTS AND EXPERIENCES FOR HIGHER PLANT EFFICIENCY WITH MODERN ADVANCED BOILER AND INCINERATION TECHNOLOGY

Journal of Chemical and Pharmaceutical Research, 2014, 6(5): Research Article

Torino Nord. Cogeneration Plant. The gas turbine. The steam generator. The Torino Nord cogeneration plant produces electricity and heat for district

Transcription:

Hitachi Review Vol. 54 (05), No. 3 145 New-generation Integrated Monitoring and Control System Shigeru Takahashi Satoru Shimizu Takaaki Sekiai OVERVIEW: Hitachi delivered a new-generation integrated monitoring and system to Shanghai Municipal Electric Power Company s Waigaoqiao Power Station in Shanghai, China. Built around the HIACS- 5000M (Hitachi Integrated Autonomic Control System-5000M), the system not only provides a powerful supervisory, operation, and system for power plant equipment, it also supports enhanced plant operating efficiency and power plant management operations. Enhanced reliability and maintainability go without saying, but the system also introduces significantly more advanced capabilities for manipulating information that supports improved plant operation efficiency and better management capabilities for dealing with the liberalization of electric power transactions and sales. This power plant is a 900-MW large-capacity coal-fired supercritical plant, and is intended to serve as a model for future thermal power plant construction in China. INTRODUCTION SHANGHAI Municipal Electric Power Company s Waigaoqiao Power Station Units 1 and 2 began commercial operation on April and September 22, 04, respectively. The two 900-MW large-capacity supercritical coal-fired power plants were built with financial assistance from The World Bank Group. s, generators and a boiler for the plant were supplied by German manufacturers, and the I&C (instrumentation and ) system was supplied by Fig. 1 Inside of Central Monitoring and Control Room Set up for New-generation Integrated Monitoring and Control System. All monitoring and equipment and functions for two plant units are centralized in one room featuring large-screen displays.

New-generation Integrated Monitoring and Control System 146 B NCS C A ADS Coal yard Supervisory information system Duplicated Terminals server for operation 5 sets Out of scope Management information system Server 10 sets Router Fire wall Control Out of scope Other system Internet SMEPC Instructor Local operator Simulator system Engineer 2 DCS DEH Exchanger Exchanger Exchanger Large screen display : Data link : Hardwired Process model computer I/O system 2 sets Electrical panels I/O system A B C PC sets Engineer for simulator DCS operator 6 sets DEH operator 2 sets Unit 1 DCS Manmachine interface µ NETWORK-100 Common DCS Manmachine interface µ NETWORK-100 Unit 2 DCS Manmachine interface µ NETWORK-100 (1) (8) (1) (16) (1) (8) Out of scope NCS: network computer and monitoring system ADS: automatic dispatch system DEH: digital electro-hydraulic system SMEPC: Shanghai Municipal Electric Power Company I/O: input and Fig. 2 Overall System Configuration of the New-generation Integrated Monitoring and Control System. All DCSs, SISs, MISs, and subsystems are organically interconnected by a high-speed, large-capacity network. Hitachi. In China as elsewhere, greater demands are being placed on I&C systems. In addition to supervisory, operation, and capabilities, clients are also demanding more advanced capabilities for manipulating information that supports improved operating efficiency, better plant management operations, and other capabilities. Even in terms of performance specifications, the requirements of the Waigaoqiao project were more exacting than the required performance specifications of Japan. OVERVIEW OF NEW-GENERATION INTEGRATED MONITORING AND CONTROL SYSTEM FOR WAIGAOQIAO POWER STATION The integrated monitoring and system consists of a DCS (distributed system) that monitors and s the plant status, a SIS (supervisory information system) that keeps the plant operating at peak efficiency through optimal load distribution of each plant unit, an MIS (management information system) that supports management operations with a full range of office automation functions including management, recording, searching plant data, management of documentation, e-mail, electronic bulletin-board capabilities, and more. The plant simulator system that is linked to plant data via the MIS, and various plant subsystems such as the water treatment system and a coal-handling system. All of these systems are interconnected by a highspeed large-capacity network enabling centralized monitoring by the DCS, and all constituent functions and systems to organically interwork (see Fig. 2). FEATURES OF NEW-GENERATION INTEGRATED MONITORING AND CONTROL SYSTEM DCS A DCS is the heart of a power plant s I&C system, and for this, we used Hitachi s HIACS-5000M, which has proven to be very effective in plant installations in Japan and throughout the world. The proposed HIACS- 5000M has the following features:

