Heat Pump Water Heater IOM Manual



Similar documents
CARING FOR YOUR WATER HEATER

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

SWIMMING POOL HEAT PUMP

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Oil and Coolant Circulating Heating System. Model - OCSM

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

ALL IN ONE. Heat Pump Water Heater

Troubleshooting Your Refrigerator

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

ICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t.

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Miami Heat Pump HP Series Installation Guide

Geyser-R Heat pump water heater Installation manual

Tankless Water Heater

Evaluate, Clean, and Tune Guidance

Portable Air Conditioner

Instruction manual for Firstline FCS12000CH

Dehumidifier Users manual. For Models: DH45S DH65S

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

Operating Instructions Split System Air Conditioner

Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR İ-COLD Rev. 00

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service

Panel Mounted Air Conditioners by Dantherm, Inc.

DUCT TYPE AIR CONDITIONER

Split Air Conditioner

Water Priming Mode Purge air from plumbing system. How do I solve ER-3 WATER PRIME: TIPS ON FILLING SPA IMPORTANT NOTE WARNING

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Failure code manual. content

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

Electric Water Heater

Split Type Room Air Conditioner. KSWM units

Hoshizaki America, Inc.

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS

, User s Manual

CDS TROUBLESHOOTING SECTION I. VACUUM Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

Installation and maintenance instructions. Danfoss Vent

T15 AIR CONDITIONER INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS

LOBOY 16 AIR CONDITIONERS

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

ON-VEHICLE INSPECTION

MINI-BRUTE II HOT WATER POWER WASHER MODEL# MBII

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

For installation guide see reverse of book

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

AIR CONDITIONER Duct Type OPERATING MANUAL

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

Ceiling Mount Air Handler Manual

Air Conditioner Water Heater Model ACWH18

How To Understand Evaporator

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump

T-Series Air Conditioner T62 Model

SWIMMING POOL HEAT PUMP Owners Manual

USER S MANUAL. Duct Type Series. Free Joint Multi Air Conditioner (Cooling and Heating) FUEA Series E S F I P D G DB A(1) ENGLISH ESPAÑOL

PC1131 Electric Air Compressor

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

Use and Care Manual. Model CPA12KH AIR CONDITIONER

What you can expect from your Solar Hot Water System

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

PORTABLE AIR CONDITIONER

USER S MANUAL HSC-24A

How To Defrost A Truck

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Instruction Manual Model: GT-SKR010B GT-SKR015B GT-SKR020B GT-SKR030B

Glossary of Heating, Ventilation and Air Conditioning Terms

PORTABLE AIR CONDITIONER

Training Syllabus to Instruct/Prepare for the ASE Transit Bus HVAC Test

INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER

Trouble Shooting. Pump

Programmable Thermostat MODEL XXX With Dehumidify XXX With Out Dehumidify

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

T-SERIES Air Conditioners. T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N

DEFROSTING. Service Engineers Section Technical Bulletin No 3

Overheating limit control

PC1130 Electric Air Compressor

Air Conditioning System

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM EXPLOSION VIEW 16 6

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS

Central Air Conditioner

Continuous Flow Water Heaters

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

HP switch LP switch Discharge thermo Comp. Surface thermo

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

Transcription:

Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump water heater. Read this manual carefully before attempting to install or operate the heat pump water heater. failure to follow these instructions may cause a Fault of the heat pump, resulting in electrical shock, scald injury and/or property damage. Installer: Before leaving the premises, review this manual to be sure the water heater has been installed correctly. Start or operate the unit for one complete cycle and make sure the water temperature is acceptable to the consumer. -1 -

1 Safety Instructions Do not use this unit if it has been dropped or damaged in any way. This unit should not be installed in any area where flammable liquids or vapors may be present. Do not store or use gasoline or other combustible materials or liquids near or adjacent to this water heater. Check the rating plate on the unit before installation to make certain the voltage shown is the same as the electricity supply to the water heater. The unit must be connected only to a properly grounded electrical supply. Do not fail to properly ground the unit. This unit should only be serviced by qualified service personnel. Always shut off electric power before making unit connections or removing any panels and be extremely careful to avoid injury. Components may have sharp edges or protrusions which can cut you. Tubing and compressor contain high pressure refrigerant and they should not be exposed to high temperature or be punctured. Water temperature over 52ºc (125º f) can cause severe burns or death from scalding. Feel the water before bathing or showering. Children, disabled, and elderly are at highest risk of being scalded. Tampering with the thermostat, heater, elements or electrical connections is dangerous and may result in serious injury. Only properly trained, qualified service personnel should service these components. Do not attempt to modify or change this water heater in any way. 2 Pre-installation and code requirements Important Note The Heat Pump Water Heater should never be stored or installed on its side. Upright transportation is recommended. If it becomes necessary to transport the water heater on its side, the manufacturer recommends that the unit be in the upright position for a minimum of two hours prior to operation. Failure to follow these instructions may result in damage to the water heater. After removing the unit from the crate/carton, immediately remove the panels and inspect for any damage that might have occurred during shipment. Report concealed damage immediately to the transportation company and request inspection. -2 -

