Limitation of Minimal Excitation Current by Load Angle Regulation



Similar documents
Determination of Load Angle for Salient-pole Synchronous Machine

SYNCHRONOUS MACHINES

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

Advance Electronic Load Controller for Micro Hydro Power Plant

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS

Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection

Transient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink

Understanding Delta Conversion Online "Power Regulation" - Part 2

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Lab 8: DC generators: shunt, series, and compounded.

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Physical Address: City: State: Zip Code:

VOLTAGE REGULATOR AND PARALLEL OPERATION

Topics. HVDC Fundamentals

POWER QUALITY ISSUES IN A STAND-ALONE MICROGRID BASED ON RENEWABLE ENERGY

Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting, excitation system

Available online at Available online at

Simulation and Analysis of Parameter Identification Techniques for Induction Motor Drive

Control Strategies of the Doubly Fed Induction Machine for Wind Energy Generation Applications

Modeling and Simulation of a Novel Switched Reluctance Motor Drive System with Power Factor Improvement

Renewable Energy Laboratory for Engineering Students

8 Speed control of Induction Machines

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Lab 14: 3-phase alternator.

AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION

Reactive Power Control of an Alternator with Static Excitation System Connected to a Network

7. Reactive energy compensation

Appendix N: GENERATOR DATA SHEET FOR SYNCHRONOUS GENERATORS CONNECTED TO PG&E ELECTRIC SYSTEM

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

A COMPARISON ON PERFORMANCE OF TCSC/SSSC FOR A RADIAL SYSTEM

Basics of Electricity

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Large Generators and High Power Drives

THIS paper reports some results of a research, which aims to investigate the

ε: Voltage output of Signal Generator (also called the Source voltage or Applied

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS

System Protection Schemes in Eastern Denmark

ABB PSPS Erich Steinmann; Generator control-2013

Verification of Short Circuit Test Results of Salient Poles Synchronous Generator

Full representation of the real transformer

Mathematical Modelling of PMSM Vector Control System Based on SVPWM with PI Controller Using MATLAB

LOSSELESS STARTING METHOD FOR THE WOUND ROTOR INDUCTION MOTOR

Control of a Three Phase Inverter Feeding an Unbalanced Load and Operating in Parallel with Other Power Sources

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

Chapter 24. Three-Phase Voltage Generation

Performance Analysis of Grid connected Wind Energy Conversion System with a DFIG during Fault Condition

Synchronous motor. Type. Non-excited motors

Distributed Flexible AC Transmission System (D FACTS) Jamie Weber ext. 13

Qatar University College of Engineering Electrical Engineering Department. A Graduation Project Report

A bidirectional DC-DC converter for renewable energy systems

Inductors in AC Circuits

WIND TURBINE TECHNOLOGY

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

REPORT ON CANDIDATES WORK IN THE CARIBBEAN ADVANCED PROFICIENCY EXAMINATION MAY/JUNE 2008 ELECTRICAL AND ELECTRONIC TECHNOLOGY (TRINIDAD AND TOBAGO)

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

(3 )Three Phase Alternating Voltage and Current

TDMS Test & Data Management Software

Application of GA for Optimal Location of FACTS Devices for Steady State Voltage Stability Enhancement of Power System

Control Development and Modeling for Flexible DC Grids in Modelica

dspace DSP DS-1104 based State Observer Design for Position Control of DC Servo Motor

Genetic Algorithm approach to find excitation capacitances for 3- phase smseig operating single phase loads

Current Loop Tuning Procedure. Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) General Procedure AN-015

ELECTRICAL ENGINEERING

Design of Four Input Buck-Boost DC-DC Converter for Renewable Energy Application

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

Alternative and Renewable Energy Systems

Power Quality Paper #3

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

PHYSICS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits

Fault Monitoring of the Electric Machine in a Hybrid Vehicle

POWER TRANSMISSION FROM OFFSHORE WIND FARMS

Hybrid Power System with A Two-Input Power Converter

Microcontroller-based experiments for a control systems course in electrical engineering technology

ELECTRICAL ENGINEERING

Simulation of VSI-Fed Variable Speed Drive Using PI-Fuzzy based SVM-DTC Technique

Three phase circuits

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

Performance Enhancement of Wound Rotor Induction Motor by VSI with Dynamic Capacitor Controlled Rotor Circuit

RECENTLY, interest in distributed generation systems

Synchronized real time data: a new foundation for the Electric Power Grid.

Microcontroller based speed control of three phase induction motor using v/f method

Micro-Step Driving for Stepper Motors: A Case Study

operating under normal conditions supplying - isolated loads - an infinite bus - a fin1 te bus load.