Hitachi Review Vol. 54 (05), No. 3 147 (1) The CPUs (central processing units) supporting the DCS are thoroughly distributed and are implemented in a double redundant configuration to ensure safe and continuous operation of the plant. (2) The network is connected to these CPUs through a high-speed and large-capacity optical network with a transmission rate of 100 Mbps. Because this network provides a loop-back function, possible malfunctions are avoided when cables break, communication equipment breaks down, or when other similar problems occur during transmission. Thus, communication can continue without a significant system disturbance. (3) An APS (automatic plant startup system) was installed to promote plant automation. Moreover, a rational and excellent operability HMI (humanmachine interface) system was offered. All plant operations can mainly be done on the HMI system, which features 70-inch 6 multi-screens. (4) The DCS is connected to some subsystems including the water treatment system, the coal handling system, and the fuel oil system over redundant optical fiber lines so that all of the systems can be centrally monitored and operated from the DCS. With this arrangement, both plant units can be operated and monitored by one supervisor and four operators. (5) An RTB (remote terminal block) is used for the connection between the DCS and the field, so the number of cables and the cost of construction are significantly lower. (6) We applied a digital protection system with Hitachi s dedicated module for boiler protection. The dedicated module is triple redundant with each system separate and independent so that the protective functions will not be lost in the event of a single failure or malfunction. Thus, high reliability and maintainability is ensured. The trip causes are input to a trip interlock in each dedicated module, and the trip signals from each dedicated module are initiated through 2 out of 3 logic trip circuits. Thus, its reliability is also guaranteed. (7) Hitachi s experience with super critical plant has proven useful with technology. Therefore, the response to the demand for electric power systems has been improved. Runback and FCB (fast cutback) functions are applied to prevent abnormalities from being generated in the plant equipment and the electric power system. These functions were verified to be effective in the commissioning test. The FCB function was first successfully applied in China. It led to an improvement in dealing with abnormalities in the electric power system. Supervisory Information System, Management Information System, and Simulator For convenience in carrying out actual operations, domestic Chinese manufacturers supplied these systems. The SIS carries out processing and managing realtime data from the equipment at the plant s six existing units, also calculates performance, monitors performance, analyzes the economic factors, and enforces the optimum load distribution of each unit. The MIS creates an open database using the data collected in real time by the SIS, and also supports enterprise resource capabilities as well as data storage and retrieval functions. Central plant management has access to this information and uses it to support policy and decision making for the plant. The system is also capable of generating electric power rate estimates supporting future power transactions and sales, and exchanging information not only within the plant but with the Shanghai Municipal Electric Power Company and government agencies as well. The simulator is capable of simulating all processes of a 900-MW capacity supercritical plant with a high degree of accuracy. In addition, system software and new application software when equipment is upgraded or modified can be directly uploaded to the simulator with all changes immediately reflected by the simulator without additional ming. The simulator is capable of simulating any and every process led from the central room on a one-to-one basis, and thus is extremely effective for testing and trying out operator actions, improved incident processing capabilities, and systems. CONTROL TECHNOLOGIES THAT SATISFY OTHER COMPANIES BOILER CONTROL AND MORE RIGOROUS CONTROL PERFORMANCE STANDARDS Overview Let us next take a closer look at Hitachi s technologies. The boilers used for the Waigaoqiao project are structurally very different from the boilers manufactured by Hitachi. In addition, the boiler scheme provided by the client was also very different from Hitachi s conventional approach. Fig. 3 summarizes the key differences. At the same time, the performance specifications stipulated in the purchase agreement