The electric power source must be the same voltage and phase as shown on the rating plate. Line and low voltage wiring must be done in accordance with local codes or the national electric code. Make a survey of the final location of the unit before setting it in place. The unit should be centrally located with respect to the distribution system. Install the unit within a heated area if possible. Exposure to inclement weather conditions may cause lower efficiency performance. 3 Installation Mounting the unit The unit should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and floor. Do not install the unit in any area where a polluted source, flammable liquids or vapors may be present or where dirt and defoliation will accumulate. The unit should be installed in a place with sufficient space and good ventilation. A minimum of 24 clearance in front and sides of the unit should be provided to allow sufficient room to make water and electrical connections. If the unit is located in a confined space such as a closet, provisions must be made for unit servicing. Water tank should be installed in a place with an ambient air temperature over 0ºc. -3 -

Piping the Unit Both source and load connections must be at least as large as the unit connection on the unit. Never use flexible hoses that are smaller (inside diameter) than that of the water connection on the unit. Make sure hoses and pipes are suitable for system water pressure and sized for proper flow rate. The supply and the discharge pipes should be insulated to prevent heat loss. The pressure of tap water should be smaller than 1Mpa. After the piping is complete, test the piping to make certain that it is free of leaks.. Discharge Valve Water Tank Temperature Sensor Supply Valve Water Tank Heat Pump Water Heater Drain Valve Isolation Valve Water Pump Water Flow Sensor Caution: Improper water flow in the system due to piping, valving or improper pump operating could cause unit damage. 4 Start up Check the following before powering the unit: High voltage supply matches the nameplate rating. Field wire size, breakers and fuses are the correct size. Low voltage control circuit is correct. Water piping is complete and correct. Isolation valves are open. -4 -

Loop pumps are correctly wired. Access panels are in place and secured. Water flow switch is installed. If not, terminal 1 and 2 on the control board should be loop wired. Compressor Time Delay: Be aware there is a 3 minute time delay before the compressor will start once the unit is turned on or whenever it restarts. 5 Unit operation Important note Never operate a water heater when the tank is empty or partially filled. This can result in serious damage to the tank and will destroy the heating elements. 1. When all piping and electrical connections have been completed, turn on the water supply to the unit and allow it to fill completely. To ensure the unit is completely filled, open all hot water faucets to allow air to escape from the piping. Then close the faucets. 2. Turn on the power supply to the water heater. The display screen on the control panel shows the temperature of the water in the tank. 3. Press the On/Off button on the control panel. The compressor will energize if three minutes elapses since last time the unit is shut down and the water temperature in the tank (read by the tank water temperature sensor) is below the set water temperature. 4. The heat pump continues to operate until the water temperature reaches t1 when the compressor de-energizes. Important: The unit will emit sounds similar to a refrigerator or dehumidifier when the heat pump is running. Certain noises will be heard. These noises are common and may result from: a) Operations of compressor and fans b) Normal expansion/contraction of metal parts during heat-up and cool-down. c) Sediment build-up on the tank bottom on the heating elements 5. When the water temperature drops below the set water temperature, the compressor will start to work and the unit will run automatically. When there is no hot water demand, the heat pump will run continually to keep the water temperature constant. 6. The fan motor will energize/de-energize once the compressor energizes/de-energizes. 7. The water pump will start 30 seconds before the compressor starts and cease 60 seconds after the compressor ceases. -5 -

8. The unit will enter the defrost state if the compressor has worked for 20 minutes uninterruptedly and the evaporator coil temperature (read by the evaporator coil temperature sensor) is below -2ºc. When the unit enters defrost state, the 4-way reversing valve solenoid de-energizes, directing the hot gas to evaporator coil to defrost. The fan motor will de-energize but the compressor and the water pump will continue to work in the defrost state. 9. The unit will be restored from defrost state to heating mode if the coil temperature is above15ºc or the unit has been in defrost state for over 8 minutes. 6 Panel Regulation On/off Button Press On/Off button to switch on/off the unit. Set Button Press Set Button for five seconds and then Up/Down Buttons to set parameters. Press Set Button for ten seconds to check evaporator coil temperature or purged air temperature. Timer Button Press Timer Button for five seconds and then Up/Down Button to set time. Up Button Press Up Button to set temperatures upwards. -6 -

