Fisher FIELDVUE DLC3010 Digital Level



Similar documents
Fisher FIELDVUE DLC3010 Digital Level

Fisher FIELDVUE DVC2000 Digital Valve

Fisher 3710 and 3720 Positioners and 3722 Electro-Pneumatic Converter

Fisher 846 Electro-Pneumatic Transducer

Simulation of Process Conditions for Calibration of Fisher Level Controllers and Transmitters Supplement to 249 Sensor Instruction Manuals

Fisher FIELDVUE DVC6200 SIS Digital Valve Controller for Safety Instrumented Systems (SIS)

Fisher 3610J and 3620J Positioners and 3622 Electro-Pneumatic Converter

Fisher D3 Control Valve

Baumann Little Scotty Bronze Control Valve

Rosemount 333 HART Tri-Loop

Fisher 657 and 667 Diaphragm Actuators

Fisher 4320 Wireless Position Monitor, with On/Off Control Option

Rosemount 333 HART Tri-Loop

M Series Manual Handwheel Gear Actuators for Fisher Butterfly Valves

Fisher 377 Trip Valve

Mobrey Ultrasonic. MSP900SH Level and MSP900FH Flow Transmitters. Product Data Sheet February 2015 IP2032, Rev BA

Baumann Way Bronze or Stainless Steel Control Valve

Fisher 646 Electro Pneumatic Transducer

Micro Motion Model D and DL Coriolis Flow and Density Meters

Electro-Magnetic Flowmeters COPA-XT 2-Wire DT43

Micro Motion 3098 Gas Specific Gravity Meter

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits

Fisher 846 Current-to-Pressure Transducer

Model 3051 Pressure Transmitter with HART Protocol

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

Rosemount 751 Field Signal Indicator

RTX 1000 Series. Versatile Transmitters for a World of Pressure. GE Measurement & Control Solutions. Features

Fisher 249 Caged Displacer Sensors

Technical Information RIA14

Hazardous Area Classifications and Protections

BULLET. Description. Features. WirelessHART Adapter for Use with Wired HART Field Devices

Baumann Flexsleev Sanitary Control Valve

3DLevelScanner II TECHNICAL DATA SHEET

Baumann Mikroseal Control Valve

APT3200 SMART PRESSURE TRANSMITTER. Application Areas: For Gauge And Absolute Pressure Measurement

Hazardous Area Classifications and Protections

Rosemount 752 FOUNDATION fieldbus Remote Indicator

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

Rosemount 248 Temperature Transmitter

Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Fisher i2p-100 Electro Pneumatic Transducer

For Multi-Parameter Meters see mvx

MTII4200 level Transmitter Installation, Operation & Maintenance Instructions

Fisher FIELDVUE DVC6200 Digital Valve Controller / Magnet Assembly Dimensions

S-series Mass Connection Solutions

Rosemount 644 Temperature Transmitter

AT500 Magnetostrictive Level Transmitter. Compact magnetostrictive liquid level transmitter for direct insertion K-TEK Products

Fisher FIELDVUE DVC6000 Digital Valve Controllers Instruction Manual (Supported)

Isolating Barriers for our sensors A5S1 in Ex-areas Series D461

Rosemount DIN-Style Temperature Sensors and Thermowells (Metric)

Microcor Wireless Transmitter (MWT)

Technical Data. Dimensions

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

Analog signal converters CC-E I/I Current / current isolators

Compact pressure switch Flameproof enclosure Ex d Model PCA

Fisher CV500 Rotary Globe Control Valve

System 6000 Electropneumatic Converter for Direct Current Signals Type 6116 i/p Converter

Certified according to DIN EN ISO 9001 Technical Datasheet KVO Series Vortex Flow Meter

Wireless Gauge and Absolute Pressure Transmitters Series XYR 5000, Model WG5xx/WA5xx Specifications - Americas

1701/22 FieldMonitor Management Interface Module

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

STRATO LED Drivers 70W, Single output

OPTIMASS 6000 Technical Datasheet

key- precision Tecum cuil Ludere ipsae. Possem Precision level detection When space and price matter Pointek CLS 100

UNIK 5800/5900. Flameproof/Explosion-Proof Pressure Sensing Platform. GE Measurement & Control. High Quality. Features. Bespoke as Standard.

Level Switch LBFS. Technical Data. ATEX data Internal inductivity Li < 10 μh Internal capacity Ci < 43 nf Barrier data. Sensor

ValveLink Mobile Software

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

Fisher FIELDVUE DVC6200 Digital Valve

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

OPTIMASS 1400 Technical Datasheet

Certified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters

1805 Series Relief Valves

NI NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module

3500/62 Process Variable Monitor

Instruction Manual. T3111 T3111L T3111P T3111Ex

3500/25 Enhanced Keyphasor*Module

OEM Pressure Transmitters for heavy-duty applications, Type MBS 1200 and MBS 1250

STX2100. Differential Pressure (Flow) Transmitter. GE Measurement & Control. Models FKC...5. Features

Level Plus. Magnetostrictive Liquid-Level Sensors with Temposonics Technology. M-Series Model MR Transmitter with Analog Output.

