Clayton State University 2000 CLAYTON STATE BLVD. Morrow, Georgia 30262 DRAFT SPILL PREVENTION, CONTROL, AND COUNTERMEASURES (SPCC) PLAN



Similar documents
SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN

Spill Prevention, Control and Countermeasure (SPCC) Rule

ACTIVITY NAME. Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas

ABOVE-GROUND STORAGE TANKS

Spill Prevention, Control and Countermeasure (SPCC)

Spill Control Prevention Plan (SCPP)

DISCLAIMER - APPENDIX D

UNIVERSITY OF WISCONSIN MADISON

SPILL PREVENTION CONTROL AND COUNTERMEASURE PLAN

SPILL PREVENTION, CONTROL AND COUNTERMEASURE (SPCC) PLAN

Section 5. Secondary Containment and Impracticability. (as applicable to APSA tank facilities)

TRAINING SPCC/SWPP Training UGA. Automotive Center. Campus Transit

SPILL PREVENTION CONTROL AND COUNTERMEASURE PLAN PREPARED FOR: ARKANSAS STATE UNIVERSITY JONESBORO, ARKANSAS ORIGINAL DATE OF PLAN: APRIL 2005

Kurt Wilson Louisiana Dept. of Environmental Quality Business & Community Outreach Division Small Business/Small Community Assistance Program

Appendix VIII: Spill Prevention, Control and Countermeasure (SPCC) Plans

MASSACHUSETTS INSTITUTE OF TECHNOLOGY MASSACHUSETTS INSTITUTE OF TECHNOLOGY CAMPUS SPILL PREVENTION, CONTROL, AND COUNTERMEASURE (SPCC) PLAN

OIL STORAGE REQUIREMENTS OF THE SPCC REGULATIONS. Christopher J. Ecsedy, P.E. Fuss & O'Neill, Inc. 146 Hartford Road Manchester, CT 06040

The Federal Spill Prevention, Control & Countermeasures (SPCC) Rule Overview

woodardcurran.com Oil Spill Prevention Control and Countermeasure Plan


If your campus has. Oil Pollution Prevention Rules (con.) Oil Pollution Prevention Rules (con.)

Spill Prevention, Control, and Countermeasure Plan. Roger Williams University One Old Ferry Road Bristol, Rhode Island

Spill Prevention, Control, and Countermeasures (SPCC) Regulations Update

CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN

SPILL PREVENTION, CONTROL AND COUNTERMEASURE (SPCC) PLAN

SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN. for the PIÑON RIDGE MILL HIGHWAY 90 BEDROCK, COLORADO Prepared by:

Spill Prevention Control and Countermeasures (SPCC) Plan (Onshore, Nonproduction Facility) Kennesaw State University

SPCC. Created by EPA in 1973 under the Clean Water Act. 10/22/2014. Spill Prevention Control & Countermeasure Plan

Civil Engineering Sector Labour-Management Health and Safety Committee

MODULE IV Secondary Containment, Oil Spill Control & Spill Prediction

History of the SPCC Rule

The Federal Spill Prevention, Control & Countermeasures (SPCC) Rule Overview

Management Approval/Certification Statement

Spill Prevention Control and Countermeasure (SPCC) Regulations Fact Sheet

SPILL PREVENTION, CONTROL AND COUNTERMEASURES (SPCC) PLAN

Safety Manual Title: Spill Prevention & Response Review Date: 6/1/2014

Spill Prevention, Control. and. Countermeasures Plan

ALLEGANY WIND POWER PROJECT CONSTRUCTION SPILL PREVENTION PLAN

Spill Prevention, Control and Countermeasure Plan

~CSRMA ALERT~ REVISED SPCC RULE WILL IMPACT MOST POTW S

for Gary Hughes GARY HUGHES SELF SERVICE LLC State of Missouri ID: ST

SPCC for Food Services

Spill Prevention, Control, and Countermeasure Plan Daneros Mine

FACILITY ENVIRONMENTAL COMPLIANCE

OIL POLLUTION PREVENTION REGULATIONS

SPILL PREVENTION, CONTROL, AND COUNTERMEASURE PLAN

Spill Prevention, Control and Countermeasure (SPCC) Training

Chaffee Landfill & CID Hauling Olean Road Chaffee, New York 14030

SPILL PREVENTION, CONTROL, AND COUNTERMEASURE PLAN Community College of Rhode Island Warwick, Rhode Island

SPILL PREVENTION, CONTROL, AND COUNTERMEASURE PLAN

Inspections Standard Operating Procedure 5 Aboveground Storage Tanks

MAINE DEPARTMENT OF ENVIRONMENTAL PROTECTION

SPILL PREVENTION CONTROL AND COUNTERMEASURE PLAN RUTGERS, THE STATE UNIVERSITY OF UNIVERSITY. Rutgers Health Sciences at Newark

APPENDIX O. Spill Prevention and Emergency Response Plan. G3 Terminal Vancouver Port Metro Vancouver Project Permit Application APPENDIX O

Spill Prevention, Control and Countermeasure Plan Checklist

Spill Prevention Control & Countermeasure (SPCC) for Farms

How To Safely Handle A Spill

Good Housekeeping Practices for DPW/Fleet Maintenance Facilities

OIL SPILL PREVENTION, CONTROL, AND COUNTERMEASURE PLAN. St. Lawrence University Canton, New York. January 2007

How To Plan Out An Oil Storage Tank At New York City College Of Technology

July 1, Job No

U.S. ENVIRONMENTAL PROTECTION AGENCY TIER I QUALIFIED FACILITY SPCC PLAN TEMPLATE

WESTERN CONNECTICUT STATE UNIVERSITY SPILL PREVENTION, CONTROL, AND COUNTERMEASURES PLAN PROCEDURE E-104. Prepared by:

SPILL PREVENTION CONTROL AND COUNTERMEASURES PLAN

SPILL PREVENTION CONTROL AND COUNTERMEASURE PLAN for PETROLEUM PRODUCTS FACILITY WIDE

Outdoor Storage of Raw Materials SC-33

W250. The Agricultural Producers Comprehensive Guide to Federal Oil Pollution Prevention Regulations

Contact Person Sarah Morris-Benavides Revision 1.1 Document Plan Effective Date 07/01/2014 Review Date 03/15/2017.

Port of Portland Terminal 2

Improper storage of fuel on construction sites will increase the risk of water pollution that may occur as a result of leaks or spills.

