Hilti KWIK HUS-EZ I (KH-EZ I) Internally Threaded Carbon Steel Screw Anchor



Similar documents
The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.

Hilti, Inc South 122 nd East Avenue Tulsa, OK

CITY OF LOS ANGELES CALIFORNIA

HUS-H Screw Anchor. Technical data. Seismic design data. HUS-H Carbon steel screw anchor. HUS-H diameter 8, 10, 14. Seismic design data

Hilti, Inc South 122 nd East Avenue Tulsa, OK

TZ WEDGE ANCHOR FOR CRACKED AND UNCRACKED CONCRETE

Submittal Information

ICC-ES Evaluation Report

Hilti HIT-V and HAS Threaded Rod and Hilti HIT-Z Anchor Rod

HUS-A 6 / HUS-H 6 / HUS-I 6 / HUS-P 6 Screw anchor in precast prestressed hollow core slabs

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015

HUS-V Screw anchor. HUS-V Screw anchor. Basic loading data (for a single anchor) Mean ultimate resistance

HUS-HR Stainless steel Concrete Screw A CE conformity. Corrosion resistance. European Technical Approval

HUS-HR, CR Screw anchor, stainless steel

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

HSL-3 Heavy duty anchor carbon steel. Anchor Fastening Technology Manual HSL-3. Heavy duty anchor. Version /

HUS-HR, CR Screw anchor, stainless steel

CITY OF LOS ANGELES CALIFORNIA

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.

Europeiskt Tekniskt Godkännande European Technical Approval

PC-Concrete Injectable Concrete Anchoring and Repair System

Technical Notes 3B - Brick Masonry Section Properties May 1993

HVU with HAS/HAS-E rod adhesive anchor

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued November 1, Legacy report on the 1997 Uniform Building Code

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

EUROPEAN ORGANISATION FOR TECHNICAL APPROVALS

DIVISION: EARTHWORK SECTION: BORED PILES REPORT HOLDER: HUBBELL POWER SYSTEMS, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

PART E SPECIFICATIONS

RPS - sales@rpssolar.com San Bruno Cove, San Diego, CA 92130

Residential Deck Safety, Construction, and Repair

The Effects of Hole Cleaning on Post-Installed Anchor Systems in Concrete

Type of Force 1 Axial (tension / compression) Shear. 3 Bending 4 Torsion 5 Images 6 Symbol (+ -)

Screw Thread Design. Rev

Concrete Design Manual

Fero Angle Support Technology TECHNICAL REPORT. Yasser Korany, Ph.D., P.Eng. Mohammed Nazief

Detailing of Reinforcment in Concrete Structures

Guide to the Concrete Capacity Design (CCD) Method Embedment Design Examples

Connection Solutions

REPORT HOLDER: JENWEST ENTERPRISES LLC, DBA ADVANCED CONNECTOR SYSTEMS 321 SOUTH 1240 WEST #15 LINDON, UTAH EVALUATION SUBJECT:

C E L CONSULTING A D I V I S I O N O F C O N S O L I D A T E D E N G I N E E R I N G FOR THE

Operations and Instruction Manual Might Swivel - Part # Concrete and Steel Anchorage Connector ANSI Z ,000 lbs / 44kn

Structural Bolting. Notice the Grade 5 has a much smaller head configuration and a shorter shank then the A325 structural bolt. Rev.

GUARDRAIL POST STEEL

Seismic Installation for Attic Storage System

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...

(English language translation, the original version is in French language) Hilti HSL-3

European Technical Assessment ETA-10/0153 of 10/06/2015

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing

Hilti HIT-HY 200 with rebar

PPM High-Strength Anchor Bolt

Seismic Technical Guide

Hilti HIT-HY 150 MAX with rebar

The following sketches show the plans of the two cases of one-way slabs. The spanning direction in each case is shown by the double headed arrow.

Metric System & Specifications

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

Draft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI

Featuring TJ Rim Board and TimberStrand LSL

INSTRUCTIONS FOR USE

MEZZANINE SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3.

