Back-UPS 650 VA 120 V with AVR (BX650CI-LM)



Similar documents
Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Back-UPS Pro 1300/1500 Installation and Operation

Installation and Operation Back-UPS 1250, 1300, 1500

Powerware 5110 UPS User s manual

Operation Manual. Smart-UPS C. Uninterruptible Power Supply. Tower 1000/1500 VA. 120/230 Vac. su0813a

User Manual. English. APC Smart-UPS 1000/1500 VA 100/120/230 VAC 750/1000XL VA 120/230 VAC. Tower Uninterruptible Power Supply

User Manual. English. APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC. Tower Uninterruptible Power Supply

CAUTION. CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage and minor or moderate injury.

User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply

Match. GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match UPS. GE Digital Energy.

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out

How To Use A Power Supply Unit (Upu)

Installation and Operation

750VA/1000VA/1500VA 100/120/230VAC 2U

User s Manual AURORA 1.2K/2.2K

User Manual. Smart-UPS. Uninterruptible Power Supply 750/1000/1500 VA. 100/120/230 Vac. Rack Mount 2U

User Manual. English. APC Smart-UPS RT. 3000/5000/6000 VA VAC Tower/Rack Mount 3U Uninterruptible Power Supply

SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial

User Manual. Smart-UPS TM C. Uninterruptible Power Supply SRC250 SRC /120/230 Vac. Tower/Rack-Mount 1U

Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V

User Manual. English. APC Smart-UPS RT. 8000/10000 VA Vac Tower/Rack-Mount 6U Uninterruptible Power Supply

Uninterruptible Power Supply

User Manual. English. APC Smart-UPS VA 120/230 Vac VA 100/120/208/230 Vac. 2U Rack Mount Uninterruptible Power Supply

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Installation and Operation

Operation Manual. Smart-UPS UPS. 750/1000/1500/2200 VA Rack-mount 2U 120/230 VAC VA Rack-mount 2U 120/208/230 VAC

APC Smart-UPS 2400/3000 VA 100/ VAC 3U. Uninterruptible Power Supply

REGULINE 600VA / 1000VA REGULATOR USER MANUAL

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

SmartOnline V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial

EKOS Cart. Instructions for Use

SmartPro 230V 750VA 500W Line-Interactive Sine Wave UPS, SNMP, Webcard, Tower, USB, DB9 Serial

SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial

SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial

SmartOnline V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire

350, 500, 650 and 1000 MODELS

Audio/Video AVR Series UPS - Intelligent Automatic Voltage Regulated Power Management System

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial

Operation Manual. Smart-UPS X Uninterruptible Power Supply

SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial

OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port

Owner s Manual. Not suitable for mobile applications. Important Safety Instructions 2. Quick Installation 3. Basic Operation 4. Storage & Service 7

Model #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V

3U, 2200 VA Audio/Video Pure Sine Wave UPS System

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial

SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial

APC. DIN Rail Control Panel Mounting Uninterruptible Power Supply. Catalog

Model #: SMART2200CRMXL

Galleon 6-10K Online UPS. Voltronic Power Technology Corporation

Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system

Installation Guide Smart-UPS X Tower/Rack-Mount 2U 2000/2200/3000 VA

USER S MANUAL. MaxPower UPS. Uninterruptible Power System 28-2MAXPO0018

Internet Office 750VA Ultra-compact Standby 120V UPS with USB port

Internet Office UPS System Standby UPS for PCs, workstations and more

TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial

User s Manual. Professional Rack Mount LCD Series PR1000ELCDRT2U/PR1500ELCDRT2U/ PR2200ELCDRT2U K

SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial

PC Personal 120V 600VA 375W Standby UPS with Pure Sine Wave Output, Tower, 6 Outlets

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications

BroadBand PowerShield. User Manual

User s Manual Before using the inverter, you need to read and save the safety instructions.

BC Pro UPS System Standby UPS System

USER MANUAL Online UPS 1K/2K/3K Rack

PowerSource 400 Owner s Guide

Line Interactive UPS. PowerWalker VI 500T/HID PowerWalker VI 750T/HID PowerWalker VI 1000T/HID PowerWalker VI 1500T/HID.

Internet Office 500VA Tower Standby 120V UPS with USB port

APC Smart-UPS 2200/3000 VA 100/120/230 VAC. Uninterruptible Power Supply C 12/20005

Symmetra LX. Operations Guide

User Manual 1K/2K/3K Online UPS

Online UPS. PowerWalker VFI 1000R/1U

Line Interactive UPS

UPS-2200R-HH/UPS-2200R-HHIP

For protection from laptops to high availability facilities - and everything in between - APC is a partner you can count on

PowerSource 1800 Owner s Guide

Smart-UPS 120 V. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS

3000W Power Inverter

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply

How To Use A Power Supply Unit (Upland)

USER MANUAL Online UPS 1K/2K/3K

Preface. Manual Revisions

QuickSpecs. Models HP T1500 UPS JPN/TWN. HP UPS T1000 G2, T1500 G2 Models Overview

Instructions & Safety Information Models A220-20D and A220-20L Version 2

Home Solar Kit Owner s Manual. Model: HS

Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications

SPL 2-00/-01 OPERATION INSTRUCTIONS

Entrust Series UPS. User's Manual

NEWTECH PRO KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL

Operation Manual. Smart-UPS UPS. 750/1000/1500/2200/3000 VA Tower 120/230 VAC

Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6. User s manual

Liebert GXT3 Reliable On-Line UPS Protection In A Compact 2U Package 700VA -3000VA

LAP ENERGIA PARA DATACENTERS

NEW APC Smart-UPS. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS.

Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P

OWNER S MANUAL 2.5/3.0 ACS PANEL (ADVANCED CONTROL SYSTEM) 7725 Lougheed Highway Burnaby, BC V5A 4V8 Canada

Residential Gateway (RG) Battery Backup REV B

10000HXL31/15000HXL31/20000HXL31

Installation Guide Smart-UPS X External Battery Pack SMX120BP

HP UPS R1500 Generation 3

NEW APC Smart-UPS. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS.

Transcription:

Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit breaker Input power cord Battery and surge protected outlets bu205a Setup and Installation Connect the battery Pull the battery connector handle down, and then push it into the unit. Connect the equipment to Battery Backup+Surge Protection Outlets Connect equipment to the BATTERY BACKUP + SURGE PROTECTION outlets. These outlets provide backup power to the connected equipment during power outages. The Back- UPS must be turned ON in order to supply backup power. These outlets also provide protection to the connected equipment from power surges or spikes, even if the Back-UPS is turned OFF. Connect a computer, monitor, modem or other critical devices you want to stay powered during outages or utility problems into these outlets. Connect the power cord Connect the Back-UPS power cord to the outlet on the back of the unit and to a wall outlet. Do not connect the power cord to a surge protector or power strip. The outlet should be near the equipment and easily accessible. Turn on the power to the unit Press the ON/OFF button on the front of the unit. The unit will emit a single, short beep and the green POWER ON indicator will illuminate to confirm that the unit is on and is providing power protection. To provide maximum runtime, the Back-UPS should charge for at least 10 hours. The unit is being charged whenever it is connected to utility power, even if the unit is OFF.

Transfer Voltage and Sensitivity Settings Automatic Voltage Regulation This Back-UPS unit has Automatic Voltage Regulation (AVR). If the input utility voltage drops below a level that is safe for the operation of the connected equipment, the unit will boost utility voltage up to safe level. It will also compensate for high input utility voltage by lowering it to a level that is safe for the connected equipment. The Back-UPS will switch to battery power if the input voltage level becomes too low for the Automatic Voltage Regulation to compensate, or if the utility power is distorted. No-load Shutdown If the UPS is operating on battery power and detects that the connected equipment is using less than 15 W of energy for more than 15 minutes, it will shut down to conserve energy. When the UPS is reconnected to utility power, the UPS will automatically switch on. Note: Even if the UPS is OFF, it is still protecting connected equipment from power surges. Adjust the settings If the Back-UPS switches to battery power too frequently or too infrequently, adjust the transfer voltage and sensitivity settings: 1. Ensure the battery is connected and that the Back-UPS is OFF, but connected to utility power. 2. Press and hold the ON/OFF button until the LED repeatedly flashes.the unit is now in Program Mode. 3. Release the button. The LED will indicate the current setting by flashing once, twice, or three times per, and emitting audible beeps. 4. Press ON/OFF within two s to change the setting. Continue pressing the button until the desired setting is reached. If the button is not pressed within five s, the Back-UPS will exit the Program Mode. LED Flashing Audible Indicator Transfer Voltage Setting Input Voltage Range No-load Shutdown Description 2 Once per Once per Twice per Twice per Three times per Three times per None Low 78-150 Disabled The Back-UPS will switch to battery power less often. Use this setting for equipment that is not sensitive to low or high level voltage levels or minor voltage waveform distortions. 4 beeps per Low 78-150 Enabled The Back-UPS will switch to battery power less often. Use this setting for equipment that is not sensitive to low or high level voltage levels or minor voltage waveform distortions. None Medium 81-147 Disabled Use when the input utility power is normal, without any fluctuation in voltage levels. 4 beeps per Medium (factory default) 81-147 Enabled Use when the input utility power is normal, without any fluctuation in voltage levels. None High 81-144 Disabled The Back-UPS will switch to battery power during any small fluctuation in voltage. Use this setting for equipment that is sensitive to low or high level voltage levels or minor voltage waveform distortions. 4 beeps per High 81-144 Enabled The Back-UPS will switch to battery power during any small fluctuation in voltage. Use this setting for equipment that is sensitive to low or high level voltage levels or minor voltage waveform distortions.

