page 2
Technical data /mean values including torsion Technical data 50 50 90 0 25 90 s = 3.5 25 90 s = 4 MI-90 MI-0 Material thickness s [mm] 3.5 4.0 Cross-sectional area A [mm 2 ] 1002.6 1375.7 Weight of girder [kg /m] 9.43.60 Material Elastic limit (yield strength) f y,k [N/mm 2 ] 235.0 235.0 Permissible tensile stress* σ Zul [N/mm 2 ] 152.6 152.6 Modulus of elasticity [N/mm 2 ] 210000 210000 Shear modulus [N/mm 2 ] 81000 81000 Surface Hot-dip galvanized 70 µm Cross-section values y-axis Axis of gravity ey [mm] 45.0 60.0 Moment of inertia ly [cm 4 ] 115.34 265.78 Section modulus Wy [cm 3 ] 25.63 44.30 Radius of gyration iy [cm] 3.39 4.40 Cross-section values x-axis Axis of gravity ez [mm] 45.00 45.00 Moment of inertia lz [cm 4 ] 115.34 173.58 Section modulus Wz [cm 3 ] 25.63 38.57 Radius of gyration iz [cm] 3.39 3.55 Torsion data Torsional moment of inertia Σ lt [cm 4 ] 155.56 297.02 Torsional section modulus Wt =2*ABredt * [cm 3 ] 45.25 71.63 * The permissible stress is calculated from σd / γg/q with γ = 1,4. σd results from higher yield strength due to cold forming in accordance with DAST-RILI016, issued 1992: σd = fyk / γm mit γm = 1,1 page 3
Single-span subject to bending in one axis F 1 when f=l/200, F 2 when f=l/300, F when σ zul including the framing section s own weight MI-90, one single load MI-0, one single load F 50 F 50 L/2 L/2 L 90 25 L/2 L/2 L 0 25 90 s = 3.5 90 s = 4 Length of F [kn] f [mm] F1 [kn] f [mm] F2 [kn] f [mm] span [mm] σ zul L/200 L/300 250 58.75 < 0.1 500 30.75 0.3 750 20.67 0.8 1000 15.54 1.3 50.43 2.1 1500 10.34 3.0 1750 8.85 4.1 2000 7.72 5.4 2250 6.85 6.8 2500 6.14 8.4 6.06 8.3 2750 5.56 10.2 4.97 9.2 3000 5.08.2 4.14 10.0 3250 4.67 14.3 3.49 10.8 3500 4.31 16.6 2.97 11.7 3750 4.00 19.1 3.92 18.8 2.55.5 4000 3.73 21.8 3.41 20.0 2.20 13.3 4250 3.50 24.6 2.98 21.3 1.91 14.2 4500 3.30 27.6 2.62 22.5 1.66 15.0 4750 3.10 30.8 2.31 23.8 1.45 15.8 5000 2.90 34.2 2.05 25.0 1.27 16.7 5250 2.70 37.8 1.82 26.3 1.11 17.5 5500 2.60 41.6 1.61 27.5 0.97 18.3 5750 2.50 45.5 1.44 28.8 0.85 19.2 6000 2.30 49.7 1.28 30.0 0.74 20.0 Length of F [kn] f [mm] F1 [kn] f [mm] F2 [kn] f [mm] span [mm] σ zul L/200 L/300 250 101.32 < 0.1 500 53.13 0.2 750 35.73 0.6 1000 26.86 1.0 50 21.50 1.6 1500 17.90 2.3 1750 15.32 3.1 2000 13.38 4.0 2250 11.87 5.1 2500 10.66 6.3 2750 9.66 7.7 3000 8.83 9.1 3250 8. 10.7 3500 7.51.4 7.03 11.7 3750 6.98 14.3 6.07.5 4000 6.52 16.3 5.28 13.3 4250 6.10 18.4 4.62 14.2 4500 5.74 20.7 4.07 15.0 4750 5.41 23.1 3.60 15.8 5000 5.11 25.6 4.98 25.0 3.20 16.7 5250 4.80 28.2 4.47 26.3 2.85 17.5 5500 4.60 31.0 4.01 27.5 2.54 18.3 5750 4.50 34.0 3.62 28.8 2.27 19.2 6000 4.10 37.1 3.27 30.0 2.03 20.0 Selection of framing section for single span with max. load when f < L/200 Single central load incl. framing section s own weight L F[kN] 50.00 Load F (kn) 45.00 40.00 35.00 30.00 25.00 MI-90 MI-0 MQ-21 D/F* MQ-41 D/F* MQ-41/F* MQ-52-72 D/F* 20.00 15.00 10.00 5.00 0.00-5.00 0 500 1000 1500 2000 2500 3000 Length of span (mm) * Technical data for the MQ System can be found in the Installations Systems main catalogue. page 4
MI connector on MI girder (recommended loads 1) ) MIC-90-U or MIC-0-U on MI-90 ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 9.70 1.70.00 Fy + Fx + Fz 9.70 1.70.00 * Force permissible in only one direction (// = or) Note: Not to be used for cantilevers. Section always requires support at both ends. MIC-90-U or MIC-0-U on MI-0 MI-90 or MI-0 Each with single screw (84 Nm) Fy MI-90 ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 10.30 1.70 13.70 Fy + Fx + Fz 10.30 1.70 13.70 * Force permissible in only one direction (// = or) Note: Not to be used for cantilevers. Section always requires support at both ends. Fx Fz MIC-90-L auf MI-90 oder MI-0 Single screw (84 Nm) ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 13,20 8,26 18,60 Fy + Fx + Fz 13,20 3,10 18,60 * Force permissible in only one direction (// = or) Note: Designed for use with cantilevers. May be supported at only one end. 2) 2 screws crosswise (84Nm) Fx Fy Single screw (84 Nm) Fz MI beam clamps (recommended loads 1) ) M x 85 MI-GC-M Fz ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fz 1.50-1.50 Fy + Fx + Fz 0.78 5.80 0.78 All loads apply to 1 beam clamp. Recommended shear loads apply to galvanized steel on galvanized steel. Clamps must always be used in pairs. Tightening torque M D :69 Nm Fy 30 M Fx 1) Calculation of rated values: F d = F rec. 1,5 2) Our technical advisory service would be pleased to assist with design and calculation. page 5