Spill Plan Reviewer s Guidance

Critical Regulations SUMMARY OF. Stormwater Management Regulations (National Pollutant Discharge Elimination System or "NPDES ) 40 CFR 122.

SPILL PREVENTION, CONTROL, AND COUNTERMEASURES PLAN FOR THE UNIVERSITY OF VIRGINIA CHARLOTTESVILLE, VIRGINIA

SPCC Rule Review. Spill Prevention Control & Countermeasures NON-TRANSPORTATION RELATED ONSHORE AND OFFSHORE FACILITIES

SOP 4: Spill Response and Cleanup Procedures SOP 4: SPILL RESPONSE AND CLEANUP PROCEDURES

Steel Tank Institute AST Inspections. Dana Schmidt, PE STI/SPFA

SPILL PREVENTION AND RESPONSE PLAN TEMPLATE FOR BUSINESSES IN DAYTON S SOURCE WATER PROTECTION AREA

Facility Scenario - Example Tier I Qualified Facility SPCC Plan

RUTGERS, THE STATE UNIVERSITY OF NEW JERSEY SPILL PREVENTION CONTROL & COUNTERMEASURE PLAN

Temporary Batch Plants

U.S. ENVIRONMENTAL PROTECTION AGENCY TIER I QUALIFIED FACILITY SPCC PLAN TEMPLATE

Spill Prevention Control and Countermeasure Plan

DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY. August 2012

BEST MANAGEMENT PRACTICES FOR LEAK AND SPILL CONTROL

SPCC Plan. Spill Prevention Control and Countermeasure Plan. Southwestern University

Spill Prevention, Control, and Countermeasures (SPCC) Course Material

Farm Fuel Tank Safety Guide

SPILL RESPONSE PLAN. What is the Issue? Regulatory Requirements. General Information

Spill Prevention, Control & Cleanup SC-11

Safe Operating Procedure

University of California, Riverside Spill Prevention, Control & Countermeasures Plan January 2015

Suffolk County Department of Health Services. Division of Environmental Quality

UltraTech International, Inc. Canadian Secondary Containment Requirements

Outdoor Liquid Container Storage

Tank Environmental Regulations. Aisha Beaty Barr Engineering Company

Chapter 2 Stormwater Pollution Prevention Plan (SWPPP) for Park Operations

IAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1

Environmental Health & Safety

SUFFOLK COUNTY DEPARTMENT OF HEALTH SERVICES TOXIC/HAZARDOUS MATERIAL TRANSFER FACILITY DESIGN GUIDELINES

Transcription:

Clayton State University 2000 CLAYTON STATE BLVD. Morrow, Georgia 30262 DRAFT SPILL PREVENTION, CONTROL, AND COUNTERMEASURES (SPCC) PLAN June 22, 2011

Professional Engineer Certification CSU s Plan has been reviewed and certified by a registered professional engineer (PE), as shown below: I herby attest that: I am familiar with the requirements of 40 CFR 112; I or my agent has visited and examined: Clayton State University 2000 Clayton State Blvd. Morrow, Georgia 30262 The SPCC Plan has been prepared in accordance with good engineering practice, including consideration of applicable industry standards, and with the requirements of 40 CFR 112; Procedures for required inspections and testing have been established; and The SPCC Plan is adequate for the facility. Professional engineer (PE): (Print or type name) Signature: Date: PE registration number: State(s): A 22 June 2011 1

Contents Acronyms and Abbreviations Section 1 Introduction 1.1 Purpose... 6 1.2 Plan Administration... 7 1.2.1 Management Approval [40 CFR 112.7]... 7 1.2.2 Location of SPCC Plan [40 CFR 112.3(e)]... 7 1.3 Plan Review... 7 1.3.1 Amendment by the Regional Administrator [40 CFR 112.4(a)]... 7 1.3.2 Plan Amendments Due to Facility Changes [40 CFR 112.5(a)]... 7 1.3.3 Scheduled Plan Reviews [40 CFR 112.5(b)]... 8 1.4 Facilities, Procedures, Methods, or Equipment Not Yet Fully Operational [40 CFR 112.7]... 8 1.5 Cross-Reference with SPCC Provisions [40 CFR 112.7]... 8 1.6 Certification of the Applicability of Substantial Harm... 9 Section 2 Facility Information 2.1 Facility Owner, Address, and Telephone [40 CFR 112.7(a)(3)]... 11 2.2 Facility Contacts [40 CFR 112.7(a)(3)]... 11 2.3 Facility Operations, Layout, and Site Plan [40 CFR 112.7(a)(3)]... 11 2.4 Facility Storage [40 CFR 112.7 (a)(3)(i)]... 12 2.5 Drainage Pathway and Distance to Navigable Waters [40 CFR 112.8(b)]... 12 2.6 Spill History [40 CFR 112.7]... 13 Section 3 Potential Spill Predictions, Volumes, Rates and Control [112.7 (b)] 3.1 Potential Discharge Volumes and Direction of Flow [40 CFR 112.7(b)]... 21 Section 4 Discharge Prevention 4.1 Drainage Control [40 CFR 112.7 (c)]... 23 4.2 Practicability of Secondary Containment [40 CFR 112.7(d)]... 23 4.3 Inspections/Record Keeping [40 CFR 112.7(e)]... 23 4.3.1 Weekly, Monthly, and Quarterly Inspections... 23 4.3.2 Periodic Integrity Testing... 24 4.4 Personnel Training and Spill Prevention Procedures [40 CFR 112.7(f)]... 24 4.4.1 Personnel Instruction... 24 4.4.2 Designated person accountable for spill prevention... 24 4.4.3 Spill prevention briefings... 25 A 22 June 2011 2