REMOTE HOST PROCESS CONTROL AND MONITORING OF INDUSTRY APPLIANCES

Test & Data Management Software

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture phase System 4

Wind Turbine Operation in Power Systems and Grid Connection Requirements

Dually Fed Permanent Magnet Synchronous Generator Condition Monitoring Using Stator Current

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Keywords: Self-Excited Induction Generator (SEIG), Single Phase Synchronous D-Q Frame Theory, Static Synchronous Compensator (STATCOM).

300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal

Transcription:

Limitation of Minimal Excitation Current by Load Angle Regulation Tomislav Idzotic 1), Gorislav Erceg 2), Damir Sumina 3) Faculty of Electrical Engineering and Computing Unska 3, Zagreb, Croatia Tel. / Fax: + (385 1) 6129-999/ 6129-75 1) tomislav.idzotic@fer.hr, 2) gorislav.erceg@fer.hr, 3) damir.sumina@fer.hr Abstract - A synchronous generator connected to an AC system in capacitive operating mode is near its stability limit. In such conditions, if some disturbances in the system appear, a synchronous generator could lose the synchronism. The classical solution of this problem is to keep a generator in stabile operating range of P-Q diagram by limiting the minimal excitation current. This article analysis impact of additional control algorithms which are included in classical excitation regulation system with the purposes of keeping a generator in synchronism when some disturbances appear and generator is near its stability limit. These control algorithms include load angle estimation by corresponding P-Q diagram and load angle regulator which task is to keep the load angle of a synchronous generator operating in capacitive mode on the reference value so that generator remains in synchronism. I. INTRODUCTION. A synchronous generator which is connected to an AC system has to remain in synchronism even in some extreme situations that can appear in the operating conditions keeping a generator in the range of permissible loading. In the real system, the exceeding of allowed loading would cause the activation of generator protection and disconnection of a synchronous generator from an AC system. The voltage regulators of synchronous generators have the excitation current limitations as it is dictated by P- Q diagram (fig. 1.). This enables optimal utilization of the permissible loading and safer work of a generator that is operating in parallel with a distribution network. of the excitation current, limit the load angle and a generator will not lose synchronism. These minimal limitations in excitation current can be done based on P-Q diagram of a synchronous generator or by load angle regulation in under-excitation operating mode. These papers present minimal limitation of the excitation current based on the load angle regulation. Presented solution in classical regulation structure, in which the voltage regulator is superior to excitation current regulator, includes the load angle regulator. When load angle is near its unstable value, the voltage regulator is turned off and the load angle regulator is turned on until load angle is decreased. In this situation load angle regulator sets the excitation current reference to its maximal value and on that way decreases the load angle so that generator remains in synchronism. So this regulation method enables stabile work of generator near the stability limits and expands the operating range of generator. The load angle estimation is based on voltage and current measurement of a synchronous generator. By load angle estimation is avoided additional sensor. II. THE EXCITATION REGULATION STRUCTURE OF A SYNCHRONOUS GENERATOR The excitation regulation structure with load angle estimation and additional load angle regulator is presented on the fig. 2. uref Ugen controller ifref If controller pwm if ϑ ref ϑ controller ϑkrit ugen ϑestimated Q if iw uuv uwv Fig. 1. P-Q diagram of a synchronous generator including all limitations Under-excitation (capacitive) operating mode of a synchronous generator is appeared in systems with underloaded long power transmission lines, by connecting long power transmission lines to voltage and by asynchronous work of regulating transformer regulators. Minimal limits DIGITAL CONTROL SYSTEM Fig. 2. The excitation regulation structure of a synchronous generator with load angle estimation and additional load angle regulator According to the simulation results it is chosen PID regulator. Proportional and derivative part of the PID regulator determine the system response during start up and

integral part assures that the load angle is equal to its wanted reference value in static operating conditions. In the moment of turning off the voltage regulator and turning on the load angle regulator the state of the integrator of the voltage regulator is written into the integrator of the load angle regulator. So this transition between two regulators is smooth and there is no unwanted step in excitation current reference. III. MEASUREMENT AND ESTIMATION OF THE LOAD ANGLE OF A SYNCHRONOUS GENERATOR For load angle estimation is used voltage-current vector diagram (fig. 3.). I ( X q E X d ) I X q ϑ I ϕ U I X q cos ϕ I R sin ϕ tg ϑ = (1) U + I X q sin ϕ + I R cos ϕ respectively I X q P I R Q ϑ = arctg. (2) U S + I X q Q + I R P Quadrature-axis synchronous reactance X q is needed for this estimation method. Its value is well known from the producers and is not very dependent on saturation. In situations when short circuit appears, generator voltage suddenly falls and generator current rises. In such situations, measuring equipment goes to saturation, and the measured results of active and reactive power are not reliable. The estimated value for load angle is not correct too. In such cases, the system forces the excitation current. The excitation current rises to its maximal value that is determined by its maximal limit. When short circuit appears, the load angle estimator sets the load angle to its maximal value and force the excitation current to its maximum limit. The load angle estimation algorithm is implemented in the developed digital system DIRES 21 [2] (fig. 4.). IV. EXPERIMENT Fig. 3. Vector diagram From diagram on the fig. 3. is obtained: Experimental verification of the excitation regulation system of a synchronous generator is made on the laboratory model of the aggregate (fig. 5.). Digital excitation regulation system includes four DSPs ADMC3 [2]. The excitation winding of a synchronous generator is fed by IGBT converter. Fig. 4. Load angle estimation algorithm