MI connector on steel beams (recommended loads 1) ) 140 beam clamps (69 Nm) 60 x 13 MIC-S-90-AA ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 3.00 9.00 3.00 Fy + Fx + Fz 1.56 5.00 1.56 * Force permissible in only one direction (// = or) Note: Not to be used for cantilevers. Always requires support at both ends. MI-90 Fx Fy 100 B 300 MIC-S-90-A Fz 2 x screws crosswise (84 Nm) ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 6.00 14.70 6,00 Fy + Fx + Fz 3.11 14.70 3,11 * Force permissible in only one direction (// = or) Note: Designed for use with cantilevers. May be supported at only one end. 2) 4 x beam clamps (69 Nm) MIC-S-90-B Fy 140 ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 6.00 10.20 6.00 Fy + Fx + Fz 3.11 10.20 3.11 * Force permissible in only one direction (// = or) Note: Designed for use with cantilevers. May be supported at only one end. 2) MIC-S-90-C MI-90 Fx 14 60 x 13 Fz 150 155 220 2 x screws crosswise (84 Nm) ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 6.00 7.20 6.00 Fy + Fx + Fz 3.11 7.20 3.11 * Force permissible in only one direction (// = or) Note: Designed for use with cantilevers. May be supported at only one end. 2) MIC-S-0-A 4 x beam clamps (69 Nm) ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 6.00 16.50 6.00 Fy + Fx + Fz 3.11 16.50 3.11 * Force permissible in only one direction (// = or) Note: Designed for use with cantilevers. May be supported at only one end. 2) MIC-S-0-B MI-0 Fy 140 ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 6.00 11.30 6.00 Fy + Fx + Fz 3.11 11.30 3.11 * Force permissible in only one direction (// = or) Note: Designed for use with cantilevers. May be supported at only one end. 2) MIC-S-0-C Fx 14 60 x 13 Fz 150 155 220 2 x screws crosswise (84 Nm) ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 6.00 8.10 6.00 Fy + Fx + Fz 3.11 8.10 3.11 * Force permissible in only one direction (// = or) Note: Designed for use with cantilevers. May be supported at only one end. 2) 1) Calculation of rated values: F d = F rec. 1,5 2) Our technical advisory service would be pleased to assist with design and calculation. page 6
MI connector on concrete (recommended loads 1) ) screws crosswise (84 Nm) 100 MIC-C90-AA 3) ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 8.73 8.80 13.20 Fy + Fx + Fz 1.60 3.60 1.60 *Force permissible in only one direction (// = or) Note: Designed for use with cantilevers. May be supported at only one end. 2) MI-90 Fx Fy 140 Fz 200 MIC-C90-D 4) 230 156 screws crosswise (84 Nm) ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 28.10 22.00 28.10 Fy + Fx + Fz 15.00.00 15.00 *Force permissible in only one direction (// = or) Note: Designed for use with cantilevers. May be supported at only one end. 2) Fx MI-90 Fy 140 15 156 230 47 x 17 MIC-C0-D 4) Fz ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fx // Fz* 28.10 22.00 28.10 Fy + Fx + Fz 15.00.00 15.00 *Force permissible in only one direction (// = or) Note: Designed for use with cantilevers. May be supported at only one end. 2) Fy 140 230 156 screws crosswise (84 Nm) 15 156 230 Fx 47 x 17 Fz MIC-C90-U 3) ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fy // Fz* 5.82-13.20 Fy + Fz 5.82-11.67 *Force permissible in only one direction (// = or) Note: Not to be used for cantilevers. Always requires support at both ends. MI-90 Fy 100 Single screw (84 Nm) 8 200 1) Calculation of rated values: F d = F rec. x 1,5 2) Our technical advisory service would be pleased to assist with design and calculation. 3) Fx rec. : Given values apply only to use of HST/HST-R M anchors; higher values possible when other anchors are selected. Fy rec. : Given values apply to all M anchors Note: When loading with Fy, the elongated hole in the base plate in line with the direction of force must be filled with high-strength mortar (e.g. HIT-HY 150). 4) Fx rec.,fy rec.,fz rec. : Given values apply only to use of HST/HST-R M16 anchors; higher values possible when other anchors are selected. Fx Fz page 7
MI girder extension (recommended loads 1) ) 4 screws crosswise in end of each girder (84 Nm) MIC-90-E Fy 250 The loading capacity of the extension depends on the moments acting in the Y- and Z-axes. Please consult our technical advisory service. Fx Fz MI-90 MIC-0-E The loading capacity of the extension depends on the moments acting in the Y- and Z-axes. Please consult our technical advisory service. Fy 4 screws crosswise in end of each girder (84 Nm) 250 MI-0 Fx Fz MI connector / pedestal connector (recommended loads 1) ) MIC-T Fy 2 screws (84 Nm) ±Fy rec. [kn] ± Fx rec. [kn] ± Fz rec. [kn] Fz* - - 20.00 Fy + Fx + Fz 3.50 1.00 10.00 * Force permissible in only one direction (// = or) Note: Always to be fitted on both sides. Fx 1) Calculation of rated values: F d = F rec. x 1,5 Fz page 8
