Geotechnical Investigation Reports and Foundation Recommendations - Scope for Improvement - Examples

Similar documents
Geotechnical Measurements and Explorations Prof. Nihar Ranjan Patra Department of Civil Engineering Indian Institute of Technology, Kanpur

Anirudhan I.V. Geotechnical Solutions, Chennai

Local Authority Building Control Technical Information Note 3 Driven and In-situ Piled Foundations

FINAL REPORT ON SOIL INVESTIGATION

PILE FOUNDATIONS FM 5-134

USE OF MICROPILES IN TEXAS BRIDGES. by John G. Delphia, P.E. TxDOT Bridge Division Geotechnical Branch

An Automatic Kunzelstab Penetration Test

A study on the Effect of Distorted Sampler Shoe on Standard Penetration Test Result in Cohesionless soil

ENCE 4610 Foundation Analysis and Design

Site Investigation. Some unsung heroes of Civil Engineering. buried right under your feet. 4. Need good knowledge of the soil conditions

Geotechnical Investigation Test Report

1.0 INTRODUCTION SCOPE OF WORK EXECUTION OF FIELD WORK LABORATORY TESTS FINDINGS OF THE GEOTECHNICAL INVESTIGATION 9

How To Design A Foundation

HOUSE BUILDING DIGEST

COSMOS 2012: Earthquakes in Action COSMOS 2012

Design, Testing and Automated Monitoring of ACIP Piles in Residual Soils

Method Statement FOR. Soil Investigation

product manual HS-4210 HS-4210_MAN_09.08 Digital Static Cone Penetrometer

KWANG SING ENGINEERING PTE LTD

Engineered, Time-Tested Foundation Repairs for Settlement in Residential and Light Commercial Structures. The Leading Edge.

COMPENDIUM OF INDIAN STANDARDS ON SOIL ENGINEERING PART 2

Module 1 : Site Exploration and Geotechnical Investigation. Lecture 4 : In-situ tests [ Section 4.1: Penetrometer Tests ] Objectives

STRUCTURES Excavation and backfill for structures should conform to the topic EXCAVATION AND BACKFILL.

CIVL451. Soil Exploration and Characterization

SPECIFICATION FOR DYNAMIC CONSOLIDATION / DYNAMIC REPLACEMENT

ASSESSMENT OF SHEAR WAVE VELOCITY FROM INDIRECT INSITU TESTS

METHOD OF STATEMENT FOR STATIC LOADING TEST

FOUNDATION DESIGN. Instructional Materials Complementing FEMA 451, Design Examples

INDIRECT METHODS SOUNDING OR PENETRATION TESTS. Dr. K. M. Kouzer, Associate Professor in Civil Engineering, GEC Kozhikode

BRIDGE RESTORATION AND LANDSLIDE CORRECTION USING STRUCTURAL PIER AND GRADE BEAM

Geotechnical Testing Methods II

GUJARAT NARMADA VALLEY FERTILIZER CO. LTD. (GNFC Ltd) TECHNICAL REPORT GEOTECHNICAL INVESTIGATION FOR PROPOSED TDI PLANT AT VILLAGE RAHIYAD, DAHEJ

2009 Japan-Russia Energy and Environment Dialogue in Niigata S2-6 TANAKA ERINA

ALLOWABLE LOADS ON A SINGLE PILE

BUTE Department of Construction Management and Technology

INSITU TESTS! Shear Vanes! Shear Vanes! Shear Vane Test! Sensitive Soils! Insitu testing is used for two reasons:!

Chittagong Hill Tract Development Facilities (CHTDF) United Nations Development Programme

load on the soil. For this article s examples, load bearing values given by the following table will be assumed.

Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. The design of any foundation consists of following two parts.

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 3, No 3, 2013

GUIDELINES FOR GEOTECHNICAL INVESTIGATION OF BRIDGE STRUCTURES. Materials Engineering Report No M (Supersedes Report No.