European Technical Approval ETA-10/0005

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

(English language translation, the original version is in Czech language) DEWALT PTB-PRO. DeWalt Black-&-Decker Str Idstein Germany

HPM Rebar Anchor Bolt. For bolted connections. Technical Manual. European Technical Approval ETA-02/0006. Version: Peikko Group 01/2015

Wisconsin Building Products Evaluation

Eurooppalainen tekninen hyväksyntä ETA 08/0173 European Technical Approval. Sormat S KA kiila ankkurit Sormat through bolt S KA

(English language translation, the original version is in French language) Powers Throughbolt PTB-XL-ETA7-PRO 01/02/ /01/2018.

CivilBay Anchor Bolt Design Software Using ACI and CSA A Code

CITY OF LOS ANGELES CALIFORNIA

Guidelines for Earthquake Bracing of Residential Water Heaters

Guidelines for Earthquake Bracing Residential Water Heaters

Evaluation Report CCMC R Pieux Vissés Vistech / Postech Screw Piles

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona

Eurooppalainen tekninen hyväksyntä ETA 01/0003. Sormat Oy Harjutie 5 FIN Rusko. Sormat Oy Harjutie 5

Report on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars

ICC-ES Evaluation Report Reissued September, 2010 This report is subject to re-examination in one year.

SECTION 3 DESIGN OF POST TENSIONED COMPONENTS FOR FLEXURE

Diameter. Swift Lift Round Recess Plug. Note: The diameter of the narrow recess plug is the same as the diameter of the round recess plug.

TEST PROCEDURE FOR FIELD WITHDRAWAL RESISTANCE TESTING

Load Design Charts. R-CONTROL SIPs STRUCTURAL INSULATED PANELS. CONTROL, NOT COMPROMISE.

CHAPTER 6 CONSTRUCTION TYPES

Reproduced with the permission of the American Welding Society (AWS), Miami, Florida - 09/15/ Stud Welding

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

Veneer Anchors. Masonry Veneer Anchors. Description. Applications

DESIGN OF PRESTRESSED BARRIER CABLE SYSTEMS

Design and Construction of Cantilevered Reinforced Concrete Structures

PRESENTATION ON REPAIR AND REHABILITATION OF BUILDINGS DAMAGED IN EARTHQUAKE. By H P Gupta & D K Gupta

Numerical modelling of shear connection between concrete slab and sheeting deck

TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE

Structural fire design Eurocode Timber structures

SECTION 3 DESIGN OF POST- TENSIONED COMPONENTS FOR FLEXURE

Tex-421-A, Splitting Tensile Strength of Cylindrical Concrete Specimens

DESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab,

English translation prepared by DIBt Original version in German language

MultiPost-AP anchorage device

Comprehensive Design Example 2: Foundations for Bulk Storage Facility

SLAB DESIGN. Introduction ACI318 Code provides two design procedures for slab systems:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CONCRETE ROOF TILES REPORT HOLDER: BORAL ROOFING

Transcription:

Hilti KWIK HUS-EZ I (KH-EZ I) Internally Threaded Carbon Steel Screw Anchor Supplement to Hilti North American Product Technical Guide Volume 2: Anchor Fastening Technical Guide 2011 Edition