cos ϕ =.8 3 x 38V 3 x 38V Fig. 5. Digital regulation system and laboratory model of the aggregate The analysis is made with and without load angle regulator on the step change of the prime mover moment of the aggregate. Experimental responses of the excitation system of the synchronous generator operating in capacitive mode (capacitive loading Q=.8 pu of the nominal power) on the step change of active power P=1. pu without load angle regulator are shown on the fig. 6. In this case the generator loses the synchronism. When load angle regulator is included in excitation system the generator remains in synchronism (fig. 7.). 98 96 94 92 9 Voltage ( % ) Current ( % ) 35 3 25 2 15 1 5 2 15 1 5 Active power ( % ) -5-1 -15-2 Reactive power ( % ) -5-25

Excitation current ( % ) 8 6 4 2-2 -4-6 -8 15 1 5-5 Estimated load angle (degrees ) Fig. 6. Experimental responses on the step change of moment without load angle regulator and Q=.8 pu Voltage ( % ) 98,5 98 97,5 97 96,5 96 95,5 95 25 2 15 1 5 Current ( % ) 15 Active power ( % ) Reactive power ( % ) 1 5-5 -1-5 -15 5 4 3 2 1 Excitation current ( % ) 8 6 4 2-2 Estimated load angle (degrees ) Fig. 7. Experimental responses on the step change of moment with load angle regulator and Q=.8 pu (cap) Maximal load angle value is 7 º el. Even when the voltage regulator reference is set to zero, the generator remains in synchronism during step change of active power P=1. (fig. 8.).

98 97 96 95 94 93 92 Voltage ( % ) 25 2 15 1 5 Current ( % ) 15 Active power ( % ) Reactive power ( % ) 1-5 5-1 -15-5 -2 5 4 3 2 1-1 Excitation current ( % ) 1 8 6 4 2-2 Estimated load angle (degrees) Fig. 8. Experimental responses on the step change of moment with voltage regulator reference equal to zero V. CONCLUSIONS Presented experimental results show positive performance of the load angle regulator, which is added in classical excitation regulation system, on the stability of a synchronous generator in static as well as in dynamic operating conditions. In static operating conditions with increased active power, load angle regulator keeps the load angle on its reference value so that generator remains in stabile operating range. In dynamic operating conditions load angle regulator quickly increases the excitation current of a synchronous generator and on that way improve the stability of a synchronous generator which is connected to an AC system. Load angle regulator added in classical excitation system improves the stability of a synchronous generator in capacitive operating mode. SYMBOLS ϑ - load angle of a synchronous generator X d, X q reactances of a synchronous generator R armature resistance of a synchronous generator P active power of a synchronous generator Q reactive power of a synchronous generator S apparent power of a synchronous generator U, I voltage and current of a synchronous generator ϕ - phase angle REFERENCES [1] Analog Devices, ADSP-21 Family User s Manual, Analog Devices Inc, Third Edition, 1995 [2] Erceg G., Idzotic T., Tonkovic N., "Digital Control System of a Synchronous Generator", EPE-PEMC, 22. [3] Erceg G., Idzotic T., Tonkovic N., "Hydro generating unit digital control system, Hydro, 23.

[4] Girgis G.K., Vu H.D., Verification of limiter performance in modern excitation control systems, IEEE Trans. on Energy Conversion, Vol. 1, No. 3, 1995. [5] Eberly T.W., Schaefer R.C., Minimum/maximum excitation limiter performance goals for small generation, IEEE Trans. on Energy Conversion, Vol. 1, No. 4, 1995. [6] Ramos A.J.P., Lins L.R., Fittipaldi E.H.D., Monteath L., Performance of under excitation limiter of synchronous machines for system critical disturbances, IEEE Trans. on Power Systems, Vol. 12, No. 4, 1997. [7] Working group of the excitation systems subcommittee, Underexcitation limiter models for power system stability studies, IEEE Trans. on Energy Conversion, Vol. 1, No. 3, 1995.