High Strain Dynamic Load Testing of Drilled Shafts

King Saud University College of Engineering Civil Engineering Department DEFORMATION OF PARTIALLY SATURATED SAND. Sultan Musaed Al-Ghamdi

Geotechnical Investigation using Standard Penetration Test (SPT) in Rangamati, Bandarban and Khagrachari Towns

Pile test at the Shard London Bridge

Quality control: Annex-A.

SERVICES 2015 ISO 18001

Pavements should be well drained both during and upon completion of construction. Water should not be allowed to pond on or near pavement surfaces.

DESIGNING STRUCTURES IN EXPANSIVE CLAY

Civil. 2. City of Seattle Supplement to the Specification for Road, Bridge and Municipal Construction, most current addition.

ENGINEERED FOUNDATIONS. Department of Public Works Jeff Hill, PE

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

c. Borehole Shear Test (BST): BST is performed according to the instructions published by Handy Geotechnical Instruments, Inc.

Eurocode 7 - Geotechnical design - Part 2 Ground investigation and testing

SETTLEMENT MONITORING OF DISCRETE REINFORCED SOIL LAYER BENEATH MAT FOUNDATIONS, CALIFORNIA, USA

Estimation of Adjacent Building Settlement During Drilling of Urban Tunnels

EVALUATING THE IMPROVEMENT FROM IMPACT ROLLING ON SAND

GEOTECHNICAL ENGINEERING FORMULAS. A handy reference for use in geotechnical analysis and design

Use of a Reinforced Jet Grout Excavation Support System for a Major Sewer Line Repair

Strength Determination of "Tooth-Paste" Like Sand and Gravel Washing Fines Using DMT

GLOSSARY OF TERMINOLOGY

Load Testing of Drilled Shaft Foundations in Limestone, Nashville, TN Dan Brown, P.E., Ph.D.

Caltrans Geotechnical Manual

UNDERPINNING OF NEW STUDENT HOUSING BUILDING USING MICROPILES, NORTH CAROLINA USA

vulcanhammer.net This document downloaded from

Table of Contents 16.1 GENERAL Overview Responsibilities

Comprehensive Design Example 2: Foundations for Bulk Storage Facility

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued November 1, Legacy report on the 1997 Uniform Building Code

and the design of construction working platforms

SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS

The Manitoba Water Services Board SECTION Standard Construction Specifications PIPE EXCAVATION, BEDDING AND BACKFILL Page 1 of 11

Work Type Definition and Submittal Requirements

Dead load (kentledge) A structure over the test pile. Ground anchorage either by tension piles or ground anchors. Bi-directional (Osterberg-cell)

FRANKIPILE. High Pile Loads Optimum Adaptation to Foundation Soil Low-noise Manufacturing Process

Permafrost in Marine Deposits at Ilulissat Airport in Greenland, Revisited

Jack-in Piling Environmental Friendly Piling System

Electronic Soil Test Logging. Strategic Advantage or Unnecessary Headache?

ATLAS RESISTANCE Pier Foundation Systems

Emergency repair of Bridge B421

NOTES TO THE PERFORMANCE BASED SPECIFICATION FOR HOTMIX ASPHALT WEARING COURSE SURFACING

STATUS REPORT FOR THE SUBMERGED REEF BALL TM ARTIFICIAL REEF SUBMERGED BREAKWATER BEACH STABILIZATION PROJECT FOR THE GRAND CAYMAN MARRIOTT HOTEL

1 Mobilisation and demobilisation 1 Deep boring sum 2 Cone penetration tests sum 3 Miscellenous tests sum

Requirements for an Excavation and Lateral Support Plan Building (Administration) Regulation 8(1)(bc)

SITE INVESTIGATION FACILITIES

Appendix A Sub surface displacements around excavations Data presented in Xdisp sample file

patersongroup Geotechnical Investigation Proposed Multi-Storey Buildings 267 O Connor Street Ottawa, Ontario Prepared For Mastercraft Starwood Group

FREDERICK SHERRELL LTD

patersongroup Geotechnical Investigation Proposed Residential Development 590 Hazeldean Road - Ottawa Prepared For Ontario Inc.