Status Indicators LED Audible Alarm Condition On Off On-line - The Back-UPS is supplying utility power to the connected equipment Constant Tone On Line Overload - The power being used by the connected equipment has exceeded the capacity of the unit. Disconnect some equipment Constant beeping Over-temperature Warning - The unit is overheating and will shut down if the temperature is not lowered. Disconnect some of the connected equipment. On (Off during 4 beeps) Flashing Off 4 beeps repeated every 30 s Rapid Beeping (every 1/2 ) Constant tone Chirp every 2 s Short beep every 4 s Constant Tone Constant Tone Constant Tone Troubleshooting On-Battery - The Back-UPS is supplying battery power Low Battery Warning - The Back-UPS has 2 minutes of runtime remaining Bad Battery Detected - The battery needs to be charged, or is at end of life. (See Battery Replacement.) Charger Warning - The Back-UPS has experienced an internal problem, but is still providing power to the connected equipment. Contact APC Technical Support Low Battery Shutdown - During On Battery operation the battery power was almost completely exhausted, and the Back-UPS is waiting for utility power to return to normal On Battery Overload - The connected equipment requires more power than provided by the Back-UPS battery. Unplug devices one at a time to remove overload. If the problem is not corrected, contact APC Technical Support Charger Fault - Back-UPS has an internal problem, and is no longer powering the load. Contact APC Technical Support Temperature Fault - The Back-UPS has overheated and has shut down. Problem Probable Cause Solution Back-UPS will not turn on. The circuit Breaker has tripped. Disconnect some of the equipment that is plugged into the BATTERY BACKUP + SURGE PROTECTION outlets. Reset the circuit breaker. Utility power is not available at the Check if the circuit breaker for the wall outlet has wall outlet. been tripped, if it has, reset the breaker. Connected equipment loses power. The ON/OFF button is lit, and the unit is beeping four times every 30 s, or it is emitting a constant tone. The Back-UPS is overloaded. The Back-UPS has exhausted its available battery power. Ensure that the equipment plugged into the unit is not overloading the capacity of the unit. Try disconnecting some of the equipment one device at a time, and see if the problem continues. The unit can only operate on battery power for a limited amount of time. The unit will eventually turn off when the available battery power has been used. Allow the unit to recharge for 10 hours before continuing to use the unit. The equipment connected to the The output waveform is designed for computers Back-UPS does not accept the stepapproximated sine waveform from designed for use with motor-type equipment. and computer-related equipment. It is not the unit. The Back-UPS may require service. Contact APC Technical Support for further troubleshooting. The unit is using battery. The unit is operating normally and using battery power. Save any current work, turn off all equipment, and turn the unit OFF. Once normal power is restored, turn the unit back ON, and turn on all equipment. 3

Problem Probable Cause Solution The On/Off button flashes once Battery capacity is low (there are The unit is about to shut down due to a low per ½, and the Back- UPS beeps once per at the same time. about 2 minutes of runtime remaining). battery charge condition. When the unit beeps once every, the battery has about 2 minutes of runtime remaining. Immediately power down your computer, and turn the unit OFF. When power returns to normal, the unit will recharge the battery. Inadequate runtime. The battery is not fully charged. Allow the unit to charge by leaving it plugged in, and switched on for 10 hours. Battery Replacement The battery in the Back-UPS 650 is not user-replaceable. Contact APC Sales and Technical Support for a list of authorized service centers near you. Specifications The battery is near the end of useful life. Input Voltage 120 VAC nominal Frequency 45-65 Hz Brownout Transfer 78 VAC, typical Over-voltage Transfer 150 VAC, typical Output UPS Capacity (total) 650 VA / 390 W Voltage On Battery 120 Vac rms (step-approximated sine wave) Frequency - On Battery 50 Hz ±1 Hz, 60 Hz ±1 Hz Transfer Time 6ms typical Protection AC Surge Protection Full time, 273 joules and Filtering AC Input Resettable circuit breaker Battery Type (maintenance-free) 12V, 7.2 AH Average Life 2-5 years depending on the number of discharge cycles and environmental temperature Typical Recharge Time 8 Hours Physical Net Weight 6.2 kg Dimensions (H x W x D) 20 cm x 11.5 cm x 25.7 cm Operating Temperature 0 o C to 40 o C (32 o F to 104 o F) Storage Temperature -15 o C to 45 o C (5 o F to 113 o F) Operating Relative 0 to 95% non-condensing Humidity Operating Elevation 0 to 3000 m (0 to 10,000 ft) As a battery ages, the amount of runtime available will decrease. Batteries also age prematurely if the unit is placed near excessive heat. If the battery will not charge, the Back-UPS is no longer operable. 4

Service DO NOT RETURN Back-UPS to the place of purchase under any circumstances. 1. Consult the Troubleshooting section to eliminate common problems. 2. If you still have problems or questions, please contact APC via the internet or at one of the phone numbers listed below. 3. Before contacting APC, please be sure to record the date purchased, UPS model, and serial number (on bottom of unit). 4. Be prepared to troubleshoot the problem over the telephone with a Technical Support Representative. If this is not successful, the representative will issue a Return Material Authorization Number (RMA#) and a shipping address. 5. Pack the unit in its original packaging. If the original packaging is not available, ask APC Technical Support about obtaining a new set. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty (insuring the package for full value is recommended). Write the RMA# on the outside of the package. Contact Information Internet http://www.apc.com Customer support and warranty information is available at the APC Web site, www.apc.com. 2010 APC by Schneider Electric. APC, the APC logo, and Back-UPS are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners. 990-3916-008 10/2010