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

Vehicle Brake System Monitoring 2-wire, 4-20 ma option; Intrinsic Safety Approval to E Exia IIC T4 (Tamb=60 C) BASEEFA, CENELEC EN50-020

T0118 T2118 T3118. Instruction Manual

Terminal Boxes Series 8146

S-series SQ Controller

T U R B I N E G A S M E T E R

Brooks Models SLA5850, SLA5851, SLA5853 Mass Flow Controllers and Models SLA5860, SLA5861, SLA5863 Mass Flow Meters

TEIP11 I/P signal converter for standard signals. Measurement made easy

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

Digital inductive conductivity transmitter

PRODUCT PROFILE FEATURES

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

3500/93 System Display

Certified according to DIN EN ISO 9001 Technical Datasheet C-Flow Coriolis Mass Flow Meter

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Waveguide Access Point WGA631. Product Guide

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

Transcription:

Product Bulletin Fisher FIELDVUE DLC3010 Digital Level Controller The FIELDVUE DLC3010 digital level controller is used with level sensors to measure liquid level, the level of the interface between two liquids, or liquid specific gravity (density). Changes in level or specific gravity exert a buoyant force on a displacer, which rotates a torque tube shaft. The digital level controller converts this rotational motion to an electronic signal. The DLC3010 is a communicating, microprocessor-based instrument that can be configured to sense the level, interface level, or density of liquids. In addition to the normal function of providing a 4 to 20 milliampere current signal, the DLC3010, using HART communications protocol, gives easy access to information critical to process operation. You can obtain information about the process, instrument, or sensor using the 475 or 375 Field Communicator. The DLC3010 can be used in analog or HART digital signaling mode with the Emerson Process Management DeltaV system. The connection for HART communication may be made at any point in the field wiring that meets the HART impedance requirements. Configuration, calibration, diagnostics, parameter review, signal monitoring and alert monitoring are all available W7977-2 through the HART protocol. Information from the field can be integrated into control systems or be received on a single loop basis. The DLC3010 digital level controller is designed to directly replace standard pneumatic and electronic level transmitters. It mounts on a wide variety of Fisher 249 caged and cageless level sensors. www.fisher.com

Product Bulletin Specifications Available Configurations : Mounts on caged and cageless 249 sensors. See tables 4 and 5 and sensor description. Function: Transmitter Communications Protocol: HART Input Signal Level, Interface, or Density: Rotary motion of torque tube shaft proportional to changes in liquid level, interface level, or density that change the buoyancy of a displacer. Process Temperature: Interface for 2- or 3-wire 100 ohm platinum RTD for sensing process temperature, or optional user-entered target temperature to permit compensating for changes in specific gravity Output Signal Analog: 4 to 20 milliamperes DC ( direct action increasing level, interface, or density increases output; or reverse action increasing level, interface, or density decreases output) High saturation: 20.5 ma Low saturation: 3.8 ma High alarm: 22.5 ma Low Alarm: 3.7 ma Only one of the above high/low alarm definitions is available in a given configuration. NAMUR NE 43 compliant when high alarm level is selected. Digital: HART 1200 Baud FSK (frequency shift keyed) HART impedance requirements must be met to enable communication. Total shunt impedance across the master device connections (excluding the master and transmitter impedance) must be between 230 and 600 ohms. The transmitter HART receive impedance is defined as: Rx: 42K ohms and Cx: 14 nf In point-to-point configuration, analog and digital signalling are available. The instrument may be queried digitally for information, or placed in Burst mode to regularly transmit unsolicited process information digitally. In multi-drop mode, the output current is fixed at 4 ma, and only digital communication is available. Performance Performance Criteria Independent Linearity Hysteresis Repeatability Dead Band Hysteresis plus Deadband DLC3010 Digital Level Controller (1) 0.25% of output span <0.2% of output span 0.1% of full scale output <0.05% of input span - - - NOTE: At full design span, reference conditions. 1. To lever assembly rotation inputs. w/ 3-Inch 249W, Using a 14-inch Displacer 0.8% of output span w/ All Other 249 Sensors 0.5% of output span - - - - - - 0.5% of output span 0.3% of output span - - - - - - <1.0% of output span <1.0% of output span Note: At effective proportional band (PB)<100%, linearity, dead band, repeatability, power supply effect, and ambient temperature influence are potentially derated by the factor (100%/PB) Operating Influences Power Supply Effect: Output changes <±0.2% of full scale when supply varies between minimum and maximum voltage specifications. -continued- Table of Contents DLC3010 Specifications... 2 Features... 7 Principle of Operation... 9 249 Level Sensor Specifications... 10 249 Level Sensors... 10 Installation... 12 Ordering Information... 12 Construction... 13 Heat Insulator... 13... 13 2

