Automated Clay Conditioning for Foundation (ACCF)



Similar documents
Soaker Hoses for Trees & Foundations. Patty Sipe Heads Up Sprinkler Company

OPL BASIC. Dosing System for Professional Laundry machines. Contents

HEAVY WATER LEAK DETECTOR

Green House Monitoring and Controlling Using Android Mobile Application

Project Plan. Project Plan. May Logging DC Wattmeter. Team Member: Advisor : Ailing Mei. Collin Christy. Andrew Kom. Client: Chongli Cai

A guide to preventing structural damage

Eric Mitchell April 2, 2012 Application Note: Control of a 180 Servo Motor with Arduino UNO Development Board

DAMAGE TO FOUNDATIONS FROM EXPANSIVE SOILS

Coexisting with Expansive Soil. An Informational Guide for Homeowners

ECE 495 Project 3: Shocker Actuator Subsystem and Website Design. Group 1: One Awesome Engineering

Servo Info and Centering

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

How To Use A Watt Saver On A Microcontroller (Watt Saver) On A Cell Phone Or Mp3 Player

HOW TO ORDER SAFETY PRODUCTS/SAFETY CONTROL SYSTEMS ELECTRICAL SAFETY CONTROLS

Irrigation System Maintenance

The Control of ph and Oxidation Reduction Potential (ORP) in Cooling Tower Applications By Charles T. Johnson, Walchem Corporation

Failure code manual. content

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

Selecting and Implementing H-Bridges in DC Motor Control. Daniel Phan A

TELE-SAFE HOME SECURITY SYSTEM

SOIL MOISTURE SENSORS: ARE THEY A NEGLECTED TOOL The Experience In Boulder, CO

Fig 3. PLC Relay Output

ProScan v.1.2. Owner s Manual

WIND ALARM. Wind Speed Alarm. Wind Speed. Set Point 2. Set Point 1 NEW BEDFORD, MA USA

DEPARTMENT OF CODES AND BUILDING SAFETY FLOOD RECOVERY INFORMATION

Centro-Matic Automatic Lubrication Systems System Controls

How to read this guide

Energy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management

Manual for Fire Suppression & Methane Detection System

Freezing and Bursting Pipes. How pipes freeze and burst, and what to do to prevent damage.

Subminiature Load Cell Model 8417

BLUE RIBBON CORP. BC001 Birdcage Installation Manual

HM-W536 Install Guide

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS

Electronic faucets for every occasion, every application

A High Bill Usually Means a Leak

Product Manual. ABB i-bus KNX Data Logging Unit BDB/S 1.1. Intelligent Installation Systems ABB

INTREPID Perimeter Intrusion Detection System

Perimeter Security System

Fundamentals of Mass Flow Control

SECTION 13XXX CONTROL DESCRIPTION (DICP Models NC, 412, 622, 826, 1030)

ELECTRIC CENTRAL HEATING FLOW BOILER

AUTODIALLER / QUICKDIALLER - SA132

Streaming Potential System (SPT1000, SPD1000)

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

RESIDENTIAL WATER SURVEY

PLC Based Liquid Filling and Mixing

Design of Fuzzy Drip Irrigation Control System Based on ZigBee Wireless Sensor Network

AC-115 Compact Networked Single Door Controller. Installation and User Manual

Protection Systems. A UTC Fire & Security Company F Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS

Inwall Room Temperature Unit

Electric Panel Pump Control System. Operation, Maintenance and Installation Manual

Oil and Coolant Circulating Heating System. Model - OCSM

SYSTEM 45. C R H Electronics Design

Programmable Logic Controller PLC

Engineered, Time-Tested Foundation Repairs for Settlement in Residential and Light Commercial Structures. The Leading Edge.

Using Web-based Software for Irrigation and Nitrogen Management in Onion Production: our Research Plan for 2013

OPERATING INSTRUCTIONS

Flow Measurement Options for Pipeline and Open Channel Flow

PC INTERFACE MODULES FOR TOLL-PLAZA CLASSIFICATION SENSORS

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

A Practical Guide to Free Energy Devices

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

14. Troubleshooting Guide

Design and Implementation of an Accidental Fall Detection System for Elderly

AMC1100: Replacement of Input Main Sensing Transformer in Inverters with Isolated Amplifier

Battery Backup Sump Pump System

Color Mark Sensor with Red or Green LED E3S-VS

How To Size A Stenner Pump

LB Sky Global. 92 Lobachevskogo St, Bld 92, Office 5, Moscow, Russia Tel/Fax 7(495) , Site:

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

User s Guide. Automatic Sprinkler System Control Timer. ECXTRA Features

Model: DC-A2IO Advanced HVAC Controller

Total solder points: 129 Difficulty level: beginner advanced LIQUID LEVEL CONTROLLER K2639 ILLUSTRATED ASSEMBLY MANUAL H2639IP-1

INSTALLATION MANUAL 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS

REMOTE MONITORING AND CONTROL SYSTEM

DISTRICT OF COLUMBIA WATER AND SEWER AUTHORITY. a guide to PREVENTING SEWER BACKUPS AND FLOODING

Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)

Questions and Answers for Heating and A/C Contractors

MBA-MM-1040/10/13/1665 MULTI MEDIA FILTERS

Attachment G-1: Pit Latrine Diagram. Fig E.1a: Pit Latrine. Fig E.1b: Plan View of Twin Pits

Detection of Leak Holes in Underground Drinking Water Pipelines using Acoustic and Proximity Sensing Systems

The Natural Lawn & Garden Healthy Landscapes for a Healthy Environment. Smart. Watering. Iris germanica Gracchus

MODULE BOUSSOLE ÉLECTRONIQUE CMPS03 Référence :

Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5

Palaparthi.Jagadeesh Chand. Associate Professor in ECE Department, Nimra Institute of Science & Technology, Vijayawada, A.P.

SingleNet Single Cable Control System

R E S I D E N T I A L H O U S I N G

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

VK-250 WARRANTY REGISTRATION FORM

, User s Manual

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Measuring, Controlling and Regulating with labworldsoft

FP2 Relay. The Best Relaytion

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

Solar Powered Smart Irrigation System

Leak Detector Guide. Your Guide to Home Water Conservation

Transcription:

Automated Clay Conditioning for Foundation (ACCF) by Kevin Aldridge ktaldridge@uh.edu Department of Engineering Technology Aron Hodge arhodge@uh.edu Department of Engineering Technology J. Collin Gallagher Jcgallagher@uh.edu Department of Engineering Technology Sevin Phu sphu@uh.edu Department of Engineering Technology Bahvit Mehta Teaching Assistant bmmehta@mail.uh.edu Department of Electrical Engineering Farrokh Attarzadeh Project Advisor FAttarzadeh@uh.edu Department of Engineering Technology ABSTRACT Soils with high clay content can have varying moisture content along the foundation, creating a condition where the soil contracts on one side of the foundation while expanding on others. This condition can cause cracking or expulsion of the foundation due to the tilting created [1]. Maintaining even moisture content around the foundation provides a level surface for the foundation to rest upon thereby preventing cracks or expulsion due to tilting [2]. The Automated Clay Conditioning System for Foundations (ACCF) is the proposed solution to foundation damage due to tilting caused by expansive soils such as clay, using sensors to monitor soil moisture around the foundation and solenoid valves to isolate the watering zones. This project was completed as a senior project capstone course in 2006 and was awarded a provisional patent in 2008.

INTRODUCTION The clay conditioning systems for foundations that are in existence today are timer based. These systems waste water and can cause damage due to the excessive watering that can cause dramatic shifts in the slab. A timer based system needs to be manually turned off in case of rain, to save the foundation from being damaged. The cost of foundation repair is exponentially more expensive when compared to the cost of an automatic foundation watering system. ACCF employs moisture sensors which detect the moisture level for each section of the soil underneath the foundation of a building. The areas with a lower concentration of moisture will get watered more and vice versa. The system will be turned off automatically during rainy season when the moisture levels increase beyond a certain point. The prototype of the ACCF is shown in Figure 1. Figure 1. ACCF Prototype The block diagram of the system is shown in Figure 2. Only two watering areas have been used to implement the prototype but the system can be extended to any number of watering zones as per the size of the foundation and structure. The system will detect the level of moisture in each zone the ACCF is responsible for and compares these readings against one another. Based on this data, ACCF will determine the necessary watering time to bring the moisture levels in line with each other. Incorporation of moisture sensors and independent watering zones in the ACCF allows for control of shrinking and swelling of each area around a structure. Moisture is maintained evenly on all sides of the foundation creating a situation that while the foundation is still rising and falling with

Figure 2. ACCF System Block Diagram the soil it is doing so without tilting thereby relieving stresses on the structure. This relief of stress on the foundation prevents cracking and even possible expulsion from the ground. DESIGN DESCRIPTION The ACCF can maintain even moisture content throughout the clay soils surrounding a structure using sensors to monitor soil moisture around the foundation and solenoid valves to isolate the watering zones. A schematic diagram of the system is shown in Figure 3. A splitter pipe is attached to the water source outside the building to create the desired amount of watering zones. Solenoid valves control each outlet allowing for independent watering cycles. Hoses are attached to each solenoid and are run to each independent watering zone. Perforations in the hose begin as the hose reaches its specified zone, and water pressure is maintained by activating each solenoid individually. Figure 4 shows the Solenoid Valves and the Splitter in the prototype. The central control of the ACCF is the