New-generation Integrated Monitoring and Control System 148 Hitachi s standard Governor Waigaoqiao project Governor Fig. 3 Comparison of Hitachi and Waigaoqiao Project s. The boilers are substantially different in structure, combustion method, and method. structure X X Fuel X-X cross-section Twice-through type Fixed burner Facing combustion Control method Water-fuel ratio scheme scheme Fuel Tower type Tilting burner Up-down variable angle Corner combustion were extremely rigorous. According to the specifications, for example, the permissible value for the main steam deviation at a 3% per minute load change is ±0.2 MPa, and the permissible range for main steam deviation is within +8 and 5. By comparison, the usual guaranteed performance specifications at commercial thermal power plants in Japan are ±0.8 MPa for the main steam deviation, and +8 and 14 for the main stream deviation. Hitachi was able to meet this challenge by leveraging and extending its considerable expertise in plant simulation technology. Analysis by Simulation For this project, we started by constructing a boiler model. The basic challenge was to develop a model that could simulate the characteristics of a tilting burner that was used in the boilers of the Waigaoqiao project. A tilting burner is essentially a method of ling reheater steam by changing the angle of the burner to alter the heat distribution inside the furnace. Hitachi has never used this method, so the simulation model had to be developed from scratch. We succeeded in developing an effective tilting burnerbased boiler model by first partitioning a furnace model for different burner alignments so we could simulate changes in the heat-transfer amounts attributable to variations in the burner angle, then calculating the furnace transient gas s of each element of the partitioned model. Next we investigated the system using the new boiler model. For this project, the basic scheme for the boiler was provided by the client. For once-through boilers of the type used in Waigaoqiao project, the steam is determined by the ratio of fuel to feedwater. Hitachi s this ratio by changing the fuel as an indicator of steam, but the client stipulated an alternative approach of changing the feedwater as an indicator of enthalpy. We considered three schemes for constructing a master system based on the boiler method stipulated by the client: follow : generator is led by the turbine, and main steam is led by the boiler. (1) follow : main steam is led by the turbine, and generator is led by the boiler. (2) Coordinated : disadvantages of the boiler follow and turbine follow are corrected by adding compensation to both the turbine and boiler based on the turbine follow. (3) First we incorporated the boiler method stipulated by the client in the simulator, then carried out simulation analysis of different configurations of the master schemes. Through the analysis we derived evaluation indices determining: (a) whether the performance guaranteed value was fulfilled, or (b) which scheme had to be adjusted in order to fulfill the guaranteed value.

Hitachi Review Vol. 54 (05), No. 3 149 Output target set point valve input signal Superheater inlet steam enthalpy set point (MW) (MP) 1000 target set point Deviation 30 5.2 MPa 580 Reheater steam Guaranteed range 10 0 10 30 50 60 0 10 30 50 60 Fig. 4 Follow Control Scheme. is led by the turbine and main steam is led by the boiler. Output target set point valve input signal Superheater inlet steam enthalpy set point (MW) (MPa) 1000 target Deviation 158 MW set point Deviation 30 0.1 MPa 580 Reheater steam Guaranteed range 10 0 10 30 50 60 0 10 30 50 60 Fig. 5 Follow Control Scheme. is led by the boiler and main steam is led by the turbine. We found that with the boiler follow, the generation follow performance improved during load changes, but the changes in steam and steam increased (see Fig. 4). Both the turbine follow and coordinated showed good prospects that the performance guaranteed values could be satisfied. At the same time, we should note that one characteristic of the turbine follow method is that the on generator is delayed (see Fig. 5). Note too that, although coordinated yields better generator follow performance than the turbine, the coordinated is somewhat more difficult to adjust (see Fig. 6). Table 1 compares the differences. Having obtained simulation analysis results as outlined above and formulated system adjustment guidelines through trial adjustments of systems based on the simulation results, we