Product Bulletin Specifications (continued) Transient Voltage Protection: The loop terminals are protected by a transient voltage suppressor. The specifications are as follows: Pulse Waveform Rise Time s) Decay to 50% s) Max V CL (Clamping Voltage) (V) Max I PP (Pulse Peak @ Current) (A) 10 1000 93.6 16 8 20 121 83 Note: μs = microsecond Ambient Temperature: The combined temperature effect on zero and span without the 249 sensor is less than 0.03% of full scale per degree Kelvin over the operating range -40 to 80 C (-40 to 176 F) Process Temperature: The torque rate is affected by the process temperature (see figure 1). The process density may also be affected by the process temperature. Process Density: The sensitivity to error in knowledge of process density is proportional to the differential density of the calibration. If the differential specific gravity is 0.2, an error of 0.02 specific gravity units in knowledge of a process fluid density represents 10% of span. Electromagnetic Compatibility Meets EN 61326 1:2013 and EN 61326 2 3:2006 Immunity Industrial locations per Table 2 of EN 61326 1 and Table AA.2 of EN 61326 2 3. Performance is shown in table 1 below. Emissions Class A ISM equipment rating: Group 1, Class A Supply Requirements (See figure 3) 12 to 30 volts DC ; 22.5 ma Instrument has reverse polarity protection. A minimum compliance voltage of 17.75 is required to guarantee HART communication. Compensation Transducer compensation: for ambient temperature. Density parameter compensation: for process temperature (requires user-supplied tables). Manual compensation: for torque tube rate at target process temperature is possible. Digital Monitors Linked to jumper-selected Hi (factory default) or Lo analog alarm signal: Torque tube position transducer: Drive monitor and signal reasonableness monitor User-configurable alarms: Hi-Hi and Lo-Lo Limit process alarms HART-readable only: RTD signal reasonableness monitor: When RTD installed Processor free-time monitor. Writes-remaining in Non Volatile Memory monitor. User-configurable alarms: Hi and Lo limit process alarms, Hi and Lo limit temperature alarms, Hi and Lo limit electronics temperature alarms Diagnostics Output loop current diagnostic. LCD meter diagnostic. Spot specific gravity measurement in level mode: used to update specific gravity parameter to improve process measurement Digital signal-tracing capability: by review of troubleshooting variables, and Basic trending capability for PV, TV and SV. LCD Meter Indications LCD meter indicates analog output on a percent scale bar graph. The meter also can be configured to display: Process variable in engineering units only. Percent range only. Percent range alternating with process variable or Process variable, alternating with process temperature (and degrees of pilot shaft rotation). Electrical Classification Pollution Degree IV, Overvoltage Category II per IEC 61010 clause 5.4.2 d Hazardous Area: CSA Intrinsically Safe, Explosion proof, Division 2, Dust Ignition proof FM Intrinsically Safe, Explosion proof, Non incendive, Dust Ignition proof ATEX Intrinsically Safe, Type n, Flameproof IECEx Intrinsically Safe, Type n, Flameproof Refer to tables 8, 9, 10, and 11 for additional approval information. Electrical Housing: CSA Type 4X FM NEMA 4X ATEX IP66 IECEx IP66 -continued- 3