MI Multi-angle connectors ( recommended loads 1) ) MIC-U-MA (connection to MI girder ) 8 0 Tension or compression F rec. [kn] 2) Angle 0 30 45 60 90 24.00 11.80 10.00 9.20 9.70 Note: Always to be fitted in pairs. 130.5 197,5 2 screws (84 Nm) MIC-SA-MA (connection to steel beam) Tension or compression F rec. [kn] 2) Angle 0 30 45 60 90 16.00 10.00 7.00 6.00 5.00 80 4 beam clamps (69 Nm) D C B MIC-SB-MA (connection to steel beam) Tension or compression F rec. [kn] 2) Angle 0 30 45 60 90.00 10.00 7.00 6.00 5.00 0 80.5 6 100 60 x 13 90 14 155 2 MIC-SC-MA (connection to steel beam) Tension or compression F rec. [kn] 2) Winkel 0 30 45 60 90 8.00 8.00 7.00 6.00 5.00 MIC-CU-MA (connection to concrete) 8 200 Tension or compression F rec. [kn] 2)3) Angle 0 30 45 60 90 7.10 5.00 4.00 4.00 5.30 1) Calculation of rated values: F d = F rec. 1,5 2) F rec. always acts in the longitudinal axis of the girder, irrespective of angle. 3) F rec. : Given values apply only to use of HST/HST-R M anchors; higher values possible when other anchors are selected. 0 80.5 6 150 100 100 25 x 14 90 page 9
page 10
MI girder Torsionally rigid girder. Pipes may be mounted on all four sides simultaneously. Scale marks facilitate installation /cutting to length. Crimped-in depression for 100% compatibility with MQ channel system. Technical data Material: S235JRG2 as per DIN 10025 Galvanizing: Hot-dip galvanized 75 µm Section height Length Material thickness Weight Ordering designation Item no. Packaged [mm] (m) [mm] (kg/m) in lengths of 90 3 3.5 9.43 ➀MI-90 3m 304798 3m 90 6 3.5 9.43 ➀MI-90 6m 304799 6m 0 3 4.60 ➁MI-0 3m 304800 3m 0 6 4.60 ➁MI-0 6m 304801 6m 50 90 90 s = 3.5 25 50 0 25 90 s = 4 page 11
MI connectors: Crossbeam connectors Fine adjustment in 5 mm increments for maximum flexibility. Only two connecting screws required. Keyed hold for optimum transmission of forces and moments. Self-locking nuts for vibration-resistant screw connections. Technical data Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 55µm Note Always to be supported at opposite end. Crossbeam connectors with connecting parts For girder type Weight per Ordering designation Item no. Package set [kg] MI- 90 2.36 MIC-90-U 304803 4 MI-0 2.79 MIC-0-U 304804 4 100 75 8 MI-90 192 Items Set besteht in set aus: 100 75 8 Crossbeam connectors without connecting parts For girder type Weight per Ordering designation Item no. Package set [kg] MI- 90 1.78 MIC- 90-U-AP 305708 4 MI-0 2.18 MIC-0-U-AP 305709 4 MI-0 220 page
MI connectors: Cantilever connectors Fine adjustment in 5 mm increments for maximum flexibility. Only four connecting screws required. Keyed hold for optimum transmission of forces and moments. Self-locking nuts for vibration-resistant screw connections Technical data Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 55 µm Note Designed for cantilever applications. May be supported at only one end. Cantilever connector with connecting parts For girder type Weight per Ordering designation Item no. Package set [kg] MI-90 3.95 MIC-90-L 304805 2➀ 140 8 Items Set besteht in set aus: 4x 315 75 Cantilever connector without connecting parts For girder type Weight per Ordering designation Item no. Package set [kg] MI-90 2.80 MIC-90-L-AP 305710 2 page 13
MI connectors: Pedestal connector Fine adjustment in 5 mm increments for maximum flexibility. Keyed hold for optimum transmission of forces and moments. Technical data Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 55 µm Pedestal connector with connecting parts 8 0 For girder type Weight per Ordering designation Item no. Package set [kg] MI-90/MI-0 2.04 MIC-T 304807 2 Items Set besteht in set aus: 220 75 page 14
MI connectors: Girder extension Flexurally rigid extension/connection for MI girder. Built-in stop prevents the extension sliding right inside the girder. Technical data Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 55 µm Girder extension with connecting parts For girder type Weight per ordering designation Item no. Package set [kg] MI-90 3.57 MIC-90-E 304809 2 MI-0 4.35 MIC-0-E 304810 2 Items Set besteht in set aus : 250 8x 8x MI-90 Items Set besteht in set aus : 4x 4x 250 MI-0 8x page 15
MI steel connectors: Connection to steel beams For connection to standard steel beams without drilling or welding. Suitable for connection to flange or web. For use with MI-GC-M beam clamp. B Technical data Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 55 µm Steel connectors with connecting parts For girder type Steel beam width B C D Weight per Ordering designation Item no. Package [mm] [mm] [mm] set [kg] MI-90 75 165 4.37 MIC-S90-AA 304811 2 MI-90 75 165 200 280 7.14 MIC-S90-A 3048 2 MI-90 165 235 300 350 8.59 MIC-S90-B 304813 2 MI-90 235 300 350 430 10.24 MIC-S90-C 304814 2 MI-0 75 165 200 280 7.54 MIC-S0-A 304818 2 MI-0 165 235 300 350 8.99 MIC-S0-B 304819 2 MI-0 235 300 350 430 10.65 MIC-S0-C 304820 2 140 60 x 13 D C B D C B 140 140 B 300 MI-0 MI-90 100 MI-90 14 60 x 13 150 155 220 14 60 x 13 150 155 220 Note: Always to be supported at opposite end. Note: + Designed for cantilever applications. May be supported at only one end. Items Set besteht in set aus: page 16