4.4.4 Site Security [40 CFR 112.7(g)]... 25 4.4.5 Flow Valves Locked... 25 4.4.6 Starter Controls Locked... 25 4.4.7 Pipeline loading/unloading connections securely capped... 25 4.4.8 Lighting adequate to detect spills... 25 4.4.9 Facility Truck Loading/Unloading Operations [40 CFR 112.7(h)]... 25 4.4.10 Loading/unloading procedures meet DOT regulations... 26 4.4.11 Secondary containment for vehicles... 26 4.4.12 Warning or barrier system for vehicles... 27 4.4.13 Vehicles examined for lowermost drainage outlets before leaving... 27 4.5 Brittle Fracture Testing [40 CFR 112.7 (i)]... 27 4.6 Facility Drainage [40 CFR 112.8(b)]... 27 4.7 Bulk Storage Tanks/Secondary Containment [40 CFR 112.8(c)]... 27 4.7.1 Tank compatibility with its contents... 27 4.7.2 Diked area construction and containment volume for storage tanks... 28 4.7.3 Diked area, inspection and drainage of rainwater... 28 4.7.4 Corrosion protection of buried metallic storage tanks... 28 4.7.5 Corrosion protection of partially buried metallic tanks... 28 4.7.6 Control of leakage through internal heating coils... 28 4.7.7 Tank installation fail-safe engineered... 28 4.7.8 Observation of disposal facilities for effluent discharge... 29 4.7.9 Visible oil leak corrections from tank seams and gaskets... 29 4.7.10 Appropriate position of mobile or portable oil storage tanks... 29 4.8 Facility Transfer Operations [40 CFR 112.8(d)]... 29 4.9 Spill Control Equipment... 29 4.10 Discharge Response and Countermeasure [40 CFR 112.7(a)(3)]... 29 4.11 Discharge and Drainage Controls... 30 Section 5 Discharge Response 5.1 Spill/Discharge Response and Countermeasures [40 CFR 112.7(a)(3)]... 32 5.2 Spill Reporting [40 CFR 112.7(a)(4)]... 34 5.3 Waste Disposal... 35 5.4 Discharge Notification [40 CFR 112.7(a)(5)]... 35 Figures Figure 2-1 Site Vicinity Map... 14 Figure 2-2 Site Layout Oil Containing Equipment Locations... 15 Figure 2-3 Site Layout Clayton Station Oil Containing Equipment Locations... 16 A 22 June 2011 3

Tables Table 1-1 Cross-Reference with SPCC Provisions... 8 Table 2-1 Facility Contacts... 11 Table 2-2 Facility Oil Storage... 17 Table 3-1 Spill Prediction Analysis... 22 Table 4-1 Spill Response Equipment List... 31 Table 5-1 Emergency Contacts... 37 Appendices Appendix A Plan Review, Evaluation Log, and Conformance Requirements Appendix B Certification of the Applicability of the Substantial Harm Criteria Checklist Appendix C Facility Inspection Checklists Appendix D Spill Log and Reporting Forms Appendix E Georgia Power Transformer Responsibility Letter Appendix F Rainwater Discharge Form A 22 June 2011 4

Acronyms and Abbreviations AST CDM CSU EPD GA DNR MSDS NRC PE SPCC USEPA UST Aboveground Storage Tank Camp Dresser & McKee, Inc. Clayton State University Environmental Protection Division Georgia Department of Natural Resources Material Safety Data Sheet National Response Center Professional Engineer Spill Prevention Control and Countermeasures United States Environmental Protection Agency Underground Storage Tank A 22 June 2011 5

Section 1 Introduction 1.1 Purpose This Spill Prevention, Control and Countermeasure Plan (Plan) was prepared by Camp Dresser & McKee, Inc. (CDM) for Clayton State University (CSU) at 2000 Clayton State Blvd., Morrow, Georgia. The purpose of the Plan is to describe the university s operating practices intended to prevent potential spill events and to minimize the impact of any spills to human health and to the environment. In the unlikely event that an oil spill occurs, this Plan outlines facility response efforts. This Plan has been prepared to meet the requirements of Title 40, Code of Federal Regulations, Part 112 (40 CFR Part 112) Oil Pollution Prevention. In addition to fulfilling regulatory requirements, this SPCC Plan is used as a reference for oil storage information, as a tool to communicate practices on preventing and responding to discharges with employees, as a guide to facility inspections, and as a resource during emergency response. This facility is subject to the SPCC rule because it meets three criteria: It is non-transportation related. It has an aggregate aboveground storage capacity greater than 1,320 gallons. There is a reasonable expectation of a discharge into or upon navigable waters of the United States. Applicability This Plan applies to all work operations at our university where employees may be exposed to potential oil discharge situations under normal working conditions or during an emergency situation. Responsibility The Director of Facilities Management for CSU is responsible for developing and maintaining this Plan and for making sure that the Plan is available to the EPA Regional Administrator for on-site review during normal working hours. Copies of the written Plan are located at Public Safety and are available twenty-four hours per day and seven days a week, and also at Facility Management. A 22 June 2011 6

1.2 Plan Administration 1.2.1 Management Approval We are committed to the prevention of discharges of oil to navigable waters and the environment. This Plan has the full approval of management at a level of authority to commit the necessary resources to fully implement it. Responsible Officer: _Ms. Corlis Cummings (Print or type name.) Title: Vice President, Business and Operations Signature: Date: 1.2.2 Location of SPCC Plan A complete copy of this Plan is maintained at the university with Public Safety and Facility Management. Normal operation hours for the office are Monday through Friday from 8am to 5pm, however, the plan is available at any time at Public Safety. Public Safety can be reached at any time in the event of a spill. (Please refer to Section 2.2 for contact information). 1.3 Plan Review 1.3.1 Amendment by the Regional Administrator If this facility discharges (i.e. spills): (1) more than 1,000 U.S. gallons of oil in a single discharge, or (2) discharged more than 42 U.S. gallons of oil in each of two discharges, occurring within any twelve month period, a written report must be submitted to the Regional Administrator of the U.S. EPA within 60 days. Refer to Section 5.4 for additional report information. 1.3.2 Plan Amendments Due to Facility Changes The Director of Facilities Management will amend this SPCC Plan in accordance with Section 112.7 and other applicable Sections of Part 112, when there is a change in the facility design, construction, operation, or maintenance that materially affects its potential for a discharge. The amendment will be prepared within six months of the change. Examples of changes that may require amendment to the Plan include, but are not limited to: Commissioning or decommissioning containers; Replacement, reconstruction, or movement of containers; Reconstruction, replacement, or installation of piping systems; Construction or demolition that might alter secondary containment structures; Changes of product or service; or Revision of standard operation or maintenance procedures at the A 22 June 2011 7