3.3. KWIK HUS-EZ I (KH-EZ I) Carbon Steel Screw Anchor 3.3..1 Product Description 3.3..2 Material Specifications 3.3..3 Technical Data 3.3..4 Installation Instructions 3.3.. Ordering Information 3.3..1 Product Description Hilti KWIK HUS-EZ I (KH-EZ I) anchors are comprised of a body with an internally threaded hex washer head. The anchor is manufactured from carbon steel and is heat treated. It has a minimum 0.0003 inch (8 μm) zinc coating in accordance with DIN EN ISO 4042. The internally threaded head is larger than the diameter of the anchor and is formed with serrations on the underside. The anchor body is formed with threads running most of the length of the anchor body. The anchor is installed in a predrilled hole with a powered impact wrench or torque wrench. The anchor threads cut into the concrete on the sides of the hole and interlock with the base material during installation. Applicable base materials include normal-weight concrete, structural lightweight concrete and lightweight concrete over metal deck. Thread design enables quality setting and exceptional load values in wide variety of base material strengths. Anchor is fully removable Anchor size is same as drill bit size and uses standard ANSI B212.1 1994 drill bits. Suitable for reduced edge distances and spacing. 3.3..2 Material Specifications Hilti KWIK HUS-EZ I anchors are manufactured from carbon steel. The anchors are bright zinc plated to a minimum thickness of 8µm. 3.3..3 Technical Data The data contained in Tables 1-4 of this section have been evaluated in accordance with AC 193. For more detail, see ICC-ES ESR 3027. Listings/Approvals ICC-ES (International Code Council) ESR-3027 (Cracked & Uncracked ) FM Approved Independent Code Evaluation IBC / IRC 2009 (AC 193 / ACI 3.2) IBC / IRC 2006 (AC 193 / ACI 3.2) IBC / IRC 2003 (AC 193 / ACI 3.2) Guide Specifications Screw anchors shall be KWIK HUS-EZ I as supplied by Hilti, Inc. Anchors shall be manufactured from heat treated carbon steel material, zinc plated to a minimum thickness of 8µm. Anchors shall be installed using a drill bit of same nominal diameter as anchor. Product Features Suitable for cracked and uncracked normal weight and lightweight concrete, and lightweight concrete over metal deck. Suitable for seismic and nonseismic loads. Quick and easy to install. Figure 1 KWIK HUS-EZ I anchor installation details 2 Hilti, Inc. (US) 1-800-879-8000 www.us.hilti.com I en español 1-800-879-000 I Hilti (Canada) Corp. 1-800-363-448 I www.hilti.ca I Anchor Fastening Technical Guide 2011

Table 1 KWIK HUS-EZ I (KH-EZ I) Mechanical Anchoring Systems KWIK HUS-EZ I (KH-EZ I) Carbon Steel Screw Anchor 3.3. Design Guidelines For KWIK HUS-EZ I 1 Values for Normal Weight and Lightweight Characteristic Symbol Units Value Internal Thread Diameter of Head d it in. 1/4 or 3/8 Wrench Socket Size w s in. 3/8 or 1/2 Nominal Diameter d a in. 1/4 Drill Bit Diameter d bit in. 1/4 Maximum Installation Torque 4 T inst,max ft-lbf 18 Maximum Impact Wrench Torque Rating 3 T impact,max ft-lbf 114 137 Minimum Nominal Embedment Depth h nom in. 1 /8 2 1/2 Minimum Hole Depth h hole in. 2 2 7/8 Critical Edge Distance 2 c ac in. 2.00 2.78 Minimum Spacing at Critical Edge Distance s min,cac in. 1.0 Minimum Edge Distance c min in. 1.0 Minimum Spacing at Minimum Edge Distance s min in. 3.0 Minimum Thickness h min in. 3.2 4.12 Anchor Category 3 1 Steel Strength in Tension (ACI 318 D..2) Tension Resistance of Steel N sa lb. 6,070 Reduction Factor for Steel Strength Φ sa - 0.6 Breakout Strength in Tension (ACI 318 D..2) Effective Embedment Depth h ef in. 1.18 1.92 Effectiveness Factor - Uncracked K uncr - 24 Effectiveness Factor - Cracked K cr - 17 Modification Factor for cracked and uncracked concrete Ψ c,n - 1 Reduction Factor for Breakout Strength Φ cb - 0.4 0.6 Pullout Strength in Tension (ACI 318 D..3) Characteristic pullout strength, uncracked concrete (200 psi) N p,uncr lb 130 6 238 7 Characteristic pullout strength, cracked concrete N p,cr lb 667 6 1166 7 Reduction Factor for pullout strength Φ p - 0.4 0.6 Characteristic Pullout Strength, Seismic (200 psi) N p,eq lb 34 6 1166 7 Reduction Factor for pullout strength Φ eq - 0.4 0.6 Values for Installation in the underside of -Filled Profile Steel Deck Assemblies 2 Pullout Resistance, (uncracked concrete) - Lower Flute N p,deck,uncr lb 1210 8 187 9 Pullout Resistance, (uncracked concrete) - Upper Flute N p,deck,uncr lb 1490 8 1960 9 Pullout Resistance, (cracked concrete and seismic loads) - Lower Flute N p,deck,cr lb 620 8 930 9 Pullout Resistance, (cracked concrete and seismic loads) - Upper Flute N p,deck,cr lb 760 8 97 9 1 The data presented in this table is to be used in conjunction with the design criteria of ACI 318 Appendix D. 2 For installations through the soffit of steel deck into concrete, anchors installed in the lower flute may be installed with a maximum one inch offset in either direction from the center of the flute. See Figure 2. 3 Because of variability in measurement procedures, the published torque of an impact tool may not correlate properly with the above setting torques. Over-torquing can damage the anchor and/or reduce its holding capacity. 4 T inst,max applies to installations using a calibrated torque wrench. Additional combinations for minimum edge distance, c min and minimum spacing distance, s min or s min,cac may be derived by linear interpolation between the given boundary values. 6 The characteristic pullout resistance for concrete compressive strengths greater than 2,00 psi may be increased by multiplying the value in the table by (f'c/2,00) 0.3 7 The characteristic pullout for concrete compressive strengths greater than 2,00 psi may be increased by multiplying the value in the table by (f'c/2,00) 0. 8 The characteristic pullout resistance for concrete compressive strengths greater than 3,000 psi may be increased by multiplying the value in the table by (f'c/3,000) 0.3 9 The characteristic pullout for concrete compressive strengths greater than 2,00 psi may be increased by multiplying the value in the table by (f'c/2,00) 0. Hilti, Inc. (US) 1-800-879-8000 www.us.hilti.com I en español 1-800-879-000 I Hilti (Canada) Corp. 1-800-363-448 I www.hilti.ca I Anchor Fastening Technical Guide 2011 3