MI steel connectors: Connection to steel beams For connection to standard steel beams without drilling or welding. Suitable for connection to flange or web. Lightweight for easy one man installation. B Technical data Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 75 µm Steel connectors welded bracket Fz 1/2 1/2 For girder type Length L Steel beam width B C D Weight per Ordering designation Item no. [mm] [mm] [mm] [mm] set [kg] Recommended working load F z [kn] MI-90 500 75 165 200 280 10.18 4.660 2.970 MIC-S90-A-500 267774 MI-90 750 75 165 200 280.53 3.920 1.960 MIC-S90-A-750 267775 MI-90 1000 75 165 200 280 14.89 2.900 1.450 MIC-S90-A-1000 267776 MI-90 1500 75 165 200 280 19.61 1.850 0.920 MIC-S90-A-1500 267777 MI-90 2000 75 165 200 280 24.32 1.310 0.650 MIC-S90-A-2000 267778 MI-90 500 165 235 300 350 11.63 4.660 2.970 MIC-S90-B-500 267779 MI-90 750 165 235 300 350 13.98 3.920 1.960 MIC-S90-B-750 267780 MI-90 1000 165 235 300 350 16.34 2.900 1.450 MIC-S90-B-1000 267781 MI-90 1500 165 235 300 350 21.06 1.850 0.920 MIC-S90-B-1500 267782 MI-90 2000 165 235 300 350 25.77 1.310 0.650 MIC-S90-B-2000 267783 MI-90 500 235 300 350 430 13.29 4.230 2.110 MIC-S90-C-500 267784 MI-90 750 235 300 350 430 15.64 2.780 1.390 MIC-S90-C-750 267785 MI-90 1000 235 300 350 430 18.00 2.040 1.020 MIC-S90-C-1000 267786 MI-90 1500 235 300 350 430 22.72 1.280 0.640 MIC-S90-C-1500 267787 MI-90 2000 235 300 350 430 27.43 0.880 0.440 MIC-S90-C-2000 267788 MI-0 500 75 165 200 280 11.76 4.640 3.610 MIC-S0-A-500 267794 MI-0 750 75 165 200 280 14.91 4.640 2.380 MIC-S0-A-750 267795 MI-0 1000 75 165 200 280 18.06 3.510 1.750 MIC-S0-A-1000 267796 MI-0 1500 75 165 200 280 24.36 2.230 1.110 MIC-S0-A-1500 267797 MI-0 2000 75 165 200 280 30.66 1.560 0.780 MIC-S0-A-2000 267798 MI-0 500 165 235 300 350 13.21 4.640 2.960 MIC-S0-B-500 267799 MI-0 750 165 235 300 350 16.36 3.900 1.950 MIC-S0-B-750 270459 MI-0 1000 165 235 300 350 19.51 2.870 1.430 MIC-S0-B-1000 270460 MI-0 1500 165 235 300 350 25.81 1.810 0.900 MIC-S0-B-1500 270461 MI-0 2000 165 235 300 350 32.11 1.240 0.620 MIC-S0-B-2000 270462 MI-0 500 235 300 350 430 14.87 4.640 2.320 MIC-S0-C-500 270463 MI-0 750 235 300 350 430 18.02 3.040 1.520 MIC-S0-C-750 270464 MI-0 1000 235 300 350 430 21.17 2.230 1.110 MIC-S0-C-1000 270465 MI-0 1500 235 300 350 430 27.47 1.230 0.690 MIC-S0-C-1500 270466 MI-0 2000 235 300 350 430 33.77 0.810 0.460 MIC-S0-C-2000 270467 Fz 1/3 1/3 Fz 1/3 Note: + Designed for cantilever applications. May be supported at only one end. Calculated by: Suitable Hilti beam clamps MI-GC-M, Item No. 304894 F Z L D C B F Z L D C B 14 60 x 13 155 220 14 60 x 13 150 155 220 page 17
MI concrete connectors: Connection to concrete Four elongated holes for easy wall mounting. Designed for ceiling, wall and floor mounting. Technical data Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 55 µm Concrete connector with connecting parts For girder type Weight per Ordering designation Item no Package set [kg] MI-90 3.51 MIC-C90-AA 304825 2 MI-90 7.32 MIC-C90-D 304827 2 MI-0 7.69 MIC-C0-D 304829 2 100 230 230 156 156 140 15 140 15 MI-90 140 200 MI-90 156 230 156 230 47 x 17 47 x 17 Note: Always to be supported at opposite end. Note: + Designed for cantilever applications. May be supported at only one end. Items Set besteht in set aus: page 18
MI concrete connectors: Connection to concrete Four elongated holes for easy wall mounting. Designed for ceiling, wall and floor mounting. Lightweight for easy one man installation. Technical data Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 75 µm Concrete connector welded bracket 1/2 Fz 1/2 Fz 1/3 1/3 Fz 1/3 For girder type Length L Weight per Ordering designation Item no. [mm] set [kg] Recommended working load F z [kn] MI-90 500 10.60 9.380 4.690 MIC-C90-D-500 267789 MI-90 750.95 6.210 3.100 MIC-C90-D-750 267790 MI-90 1000 15.31 4.610 2.300 MIC-C90-D-1000 267791 MI-90 1500 20.03 3.000 1.500 MIC-C90-D-1500 267792 MI-90 2000 24.74 2.160 1.080 MIC-C90-D-2000 267793 MI-0 500.18 10.000 5.320 MIC-C0-D-500 270468 MI-0 750 15.33 7.040 3.520 MIC-C0-D-750 270469 MI-0 1000 18.48 5.230 2.610 MIC-C0-D-1000 270470 MI-0 1500 24.78 3.380 1.690 MIC-C0-D-1500 270471 MI-0 2000 31.08 2.420 1.210 MIC-C0-D-2000 270472 230 230 F Z 156 15 F Z 156 15 L L 156 230 156 230 47 x 17 47 x 17 Note: + Designed for cantilever applications. May be supported at only one end. Anchor Calculated by: Approved Hilti HST(R) M16 anchors; alternative approved Hilti anchors are the Hilt HVZ, HIT-TZ(R) of the same nominal diameter and same version. page 19