facility. 1.3.3 Scheduled Plan Reviews The Director of Facilities Management reviews this Plan at least once every five years from the date the facility becomes subject to 40 CFR 112 and five years from the date of the last review. Amendments are then prepared within six months of the review. Any technical amendments to our SPCC Plan are certified by a professional engineer or self-certified. Selfcertification is permitted based on 10,000 gallons or less in aggregate aboveground oil storage capacity at the CSU, and not having had (1) a single discharge of oil to navigable waters exceeding 1,000 U.S. gallons or (2) two discharges of oil to navigable waters each exceeding 42 U.S. gallons. Certification is not required for non-technical amendments like changes to telephone numbers, names, etc. The plan review dates and certifications (as necessary) are included in Appendix A. 1.4 Facilities, Procedures, Methods, or Equipment Not Yet Fully Operational CDM inspected for items that CSU would need to address to improve compliance with the SPCC regulations. Items that CSU needs to address are presented in Appendix A. 1.5 Cross-Reference with SPCC Provisions This SPCC Plan does not follow the exact order presented in 40 CFR Part 112. Section headings identify, where appropriate, the relevant sections of the SPCC rule. The following table (Table 1-1) presents a cross-reference of the Plan sections relative to applicable parts of 40 CFR Part 112. Table 1-1: Cross-Reference with SPCC Provisions Section of Regulation Regulatory Requirement Location in SPCC 112.3(d) Professional Engineer certification Page 1 112.3(e) Location of SPCC Plan Section 1.2.3 112.5 Plan review Section 1.3 112.7 Management approval Section 1.2.1 112.7 Cross-Reference with SPCC Rule Section 1.5 112.7(a)(3) General facility information, site plan, and facility diagram Section 2 Figures 1 & 2 112.7(a)(4) Discharge notification Section 4.9 A 22 June 2011 8

Section of Regulation Regulatory Requirement Location in SPCC Table 5-1 112.7(a)(5) Discharge response Section 4.10 112.7(b) 112.7(c) 112.7(d) Potential discharge volumes and direction of flow Containment and diversionary structures Practicability of secondary containment Section 3.3, Tables 2-2 & 3-1, Figures 1, 2 & 3 Section 4.7 Section 4.2 112.7(e) Inspections, tests and records Section 4.3 112.7(f) Personnel training, and discharge prevention procedures Section 4.4 112.7(g) Security Section 4.4.3 112.8.b Facility drainage Section 4.6 112.8(c)(1-5) Bulk Storage Containers / Secondary Containment Section 4 112.8(c)(6) Inspections Section 4.3 Appendix C 112.8(c)(7) Leakage control Section 4.7.6 112.8(c)(8) Overfill prevention system Section 4.7 112.8(c)(9) Effluent treatment facilities Section 4.6 112.8(c)(10) Visible discharges Section 4.6 112.8(c)(11) Mobile and portable containers Section 4.7.10 112.8(d) Transfer operations, pumping, and in-plant processes Section 4.8 1.6 Certification of the Applicability of the Substantial Harm Criteria Checklist Section 112.20(e) of the facility response plan regulation requires that all facilities regulated by 40 CFR Part 112 conduct an initial screening to determine whether they are required to A 22 June 2011 9

develop a facility response plan. The criteria in this checklist can be found in 40 CFR 112.20(f)(1) and is included in Appendix B. A 22 June 2011 10

Section 2 Facility Information 2.1 Facility Owner, Address, and Telephone The facility owner name, address, and telephone number is as follows: The Board of Regents of the University System of Georgia 270 Washington Street, S.W. Atlanta, GA 30334 (404) 657-7099 The facility operator name, address, and telephone number is as follows: Clayton State University 2000 Clayton State Blvd. Morrow, GA 30262 (678) 466-4050 (404) 961-3540 2.2 Facility Contacts Facility contact(s) in case of a spill include the following: Table 2-1: Facility Contacts Contact Name Title Work Number Home or Alternative Number Bobby Hamil Director of Public Safety (678) 466-4050 (770) 961-3540 Darren Thomas Asst Director of Building (678) 466-4259 (404) 520-3490 Operations Cindy Knight EHA/Property Risk (678) 466-4250 (770) 312-2899 Management Donald West Project Manager (678) 466-4203 (678) 849-8000 Facilities Management Harun Biswas Director of Facilities Management (678) 466-4240 (404) 642-7173 2.3 Facility Operations, Layout, and Site Plan The physical layout of the facility is presented in Figures 2-1, 2-2, and 204, a site vicinity map and facility maps for the campus and the apartment complex, Clayton Station. A 22 June 2011 11

2.4 Facility Storage CSU is a higher-education facility that contains low quantities of used oil and fuel in aboveground storage tanks (ASTs), as well as equipment that includes an oil storage reservoir in which the oil is present solely to support the function of the device. The university also has one grease storage bin, elevators, emergency back-up generators, and transformers. All storage containers or equipment regulated under the SPCC rule are listed in Tables 2-2 and 2-3. The two diesel fuel drums are stored on a spill pallet. The elevator reservoirs are stored in rooms that act as secondary containment. Transformers are stored on cement pads on the ground surface, or on the utility post (i.e. Clayton Station) The ASTs are located at the facility maintenance area. The used oil AST is on a concrete floor and is under cover. The fuel AST is located outside and on concrete. Both are double walled. The two emergency generators are stored on concrete pads. One is on a pad on the ground surface while the other is on another concrete raised pad which is surrounded by a paved road and parking area. These generators will be contained within a concrete berm for secondary containment. See Appendix A for details on the completion of these structures. The grease storage bin is stored on a loading dock, within a secondary containment berm, and under cover. The capacities of containers present at the university are listed in Tables 2-2 and 2-2 and are also shown on the facility diagrams (Figures 2-2 and 2-3). Only containers containing 55 gallons or more of oil are included, except for one transformer whose capacity was reported as an average. Since this transformer may actually contain more than 55 gallons, it was included. Oil-filled Equipment and Reservoirs less than 55 gallons CSU also operates equipment containing less than 55 gallons of oil such as certain elevators and trash compactors. These are not listed in Table 2-2. 2.5 Drainage Pathway and Distance to Navigable Waters The CSU Facility is located in Clayton County, Georgia. The storm water from this university flows to drainage ditches and storm water drains and then to the Swan Lake, located on the south of the subject site. Figure 2-1 shows the topographic map and drainage pathway for the area. A 22 June 2011 12

Equipment that contains oil within the university buildings are not located near any floor drains that empty into the storm sewer, but some transformers located outside are. In the event of a spill, the oil will be cleaned up using absorbents and booms. If any oil enters the drain, plant personnel will notify the Clayton County Water Authority and other appropriate agencies (Table 5-1). 2.6 Spill History Any spills are documented on a spill log (Appendix D), located in the EHS/Property Risk Coordinator s office. The facility has not experienced any spill events within the past five years that exceed 42 gallons. A 22 June 2011 13