3.3. KWIK HUS-EZ I (KH-EZ I) Carbon Steel Screw Anchor Table 2 - Calculated ACI 318-08 Appendix D Strength Design Capacity for Single anchor in Tension 3,4,,6,7 Normal Weight LWCOMD Anchor Size 1/4 x 1-/8 1/4 x 2-1/2 Internally Threaded Head Nominal Embedment Depth Uncracked 200 psi 1 4000 psi 3000 psi 2 Cracked Seismic Uncracked Cracked Seismic Uncracked Lower Flute Upper Flute Cracked Lower Flute 1/4 1-/8 87 300 240 67 346 277 4 670 280 342 3/8 1-/8 87 300 240 67 346 277 4 670 280 342 1/4 2-1/2 133 78 78 1940 98 98 1218 127 60 634 3/8 2-1/2 133 78 78 1940 98 98 1218 127 60 634 Upper Flute 1 Values for other strengths can be calculated per (f'c/200) 0.3 for 1-/8" embedment and (f'c/200) 0. for 2-1/2" embedment 2 Values for other strength can be calculated per (f'c/3000) 0.3 for 1-/8" embedment and (f'c/3000) 0. for 2-1/2" embedment 3 Based on single anchor with edge and spacing values greater than those given as critical values in Table 1. 4 Based on lower value of concrete breakout or pullout strength These loads are factored resistance loads in accordance with Chapter 9 of ACI 318-08 (ΦN n ). 6 Interpolation of values for other embedments is not permitted 7 Minimum concrete thickness and edge distance must comply with Table 1. Table 3 KWIK HUS-EZ I (KH-EZ I) Allowable Stress Design Values for Illustrative Purposes 1,2,3,4,,6,7,8,9,10,11 Internal Thread Diameter of Head Nominal Anchor Diameter 1/4 or 3/8 1/4 Embedment Depth, h nom (mm) Effective Embedment Depth, h ef (mm) Allowable Tension Load lb (kn) 1-/8 (41) 1.18 (30) 470 (2.1) 2-1/2 (64) 1.92 (49) 1340 (6.0) For SI: 1 inch = 2.4 mm, 1 lbf = 4.4 N. 1 Single anchor with static tension load only. 2 determined to remain uncracked for the life of the anchorage. 3 Load combinations are taken from ACI 318 Section 9.2 (no seismic loading). 4 40% dead load and 60% live load, controlling load combination 1.2D + 1.6L. Calculation of weighted average for conversion factor α = 1.2(0.4) + 1.6(0.6) = 1.44. 6 f c = 4,000 psi (27.6 MPa) (normal weight concrete). 7 c a1 = c a2 c ac, see Table 1. 8 h h min, see Table 1. 9 Values are for Condition B where supplementary reinforcement in accordance with ACI 318 D.4.4 is not provided. 10 Allowable Tension Load = factored Load (Lesser of N p or Breakout from Table 1) 1.44 11 Values are for single anchors installed without influence of base material edge distance or adjacent anchors. Figure 2 Installation of KWIK HUS-EZ I (KH-EZ I) in Soffit of Over Steel Deck Floor and Roof Assemblies 1 Anchors may be placed in the upper or lower flute of the steel deck profile provided the minimum concrete cover above the drilled hole is satisfied. Anchors in the lower flute may be installed with a maximum 1-inch offset in either direction from the center of the flute. The offset distance may be increased proportionally for profiles with lower flute widths greater than those shown provided the minimum lower flute edge distance is also satisfied. 4 Hilti, Inc. (US) 1-800-879-8000 www.us.hilti.com I en español 1-800-879-000 I Hilti (Canada) Corp. 1-800-363-448 I www.hilti.ca I Anchor Fastening Technical Guide 2011