MI concrete connectors: Connection to concrete walls Lighter version for structures supported at both ends. Elongated holes for easier positioning. Simple support for installation between two walls. Technical data Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 55 µm Note Always to be supported at opposite end. Concrete wall connector with connecting parts For girder type Weight per Ordering designation Item no. Package set [kg] MI-90 2.29 MIC-C90-U 304826 2 MI-90 100 200 150 8 100 Items Set besteht in set aus: 1x 25 x 14 1x page 20
MI connectors: Multi-angle connectors For supports / corner struts at angles between 0 and 180. For connecting directly to standard steel beams or concrete. Technical data Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 55 µm MI angle connectors for girder, with connecting parts For girder type Weight per Ordering designation Item no. Package set [kg] MI-90/MI-0 2.53 MIC-U-MA 304806 2 8 0 Items Set besteht in setaus: 130.5 197,5 80 MI angle connectors for steel, with connecting parts For girder type Steel beam width B C D Weight per Ordering designation Item no. Package [mm] [mm] [mm] set [kg] MI-90/MI-0 75 165 200 280 6.29 MIC-SA-MA 304815 4 MI-90/MI-0 165 235 300 350 7.74 MIC-SB-MA 304816 2 MI-90/MI-0 235 300 350 430 9.40 MIC-SC-MA 304817 2 Items Set besteht in setaus: 80 D C B.5 6 100 60 x 13 14 155 220 MI angle connectors for concrete, with connecting parts 8 200 For girder type Weight per Ordering designation Item no. Package set [kg] MI-90/MI-0 2.04 MIC-CU-MA 304828 4 Items Set besteht in setaus: 80.5 6 150 100 100 25 x 14 page 21
MI steel / concrete connectors Base plates for steel / concrete All steel beam widths from 75 300 mm covered by only 3 plate sizes. Technical data Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 55 µm MI base plates for steel / concrete, without connecting parts For girder type Steel beam width B C D Weight per Ordering Item no. Package [mm] [mm] [mm] set [kg] designation MI-90/MI-0 75 165 200 280 5.46 MIB-SA 304821 2 MI-90/MI-0 165 235 300 350 6.91 MIB-SB 304822 2 MI-90/MI-0 235 300 350 430 8.57 MIB-SC 304823 2 MI-90/MI-0 For connection to concrete 5.88 MIB-CD 304830 2 150 D C B 14 155 220 60 x 13 230 156 15 156 230 47 x 17 page 22
Flexy pack: Adaptable connector for steel or concrete The girder connection point can be positioned as desired for special cases. Supplied in a primer finish for trouble-free welding. Can be galvanized later if desired. Technical data Material: S235 JRG2 as per DIN EN 10 025 Corrosion protection: None (primer coating-basic connector) Pos. 1 Flexy pack connector for welding as desired, without connecting parts Pos. 2 Parts list Ordering designation Item no. Info Position MIC-SC90 or MIC-SC0 304824 or 304808 Pos.1 MIB-SA or MIB-SB 304821/304822 Depending on base material Pos.2 MIB-SC or MIB-CD 304823/304830 or size of steel beam MI basic connector for welding, without connecting parts 140 140 For girder type Weight per Ordering designation Item no. Package set [kg] MI- 90 1.44 MIC-SC90 304824 2 MI-0 1.81 MIC-SC0 304808 2 72 101 72 71 page 23
Pipe clamps: U-bolt clamps for uninsulated pipes Reliable fastening system for U-bolts. Elongated holes for full adjustment of pipe position. Keyed hold for optimum transmission of forces. Technical data for the clamping system Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 55 µm Connecting screws: M (connection to MI-girder) MI U-bolt clamps with connecting parts For girder type Weight per Ordering designation Item no. Package set [kg] MI-90 1.26 MIC-UB90 304831 10* MI-90 2.58 MIC-UB90 L400 304832 2 MI-0 1.38 MIC-UB0 304833 10* MI-90 1.24 MIC-UB90-M16 304834 6* MI-0 1.36 MIC-UB0-M16 304835 6* *numbers of pairs in set 28,5 49 65 x 13 49 65 x 13 49 65 x 17 49 400 177,5 x 13 15 65 x 17 49 26 x 13,5 90 90 96 35 x 13 26 x 13,5 90 96 26 x 13,5 90 90 26 x 13,5 90 96 6 Items Set in set : besteht aus: Items Set in : set besteht aus: 1x page 24
Pipe clamps: MI U-bolts for uninsulated pipes Small contact surface between U-bolt and pipe. Minimizes crevice corrosion. In compliance with DIN standard for U-bolts. h b2 d1 Technical data for the clamping system Material: S235 JRG2 as per DIN EN 10025 Galvanizing: Hot-dip galvanized 45 µm Temperatures: 300 C e d3 U-bolts with connecting parts Nominal size Pipe outside d1 b2 h Shank d3 e Weight Ordering designation Item no. Package diameter Da dia. each NW [mm] [mm] [mm] [mm] [mm] [mm] [kg] 25 33.7 38 50 76 10 M10 48 0.13 MI-UB 25-M10 304870 5 40 48.3 52 50 92 10 M10 62 0.16 MI-UB 40-M10 304871 5 50 60.3 64 50 109 M 76 0.24 MI-UB 50-M 304872 5 65 76.1 82 50 5 M 94 0.27 MI-UB 65-M 304873 5 80 88.9 94 50 138 M 106 0.29 MI-UB 80-M 304874 5 100 114.3 0 60 171 16 M16 136 0.64 MI-UB 100-M16 304875 5 5 139.7 148 60 191 16 M16 164 0.72 MI-UB 5-M16 304876 3 150 168.3 176 60 217 16 M16 192 0.80 MI-UB 150-M16 304877 3 200 219.1 228 70 283 16 M16 244 1.01 MI-UB 200-M16 304878 3 250 273.0 282 70 334 16 M16 298 1.19 MI-UB 250-M16 304879 3 page 25