Legend Campus Boundary Figure 2-1 Site Vicinity Map Clayton State University Morrow, Georgia 0 600 1,200 Feet

T-35 T-26 T-23 T-22 T-19 N Lake Dr Clayton State Blvd N Lee St T-36 North Pkwy Laker Hall Caldwell Dr E-17 D-2 T-16 School of Business Clayton T-5 Hall T-6 E-13 T-18 Arts & Sciences E-14 E-18 Lee St T-2 Facilities Management AST-1 D-1 AST-2 E-19 CSU East E-20 Trammell Rd Figure 2-2 Site Layout - Oil Containing Equipment Locations Clayton State University Morrow, Georgia Legend Transformer T-17 T-3 Faculty Hall T-14 Business & Health Sciences T-10 T-9 Elevator Grease Bin Aboveground Storage Tank Athletics & Fitness T-15 JM Baker University Center E-8 E-12 E-9 E-10 E-11 T-7 T-8 Library Student Center E-15 T-13 E-16 Drum Generator Spill Kit/Supplies* Campus Boundary T-4 Student Activities Center E-7 T-11 E-3 E-4 T-12 Spivey Hall E-6 G-2 Music Education S w a n L a k e Flow Direction *Note: Spill kits also located in every elevator closet. E-1 E-2 Harry S Downs Center for Continuing Education/ School of Nursing G-1 Twilight Trl Oxford Dr 0 150 300 Feet Yale Ct

Waterford Ct T-32 Harper Dr T-31 T-30 T-33 N Lake Dr North Pkwy T-34 T-35 T-36 Harper Ct Caldwell Dr T-29 T-28 T-27 T-26 T-25 T-21 T-24 T-20 T-23 T-22 N Lee St T-19 Clayton State Blvd Legend Transformer Spill Kit/Supplies Campus Boundary Figure 2-3 Site Layout - Oil Containing Equipment Locations Clayton Station Apartment Complex Morrow, Georgia 0 100 200 Feet

Table 2-2. Facility Oil Storage Building Name/Container Location Facilities Management Facilities Management Tank/Container Type Map/Container ID Owner Contents Total Capacity (gallons) Secondary Containment Above Ground Storage Tank AST-1 CSU Used Oil 250 On spill pallett, Inside building with concrete floor Above Ground Storage Tank AST-2 CSU Unleaded Gasoline 500 No Passive Secondary Containment. Active Only. Spill would pour onto concrete pad and then flow to the storm drain directly adjacent to the tank. Facilities Management Steel Drum D-1 CSU Diesel Fuel 110 On spill pallett, Inside building with concrete floor Harry S. Downs Center (School of Nursing) Elevator (Freight) E-1 CSU Hydraulic Fluid 100 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. James M. Bakers University Center Elevator (Freight) E-10 CSU Hydraulic Fluid 425 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Library Elevator (Passenger) E-11 CSU Hydraulic Fluid 200 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Library Elevator (Freight) E-12 CSU Hydraulic Fluid 200 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Clayton Hall Elevator (Passenger) E-13 CSU Hydraulic Fluid 125 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Arts and Sciences Elevator (Passenger) E-14 CSU Hydraulic Fluid 70 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Student Center Elevator (Freight) E-15 CSU Hydraulic Fluid 80 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Student Center Elevator (Passenger) E-16 CSU Hydraulic Fluid 100 Laker Hall Elevator (Passenger) E-17 CSU Hydraulic Fluid 100 Harry S. Downs Center (School of Nursing) Elevator (Passenger) E-2 CSU Hydraulic Fluid 100 Spivey Hall Elevator (Passenger) E-3 CSU Hydraulic Fluid 100 Spivey Hall Elevator (Freight) E-4 CSU Hydraulic Fluid 100 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Spivey Hall Elevator (Stage Lift) E-5 CSU Hydraulic Fluid 250 Building floor is Secondary Containment. Concrete floors and walls. Music Education Elevator (Passenger) E-6 CSU Hydraulic Fluid 105 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Student Activity Center Elevator (Passenger) E-7 CSU Hydraulic Fluid 150 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. James M. Bakers University Center Elevator (Passenger) E-8 CSU Hydraulic Fluid 300 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. James M. Bakers University Center Elevator (Passenger) E-9 CSU Hydraulic Fluid 300 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. James M. Bakers University Center Elevator (Passenger) E-10 CSU Hydraulic Fluid 300 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. Annex-LAB Elevator (Passenger) E-18 CSU Hydraulic Fluid 80 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. CSU-East Administration Bldg Elevator (Passenger) E-19 CSU Hydraulic Fluid 80 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. CSU-East Multi-purpose Bldg Elevator (Passenger) E-20 CSU Hydraulic Fluid 80 Inside Locked Room. Building floor is Secondary Containment. Concrete floors and walls. James M. Bakers University Center Grease Bin GB-1 CSU Used Food Grease 250 Outside and covered. Within portable 4x6 ft containment berm - on Concrete Loading Dock. Central Plant Transformer T-10 CSU Mineral Oil 255 Student Activity Center Loading Dock Transformer T-11 CSU Mineral Oil 306 No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. Page 1 of 2

Table 2-2. Facility Oil Storage Building Name/Container Location Tank/Container Type Map/Container ID Owner Contents Total Capacity (gallons) Secondary Containment Music Education Loading Dock Transformer T-12 CSU Mineral Oil 355 Student Center Loading Dock Transformer T-13 CSU Mineral Oil 429 UC Loading Dock Transformer T-14 CSU Mineral Oil 493 Athletic and Fitness Building Transformer T-15 CSU Mineral Oil 186 Technology / Clayton Hall Transformer T-18 CSU Mineral Oil 235 Facility Management (Loading Dock) Transformer T-2 CSU Mineral Oil 183 Adminstration / Faculty Hall Transformer T-3 CSU Mineral Oil 183 Tennis Courts/Soccer Field Transformer T-4 CSU Mineral Oil 211 School of Business Transformer T-5 CSU Mineral Oil 215 No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (stones) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to the santirary drain near the tank. No Passive Secondary Containment. Active Only. Spill would pool onto concrete Arts and Sciences Transformer T-6 CSU Mineral Oil 230 pad and then ground surface (grass) before going to storm drain or water body. Outside Library (Right of Entrance) Transformer T-7 CSU Mineral Oil 254 Lower Library (Near Carts) Transformer T-8 CSU Mineral Oil 255 Central Plant Transformer T-9 CSU Mineral Oil 255 Continuing Education Backup Generator G-1 CSU Diesel Fuel 299 Spivey Hall Backup Generator G-2 CSU Diesel Fuel 127 No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (gravel) before going to storm drain or water body. In addition, there is an alarm to detect any accumulation of liquid in this area. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool or drain onto concrete pad and then ground surface (grass) before going to storm drain or water body. Secondary containment structure will be built. See Appendix A. No Passive Secondary Containment. Active Only. Spill would pool or drain onto concrete pad and to paved parking area/road before going to storm drain or water body. Secondary containment structure will be built. See Appendix A. *Does not include equipment containing less than 55 gallons oil in reservoirs. Total = 8,926 gallons Page 2 of 2