Product Bulletin Specifications (continued) Other Classifications/Certifications CUTR Customs Union Technical Regulations (Russia, Kazakhstan, Belarus, and Armenia) INMETRO National Institute of Metrology, Standardization, and Industrial Quality (Brazil) KGS Korea Gas Safety Corporation (South Korea) NEPSI National Supervision and Inspection Centre for Explosion Protection and Safety of Instrumentation (China) PESO CCOE Petroleum and Explosives Safety Organisation - Chief Controller of Explosives (India) TIIS Technology Institution of Industrial Safety (Japan) Contact your Emerson Process Management sales office for classification/certification specific information Minimum Differential Specific Gravity With a nominal 4.4 degrees torque tube shaft rotation for a 0 to 100 percent change in liquid level (specific gravity=1), the digital level controller can be adjusted to provide full output for an input range of 5% of nominal input span. This equates to a minimum differential specific gravity of 0.05 with standard volume displacers. See 249 sensor specifications for standard displacer volumes and standard wall torque tubes. Standard volume for 249C and 249CP is 980 cm 3 (60 in 3 ), most others have standard volume of 1640 cm 3 (100 in 3 ). Operating at 5% proportional band will degrade accuracy by a factor of 20. Using a thin wall torque tube, or doubling the displacer volume will each roughly double the effective proportional band. When proportional band of the system drops below 50%, changing displacer or torque tube should be considered if high accuracy is a requirement. Mounting Positions Digital level controller can be mounted right- or left-of-displacer, as shown in figure 8. Instrument orientation is normally with the coupling access door at the bottom, to provide proper drainage of lever chamber and terminal compartment, and to limit gravitational effect on the lever assembly. If alternate drainage is provided by user, and a small performance loss is acceptable, the instrument could be mounted in 90 degree rotational increments around the pilot shaft axis. The LCD meter may be rotated in 90 degree increments to accommodate this. Construction Materials Case and Cover: Low-copper aluminum alloy Internal: Plated steel, aluminum, and stainless steel; encapsulated printed wiring boards; Neodymium Iron Boron Magnets Electrical Connections Two 1/2-14 NPT internal conduit connections; one on bottom and one on back of terminal box. M20 adapters available. Options Heat insulator Mountings for Masoneilan, Yamatake and Foxboro/Eckhardt displacers available Level Signature Series Test (Performance Validation Report) available (EMA only) for instruments factory-mounted on 249 sensor Factory Calibration: available for instruments factory-mounted on 249 sensor, when application, process temperature and density(s) are supplied Device is compatible with user-specified remote indicator Operating Limits Process Temperature: See table 3 and figure 2. Ambient Temperature and Humidity: See below Conditions Ambient Temperature Ambient Relative Humidity Normal Limits (1)(2) -40 to 80 C (-40 to 176 F) 0 to 95%, (non-condensing) Transport and Storage Limits (1) -40 to 85 C (-40 to 185 F) 0 to 95%, (non-condensing) Nominal Reference (1) 25 C (77 F) 40% 1. LCD meter may not be readable below -20 C (-4 F) 2. Contact your Emerson Process Management sales office or application engineer if temperatures exceeding these limits are required. Altitude Rating Up to 2000 meters (6562 feet) Weight Less than 2.7 Kg (6 lb) NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology. 4

Product Bulletin Table 1. EMC Summary Results Immunity Port Phenomenon Basic Standard Test Level Performance Criteria (1)(2) Electrostatic discharge (ESD) IEC 61000 4 2 4 kv contact 8 kv air A Enclosure Radiated EM field IEC 61000 4 3 80 to 1000 MHz @ 10V/m with 1 khz AM at 80% 1400 to 2000 MHz @ 3V/m with 1 khz AM at 80% A 2000 to 2700 MHz @ 1V/m with 1 khz AM at 80% Rated power frequency magnetic field IEC 61000 4 8 60 A/m at 50 Hz A Burst IEC 61000 4 4 1 kv A I/O signal/control Surge IEC 61000 4 5 1 kv (line to ground only, each) B Conducted RF IEC 61000 4 6 150 khz to 80 MHz at 3 Vrms A Note: RTD wiring must be shorter than 3 meters (9.8 feet) 1. A = No degradation during testing. B = Temporary degradation during testing, but is self recovering. Specification limit = +/- 1% of span. 2. HART communication was considered as not relevant to the process and is used primarily for configuration, calibration, and diagnostic purposes. 5

Product Bulletin Figure 1. Theoretical Reversible Temperature Effect on Common Torque Tube Materials 1.00 0.98 0.96 TORQUE RATE REDUCTION (NORMALIZED MODULUS OF RIGIDITY) 1 0.94 Gnorm 0.92 0.90 0.88 N05500 N06600 N10276 0.86 0.84 0.82 0.80 S31600 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 TEMPERATURE ( C) 1.00 0.98 0.96 TORQUE RATE REDUCTION (NORMALIZED MODULUS OF RIGIDITY) 1 0.94 Gnorm 0.92 0.90 0.88 0.86 N05500 N06600 N10276 0.84 0.82 0.80 S31600 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 TEMPERATURE ( F) Note: 1 Due to the permanent drift that occurs near and above 260 C (500 F), N05500 is not recommended for temperatures above 232 C (450 F). 6