KWIK HUS-EZ I (KH-EZ I) Carbon Steel Screw Anchor 3.3. Table 4 - KWIK HUS EZ I (KH-EZ I) Allowable Stress Design Tension Values for Installations in Soffit of Over Steel Deck Floor and Roof Assemblies Internal Thread Diameter of Head Nominal Anchor Diameter 1/4 or 3/8 1/4 Embedment Depth (mm) Effective Embedment Depth (mm) Allowable Tension Load lb (kn) Upper Flute Lower Flute 1-/8 (41) 1.18 (30) 466 (2.1) 378 (1.7) 2-1/2 (64) 1.92 (49) 88 (3.9) 846 (3.7) For SI: 1 inch = 2.4 mm, 1 lbf = 4.4 N. 1 Single anchor with static tension load only. 2 determined to remain uncracked for the life of the anchorage. 3 Load combinations are taken from ACI 318 Section 9.2 (no seismic loading). 4 40% dead load and 60% live load, controlling load combination 1.2D + 1.6L. Calculation of weighted average for conversion factor α = 1.2(0.4) + 1.6(0.6) = 1.44. 6 f c = 3,000 psi (27.6 MPa) (light weight concrete). 7 c a1 = c a2 c ac, see Table 1. 8 h h min, see Table 1. 9 Values are for Condition B where supplementary reinforcement in accordance with ACI 318 D.4.4 is not provided. 10 Allowable Tension Load = factored Load (Lesser of N p or Breakout from Table 1) 1.44 11 Values are for single anchors installed without influence of base material edge distance or adjacent anchors. Table - Kwik HUS-EZ I (KH-EZ) Tested Load Values for FM Approval for Automatic Sprinkler Systems Hanger Rod Size 3/8 Screw Length 1 /8 2 1/2 FM Test Load Tension lb (kn)) FM Maximum Pipe Diameter 147 (6.6) 4 1 Tested in accordance with FM Approval Standard for Pipe Hanger Components for Automatic Sprinklers Systems Class Numbers 191, 192 and 193. Table 6 - Kwik HUS-EZ I (KH-EZ I) Allowable Stress Design Values for Installations into Hollow Core Panels 1,2 Hanger Rod Size Min. Effective Embedment h ef Allowable Load 3 Ultimate Load Tension lb (kn) Shear lb (kn) 4, Tension lb (kn) Shear lb (kn) 4, 1/4 48 (2.2) 1,930 (8.6) 1 3/8 4 (2.0) 1810 (8.1) 3/8 7 (3.4) 3,02 (13.) 1 The Admissible Anchor Location must be established to prevent damage to the prestressed cable during the drilling process. Verify the location and height of the cable with the hollow core plank supplier to confirm Admissible Anchor Location. 2 Minimum compressive strength of prestressed concrete is 7,000 psi. Published ultimate loads represent the average results conducted in local base materials. Due to variations in materials and dimensionl configurations, on-site testing is required to determine the actual performance. 3 Allowable loads calculated with a 4:1 factor of safety. 4 The bottom of the shear plane adjacent to the top of the coupler. Shear values controlled by the steel strength of ASTM A193, Grade B7 (min. tensile strength 12 ksi) screws used to fasten the shear fixturing. Shear values should consider the screw or threaded rod strength. Figure 3 Installation of KWIK HUS EZ I (KH-EZ I) in Hollow Core 3.3..4 Installation Instructions Use the installation instructions that are including with the Kwik HUS-EZ I packaging box. To obtain a digital copy of the Installation Instructions, visit www.us.hilti.com, www.hilti.ca or contact Hilti Technical Support. Hilti, Inc. (US) 1-800-879-8000 www.us.hilti.com I en español 1-800-879-000 I Hilti (Canada) Corp. 1-800-363-448 I www.hilti.ca I Anchor Fastening Technical Guide 2011

