USP <797> Cleanroom Design and Environmental Monitoring. Andrew King, USP <797> Specialist CETA Member RCCP-SC



Similar documents
ENVIRONMENTAL MONITORING

Everything you want to know about USP 797

Bill Mixon, RPh, MS Senior Associate Gates Healthcare Associates

Environmental Monitoring

New Mexico Register / Volume XXVI, Number 5 / March 16, 2015

Hazardous Drug. Cleanroom. Standards

Rules for Compounded Sterile Preparations (CSPs)

Understanding USP 797

ASHP Guidelines on Compounding Sterile Preparations

Hazardous Drugs Compounded by a Prescriber.

The Microbial Bioburden of USP 797 Compliance. Simplifying Environmental Quality and Control Practices for Pharmaceutical Compounding

AMENDED January 27, 2015

RE: Comments on USP 800 Hazardous Drugs Handling in Healthcare Settings

Environmental Monitoring of Clean Rooms

Environmental Monitoring

USP <797> Introduction

Risk-Based Environmental Monitoring. Marsha Stabler Hardiman Senior Consultant Concordia ValSource Wednesday September 17, 2014 FDA/PQRI

Air and Water Balancing - Sound and Vibration Testing - Cleanroom Services - Building Commissioning Building Envelope Testing Thermal Imaging

BRIEFING 797 Pharmaceutical Compounding Sterile Preparations,

Particle Monitoring Requirements in Pharmaceutical Cleanrooms

USP Chapter <797> Update on Recent Revisions

800 HAZARDOUS DRUGS HANDLING IN HEALTHCARE SETTINGS

Hospital Pharmacy Automation: Drug Storage and Retrieval

Raleigh, NC May 12 th & 13 th Meeting The New ISO Cleanroom Standards And Changing EU Guidance How Will You Comply?

PRINCIPAL INVESTIGATOR REGISTRATION FOR SELECT AGENTS

The proposed chapter is posted online at

Manufacturing. Environmental Monitoring Particle Counts Are Easy B IOP ROCESSTECHNICAL. Scott E. Mackler

The use of risk assessment tools for microbiological assessment of cleanroom environments. by Tim Sandle

Sample Pharmacy CLEANING AND SANITIZING PROCEDURE P-304.1

Validating and Monitoring the Cleanroom

Qualification of an Environmental Monitoring Program

Risk Assessment: Biosafety Cabinet

Cleanroom. For. Sterile Manufacturing Facilities

Design, Operation and Management of GTP/GMP Cell Engineering Facilities

COMPOUNDING PHARMACY IN THE HOSPITAL SETTING SATURDAY/11:30AM-12:30PM

DRAFT GUIDANCE. This guidance document is being distributed for comment purposes only.

Cleaning. By the end of this chapter, you will be able to: Introduction. Definitions. Chapter 9

Risk Based Environmental Monitoring (EM) and EM Data Management and Trending

General Guide to USP Proposed Chapter <800>: Hazardous Drugs Handling in Healthcare Settings

GUIDELINES ON TEST METHODS FOR ENVIRONMENTAL MONITORING FOR ASEPTIC DISPENSING FACILITIES

USP <797> A Road to Compliance The New Mexico Board of Pharmacy

CLASSIFICATION OF CLEANROOMS

CLEAN ROOM MONITORING REGULATORY STANDARDS

patient safety A commitment to GE Healthcare

Chapter , Part R Hazardous Drugs

Design, Construction, Commission, and Qualification of Critical Utility Systems: Part III

Required Biosafety Level Three (BSL-3) Practices, Procedures, Facilities, and Safety Equipment For BSL-3 and BSL3/2 Laboratories

ENVIRONMENTAL TESTING & MONITORING: Deciphering Compliance Requirements for Pharmaceutical and Medical Device Manufacturers A WHITE PAPER

HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions

7 Deadly Myths of USP 797 Webinar Q&A By Eric Kastango

Both health-care facility classification and area classification, as per CSA, determine the design requirements.

Environmental Monitoring in Isolators and Clean Rooms ICR settle and contact plates ICRplus contact plates

Infection Control Checklist

Open Microphone Meeting:

48 th Annual Meeting. On the Radar: Regulatory Basics. Regulatory Agencies. The Joint Commission. Disclosure. Objectives. The Joint Commission

DISCUSSION TOOL PRESENTED TO THE AABB CT REGULATORY AFFAIRS SUBSECTION

MOHD NASRUL MOHAMAD NOOR

OCCUPATIONAL HEALTH AND INDUSTRIAL HYGIENE GUIDANCE FOR THE MANAGEMENT, USE AND DISPOSAL OF HAZARDOUS DRUGS

Laminar Flow Cabinets

EU GMP Annex 1 Update 2008: Airborne Particle Counting

Both health-care facility classification and area classification, as per CSA, determine the design requirements.