Features Simplified Setup and Calibration For quick analog transmitter replacement (4-20mA out only), the instrument may be configured with default sensor data, zero Level Offset, differential process SG, and zero/span procedure only. For full compensation and diagnostic capabilities, complete sensor data entry and calibration is recommended. Using Guided Setup, digital level controller start-up is straightforward and fast. Level and temperature alarms, specific gravity tables, calibration trim and trending are readily configurable. The DLC3010 also supports re-ranging without a fluid reference. Responsive to Small Process Changes Accurate, high-gain analog-to-digital conversion enables measurement of small changes in the process variable. This allows the DLC3010 to be used in difficult liquid level, interface, or density applications. In addition, an adjustable input filter and output damping help to attenuate displacer-induced ripple in the output signal due to liquid turbulence. Reduced Temperature Effects An internal temperature sensor enables consistent performance of the digital level controller despite ambient temperature changes. With a temperature input signal, either via HART protocol or an RTD connected to the instrument, the digital level controller can also automatically compensate for specific gravity changes due to temperature. A user-supplied table of up to ten linear segments may be entered to implement this feature. (A sample water/steam table is provided in the DLC3010 instruction manual (D102748X012). The measured torque tube rate may be manually pre-compensated for a target process temperature using the data available in the DLC3010 Device Description (DD). Product Bulletin Additional Compensation The instrument measurement algorithm corrects for the small motion of the displacer as buoyancy changes, allowing it to calculate the true cage or vessel level. This provides additional accuracy on the shorter displacers. Rugged Construction Mechanical safeguards designed into the digital level controller help it to withstand physical abuse often incurred during installation or in transport, without compromising performance. The fully encapsulated printed wiring boards resist the effects of vibration, temperature, and corrosive atmospheres. The lever assembly is pinned at the neutral position when the coupling access door is open, providing shipping stabilization for a separate transmitter purchase. Locking set screws are provided for covers and the access door handle. Easy Maintenance Field wiring connections are in a compartment separated from the electronics. This protects the electronics from any moisture brought into the housing by the field wiring. This also eases installation and maintenance. The digital level controller does not have to be removed to facilitate troubleshooting or service. Modular construction (figure 4) allows servicing in the field. However, if it is necessary to remove the digital level controller for in-shop maintenance and calibration, field wiring does not need to be disconnected. Alarm Jumper The DLC3010 digital level controller includes self-diagnostics that detect an error (e.g. electronics failure) that would render the process variable measurement inaccurate. The instrument can also be configured to indicate a process variable high or low alarm. When a process variable alarm or an error is detected the analog output signal is driven either above or below the normal 4 to 20 ma range, depending on the user-selectable position of the alarm jumper. The unit ships from the factory with the jumper in the high position. 7

Product Bulletin Figure 2. Guidelines for Use of Optional Heat Insulator Assembly Figure 3. Power Supply Requirements and Load Resistance PROCESS TEMPERATURE ( F) -40-30 800 400 0 1-325 -40 TOO COLD -20 AMBIENT TEMPERATURE ( C) -20-10 0 10 20 30 40 50 60 HEAT INSULATOR REQUIRED NO HEAT INSULATOR NECESSARY HEAT INSULATOR REQUIRED 0 20 40 60 80 100 120 140 176 160 70 TOO HOT 80 425 400 300 200 100 0-100 -200 PROCESS TEMPERATURE ( C) Load (Ohms) 783 250 Maximum Load = 43.5 X (Supply Voltage - 12.0) Operating Region AMBIENT TEMPERATURE ( F) STANDARD TRANSMITTER Notes: 1 For process temperature below -29 (C-20 F) and above 204 C (400 F) sensor materials must be appropriate for the process [refer to Fisher Bulletin 34.2:2500 (D200037X012)]. 2. If ambient dew point is above process temperature, ice formation might cause instrument malfunction and reduce insulator effectiveness. E0284 0 10 12 15 20 25 30 SUPPLY VOLTAGE (VDC) 39A4070-B A5494-1 Figure 4. FIELDVUE Assembly ADAPTER RING TERMINAL BOX TERMINAL BOX COVER LEVER ASSEMBLY TRANSDUCER ASSEMBLY ELECTRONICS MODULE LCD METER ASSEMBLY E1472-1 COVER 8

Principle of Operation The DLC3010 digital level controller is a loop-powered instrument that measure changes in liquid level, level of an interface between two liquids, or density of a liquid. A level, density, or interface level change in the measured fluid causes a change in the displacer buoyancy (figure 5). This change is transferred to the torque tube assembly. As the measured fluid changes, the torque tube assembly rotates. The rotary motion of the torque tube is transferred to the digital level controller lever assembly (figure 5). The rotary motion moves a magnet attached to the lever assembly, changing the magnetic field that is sensed by the Hall-effect sensor. The sensor converts the magnetic field signal to a varying electronic signal, which is processed digitally to provide linearity corrections, sensitivity adjustment, and temperature compensation. Product Bulletin The signal is interpreted as a buoyancy change by reference to the stored torque rate, coupling point, and moment arm data. The buoyancy change in turn is interpreted as a level, interface, or density change by reference to stored displacer volume, specific gravity, and displacer length data. In level or interface modes, the correction for displacer motion is then added, as well as user-supplied offset to change the PV reference from the bottom of the displacer or correct for a coupling point error. The resultant primary variable (PV) is then compared to PV alarm thresholds (if enabled) and used to set status bits and/or trigger the analog alarm current. If the alarm is not triggered, the PV is used to generate 4-20 ma analog and 0-100% range digital signals by reference to the stored upper and lower range values. The resultant analog command is limited at the saturation values to allow discrimination between saturated and alarm signals. Figure 5. Cutaway View of Fisher 249 Displacer Sensor with FIELDVUE TORQUE TUBE E1471-1 DISPLACER W1389-1 9