MI pipe clamps: Pipe supports for insulated pipes With mounting holes for installing light-duty fixed points. F x F y H s Fz D a B F F y s F x H L 1 Fz D a F B F y F x s H L 1 Fz D a F B W 13 13 L W L + F z + F z W + F z 13 L 1 ring / 1 rib for DN25-DN150 2 rings / 1 rib for DN25-DN300 Heavy-duty version for DN200-DN600 75 5 Technical data for the clamping system Material: S235 JRG2 as per DIN EN 10025 Galvanizing: Hot-dip galvanized 70 µm Temperatures: Up to 300 C Low-friction plate 8 Sliding support clamps Fixed point Nominal Pipe outside B s F W H L L1 Clamping Weight per Permissible loads Ordering designation Item no. Package size diameter Da screw set Fx +Fz Fz Fy NW [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [kg] (kn) (kn) (kn) (kn) 25 33.7 30 6 9 80 85 250 M10 2.8 0.4 0.8 0.3 0.3 MI-PS1/1 25-85 304844 2 25 33.7 30 6 8 82 140 250 M10 2.4 0.4 0.8 0.3 0.3 MI-PS1/1 25-140 286957 2 40 48.3 30 6 9 80 85 250 M10 2.8 0.5 1.0 0.3 0.3 MI-PS1/1 40-85 304845 2 40 48.3 30 6 8 82 140 250 M10 2.4 0.5 1.0 0.3 0.3 MI-PS1/1 40-140 286958 2 50 60.3 40 6 9 80 85 250 M 3.2 0.9 1.8 0.6 0.6 MI-PS1/1 50-85 304846 2 50 60.3 40 6 8 82 140 250 M 2.7 0.9 1.8 0.6 0.6 MI-PS1/1 50-140 286959 2 65 76.1 40 6 9 80 85 250 M 3.3 1.1 2.1 0.7 0.7 MI-PS1/1 65-85 304847 2 65 76.1 40 6 8 82 140 250 M 2.8 1.1 2.1 0.7 0.7 MI-PS1/1 65-140 286960 2 80 88.9 40 6 9 80 85 250 M 3.3 1.2 2.3 0.8 0.8 MI-PS1/1 80-85 304848 2 80 88.9 40 6 8 82 140 250 M 2.9 1.2 2.3 0.8 0.8 MI-PS1/1 80-140 286961 2 100 114.3 40 8 9 80 85 250 M 3.8 2.5 5.0 1.7 1.7 MI-PS1/1 100-85 304849 2 100 114.3 40 8 8 80 140 250 M 3.4 2.5 5.0 1.7 1.7 MI-PS1/1 100-140 286962 2 5 139.7 40 8 9 80 85 250 M 4.0 2.9 5.8 1.9 1.9 MI-PS1/1 5-85 304850 2 5 139.7 40 8 8 80 140 250 M 3.6 2.9 5.8 1.9 1.9 MI-PS1/1 5-140 286963 2 150 168.3 40 8 9 80 85 250 M 4.2 3.2 6.4 2.1 2.1 MI-PS1/1 150-85 304851 2 150 168.3 40 8 8 80 140 250 M 3.8 3.2 6.4 2.1 2.1 MI-PS1/1 150-140 286964 2 25 21.3 30 5 9 80 85 250 200 M10 3.3 0.8 1.5 0.5 0.5 MI-PS2/1 25-85 304852 2 25 21.3 30 5 9 80 140 250 180 M10 3.7 0.8 1.5 0.5 0.5 MI-PS2/1 25-140 286965 2 40 48.3 30 5 9 80 85 250 200 M10 3.4 1.0 2.0 0.7 0.7 MI-PS2/1 40-85 304853 2 40 48.3 30 5 9 80 140 250 180 M10 3.8 1.0 2.0 0.7 0.7 MI-PS2/1 40-140 286966 2 50 60.3 40 6 9 80 85 250 190 M 4.1 1.8 3.5 1.2 1.2 MI-PS2/1 50-85 304854 2 50 60.3 40 6 9 80 140 250 180 M 4.5 1.8 3.5 1.2 1.2 MI-PS2/1 50-140 286967 2 65 76.1 40 6 9 80 85 250 190 M 4.3 2.1 4.2 1.4 1.4 MI-PS2/1 65-85 304855 2 65 76.1 40 6 9 80 140 250 180 M 4.7 2.1 4.2 1.4 1.4 MI-PS2/1 65-140 286968 2 80 88.9 40 6 9 80 85 250 190 M 4.4 2.4 4.7 1.6 1.6 MI-PS2/1 80-85 304856 2 80 88.9 40 6 9 80 140 250 180 M 4.8 2.4 4.7 1.6 1.6 MI-PS2/1 80-140 286969 2 100 114.3 40 8 9 80 85 250 190 M 5.3 3.0 6.0 2.0 2.0 MI-PS2/1 100-85 304857 2 100 114.3 40 8 9 80 140 250 180 M 5.8 3.0 6.0 2.0 2.0 MI-PS2/1 100-140 286970 2 5 139.7 40 8 9 80 85 250 190 M 5.7 3.5 7.0 2.3 2.3 MI-PS2/1 5-85 304858 1 5 139.7 40 8 9 80 140 250 180 M 6.1 3.5 7.0 2.3 2.3 MI-PS2/1 5-140 286971 1 150 168.3 40 8 9 80 85 250 190 M 6.1 4.0 8.0 2.7 2.7 MI-PS2/1 150-85 304859 1 150 168.3 40 8 9 80 140 250 180 M 6.6 4.0 8.0 2.7 2.7 MI-PS2/1 150-140 286972 1 200 219.1 50 8 9 100 107 250 180 M16 8.5 4.8 9.5 3.2 3.2 MI-PS2/1 200-107 304860 1 200 219.1 50 8 9 100 142 250 180 M16 8.9 4.8 9.5 3.2 3.2 MI-PS2/1 200-142 286973 1 250 273.0 50 8 9 100 107 250 180 M16 9.5 5.3 10.5 3.5 3.5 MI-PS2/1 250-107 304861 1 250 273.0 50 8 9 100 142 250 180 M16 9.9 5.3 10.5 3.5 3.5 MI-PS2/1 250-142 286974 1 300 323.9 50 8 9 100 107 250 180 M16 10.5 5.8 11.5 3.8 3.8 MI-PS2/1 300-107 304862 1 300 323.9 50 8 9 100 142 250 180 M16 10.9 5.8 11.5 3.8 3.8 MI-PS2/1 300-142 286975 1 * The maximum permissible loads for connecting components must be taken into account when the pipe support is used! page 26
MI pipe clamps: Pipe supports for insulated pipes With mounting holes for installing light-duty fixed points. F x F y H s Fz D a B F F y s F x H L 1 Fz D a F B F y F x s H L 1 Fz D a F B W 13 13 L W L + F z + F z W + F z 13 L 1 ring / 1 rib for DN25-DN150 2 rings / 1 rib for DN25-DN300 Heavy-duty version for DN200-DN600 75 5 Technical data for the clamping system Material: S235 JRG2 as per DIN EN 10025 Galvanizing: Hot-dip galvanized 70 µm Temperatures: Up to 300 C Low-friction plate 8 Sliding support clamps Fixed point Nominal Pipe outside B s F W H L L1 Clamping Weight per Permissible loads Ordering designation Item no. Package size diameter Da screw set Fx +Fz Fz Fy NW [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [kg] (kn) (kn) (kn) (kn) 200 219.1 50 8 8 175 107 290 260 M16.4.0 4.0 4.0 MI-PS2/2 200-107 304863 1 200 219.1 50 8 8 175 142 290 260 M16 15.5.0 4.0 4.0 MI-PS2/2 200-142 286976 1 250 273.0 50 8 8 175 107 290 260 M16 13.2 15.0 5.0 5.0 MI-PS2/2 250-107 304864 1 250 273.0 50 8 8 175 142 290 260 M16 16.3 15.0 5.0 5.0 MI-PS2/2 250-142 286977 1 300 323.9 50 8 8 175 107 290 260 M16 