Environmental Monitoring Risk Assessment

Patient Safety and Peak Performance Through Pharmacy Training

PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3)

Procedures for the Effective Use of Biological Safety Cabinets

FDA and the Compounding Pharmacy

U.S. OFFICE OF SPECIAL COUNSEL 1730 M Street, N.W., Suite 300 Washington, D.C December 9, 2014

Recommendations for the Safe Use of Handling of Cytotoxic Drugs

GMP ANNEX 1 REVISION 2008, INTERPRETATION OF MOST IMPORTANT CHANGES FOR THE MANUFACTURE OF STERILE MEDICINAL PRODUCTS

Basic Requirements For Aseptic Manufacturing Of Sterile Medicinal Products A Comparison Between Europe And USA

Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health

BIOLOGICAL SAFETY CABINET PROGRAM

The following Good Compounding Practices (GCPs) are meant to apply only to the compounding of drugs by State-licensed pharmacies.

Facility Cleaning & Monitoring. Cleaning

Via

Particle Counting and Environmental Monitoring In Pharmaceutical / Life Sciences

Regulations Concerning

International Standard ISO 14644

John Keel, CPA State Auditor. An Audit Report on Inspections of Compounding Pharmacies at the Board of Pharmacy. August 2015 Report No.

CHAPTER 17 STERILE PRODUCT COMPOUNDING 17-1

Biosafety Level 2 Criteria

The following standard practices, safety equipment, and facility requirements apply to BSL-1:

Healthcare Solutions Room Pressure Monitors and Controls

Safe Handling of Hazardous Drugs

Indiana Pharmacy Inspection Report Questions

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG March 24, 2010

ASHP Technical Assistance Bulletin on Handling Cytotoxic and Hazardous Drugs

Stainless Steel Worksurface 3 Feet Hood A10-WS-PR3 A10-WS-SR3 4 Feet Hood A10-WS-PR4 A10-WS-SR4 6 Feet Hood A10-WS-PR6 A10-WS-SR6.

The year 2010 marked 4 decades of concern for health care workers. Safe Handling. Of Hazardous Drugs: Reviewing Standards for Worker Protection

ASHP Guidelines on Handling Hazardous Drugs

Eric S. Kastango, MBA, RPh, FASHP Clinical IQ, LLC Florham Park, NJ 07932

To provide direction for the safe handling, administration and disposal of hazardous drugs.

SPECIAL APPLICATIONS

VALIDATION OF CLEAN ROOMS FOR ASEPTIC MANUFACTURING. F.R.Smal Pharmaceutical Director ICCE ICCE a member of SNC-Lavalin Group

How to Estimate the Cost of a. Laboratory Renovation. Candidate Number:

HEALTH CARE GUIDELINES AND STANDARDS

Laboratory Biosafety Level 3 Criteria

GUIDANCE ON THE SAFE HANDLING OF MONOCLONAL ANTIBODY (mab) PRODUCTS

Hand and Glove Hygiene Keys to Safe Compounding

Transcription:

USP <797> Cleanroom Design and Environmental Monitoring Andrew King, USP <797> Specialist CETA Member RCCP-SC

Objectives The objectives of this presentation: To summarize basic cleanroom concepts and how they relate to USP <797> To gain better understanding of the testing and certification requirements of USP <797> To discuss possible corrective actions for non-compliant areas

What is USP <797>? An enforceable chapter of the U.S. Pharmacopeia National Formulary Defines best practices and standards for sterile compounding nationally

USP <797> Purpose The intentions behind the requirements of USP <797>: Patient Safety health violations can cause serious injury to patients Drug Sterility Assure that medication does not become contaminated during preparation

New England Compounding Center Why is USP <797> in the news lately? In September 2012, regulators investigated the NECC in Framingham, MA, in connection with a multi-state meningitis outbreak 20 States received tainted steroid injections that were compounded at NECC A total of 751 cases of fungal infections linked to the drug, the majority being meningitis and/or spinal infections 64 associated deaths Note: Data collected from CDC website as of 23 OCT 2013 (last update)

Who does it apply to? USP <797> applies to: All persons who perform sterile compounding All places where sterile compounding is performed

Enforcement Who would enforce USP <797>? FDA State Pharmacy Boards (for approved states) The Joint Commission (formerly JCAHO) Centers for Medicare and Medicaid Services (CMS) State Departments of Public Health

Why Comply? Regulation FDA, Regulations in some states Accreditation Joint Commission Best Practices Proof against liability Marketing Competitive Advantage Out of State Compounds