3.3. KWIK HUS-EZ I (KH-EZ I) Carbon Steel Screw Anchor The data below is developed from testing performed in accordance with ACI 3.2. It is intended for applications designed according to CSA A23.3-04 Update No. 3 (August 2009) Design Of Structures Annex D and is generally suitable for the conditions described in the introduction of Annex D. Table 7 KWIK HUS-EZ I (KH-EZ I) c Design Guidelines For KWIK HUS-EZ I 1 Values for Normal Weight and Lightweight Characteristic Symbol Units Value Internal Thread Diameter of Head in. 1/4 or 3/8 Wrench Socket Size in. 3/8 or 1/2 Nominal Diameter d a in. 1/4 Drill Bit Diameter d bit in. 1/4 Maximum Installation Torque 4 T inst,max ft-lbf (Nm) 18 (24) Maximum Impact Wrench Torque Rating 3 T impact,max ft-lbf (Nm) 114 (14) 137 (186) Minimum Nominal Embedment Depth h nom mm 41 64 material resistance factor Φ c - 0.6 Steel material resistance factor Φ s - 0.8 Ultimate Strength of anchor steel f ut MPa 924 Effective cross-sectional area of anchor A se mm 2 29.0 Minimum Hole Depth h hole mm 1 73 Minimum Spacing at Critical Edge Distance s min,cac mm 38 Minimum Edge Distance c min mm 38 Minimum Spacing at Minimum Edge Distance s min mm 76 Minimum Thickness h min mm 83 10 Anchor Category 3 1 Steel Strength in Tension (CSA A23.3 D.6.1) Factored Steel Resistance in Tension N sr kn 1.9 Reduction Factor for Steel Strength R - 0.70 Breakout Strength in Tension (CSA A23.3 D.6.2) Effective Embedment Depth h ef mm 30 49 Critical Edge Distance 2 c ac mm 1 71 Effectiveness Factor - Uncracked K uncr - 10 Effectiveness Factor - Cracked K cr - 7 Modification Factor for cracked and uncracked concrete Ψ c,n - 1.4 Reduction Factor for Breakout Strength R - 0.70 1.00 Pullout Strength in Tension - Non Seismic Applications (CSA A23.3 D.6.3} Factored Pullout Resistance, uncracked concrete (17.23 MPa) N pr,uncr kn 2.6 6 6.8 7 Factored Pullout Resistance, cracked concrete (17.23 MPa) N pr,cr kn 1.3 6 3.4 7 Resistance Factor for pullout strength Φ c,pull - 0.6 Factored Pullout Strength, Seismic (17.23 MPa) N pr,eq kn 1.1 6 3.4 7 Resistance Factor for pullout strength Φ c,seis - 0.6 Values for Installation in the underside of -Filled Profile Steel Deck Assemblies 2 Factored Pullout Resistance, (uncracked concrete 20.68 MPa) - Lower Flute N pr,deck,uncr kn 2.4 8.4 9 Factored Pullout Resistance, (uncracked concrete 20.68 MPa) - Upper Flute N pr,deck,uncr kn 3.0 8.7 9 Factored Pullout Resistance, (cracked concrete and seismic loads 20.68 MPa) - Lower Flute N pr,deck,cr kn 1.3 8 2.7 9 Factored Pullout Resistance, (cracked concrete and seismic loads 20.68 MPa) - Upper Flute N pr,deck,cr kn 1. 8 2.8 9 1 The data presented in this table is to be used in conjunction with the design criteria of CSA A23.3-04. 2 For installations through the soffit of steel deck into concrete, anchors installed in the lower flute may be installed with a maximum one inch offset in either direction from the center of the flute. 3 Because of variability in measurement procedures, the published torque of an impact tool may not correlate properly with the above setting torques. Over-torquing can damage the anchor and/or reduce its holding capacity. 4 T inst,max applies to installations using a calibrated torque wrench. Additional combinations for minimum edge distance, c min and minimum spacing distance, s min or smin,cac may be derived by linear interpolation between the given boundary values. 6 The characteristic pullout resistance for concrete compressive strengths greater than 17.23 MPa may be increased by multiplying the value in the table by (f'c/17.23) 0.3 7 The characteristic pullout for concrete compressive strengths greater than 17.23MPa may be increased by multiplying the value in the table by (f'c/17.23) 0. 8 The characteristic pullout resistance for concrete compressive strengths greater than 20.68 MPa may be increased by multiplying the value in the table by (f'c/20.68) 0.3 9 The characteristic pullout for concrete compressive strengths greater than 20.68 MPa may be increased by multiplying the value in the table by (f'c/20.68) 0. 6 Hilti, Inc. (US) 1-800-879-8000 www.us.hilti.com I en español 1-800-879-000 I Hilti (Canada) Corp. 1-800-363-448 I www.hilti.ca I Anchor Fastening Technical Guide 2011