Product Bulletin 249 Level Sensors Specifications Input Signal Liquid Level or Liquid-to-Liquid Interface Level:From 0 to 100 percent of displacer length Liquid Density: From 0 to 100 percent of displacement force change obtained with given displacer volume standard volumes are 980 cm 3 (60 inches 3 ) for 249C and 249CP sensors or 1640 cm 3 (100 inches 3 ) for most other sensors; other volumes available depending upon sensor construction Sensor Displacer Lengths See tables 4 and 5 footnotes Sensor Working Pressures Consistent with applicable ASME pressure/temperature ratings for the specific sensor constructions shown in tables 4 and 5 Caged Sensor Connection Styles Cages can be furnished in a variety of end connection styles to facilitate mounting on vessels; the equalizing connection styles are numbered and are shown in figure 7. Mounting Positions Most level sensors with cage displacers have a rotatable head. The head may be rotated through 360 degrees to any of eight different positions, as shown in figure 8. Construction Materials See tables 2, 4, and 5 Operative Ambient Temperature See table 3. For ambient temperature ranges, guidelines, and use of optional heat insulator, see figure 2. Options Heat insulator Gauge glass for pressures to 29 bar at 232 C (420 psig at 450 F), and Reflex gauges for high temperature and pressure applications 249 Level Sensors Figure 6. FIELDVUE and Fisher 249B Level Sensor 249 level sensors used with the DLC3010 digital level controller are available in both caged and cageless configurations. Figure 6 shows a DLC3010 mounted on a caged 249 sensor. Caged sensors provide more stable operation than do cageless sensors for vessels with internal obstructions or considerable internal turbulence. Cageless sensors are generally used on specific gravity and interface control applications requiring large displacers that are more easily accommodated by flange connections up to 8 inches. The availability of many different displacer stem lengths permits lowering the displacer down to the most advantageous depth in the vessel. W7926-1 10