USP <797> Terms CSPs Compounded Sterile Preparations PEC Primary Engineering Control Buffer Room Area where PEC is located Ante Room Transitional area adjacent to Buffer Hazardous CSPs Exposure to these drugs can cause cancer, developmental or reproductive toxicity, or organ damage Unidirectional Airflow Airflow that moves in a single direction, with no dead spots or refluxing, sweeping away particles from clean areas

ISO Classifications Per ISO 14644-1 Cleanrooms and Associated Controlled Environments

General Concepts All of the specifications and tests in this presentation serve at least one of the following: Product Sterility Hazard Containment

PEC Requirements A PEC is: A device or room that provides an ISO class 5 environment for the exposure of critical sites when compounding CSPs. Airflow must be HEPA-filtered and unidirectional Typical examples: Laminar Airflow Workbenches LAFWs (also called Unidirectional Flow Devices or cleanbenches) Biological Safety Cabinets BSC Compounding Aseptic Isolators CAIs (positively pressured) Compounding Aseptic Containment Isolators CACIs (negatively pressured)

Laminar Airflow Workbench HEPA filtered air flows over the workspace Airflow is unidirectional across workspace Recirculated air contributes to room air changes Only suitable for nonhazardous compounding

Biological Safety Cabinets Offers both contamination control and worker protection Airflow from room does not enter work area Airflow from work area does not vent into room HEPA filtered unidirectional supply air HEPA filtered exhaust air

Compounding Isolators Isolated from surrounding environment (i.e. no mixture with ambient room air) HEPA filtered, unidirectional airflow over work surface CACIs provide worker protection (allow for hazardous compounds) CAIs do not (nonhazardous compounds only)

Non-Hazardous Compounding Environmental Requirements Standard Requirements: ISO class 7 Buffer Room ISO class 8 Ante Room At least 0.02 wc positive pressure to the outside At least 30 air changes/hour of HEPA-filtered air

Hazardous Compounding Environmental Requirements Same requirements as non-hazardous, with the following exceptions: The PEC must provide worker protection (i.e. biological safety cabinet or negative-pressure isolator). The PEC should be 100% vented to the outside through HEPA filtration. The room must have at least 0.01 wc negative pressure to the outside. Note: Hazardous and non-hazardous compounding are not compliant in same area. Requires an ISO class 7 buffer AND ante area.

Hazardous Compounding Environmental Requirements Hazardous Compounding Pharmacy

Cytotoxic Residue Sampling NIOSH warns that hazardous drugs can cause acute and chronic human health effects, including cancer. USP <797> recommends sampling for hazardous drug residue every six months. Common drugs for sampling: Cyclophosphamide, Ifosfamide, Methotrexate, Fluorouracil While the literature has not selected any acceptance limits for hazardous drug residue, Cyclophosphamide levels of 1.0 ng/cm 2 have been found to result in human uptake.

Cytotoxic Residue Sampling USP <797> recommends sampling: PEC workspaces Countertops where finished CSPs are placed Areas adjacent to PEC, including floors Patient administration areas

Upcoming USP <800> USP <800> Hazardous Drugs Handling in Healthcare Settings The proposed new chapter of USP-NF is still in draft form. Current proposals include: Addressing both sterile and non-sterile compounding Unambiguously stating the need for a dedicated room More information on types of BSCs Offering guidance on a variety of room layouts Specific instructions for gowning Guidelines for cleaning/decontamination Hazardous residue sampling will be a requirement

12-hour Beyond Use Date USP <797> allows an exception to the rule of placing the PEC in an ISO class 7 Buffer area if: CSPs are to be administered within 12 hours of compounding, or per physician s orders, whichever sooner CSPs meet the definition of low-risk per USP <797> Compounding must be non-hazardous The PEC is not located near potential contamination (e.g. doors, windows, flow of traffic, food prep)

12-hour Beyond Use Date Pros: No requirements for buffer/ante area ISO classification, HEPA filtration or room pressurization May be suitable for older facilities not designed to meet the standard USP <797> specs Cons: Expensive Scheduling challenges

Isolator Considerations USP <797> allows an exception to the rule of placing the PEC in an ISO class 7 Buffer area if: The PEC is an isolator (CAI or CACI) that provides isolation from the room and meets ISO class 5 during normal operations, compounding and material transfer. Internal procedures are developed to ensure adequate recovery time between material transfer and compounding operations to return to ISO class 5 air quality.