KWIK HUS-EZ I (KH-EZ I) Carbon Steel Screw Anchor 3.3. 3.3..6 Ordering Information Order Information Description Internal Thread Diameter Internal Thread Length Hole Diameter Minimum Embedment Qty (pcs) / Box KH-EZ 1/4"x1-/8" 1/4" 1/4" 3/8" 1/4" 1-/8" 100 KH-EZ 1/4"x2-1/2" 1/4" 1/4" 3/8" 1/4" 2-1/2" 100 KH-EZ 1/4"x1-/8" 3/8" 3/8" 7/16" 1/4" 1-/8" 100 KH-EZ 1/4"x2-1/2" 3/8" 3/8" 7/16" 1/4" 2-1/2" 100 Hilti, Inc. (US) 1-800-879-8000 www.us.hilti.com I en español 1-800-879-000 I Hilti (Canada) Corp. 1-800-363-448 I www.hilti.ca I Anchor Fastening Technical Guide 2011 7

Hilti. Outperform. Outlast. P.O. Box 21148, Tulsa, OK 74121 Hilti, Inc. (US) 1-800-879-8000 www.us.hilti.com Servicio al Cliente en español 1-800-879-000 Hilti (Canada) Corporation 1-800-363-448 www.hilti.ca Hilti is an equal opportunity employer Hilti is a registered trademark of Hilti, Corp. Copyright 2012 by Hilti, Inc. 01/12 BB The data contained in this literature was current as of the date of publication. Updates and changes may be made based on later testing. If verification is needed that the data is still current, please contact the Hilti Technical Support Specialists at 1-800-879-8000. All published load values contained in this literature represent the results of testing by Hilti or test organizations. Local base materials were used. Because of variations in materials, on-site testing is necessary to determine performance at any specific site. Laser beams represented by red lines in this publication. Printed in the United States *ISO 14001 US Only