Table 2-3. Georgia Power Owned Transformers Building Name/Container Location Tank/Container Type Map/Container ID Owner Contents Total Capacity (gallons) Laker Hall Transformer T-16 Ga Power Mineral Oil 486 Main Transformer (near Athletic and Fitness Bldg) Transformer T-17 Ga Power Mineral Oil 865 5809 Northlake Dr. (Apartment Complex- Phase I) Transformer T-19 Ga Power Mineral Oil 33 5809 Northlake Dr. (Apartment Complex- Phase I) Transformer T-20 Ga Power Mineral Oil 56 5809 Northlake Dr. (Apartment Complex- Phase I) Transformer T-21 Ga Power Mineral Oil 56 5809 Northlake Dr. (Apartment Complex- Phase I) Transformer T-22 Ga Power Mineral Oil 56 5809 Northlake Dr. (Apartment Complex- Phase I) Transformer T-23 Ga Power Mineral Oil 56 5809 Northlake Dr. (Apartment Complex- Phase I) Transformer T-24 Ga Power Mineral Oil 56 5809 Northlake Dr. (Apartment Complex- Phase I) Transformer T-25 Ga Power Mineral Oil 56 5809 Northlake Dr. (Apartment Complex- Phase I) Transformer T-26 Ga Power Mineral Oil 56 5809 Northlake Dr. (Apartment Complex- Phase I) Transformer T-27 Ga Power Mineral Oil 56 5809 Northlake Dr. (Apartment Complex- Phase I) Transformer T-28 Ga Power Mineral Oil 56 5809 Northlake Dr. (Apartment Complex- Phase I) Transformer T-29 Ga Power Mineral Oil 56 Secondary Containment No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. Page 1 of 2

Table 2-3. Georgia Power Owned Transformers Building Name/Container Location Tank/Container Type Map/Container ID Owner Contents Total Capacity (gallons) 5751 Northlake Dr. (Apartment Complex- Phase II) Transformer T-30 Ga Power Mineral Oil 56 Secondary Containment No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or water body. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or 5751 Northlake Dr. (Apartment Complex- Phase II) Transformer T-31 Ga Power Mineral Oil 56 5751 Northlake Dr. (Apartment Complex- Phase II) Transformer T-32 Ga Power Mineral Oil 100 water body. 5751 Northlake Dr. (Apartment Complex- Phase II) Transformer T-33 Ga Power Mineral Oil 100 water body. 5751 Northlake Dr. (Apartment Complex- Phase II) Transformer T-34 Ga Power Mineral Oil 56 before going to storm drain or water body. 5751 Northlake Dr. (Apartment Complex- Phase II) Transformer T-35 Ga Power Mineral Oil 100 before going to storm drain or water body. 5751 Northlake Dr. (Apartment Complex- Phase II) Transformer T-36 Ga Power Mineral Oil 100 Total = 2512 gallons *Capacity was reported as an average. Since the exact capacity is not known, it was inlcuded here. No Passive Secondary Containment. Active Only. Spill would pool onto concrete pad and then ground surface (grass) before going to storm drain or No Passive Secondary Containment. Active Only. Spill would drip/drain from the overhead transformer (attached to utility pole) to ground surface (grass) No Passive Secondary Containment. Active Only. Spill would drip/drain from the overhead transformer (attached to utility pole) to ground surface (grass) No Passive Secondary Containment. Active Only. Spill would drip/drain from the overhead transformer (attached to utility pole) to ground surface (grass) before going to storm drain or water body. Page 2 of 2

Section 3 Potential Spill Predictions, Volumes, Rates and Control 3.1 Potential Discharge Volumes and Direction of Flow Based on how and where oil and other petroleum products are used and stored at this facility, Table 3-1 describes potential types of spill/release scenarios, estimated volume releases, the probable flow direction of the spill and the predicted spill rate. The probable flow directions are presented on Figures 2-2 and 2-3. A 22 June 2011 21

Table 3-1. Spill Prediction Analysis Potential Failure / Location Failure Type Predicted Volume Released (gallons) Predicted Spill Rate Direction of Flow Containment Grease Bin Leak or Spill (Bakers UC Loading Dock) Spill during transfer, leak, rupture Less than 1 and up to 250 Gradual seepage to instantaneous spill Into secondary containment structure, onto adjacent concrete loading dock, off loading dock, and then to storm drain. Spill Pallet - Holds up to 120 gallons. Elevator Reservior Leak at any location. Leak, rupture up to 425 (capacity of largest reservior) Gradual seepage to instantaneous spill Within Elevator Closet (Storage Room with concrete floor and walls). Concrete room. Drum Leak / Spill / Maintenance Area Leak, rupture up to 110 Gradual seepage to instantaneous spill To spill pallet and then to adjacent concrete floor inside before flowing outside to storm drain. Spill Pallet - Holds up to 30 gallons. Transformer Leak at any location. Leak at Used Oil Above Ground Storage Tank in Maintenance Area. Leak, rupture Leak, Rupture, Spill during offloading up to 865 (capacity of largest transformer) 10 to 250 Gradual seepage to instantaneous spill Gradual seepage to instantaneous spill To concrete pad and then adjacent ground surface (grass) and then to stormwater drain or Lake. Adjacent ground surface (concrete) and then to stormwater drain. Land-based spill response capability (spill kits) Land-based spill response capability (spill kits) Leak, spill, or overfill at Unleaded Gasoline Above Ground Storage Tank in Maintenance Area. Leak, Rupture, Spill during offloading or 10 to 500 filling of containers Gradual seepage to instantaneous t spill Adjacent ground surface (concrete) and then to stormwater drain. Land-based spill response capability (spill kits) Leak, spill, or overfill at either of the emergency generators. Leak, Rupture, Spill during filling of generator fuel reservior 10 to 299 (capacity of largest generator fuel tank) Gradual seepage to instantaneous spill Adjacent ground surface (concrete) and then to stormwater drain. Currently, land-based spill response capability (spill kits) only but a passive berm containment structure will be built. See Appendix A for completion details. Page 1 of 1