Isolator Considerations Pros: No requirements for buffer/ante area ISO classification, HEPA filtration or (possibly) room pressurization Useable in hazardous compounding areas (though the negative pressure requirement still applies) Cons: Expensive Reduced production/worker comfort

Environmental Monitoring Types of Environmental Monitoring (EM) tests for evaluating compliance with USP <797>: Certification of PEC Non-viable Airborne Particle Counting Certification of HEPA Filters Room Air Exchange Rates Room Differential Pressures Viable Airborne and Viable Surface Sampling Cytotoxic Residue Sampling

Certification of PEC Primary Engineering Controls are required to be certified to the appropriate industry standards at least semiannually. This includes, but may not be limited to: Verification of airflow velocity and direction in accordance with manufacturer s specifications and/or intended use Tested to ISO class 5 within the workspace Leak testing of HEPA filters Must be performed by a qualified individual

Particle Counting Particle Counting: Is intended to detect non-viable (i.e. non-living) particulate matter that could contaminate CSPs Is also a good way to measure the effectiveness of environmental controls Is performed semi-annually, or whenever the room/ equipment are modified, moved or repaired

Particle Counting Tested according to ISO 14644 Cleanrooms and Associated Controlled Environments USP <797> determines which ISO classifications apply to what areas

ISO Classifications Per ISO 14644-1 Cleanrooms and Associated Controlled Environments

What can be done to prevent high particle counts? HEPA-filtration and unidirectional airflow Good room isolation and pressurization Good gowning practices Proper storage of materials Restrict traffic through critical areas Clean the area regularly to remove dust/debris For areas that cannot meet ISO class 7: Use of an Isolator or low-risk non-hazardous compounding with a 12-hour beyond-use-date

HEPA Filters HEPA (High-Efficiency Particulate Air) Filters are 99.97% efficient at removing particles at 0.3µm. HEPA-filtered air must be introduced at the ceiling for ISO class 7 areas. HEPA filters should be leak tested in accordance with IEST- RP-CC001

Room Air Exchange Rate ISO class 7 Buffer and Ante Areas require sufficient HEPA-filtered airflow to provide >30 air changes per hour (ACPH) for the room. Room HEPAs only need to provide >15 AC/H if recirculated air (e.g. HEPAfiltered air from the PEC) can make up the difference.

Room Pressurization Non-hazardous Buffer and Ante Areas require between 0.02 0.05 wc of positive air pressure to the exterior. (i.e. the net flow is out of the room) For hazardous Buffer Areas, at least 0.01 wc negative air pressure to the exterior is required.

Viable Sampling Viable Sampling is intended to detect living contaminants for both hazardous and non-hazardous areas such as: Bacteria and other microorganisms Fungal growth Appropriate areas for Viable Sampling: Within the PEC s direct compounding area Devices (e.g. computers & printers), objects (e.g. carts) and work surfaces (e.g. countertops & shelves) within the Buffer and Ante Rooms

Viable Sampling Media Selection: Sampling requires a general-purpose medium that supports the growth of bacteria E.g. Soybean-Casein Digest Medium (aka Tryptic Soy Agar) High-risk compounding areas require the use of fungalselective media E.g. Malt Extract Agar, Rose Bengal Agar, Sabouraud Dextrose Agar

Viable Sampling Airborne Viable Sampling: Impaction method is preferred, using quantitative air samplers Passive settling plates not recommended 500L samples in rooms, 1000L samples in PECs Samples collected on agar plates

Viable Sampling Surface Viable Sampling: Samples collected on agar contact plates Touch and roll method Clean surface immediately after sampling to remove residue

Viable Sampling Media Incubation: TSA media incubated at 30-35 degrees Celsius for 48 to 72 hours Fungal-selective media incubated at 26-30 degrees Celsius for 5-7 days Count total number of colony forming units (CFUs) USP <797> requires that all air samples demonstrating growth be identified to at least the genus level

Viable Sampling

What causes viable growth? There are several typical sources for viable contamination: Human-borne, including organisms carried by skin, breath, mucous, clothing, etc. This is the most common source of contamination for the typical cleanroom. Airborne: carried in from the outside or elsewhere in the facility Water-borne: can be caused by splashes near sink

What can be done to prevent viable growth? Utilize good cleanroom techniques: Isolate and pressurize the room to keep out external sources of contamination Use HEPA filtration to dilute contaminants in air Regularly clean critical surfaces with approved disinfectants (e.g. 70% IPA) Use good gowning practices to prevent human-borne contamination

What are the corrective actions for viable growth? TSS recommends a battery of corrective actions when viable samples come back high: Verify that no unusual circumstances would have affected the environmental controls Review gowning requirements with personnel Clean affected area with disinfectant and retest Consider identification of organisms (USP <797> requires identification to at least genus level) Note: may be done concurrently with retesting

Questions? Thank you for attending! Presented by Andrew King, USP <797> Specialist aking@techsafety.com Visit our website at www.techsafety.com.