we are Presence in India

PLUMBING MAINTENANCE WORK FOR TOILETS IN HEAD OFFICE, SUPPLYCO ESTIMATE

How to Design Helical Piles per the 2009 International Building Code

The Stabilizer TM. Benefits. Supplemental support system for sagging beams and floor joists within a crawl space

Worked Example 2 (Version 1) Design of concrete cantilever retaining walls to resist earthquake loading for residential sites

Rehabilitation of Existing Foundation Building to Resist Lateral and Vertical Loads

Assessment. Ian Uglow Technical Director, SLR Consulting 7 th October 2010

A case study of large screw pile groups behaviour

The Impact of Market Demands on Residential Post-Tensioned Foundation Design: An Ethical Dilemma

Micropiles Reduce Costs and Schedule for Merchant RR Bridge Rehabilitation

Transcription:

Geotechnical Investigation Reports and Foundation Recommendations - Scope for Improvement - Examples Prof. V.S.Raju (Formerly: Director, IIT Delhi & Professor and Dean, IIT Madras) Email: rajuvs_b@yahoo.com Prof. V.S. Raju 1 CHOICE OF APPROPRIATE FOUNDATION AND EXECUTION Optimum foundation design should ensure: technical adequacy, cost effectiveness and ease of execution. This is not easy, because of many variables including insufficient and inaccurate information at the time of design. Variation in strata and changes in project requirement during execution 2 1

TOPICS COVERED Inadequacy of the Investigations and Inappropriate Foundation Recommendations with Illustrative Examples 1. Fertilizer Plant on the East Coast 2. Fertilizer Plant in Gangetic Belt 3. Office cum Residential Complex at Jodhpur 4. University Campus at Adilabad District 5. L&T Serene County (Residential Campus) 3 FERTILIZER PLANT ON THE EAST COAST The average soil strata consists of : top layer of dense fine sand 4 to 8 m thick. followed by soft marine clay up to a depth of 14 to 18 m below ground level. very stiff clay up to 30 to 40 m below ground level. 4 2

5 PROBLEMS DUE TO THE PRESENCE OF SOFT CLAY LAYER For site grading, 1-2 m fill is required - results in a settlement of 12 cm of soft clay. - Along with clay, sand layer also moves down. In case of pile foundation, large negative drag on piles from soft clay and sand layer. Considerable reduction in pile capacity (upto 50%), and hence increase in the number of piles. For structures like bulk storage with large area loads, the stability of soft clay layer and lateral flow to be checked. Large settlements of floors and lateral forces on neighbouring pile foundations. 6 3

FOUNDATIONS ADOPTED Precast driven piles were chosen, with bitumen coat in the top layers to reduce the negative drag. All light structures, not sensitive to settlements, are supported on shallow foundations. For structures having distributed loads over large areas (silos, water storages), surcharge provided on the periphery to achieve reduced shear stresses on soft clay. 7 CHOICE OF THE PILE The original recommendation was to go for bored piles, 45 cm in diameter. Two alternative pile types have been tested. a) Precast driven piles 40 cm x 40 cm, 22 m long (to be able to drive). b) Bored cast in situ piles, 45cm dia, 22 m long Full scale tests for a final decision on the choice of the pile type. 6 test piles, 3 each of the 2 types, installed in locations in close proximity. 3 different Bored cast in-situ piles were installed by bailer boring method. 8 4

RESULTS OF PILE LOAD TESTS 9 Table 1: WORKING LOAD IN TONS AS PER IS 2911 Pile No. (1) 2 / 3 of Load at 12 mm settlement (2) Failure Load (3) Half of Failure Load (4) Working Load (smaller of 2 and 4) (5) P1 73 160 80 73 (100) * B2 55 108 54 54 P3 110 194 97 97 B4 32 54 27 27 P5 85 164 82 82 B6 65 120 60 60 The pile length is 19.5 m, and failure load extrapolated for 22 m length is 100 tons. 10 5