Section 4 Discharge Prevention 4.1 Drainage Control At CSU, spill kits (absorbent pigs, pads, clay/granular absorbent, etc.) are maintained at facility maintenance (within the main building and near the fuel AST),the UC, and at the maintenance building at Clayton Station (the apartment complex), as shown on Figures 2-2 and 2-3. In addition, smaller spill kits are stored in every one of the elevator closets. Spill kit material is maintained in sufficient amounts to contain and control a spill of the normal quantity of oil stored in the individual area. In addition, containment is provided for the diesel drums within the facility maintenance building, and for the grease drum, a secondary containment berm. There are no drainage controls for the site as a whole. 4.2 Practicability of Secondary Containment CSU is applying the use of secondary containment, double-walled tanks, and the use of readily available spill equipment to prevent discharged oil from reaching navigable waters. This overall approach is practicable and efficient for this facility. The structures and equipment to help prevent a discharge of oil are described in Tables 2-2, 2-3 and 3-1. 4.3 Inspections/Record Keeping 4.3.1 Weekly, Monthly, and Quarterly Inspections Inspections are conducted weekly, monthly, and /or quarterly and are documented. Inspections are performed as follows. Daily Inspections: Food Grease Bin: A food service employee inspects the condition of the grease bin and spills and documents the inspection on an inspection sheet which is then forwarded to facilities on a monthly basis (Appendix C). Weekly Inspections: ASTs and drums: A CSU maintenance employee inspects ASTs and drums at facility maintenance, and logs findings on an inspection sheet (Appendix C). Monthly Inspections: Elevators and Emergency Generators: A CSU employee inspects all elevators and generators for deterioration, corrosion, or leaks (Appendix C). Quarterly Inspections: sand Spill Kits/Spill Response Supplies: A CSU employee inspects all transformers (those owned by CSU as well as those owned by Georgia Power) for deterioration, corrosion, or leaks. Georgia Power has documented to CSU via letter that they will handle any oil spill originating from their transformers (Appendix E). In addition, spill kits are inspected for accurate and sufficient contents. Findings are documented on inspection forms found in Appendix C. Any oil-filled operational equipment, waste oil, fuel, or hydraulic fluid containers, and piping problems are immediately reported to the Asst. Director of Building Operations. Equipment oil spills (leaks) that cause a loss of oil from tank walls, piping or other A 22 June 2011 23

components are repaired or replaced as soon as possible to prevent the potential for a major spill from the source. This is especially important for sources located outside or near drains or catch basins that discharge to the environment. Inspection checklists are included in Appendix C. An inspection checklist sheet shall be signed and dated, and remain on file in facilities management for five years plus the current year. The EHS/Property Risk Coordinator is responsible for maintaining them with this SPCC Plan. Employees at the facility who have been trained and are familiar with the equipment shall be responsible for conducting these inspections. 4.3.2 Periodic Integrity Testing CSU performs visual inspections from the outside of the containers for signs of deterioration and corrosion. 4.4 Personnel Training and Spill Prevention Procedures 4.4.1 Personnel Instruction CSU provides SPCC spill training to oil-handling employees to ensure that they are properly instructed in the operation and maintenance of equipment to prevent oil discharges, discharge procedures protocols, general facility operations, the contents of the facility SPCC Plan, and applicable pollution control laws, rules, and regulations. Facilities Management will conduct annual training which includes the following training topics: Introduction to pollution control laws; Rules and regulations pertaining to the use and storage of oil products; Inspection, operation and maintenance of spill equipment, and oil storage and dispensing equipment; Spill response and cleanup; Spill notification and record keeping; and Spill prevention practices. Records of attendance at training and topics covered are maintained by Facilities Management. The annual SPCC training is documented and includes the instructor s name, course outline, date and duration of training, attendant s names and signatures, and a corrective action list of SPCC Plan areas in need of improvement that were discussed, if any. This information is filed and maintained for at least three years at Facilities Management. A Certificate of Training is presented to each CSU employee that has completed the training. Facilities Management forwards a copy of this certificate to the Human Resource Department for inclusion in the employee s file. 4.4.2 Designated person accountable for spill prevention The EHS/Property Risk Coordinator is responsible for: Overseeing discharge prevention activities, Reporting on the progress of discharge prevention activities to facility management, A 22 June 2011 24

and Conducting discharge prevention briefings at least once a year for oil-handling personnel to ensure adequate understanding of the facility SPCC Plan. 4.4.3 Spill prevention briefings CSU holds annual training that discusses spill prevention scenarios. 4.4.4 Site Security CSU has established security measures for the entire university which includes where oil is handled and/or stored. While the entire university cannot be fenced, the site is monitored and patrolled 24 hours per day by university security. Access to the maintenance area (oil storage area and fueling station) is controlled by both fencing and general security patrol during both operating and non-operating hours. Elevator closets and transformers are always kept locked. The grease bin is in an area accessible by the public but the area is monitored by university security. The generators are in an area routinely monitored and patrolled. 4.4.5 Flow Valves Locked There are no flow valves on any of the containers that would allow direct outward flow of the tanks content to the surface when in non-operating or non-standby status. 4.4.6 Starter Controls Locked Starter controls on the gasoline AST is accessible only to authorized personnel and shall be manually operated by CSU personnel. 4.4.7 Pipeline loading/unloading connections securely capped There are no oil transfer pipelines at CSU. 4.4.8 Lighting adequate to detect spills CSU maintains sufficient lighting that is appropriate for a university, its location, and its security risks. The university is illuminated for students and their security but also prevents potential vandalism or other acts that may cause a discharge to occur during hours of darkness. 4.4.9 Truck Loading and Unloading Operations CSU receives a tank truck for refilling the 500-gallon gasoline AST, and a truck for removing used oil from the 250-gallon AST. CSU has an employee overseeing all truck unloading operations. The CSU employee shall ensure that, while on CSU property, the carrier follows all codes of federal regulations regarding the transportation of materials. CSU will ensure that the unloading truck is equipped with and properly uses handbrakes (parking brakes) or brake locking devices before unloading. CSU will ensure that drivers immediately set parking brake and secure trailer with chock blocks. The CSU attendant must verify that the product on the truck is the correct product A 22 June 2011 25