Product Bulletin Table 2. Displacer and Torque Tube Materials Displacer Part Standard Material Other Materials Displacer Stem, Driver Bearing, Displacer Rod and Driver 304 Stainless Steel 316 Stainless Steel 316 Stainless Steel, N10276, N04400, Plastic, and Special Alloys N10276, N04400, other Austenitic Stainless Steels, and Special Alloys Torque Tube N05500 (1) 316 Stainless Steel, N06600, N10276 1. N05500 is not recommended for spring applications above 232 C (450 F). Contact your Emerson Process Management sales office or application engineer if temperatures exceeding this limit are required. Table 3. Allowable Process Temperatures for Common Fisher 249 Sensor Pressure Boundary Materials PROCESS TEMPERATURE MATERIAL Min. Max. Cast Iron -29 C (-20 F) 232 C (450 F) Steel -29 C (-20 F) 427 C (800 F) Stainless Steel -198 C (-325 F) 427 C (800 F) N04400-198 C (-325 F) 427 C (800 F) Graphite Laminate/SST Gaskets -198 C (-325 F) 427 C (800 F) N04400/PTFE Gaskets -73 C (-100 F) 204 C (400 F) Table 4. Caged Displacer Sensors (1) TORQUE TUBE ORIENTATION Torque tube arm rotatable with respect to equalizing connections STANDARD CAGE, HEAD, EQUALIZING CONNECTION SENSOR AND TORQUE TUBE ARM PRESSURE RATING (2) MATERIAL Style Size (NPS) 249 (3) Cast Iron Screwed 1-1/2 or 2 Flanged 2 CL125 or 250 Screwed or optional socket weld 1-1/2 or 2 CL600 249B, 249BF (4) Steel Raised face or optional ring type joint 1-1/2 CL150, 300, or 600 flanged 2 CL150, 300, or 600 Screwed 1-1/2 or 2 CL600 249C (3) 316 Stainless Steel 1-1/2 CL150, 300, or 600 Raised face flanged 2 CL150, 300, or 600 249K Steel Raised face or optional ring type joint flanged 1-1/2 or 2 CL900 or 1500 249L Steel Ring type joint flanged 2 (5) CL2500 1. Standard displacer lengths for all styles (except 249) are 14, 32, 48, 60, 72, 84, 96, 108 and 120 inches. The 249 uses a displacer with a length of either 14 or 32 inches. 2. DIN flange connections available in EMA (Europe, Middle East and Africa). 3. Not available in EMA. 4. 249BF available in EMA only. Also available in DIN size DN40 with PN10 to PN100 flanges and size DN50 with PN10 to PN63 flanges. 5. Top connection is 1-inch ring-type joint flanged for connection styles F1 and F2. Table 5. Cageless Displacer Sensors (1) Mounting Mounts on top of vessel Mounts on side of vessel Sensor Standard Head (2), Wafer Body (6), and Torque Tube Arm Material Flange Connection Pressure Rating (3) 249BP (4) Steel NPS 4 raised face or optional ring type joint CL150, 300, or 600 NPS 6 or 8 raised face CL150 or 300 249CP 316 Stainless Steel NPS 3 raised face CL150, 300, or 600 249P (5) Steel or Stainless Steel NPS 4 raised face or optional ring type joint CL900 or 1500 (EN PN 10 to DIN PN 250) NPS 6 or 8 raised face CL150, 300, 600, 900, 1500, or 2500 249VS Cast Iron, Cast Steel or CF8M (316 Stainless Steel) For NPS 4 raised face or flat face For NPS 4 butt weld end, XXS CL125, 150, 250, 300, 900, or 1500 (EN PN 10 to DIN PN 160 CL2500 Mounts on top of WCC (steel) or CF8M For NPS 3 raised face CL150, 300, or 600 vessel or on 249W customer supplied LCC (steel) or CF8M For NPS 4 raised face CL150, 300, or 600 cage 1. Standard displacer lengths are 14, 32, 48, 60, 72, 84, 96, 108, and 120 inches. 2. Not used with side-mounted sensors. 3. DIN flange connections available in EMA (Europe, Middle East and Africa). 4. Not available in EMA. 5. 249P available in EMA only. 6. Wafer Body only applicable to 249W. 11

Product Bulletin Figure 7. Style Number of Equalizing Connections STYLE 1 TOP AND BOTTOM CONNECTIONS, SCREWED (S-1) OR FLANGED (F-1) STYLE 3 UPPER AND LOWER SIDE CONNECTIONS, SCREWED (S-3) OR FLANGED (F-3) STYLE 2 TOP AND LOWER SIDE CONNECTIONS, SCREWED (S-2) OR FLANGED (F-2) STYLE 4 UPPER SIDE AND BOTTOM CONNECTIONS, SCREWED (S-4) OR FLANGED (F-4) Installation A 249 sensor may be shipped with the DLC3010 digital level controller installed or they may be shipped separately. When shipping a skid mounted system, where the displacer cannot be restrained, it is recommended that the transmitter be uncoupled and the lever assembly locked to prevent damage. The transmitter must be re-coupled at commissioning, and a zero-trim will be required. Dimensions for the DLC3010 and 249 sensor product construction are shown in figure 9 and tables 6 and 7. Dimensions of other combinations are available upon request. Ordering Information When ordering, specify: Process temperature and pressure and ambient air temperature Application Liquid level service (specific gravity) Interface level service (specific gravity of both liquids and minimum differential gap or span required) Density service (minimum and maximum specific gravity required) 12

Product Bulletin Figure 8. Typical Mounting Positions for FIELDVUE on Fisher 249 Sensors SENSOR LEFT-OF-DISPLACER RIGHT-OF-DISPLACER 3 1 7 1 5 6 8 5 1 1 2 4 CAGED 3 4 2 7 8 6 CAGELESS 1 Not available for NPS 2 CL300 and 600 249C. Construction Refer to the specifications tables. Review the descriptions below each specification and in the referenced tables and figures; specify the desired choice whenever there is a selection to be made. Heat Insulator If the DLC3010 and the 249 sensor are ordered as an assembly, and a heat insulator is required for the application, order the heat insulator as a 249 sensor option. If the DLC3010 is ordered separately, the heat insulator is available as a kit. 13