CONCLUSIONS Precast driven piles with design load of 70 to 100 tonnes adopted for the following reasons : For comparable dimensions, the precast pile has 50 to 80% higher capacity than a bored pile. Precast pile offers better protection to reinforcement. This is particularly important under the present saline ground water conditions. The jetting of precast pile up to 12 m will reduce the friction over this depth, and consequently the effects of negative drag. In case of precast piles, the negative drag can be reduced by applying a slip layer of bitumen. 11 Conclusions (Contd.) Bored piles not preferred for the following reasons: Lower Capacity Boring operations through stiff fissured clay will result in softening of this layer, thereby limiting the load carrying capacity of piles. There is no possibility of applying any slip layer and to reduce the negative drag. 12 6

ANTICIPATED NEGATIVE DRAG 40 tonnes based on theoretical consideration. Field load tests on i) Short piles resting on soft clay, ii) Instrumented piles, where the load distribution with depth has been measured. Model tests for the proper choice of bitumen coating to reduce negative drag. i) Precast concrete 10 cm dia and 50 cm long piles were used. ii) Bitumen coatings using different grades of bitumen were applied, and results showed 80 to 90% reduction in friction. iii) Finally SAE 80 grade bitumen was adopted. 13 FERTILIZER PLANT IN GANGETIC BELT The Soil Strata: Silty sand with low N values (<10) upto 10 m depth, N > 20 beyond 20 m depth. N-values ranging between 10 to 20 for the layer between 10 to 20 m depth. High water table with possibility of liquefaction during earthquake. 14 7

PHASE I : INITIAL FOUNDATION DESIGN RCC Piles, Driven Cast-in situ, 400 mm dia Sand Compaction Piles, 2-3 Rows Around RCC Piles, Pile capacities Vertical downward : 50 t, Tension : 5t, Lateral : 2.5t, Result Total Requirement 16,000 RCC Piles 32,000 Compaction Piles Problem of execution on time 15 REVIEW AND FURTHER INVESTIGATION (Pile Load Tests) Revised Pile Capacities Vertical : 65t Tension : 25t Lateral : 3.5t Reduction in RCC Piles : 40% Increase in spacing of compaction piles from 3d to 4 d ; reduction in Compaction Piles : 50% Saving in construction time : 6 months Substantial cost savings as well. 16 8

SETTLEMENT (mm) 20-10-2015 PHASE II OF THE PLANT No RCC Piles. 900 mm dia Vibro-Stone Columns with varied spacing (2d,2.25d and 2.5d) to suit the foundation requirement. Full scale field trials. Several Footing tests for confirmation. Substantial savings in time and cost. 17 LOAD kg / m 2 x 10 3 0 2 0 5 10 15 20 25 30 35 40 45 4 6 8 7.5 10 12 11.77 LOAD SETTLEMENT CURVES FOR SINGLE COLUMN LOAD TEST 18 9

SETTLEMENT (mm) 20-10-2015 0 LOAD kg / m 2 x 10 3 0 5 10 15 20 25 30 35 40 2 4 6 8 10 12 Aonla (Compressor House) Single column Test 8.6 10 10.5 Aonla (Benefield) Aonla (Prill Tower) Three Column Test LOAD SETTLEMENT CURVES FOR SINGLE AND THREE COLUMN TEST 19 Office cum Residential Complex at Jodhpur 2-3 Storeyed Buildings Investigations Done 8 Bore holes drilled to 6 m depth each. As per bore logs Rocky strata. Strata starts at Ground level (GL) in all bore holes except in Bore hole 5, where it starts at 1.5 m. BH 5 is at the extreme corner of the plot where nothing is planned to be built. Bore logs do not give the core recovery, which is a must to be given. 20 10

Recommendations by Investigation Agency 1. Open foundations (footings) 2. Unconfined compressive strength of rock range given 650 to 850 t/m 2 3. Calculated safe bearing capacity (SBC) 80 to 100 t/m 2 21 FOUNDATION RECOMMENDATIONS (Contd ) 4. Recommended SBC is 40 t/m 2 at 1m below GL, except in BH 5; where SBC is 10 t/m 2 at 1.2 m depth and 40 t/m 2 from 2 m depth onwards. 5. The SBC adopted in Design is not known. It should have been written on the drawings. 22 11