14.0 16.0 5.3 5.3 MI-PS2/2 300-107 304865 1 300 323.9 50 8 8 175 142 290 260 M16 17.0 16.0 5.3 5.3 MI-PS2/2 300-142 286978 1 350 355.6 60 8 10 175 142 290 250 M16 19.2 17.8 5.9 5.9 MI-PS2/2 350-142 304866 1 350 355.6 60 8 10 175 192 290 250 M16 21.4 17.8 5.9 5.9 MI-PS2/2 350-192 286979 1 400 406.4 60 8 10 250 142 290 250 M16 24.9 18.7 6.0 6.0 MI-PS2/2 400-142 304867 1 400 406.4 60 8 10 250 192 290 250 M16 27.9 18.7 6.0 6.0 MI-PS2/2 400-192 286980 1 500 508.0 70 10 10 250 142 290 240 M20 33.5 21.3 6.0 6.0 MI-PS2/2 500-142 304868 1 500 508.0 70 10 10 250 192 290 240 M20 36.5 21.3 6.0 6.0 MI-PS2/2 500-192 286981 1 600 610.0 70 10 10 250 142 290 240 M20 36.8 28.0 6.0 6.0 MI-PS2/2 600-142 304869 1 600 610.0 70 10 10 250 192 290 240 M20 38.8 28.0 6.0 6.0 MI-PS2/2 600-192 286982 1 * The maximum permissible loads for connecting components must be taken into account when the pipe support is used! page 27
MI pipe clamps: MI sliding support clamping system for insulated pipes Pipe ring support free to move in one direction. Fully adjustable. Spacer plates permit use of pipe supports with base plates of greater thickness. Technical data for the clamping system Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 45 µm Technical data for low-friction system Material: PE-UH MW Friction value: µ = 0,15 Temperature resistance: 273,15 C to +90 C MI clamping system for sliding support, with connecting parts For girder type Weight per Ordering designation Item no. Package set [kg] MI-90 1.80 MIC-PS90 304838 4* MI-0 1.88 MIC-PS0 304839 4* MI-90/MI-0 0.22 MIC-PSP-4MM 283593 10* MI-90/MI-0 0.34 MIC-PSP-6MM 283594 10* *Number of pairs in package 45 18 M 102 130 90 18 45 M 102 130 0 130 13 102 30 4 16 130 13 102 6 30 18 MI low-friction system for sliding support 75 For girder type Weight per Ordering designation Item no. Package set [kg] MI-90/MI-0 0.1 MIC-PG 304842 10 5 8 page 28
MI pipe clamps: MI rigid support clamping system, with connecting parts Quickly and easily installed pipe support system for light-duty fixed points. Technical data for the clamping system Material: S235 JRG2 as per DIN EN 10025 Galvanizing: Hot-dip galvanized 45 µm MI clamping system for fixed points, with connecting parts 102 M 102 M For girder type Weight per Ordering designation Item no. Package set [kg] MI-90 0.60 MIA-B090-M 304840 8* MI-0 0.68 MIA-B00-M 304841 8* 6 156 *Number of pairs in package page 29
MI pipe clamps: Adaptor plate for pipe support clamping system, incl. connecting parts The adaptor plate takes the place of the steel beam flange and thus permits the use of conventional clamping systems for pipe supports. Technical data for the clamping system Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 55 µm 210 M 10 Adaptor plate with connecting parts 150 90 For girder type Weight per Ordering designation Item no. Package set [kg] MI-90 3.38 MIC-PA90 304836 2 MI-0 3.46 MIC-PA0 304837 2 210 M 10 150 0 MI pipe clamps: Twin roller support Dimensions suitable for fastening to MI-girder with MIC-PA90 or MIC-PA0. Technical data: Body material: S235 JRG2 as per DIN EN 10 025 Roller material: S355 JO as per DIN EN 10 025 Axle material: Stainless steel (1.4541) Rated load capacity: 15 kn Coefficient of friction: 0.035 For girder type Weight per Suitable pipe Ordering designation Item no. Package set [kg] diameter [mm] MI-90/MI-0 5.50 219 406 MI-DPR 304880 1 DA Items Set besteht in setaus: 225 86 E 8 DA = Outside-diameter pipe E = 0.532 x DA + 54 130 190 page 30
MI pipe clamps: Plate for weld-on tabs Easy installation of standard weld-on tabs, e.g. for spring hangers. Technical data for the clamping system Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: U-bolt galvanized 45µm, plate with primer finish For girder type Weight per Ordering designation Item no. Package set [kg] MI-90 1.01 MIC-SPH-90 304843 4 MI-0 1.10 MIC-SPH-0 283592 4 60 60 130 M 130 M 90 0 page 31
MI accessories: Individual connecting parts Parts designed for easy assembly with one hand (shaped to prevent rotation). Easy hand plate (5) for easy single-handed adjustment of the connection. Technical data Material: EN-GJMW-400-5 as per DIN EN 1562 Screws: 8.8 grade Nuts: 8 grade DIN 1661, self locking Galvanizing: 45 µm For girder type Weight per Ordering designation Item no. Packege set [kg] MI-90 0,16 MIA-EH90 304887 10 MI-0 0,19 MIA-EH0 304888 10 MI-90 0,10 MIA-OH90 304889 10 MI-0 0,13 MIA-OH0 304890 10 MI-90, MI-0 0,28 MIA-EH-P 304891 10 MI-90, MI-0 0,02 M-F hex.collar nut 283589 50 MI-90, MI-0 0,06 MIA-TP 305707 20 MI-90, MI-0 0,10 Hex.head screw M0-F/8.8 283595 40 MI-90, MI-0 0,11 Hex.head screw M130-F/8.8 283596 40 MI-90, MI-0 0,005 A 13-F washer 304771 100 36,6 36,6 M 0 36,6 36,6 M 150 Examples of applications (cantilever) Assembly procedure 1 2 2. M 95 7 2-3x M 1. 72 26 50 M 3 4 1. 2.,2 x,2 7 36,6 36,6 page 32