Down Button Press Down Button to set temperatures downwards. Function 1. Heating Tr Return Water Temperature Trd Return/outlet Water Temperature Difference Ts Set Water Temperature When Tr Ts Trd the compressor is started. When Tr Ts 1 C the compressor is shut down. Remarks: The start or shutdown of the compressor is subject to unit time delay protection. 2. Fan Motor Control The fan motor will begin to work after the compressor is started; the fan motor will cease after the compressor is shut down. Remarks: Exceptional in defrost mode 3. Compressor Time Delay Protection A minimum three minutes of time delay is required for the compressor to be restarted. 4. Temperature Sensor Fault Protection a) Return Water Temperature Sensor Fault Close all outputs b) Evaporative Coil Temperature Sensor Fault Close all outputs c) Purged Air Temperature Sensor Fault: Close all outputs d) Ambient Air Temperature Sensor Fault: Close all outputs 5 Water Flow Switch Protection If the water flow switch is observed to be disconnected for ten second continuously, insufficient water flow protection will be activated and all outputs will be closed. Remarks: Water flow switch will only be checked thirty seconds after the unit is started. 6 Pump Control The pump will begin to work thirty seconds after the compressor is started, and stop sixty seconds after the compressor is shut down. 7 Defrost Control Defrost-in Conditions only when both conditions are satisfied a) Compressor continuous running time Defrost-in time delay b) Evaporator Coil Temperature Defrost-in temperature When the unit enters defrost mode, the 4-way reversing valve will de-energize, directing the hot gas to the evaporator coil. The fan motor will stop but the -7 -

compressor and pump will continue working. Defrost-out Conditions when either condition is satisfied a) Evaporator coil temperature Set defrost-out temperature b) Defrosting time Set defrost-out time When the unit revert to heating from defrost mode, the 4-way reversing valve will energize and the fan motor will begin to work. 8 Anti-freeze Protection During unit-off state, the unit will be switched on to heat the water automatically if the water is observed to be below 3 C for a continuous sixty seconds. After the water temperature is above 15 C, the unit will be shut down. 9. Temperature Checkup Function Code Parameter 0 Evaporator Coil Temperature 1 Ambient Air Temperature 7 Unit protection No Input Port Fault Code Protection 1 CN3 Water Temperature Sensor Fault E1 Close all outputs 2 CN4 Ambient Air Temperature Sensor E2 Close all outputs Fault 3 CN6 Purged Air Temperature Sensor E3 Close all outputs Fault 4 SHUI Insufficient Water Flow E4 Close all outputs 5 63H1 High/Low Pressure E5 Close all outputs 6 7 CN5 Evaporator Coil Temperature Sensor Fault E7 Close all outputs High / Low Pressure Switches The high-pressure switch senses the refrigerant pressure in the sealed refrigeration system and shuts the heater down in the event unsafe operating pressures are reached. The low-pressure switch senses the refrigerant pressure in the sealed refrigeration system to protect against certain conditions that could be detrimental to compressor life. The switch shuts the unit down in the event of loss of refrigerant, fan motor failure, and airflow blockage. -8 -

8 Parameter setting Parameter Range Default Set Water Temperature 25 C 60 C 55 C P0 Return/Outlet Water 1 C 10 C 5 C Temperature Difference P1 Temperature Sensor 0 C 10 C 0 C Precision P2 Defrost-in Time Delay 20min 90min 20min P3 Defrost-in Temperature -15 C 5 C -2 C P4 Defrost-out Time 3min 15min 8min P5 Defrost-out Temp 5 C 25 C 15 C 9 Maintenance Proper maintenance is important to insure the most efficient operation and longest life for your equipment. The following points are to serve as a general guide. Always consult with your maintenance contractor with regard to the specific requirements of your own installation. Paint Finish The paint finish may be polished if desired. Spray paint is available in case of accidental scratching or chipping. The following should be checked only by a competent contractor. Contactor Points Check contactor points twice a year to be sure they are not burned or pitted as a result of low voltage, lightning strikes, or other electrical difficulties. Water System The water circulating pump should be checked and cleaned, to ensure that it is operating normally. Clogged coils lead to high head pressures, insufficient water flow protection or inefficient operation. If coil is limed, a cleaning treatment may be necessary. Water coils should be checked yearly for liming or clogging. -9 -