and grade to use in filling the tank. Prior to and after filling, the CSU attendant will oversee measuring and verify the level of tank contents. Adjustments must be made if the amount of product ordered exceeds the fill level of the tank. The CSU representative also reviews the tank monitor and the amount of fuel is entered into the inventory management system. The CSU attendant will verify that all fittings, hoses, and seals are in good condition (free of leaks, properly aligned, and correctly fitted) prior to unloading product. A CSU attendant must be present while the lines are being connected and disconnected. When applicable, the CSU attendant will ensure that a proper ground connection is made first before any other connection is made. To make a proper ground connection you must: connect the ground cable, connect the proper unloading hoses(s), ensure that the valves are lined open correctly, ensure that the valves are lined closed correctly, vent the pressure off of the unloading hose(s) prior to disconnecting, return the unloading hose(s) to original position, return the ground cable to the original position, and complete the required paperwork before leaving the property. Attempting to cause a false ground by tampering with the ground system will cause the driver s unloading privileges to be immediately suspended. A true ground must be established from your truck to the grounding system. Drivers and passengers will be directed to remain with the vehicle unless authorized to leave the vehicle by a designated CSU representative. A CSU authorized employee and transport personnel will be present when connecting and disconnecting. Note: the driver will be directed to remain outside the vehicle, but in the unloading areas during connecting, unloading, and disconnecting. The CSU attendant will ensure that the driver provides means for collecting product lost in the disconnecting process. A bucket is provided by CSU for this purpose if the driver does not have one available. Any residual oil is collected and comingled with other waste oil for disposal. Disposal practices will be in accordance with local, state, and federal regulations. 4.4.10 Loading and Unloading procedures meet DOT regulations Truck unloading activities include the refilling of the gasoline AST approximately two to three times per month and the removal of used oil (by vacuum truck) when necessary (approximately every two to three years). All incoming oil products are received and stored in approved containers less than 55 gallons- except for diesel fuel which is stored in 55- gallon drums. A licensed fluid recovery contractor handles disposal of used oil and grease on an as needed basis. All offloading activities are directly overseen by a trained CSU employee. 4.4.11 Secondary containment for vehicles Loading and unloading activities performed at the facility include the unloading of gasoline fuel from tanker trucks with their own pumping systems, fueling of university vehicles at the fueling station, filling of smaller containers for distribution to university vehicles and landscaping equipment, and the removal of used oil. Secondary containment is not provided for the delivery of gasoline, vehicle fueling of fuel, or removal of used oil and grease. A storm drain is located directly down-gradient of the gasoline AST / fueling area. A 22 June 2011 26

However, sorbent materials are maintained in sufficient quantities to contain a non-bulk container spill that occurs when loading or unloading trucks or vehicles and a storm drain cover is placed over the drain during fueling activities. In the event of a catastrophic release from an unprotected tanker failure during oil transfer, the trained facility personnel would implement the necessary control measures the use of a storm drain cover and/or sorbent for diking, booms, pigs, socks, etc. to divert and contain the spill until the appropriate emergency response contractor arrives onsite. The CSU attendant will assist the driver in preventing product releases. Truck valve(s) should be used to shut off product in the event of a release, regardless of the cause. Under no circumstances should the driver attempt to start the truck and move the truck in an emergency situation without the expressed direction of CSU personnel. In the event of an uncontrolled release, all efforts should be made to minimize and contain the release. Unloading should be shut down immediately and The Director of Facilities Management notified of the release. 4.4.12 Warning or barrier system for vehicles A trained CSU employee is present to observe all loading/unloading operations in order to prevent vehicle departure before complete disconnect of transfer lines. 4.4.13 Vehicles examined for lowermost drainage outlets before leaving A trained CSU employee visually inspects the vehicle prior to departing the facility. 4.5 Brittle Fracture Testing Not Applicable. The facility has no field-erected aboveground storage containers and is therefore not subject to brittle fracture testing. 4.6 Facility Drainage CSU uses many of the buildings and elevator storage closets as secondary containment. The areas are all locked, covered and no drains exist in these areas. In the event that oil or oilimpacted water collects on the building floor, the fluids will be cleaned up by properly trained personnel utilizing sorbent materials and placed in a drum for proper disposal. 4.7 Bulk Storage Tanks/Secondary Containment 4.7.1 Tank compatibility with its contents The 500-gallon gasoline AST, 250-gallon used oil AST, 250-gallon grease bin, generator fuel reservoirs, and all drums are constructed of steel. All are compatible with their contents and storage conditions. A 22 June 2011 27

4.7.2 Diked area construction and containment volume for storage tanks A spill pallet is utilized for storing the two 55-gallon drums of diesel fuel at facility maintenance. The containment volume of the spill pallet is 30 gallons. The ASTs are double walled. The grease bin is located within a 4-foot by 6-foot containment berm. The containment volume of this berm is 120 gallons. The generators are not currently within secondary containment structures but CSU is planning the construction of a concrete berm around each generator. See Appendix A for additional details. All secondary containment systems are sufficiently impervious to contain an oil spill. 4.7.3 Diked area, inspection and drainage of rainwater Any rainwater accumulation in the spill pallet or berm around the grease bin (although unlikely since they are both stored under cover) shall be manually pumped and poured back into the used oil AST. There are no drains in the spill pallet or the containment berm. Once the concrete berms are constructed around the generators, rainwater accumulation within the containment area will be inspected for fuel contamination. Non-contaminated rainwater will then be manually pumped out and allowed to flow to the stormwater drain. Impacted rainwater will be pumped and disposed of properly with other waste products. A rainwater discharge form is included in Appendix F. 4.7.4 Corrosion protection of buried metallic storage tanks CSU has no buried metallic storage tanks. 4.7.5 Corrosion protection of partially buried metallic tanks There are no partially buried tanks at CSU facility. 4.7.6 Control of leakage through internal heating coils The CSU storage tanks are not equipped with internal heating coils. 4.7.7 Tank installation fail-safe engineered The 500-gallon fuel AST does have high liquid level alarms and a high liquid level pump cutoff device set to stop flow at a predetermined container content level. In addition, it has a low level alarm in order to detect a leak from the tank. A log is also maintained so that the amount leaving and entering the tank is tracked. Offloading of diesel fuel is overseen by a trained CSU employee, who ensures that the tank is not overfilled. The driver and CSU employee will be within a short visual distance of each other during the filling procedure to allow for direct communication. A 22 June 2011 28