MI accessories: End caps Ends of girder closed securely. With built-in opening to permit drainage of liquids. Technical data Material: Temperature resistance: Moplen EP 240H 30 to +90 C For girder type Weight Ordering designation Item no. Package [kg] MI-90 0.03 MIA-EC-90 304892 25 MI-0 0.04 MIC-EC-0 304893 25 18.5 18.5 96 6 96 96 page 33
MI accessories: Beam clamps for various flange thicknesses For steel beams with a flange thickness of 3 - mm and angle of up to 15. Spacers for use with flange thicknesses greater than mm. Technical data Material: EN-GJMW-400-5 as per DIN EN 1562 Galvanizing: Hot-dip galvanized 55 µm Screws: 8.8 grade Note The flat nose must be positioned against the steel beam and the round nose on the connecting part or spacer. For girder type Weight per Ordering designation Item no. Package set [kg] MI-90/MI-0 0.27 MI-GC-M 304894 16 MI-90/MI-0 0.03 MI-GCD-6MM 283590 16 MI-90/MI-0 0.07 MI-GCD-MM 283591 16 M x 85 30 M 6 30 38 30 38 page 34
page 35
MI / MQ connector Direct connection to components of the Hilti MQ system. Keyed hold for optimum transmission of forces and moments. Technical data Material: S235 JRG2 as per DIN EN 10 025 Galvanizing: Hot-dip galvanized 55 µm MI / MQ connectors with connecting parts For channel Weight per Ordering designation Item no. Package set [kg] MQ-41, MQ-21D 0.36 MIC-MI/MQ-X 304881 16 all MQ single channels 0.05 MIC-MI/MQ-M8 304882 5 4 47 Items Set besteht in setaus: 250 4x 61 x 11 Items Set besteht in setaus: Assembly procedure 1 2 41 1. 2. M8x16 M8x16 SW13 5 Description Size Ordering designation Item no. Package Magnetic wrench SW 13 MQZ-SVS 369693 1 SW 13 with mit Magneteinsatz magnetic insert 200 mm page 36
MQV-UB U-bolt pipe clamp for MQ system Easy installation of U-bolts. Fastened with wing nuts or hex. nuts. Technical data Material: S235JR as per DIN EN 10025 Galvanizing: hot-dip galvanized, approx. 55 µm For channel Weight per Ordering designation Item no. Package set [g] MQ-41-F, MQ-41D-F, MQ-52-72D-F 70 MQV-UB-M 304884 5* 37 13 11 * Number of pairs in package 30 75 4 MQV-PS pipe support for MQ system Easy installation as guide-type pipe support. Fastened with wing nuts or hex. nuts. Technical data Material: S235JR as per DIN EN 10025 Galvanizing: hot-dip galvanized, approx. 55 µm 55 For channel Weight each Ordering designation Item no. Package [g] MQ-41-F, MQ-41D-F, MQ-52-72D-F 70 MQV-PS 304886 1* 37 11 25 4 * Number of pairs in package 94 MQP-U universal joint For D1 D2 Weight each Ordering Item no. Package [mm] [mm] [g] designation M,5,5 390 MQP-U M 284248 10 M16 16,5 16,5 390 MQP-U M16 284249 10 Item no. Max. recommended load Tightening torque M D [kn] [Nm] MQP-U M 14 20 MQP-U M16 14 20 MQP-45 -F base material connector For channel Weight each Ordering designation Item no. Package [g] MQ-21-F, MQ-41-F 350 MQP-45 -F 304164 1 105 45 14 41 42 page 37
Example of application Opposite cantilever arms at same or similar height Pos. 3 Pos. 5 Pos. 1 Pos. 2 Pos. 4 Parts list Quantity Ordering designation Item no. Info Position 2 MIC-90-L-AP 305710 Cantilever connectors Pos. 1 2 MIC-EH-90 304887 Pos. 2 2 MIA-TP 305707 Pos. 3 4 MIA-OH90 304889 Pos. 4 6 M-F hex. collar nut 283589 Self-locking nuts Pos. 5 Example of application Girder connection to steel beam Girder can be connected to steel beam without welding. Parts list (beam height up to 320 mm) Quantity Ordering designation Item no. Info Position 1 MIC-S*(A/B/C) 3048/304813/304814 To suit beam size Pos. 1 1 MIB-S* 304821/ 304822/ 304823 Size as (1) Pos. 2 4 AM -F 304774 M-F threaded rod Pos. 3 8 M-F hex. collar nut 283589 Self-locking nuts Pos. 4 *Plate size to be selected to suit width between flanges Pos. 4 Pos. 1 Pos. 3 Pos. 2 Beam height up to about 320 mm. page 38
Parts list (beam height greater than 320 mm) Quantity Ordering designation Item no. Info Position 2 MI-90 304799 Length to suit beam size Pos.1 8 MIC-UB90-M 304831 Pos.2 4 Hex.head screw M0F/ 8.8 283595 Pos.3 M-F hex. collar nut 283589 Self-locking nuts Pos.4 4 AM -F 304774 M-F threaded rod Pos.5 Pos. 2 Pos. 1 Pos. 5 Pos. 4 Pos. 3 Beam height greater than 320 mm. Further connections using MIC-90-L cantilever connector. Example of application Cross connection between MI girder Keyed hold for optimum transmission of forces and moments. Parts list Quantity Ordering designation Item no. Info Position 1 MIB-SA 304821 Pos. 1 4 MIA-EH-P 304891 Pos. 2 4 A13-F 304771 Pos. 3 4 M130F/8.8 hex screw 283596 Pos. 4 4 M hex. collar nut 283589 Self-locking nut Pos. 5 Pos. 1 Pos. 4 Pos. 5 Pos. 3 Pos. 2 Pos. 5 page 39
Hilti = registered trademark of Hilti Corp., Schaan W 2915 0906 5-en 1 Printed in Liechtenstein 2006 Right of technical and programme changes reserved S. E. & O. Hilti. Outperform. Outlast. Hilti Corporation 9494 Schaan Liechtenstein P +423-234 2111 F +423-234 2965