Improper Unit Functioning If unit is not performing properly, several readings of temperature, pressure and electrical characteristics need to be taken. The normal required troubleshooting information is listed below. Cleaning The evaporator should be cleaned at least twice a year or whenever it is visibly dirty. A dirty evaporator coil will result in decreased efficiency. The outer surfaces of the water heater may be cleaned with a sponge and warm soapy water. Do not use bleach, abrasive cleaners, or solvents which will damage the unit s finish. Draining and Flushing Closed the cold water inlet valve and open a nearby hot water faucet. Connect a hose to the drain valve and terminate it at an adequate drain. Open the drain valve and allow the tank to drain, periodically opening and closing the cold water inlet valve to flush sediment from the tank. When clear water is observed coming from the drain hose, close the drain valve and disconnect the hose. Open the cold water inlet valve to refill the tank with water. Close the hot water faucet when water begins flowing from it. Restore the power to unit. Refer to start up procedures in this manual. Important: If the water heater is going to shut down for an extended period, the drain valve should be left open. Warning: Water draining from the water heater will be hot and can result in an injury by scalding. Do not allow anyone to come in contact with draining water!!! 10 Troubleshooting Guide SYMPTON POSSIBLE REASONS REMEDY NOISY OPERATION CHATTERING CONTACTOR NOISE UNIT DOES NOT TURN ON AFTER WIRING MAY BE INCORRECT WIRING IS COMPLETE DEFECTIVE CONTROL PANEL CHECK CONTACTOR POINTS VERIFY WIRING WITH WIRE DAGRAM REPLACE CONTROL PANEL COMPRESSOR WILL NOT TURN ON WIRING MAY BE INCORRECT VERIFY WIRING WITH WIRE DAGRAM -10 -

EVAPORATOR FROSTING OR ICING NO HOT WATER LOOSE ELECTRICAL CONNECTIONS Terminals 1 & 2 NOT LOOP WIRED DEFECTIVE COIL TEMPERATURE SENSOR LOSS OF REFRIGERANT CHARGE DEFECTIVE THERMOEXPANSION VALVE INSUFFICIENT POWER TO UNIT DEFECTIVE WATER TANK TEMPERATURE SENSOR DEFECTIVE CONTROL PANEL CHECK ALL CONNECTIONS AT CONTACTOR AND COMPRESSOR TERMINAL BOX WIRE THEM IF NO WATER FLOW SWITCH IS INSTALLED REPLACE SENSOR REPAIR LEAK AND RECHARGE REPLACE VAVLE VERIFY POWER SUPPLY REPLACE SENSOR REPLACE CONTROL BOARD INSUFFICIENT HOT WATER DEFECTIVE TEMPERATURE REPLACE SENSORS SENSORS TEMPERATURE SETTING TOO INCREASE SETTING LOW UNIT UNDERSIZED FOR INSTALL ADEQUATELY SIZED APPLICATION WATER HEATER PIPING IS INCORRECT REFER TO "PIPING INSTALLATION" LONG RUNS OF EXPOSED INSULATE PIPING PIPING OR HOT WATER PIPING IS UNINSULATED SENDIMENT OR LIME IN TANK FLUSH TANK LEAKING FAUCETS LOSS OF REFRIGERANT CHARGE DIRTY AIR FILTER REPAIR FAUCETS RECHAREGE REFRIGERANT CLEAN AIR FILTER 11 Part List Part No. Description Part No. Description -11 -

1 Compressor 12 Thermal Overload Relay 2 Vapor/Liquid Separator 13 Solder Tube Union 3 Liquid Receiver 14 4-way Reversing Valve 4 Coaxial Copper Condenser 15 Low Pressure Switch 5 Evaporator Coil Temperature High Pressure Switch 16 Sensor 6 Fan 17 Thermal Protector 7 Fan Motor 18 Oil Pressure Gauge 8 Control Board 19 Fin Coil Evaporator 9 Phase-sequence Relay 20 Thermal Expansion Valve 10 Capacitor 21 R417a Refrigerant 11 AC Contactor 12 Electrical Specification Model LSQ015CR LSQ02CR LSQ03(C)R Power Supply 220V/1HP/50HZ Phase Wire Cross Section mm2 2.5 2.5 4 Power Cord Neutral Wire Number 1 1 1 Cross Section mm2 2.5 2.5 4 Earth Wire Recommended Pump Specification Number 1 1 1 Cross Section mm2 2.5 2.5 4 Number 1 1 1 Water 0.3 0.4 0.55 Flow (L/S) Pump 5 5 8 Head (m) Power >65 >90 >200 Input (W) -12 -