WHAT HAPPENED AT SITE 1. Foundation Depth adopted: 1.5m. 2. Foundation sizes 1.5m x 1.5m to 2.3m x 2.3m 3. For excavation Rock Blasting has been done 4. Instead of excavating / blasting individual pits for each footing, the entire foot print of all the buildings has been blasted and excavated. 23 What Happened at Site (Contd ) 5. This resulted in excavated rock material ranging from huge boulders to rubble of volume of about 25,000 m 3 (Actually needed 10% of this). 6. Additional issues: (a) How to dispose of the excavated material. (b) Huge quantity of soil material for plinth filling needed. 24 12

Prof. V.S. Raju s Investigation of the Situation and Foundation Recommendations Basis : Site visit Inspection of the strata in the excavated pits Study of the soil report 1. The investigation is not as per the relevant Indian Standards. 25 Prof. V.S. Raju s Recommendations (Contd ) 2. The recommendations in the report are wrong and are less by a Factor 3 to 4. 3. The correct SBC values are 150 t/m 2 (on a conservative side) with a minimum size of footing as 0.8m x 0.8m. Depth of footing 0.5m to 1m. 26 13

Prof. V.S. Raju s Recommendations (Contd ) 4. There is absolutely no justification to stipulate a foundation depth of 1.5m for the entire site. 5. There was no need at all to make the footing sizes so big as given (1.5m x 1.5m to 2.3m x 2.3m) 6. There is no need to blast the strata over the entire foot print of the building. 27 Prof. V.S. Raju s Recommendations (Contd ) 7. No need to blast for the individual footings also as the required likely sizes are 0.8m x 0.8m to 1.2m x 1.2m, depth 0.5 m to 1.0m only. Pavement breakers (jack hammers) will do the job. 28 14

Photographs of Blasted Rocks 29 rap Photographs of Blasted Rocks 30 15

5.8 m to 25m soft rock 20-10-2015 University Campus at Adilabad District Total area ~ 300 acres For Phase I development, Only 7 boreholes Bore logs improper and inadequate. First SPT at 10 m below GL. Pile Foundations recommended and executed, which are not at all required. Pile safe capacity for 600 mm dia, 12 m length : 83 tons (Very low) - Settlement of pile up to 10 % of pile diameter could not be attained by 3 times the design load. Prof. V.S. Raju 31 0.00 to 1.80 m Brown clay 1.80 mto 5.80 m yellow clay & Murrum First SPT at 10m below G.L, Required every 1m to 1.5m Typical Bore Profile Prof. V.S. Raju 32 16

Pile Load Tests: Five Initial Load Tests At 3 times the design load, settlements are only 2 mm to 27 mm as against permitted 45 mm to 60 mm. Pile capacities are not revised. Piles, which are not required in the first place are grossly over designed. Prof. V.S. Raju 33 30 Acres site L&T Serene County Strata Rocks and Boulders with local depressions, highly uneven. 10 towers between 11 and 14 floors Recommended SBC by the soil Investigation Agency 30 t/m 2 - One value for the entire site? 34 17

30 m 20-10-2015 L&T Serene County Prof. V.S. Raju 35 Extreme Issue was with one of the 10 towers built Tower Dimension : 75 m x 30 m Highly variable strata at Founding Level. 75 m Hard Rock SBC 400 t/m 2 Hard Murrum Soft Clay 80 t/m 2 4 m thick 0 t/m 2 Prof. V.S. Raju Tower Foot Print 36 18

Important: These type of variations do occur in rocky and bouldry strata The soft clay is due to a old pond, which normally gets covered up during site grading. 37 All these examples reaffirm the requirement of high quality Geotechnical Investigation, Interpretation by a qualified Foundation Engineer in close collaboration with the Structural Designer. 38 19

THANK YOU JAI HIND 20