Product Bulletin Figure 9. Dimensions for FIELDVUE Mounted on a Fisher 249B Sensor (also see tables 6 and 7) 1-1/2 11-1/2 NPT 103 (4.06) 421 (16.56) MATCH LINE (B) 244 (9.62) 102.1 (4.02) 73.7 (2.90) G A 203 503.4 F (8.00) (19.83) 125.7 W (4.95) 1/2-14 NPT M A CONDUIT CONN 106 (4.19) S-3 AND F-3 UPPER AND LOWER SIDE CONNECTIONS 3/4-14 NPT 202.4 (7.97) TOP VIEW 102.6 (4.04) 1/2-14 NPT CONDUIT CONN DETAILED FRONT VIEW OF DLC3010 DIGITAL LEVEL CONTROLLER mm (INCH) Table 6. Dimension A for FIELDVUE Mounted on a Fisher 249B Sensor SIZE (NPS) 1-1/2 2 SIZE DN40 DN50 A Screwed NPT CL150 RF CL150 RTJ CL300 RF CL300 RTJ CL600 RF CL600 RTJ mm Inches mm Inches mm Inches mm Inches mm Inches mm Inches mm Inches 121 121 4.75 4.75 145 145 5.69 5.69 152 151 6.00 5.94 148 148 DIN (1) PN10/PN16 PN25/PN40 PN63 PN100 mm mm mm mm 143 145 1. Dimension A for 249BF with din flanges. 145 147 Table 7. Dimensions F, G, M, and W for FIELDVUE Mounted on a Fisher 249B Sensor DISPLACER LENGTH F G M W mm Inches mm Inches mm Inches mm Inches mm Inches 356 14 356 14.00 197 7.75 284 11.19 394 15.50 813 32 813 32.00 425 16.75 513 20.19 851 33.50 5.81 5.81 154 155 6.06 6.12 153 153 154 157 6.06 6.19 159 159 153 - - - 6.25 6.25 14

Product Bulletin Table 8. Hazardous Area Classifications for Canada CSA Certification Body Certification Obtained Entity Rating Temperature Code CSA Ex ia Intrinsically Safe Class I, Division 1, 2 Groups A, B, C, D Class II, Division 1, 2 Groups E, F, G Class III T6 per drawing 28B5744 Explosion-proof Class I, Division 1 GP B,C,D T5/T6 Vmax = 30 VDC Imax = 226 ma Ci = 5.5 nf Li = 0.4 mh Class I Division 2 GP A,B,C,D T5/T6 - - - Class II Division 1, 2 GP E,F,G T5/T6 Class III T5/T6 - - - - - - T6 (Tamb 80 C) T5 (Tamb 80 C) T6 (Tamb 78 C) T5 (Tamb 80 C) T6 (Tamb 78 C) T5 (Tamb 80 C) T6 (Tamb 78 C) Table 9. Hazardous Area Classifications for United States FM Certification Body Certification Obtained Entity Rating Temperature Code FM IS Intrinsically Safe Class I,II,III Division 1 GP A,B,C,D,E,F,G T5 per drawing 28B5745 XP Explosion proof Class I Division 1 GP B,C,D T5 NI Non incendive Class I Division 2 GP A,B,C,D T5 DIP Dust Ignition proof Class II Division 1 GP E,F,G T5 S Suitable for Use Class II, III Division 2 GP F,G Table 10. Hazardous Area Classifications ATEX Vmax = 30 VDC Imax = 226 ma Pi = 1.4 W Ci = 5.5 nf Li = 0.4 mh T5 (Tamb 80 C) - - - T5 (Tamb 80 C) Certificate Certification Obtained Entity Rating Temperature Code ATEX Intrinsically Safe II 1 G D Gas Ex ia IIC T5 Ga Dust Ex ia IIIC T83 C Da IP66 Flameproof II 2 G D Gas Ex d IIC T5 Gb Dust Ex tb IIIC T83 C Db IP66 Type n II 3 G D Gas Ex na IIC T5 Gc Dust Ex t IIIC T83 C Dc IP66 Ui = 30 VDC Ii = 226 ma Pi = 1.4 W Ci = 5.5 nf Li = 0.4 mh T5 (Tamb 80 C) - - - T5 (Tamb 80 C) - - - T5 (Tamb 80 C) 15

Product Bulletin Table 11. Hazardous Area Classifications IECEx Certificate Certification Obtained Entity Rating Temperature Code IECEx Intrinsically Safe Gas Ex ia IIC T5 Ga Dust Ex ia IIIC T83 C Da IP66 Flameproof Gas Exd IIC T6 Gb Dust Ex t IIIC T83 C Db IP66 Type n Gas Ex na IIC T5 Gc Dust Ex t IIIC T83 C Dc IP66 Ui = 30 VDC Ii = 226 ma Pi = 1.4 W Ci = 5.5 nf Li = 0.4 mh T5 (Tamb 80 C) - - - T5 (Tamb 80 C) - - - T5 (Tamb 80 C) Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher, FIELDVUE, and DeltaV are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a registered trademark of the FieldComm Group. All other marks are the property of their respective owners. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Emerson Process Management Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore www.fisher.com 162000, 2016 Fisher Controls International LLC. All rights reserved.