New-generation Integrated Monitoring and Control System 150 Fig. 6 Coordinated Control Scheme. Disadvantages of boiler follow and turbine follow are corrected by adding compensation to both the turbine and boiler contnrol based on the turbine follow contnrol. set point Output target Coordinated valve input signal (MW) (MPa) 1000 Superheater inlet steam enthalpy set point target Deviation 35 MW set point Deviation 30 0.2 MPa 580 Reheater steam Guaranteed range 10 0 10 30 50 60 0 10 30 50 60 TABLE 1. Comparison of Master Control Schemes follow or coordinated is effective for ling main steam and. Control scheme Simulation results Control deviation Reheat steam follow input NG 5.2/ 5.2 MPa 3.8/ 5.6 3.3/.1 24.4/ 78.2 MW follow input are now ready to conduct actual trial operation adjustment tests. Site Commissioning Results In the actual equipment for testing, we incorporated circuitry for all of the schemes that we considered in the simulation analysis so that we could freely select whatever scheme we wanted to test. The actual trial operations were done using the turbine follow scheme that was shown OK 0.0/ 0.1 MPa 3.0/ 1.4 3.0/ 0.7 5.5/ 158.3 MW Coordinated input/ turbine OK 0.0/ 0.2 MPa 6.9/ 4.6 7.6/ 4.7 24.4/ 33.5 MW Output (MW) (MPa) Temperature () 900 700 500 22 18 16 14 550 set point set point MW 8 MW (2%/min) deviation ± 0.1 MPa 530 deviation ± 5 0 10 30 50 60 Fig. 7 Example Trial Operation Results. and satisfy the performance specifications as predicted by the simulation analysis.

Hitachi Review Vol. 54 (05), No. 3 151 Actual operation s Simulator Steam Steam 550 Air Flow (kg/s) Flow (kg/s) 500 500 300 50 45 0 10 30 50 60 70 (MPa) 530 555 545 535 14 13 12 Calculated results Reheater steam Calculated results Calculated results 0 10 30 50 60 70 Fig. 8 Simulator Verification Using Site Commissioning. Actual plant process behavior closely corresponds to the plant behavior predicted by developed simulator. to be advantageous for ling the main steam and. Fig. 7 shows an example of the trial operation results. Just as the simulation analysis predicted, the main steam and performance guarantee specifications were satisfied. In order to verify the suitability of the simulator, we compared data yielded by the simulator against actual measured data. Fig. 8 shows some of the results. One can see that the simulator developed for this Waigaoqiao project yields acceptably accurate results even with respect to dynamic behavior. CONCLUSIONS This article provided an overview of a newgeneration integrated monitoring and system that Hitachi supplied to Shanghai Municipal Electric Power Company s Waigaoqiao Power Station in Shanghai, China. Present-day China is witnessing remarkable growth and demand for more information-intensive systems and electric power, and we can anticipate increased demand from the mainland for the type of system described here. Hitachi is well positioned to provide such systems based on reliability and experience to meet this demand. Although we successfully met the challenge of more rigorous performance specifications through the technologies described here, we must redouble our efforts if we are to keep ahead of the competition and develop products that satisfy even more exacting performance specifications in the years ahead. ABOUT THE AUTHORS Shigeharu Takahashi Joined Hitachi, Ltd. in 1978, and now works at the Power Plant Control Systems Engineering Department, the Information & Control Systems Division, the Information & Telecommunication Systems. He is currently engaged in engineering work on thermal power plant systems. Mr. Takahashi can be reached by e-mail at takahashi_shigeharu@pis.hitachi.co.jp. Satoru Shimizu Joined Hitachi, Ltd. in 1994, and now works at the Power Plant Control Systems Engineering Department, the Information & Control Systems Division, the Information & Telecommunication Systems. He is currently engaged in engineering work on thermal power plant systems. Mr. Shimizu is a member of the Institute of Electrical Engineers of Japan (IEEJ), and can be reached by e-mail at satoru_shimizu@pis.hitachi.co.jp. Takaaki Sekiai Joined Hitachi, Ltd. in 02, and now works at the Coal Science Project, the Plant Analysis Group, the Power & Industrial Systems R&D Laboratory, the Power Systems. He is currently engaged in R&D of systems for thermal power plants. Mr. Sekiai is a member of The Society of Instrument and Control Engineers (SICE), and can be reached by e-mail at takaaki_sekiai@pis.hitachi.co.jp.