Piping Solenoid Valve Splitter Solenoid Valve Figure 3. Test Module Figure 4. Solenoid Valves and the Splitter in the Actual ACCF 8051 microcontroller with peripheral boards supplying relays to control the solenoid valves and Analog-to-Digital Converters (ADCs) to interpret the sensor readings. All solenoid valves are powered by one 24V AC transformer that runs through the relays. A 5V pulse sent from the microcontroller is used to activate the relays individually. The microcontroller controls the watering time through moisture data sent back from each sensor. The data received from the sensors is compared to determine variance of moisture throughout the zones. A default watering time, which can be specified by the user, is incremented or decremented by a specified amount for each zone due to variance

to bring moisture levels into equilibrium. In order to reach equilibrium as fast as possible if moisture content fluctuates outside the minimum or maximum range which can be set by the user, then the dry zones will be watered alone for the default time before the system continues with normal watering cycles. After soil moisture reaches equilibrium the system continues to monitor the soil while reverting to the specified default watering time for each zone unless future variance is detected. A Non-Disclosure Agreement with Irrometer Co., Inc. [3], the manufacturer of the moisture sensor, prevents additional details about the sensor from being disclosed. It suffices to say that a 5V pulse with less than 50 na current sent from the microcontroller across the sensor for no longer than 50 ms is read back into the ADC. The value of this voltage data is higher if the soil is wet. The sensors then need to be grounded for at least thirty seconds to discharge any current after being read. In a full-scale system the grounding would last longer so damage to the sensor would be prevented. HARDWARE DESCRIPTION The Automated Clay Conditioning System for Foundations (ACCF) consists of several main components. The BiPOM 8051 microcontroller and two peripheral boards, two solenoid water valves with flow control [4-6], two Watermark soil moisture sensors [3], and a controller enclosure box with accompanying LED s for user interface [7]. The BiPOM microcontroller and associate peripheral boards are packaged in a plastic box for safety and modularity purposes. On the exterior face of the box is a three LED user interface. The red LED signifies standby and the two yellow LED signify the system is watering the associated zones. Products from BiPOM BiPOM 8051 Microcontroller Board The schematic diagram for the BiPOM 8051 microcontroller board is shown in Figure 5 and is considered to be the brain of the entire system. It turns on the sensors, acquires the data, and then determines watering times from said data. The microcontroller is accompanied by two peripheral boards, also made by BiPOM, each connected through the integrated expansion bus.

Figure 5. BiPOM Microcontroller Board Training Board 1 (TB1) The TB1 board, shown in Figure 6, was selected primarily for the Analog-to-Digital Converter for sensor voltage interpretation and the associated analog inputs. Figure 6. TB1 Board Relay-4 Reed Board The purpose of the Relay-4 Reed board (Figure 7) is to allow the microcontroller to control the AC voltage required by the solenoid valves through its 5V DC output pins. A 5V DC pulse sent from the microcontroller is used to activate each of the 4 relays individually. Two of the board s relays are each dedicated to the control of the solenoid valves, while the remaining two are used for activating and grounding the soil moisture sensors.

Figure 7. Relay-4 Reed Board Layout Solenoid Valves Solenoid Water Valves (Direct Lift) The purpose of these valves (Figure 8) is to supply water flow to the various zones of the foundation. The solenoid valves are powered by a 24 VAC, 650 ma signal fed through and controlled by relays on the Reed-4Relay peripheral board. Figure 8. Solenoid Connection Schematic The valves are connected via a splitter to either a typical outdoor faucet through the use of an adapter, or may be tied directly into the water main of the building, much the same as a sprinkler system would. PVC tubing is connected to each of the valves and is run underground to the corresponding side of the house where water emitters distribute the water along its zone. The water emitters consist of length of PVC pipe with 3/16 inch holes drilled along their length.

Soil Moisture Sensors Watermark Soil Moisture Sensors The two soil moisture sensors (Figure 9) from Watermark [3] were selected due to their inexpensive nature, fast response time and ease of interface. The Watermark Soil Moisture Sensor (granular matrix sensor) is an indirect, calibrated method of measuring Figure 9. Watermark Soil Moisture Sensor soil water. It is an electrical resistance type sensor, consisting of two electrodes surrounded with a permeable barrier. The sensors are read by applying a pulse with duration between 1 to 50ms with a potential of 5 to 20V DC and no greater than 50nA of current. The sensor connects to the ADC on TB-1 peripheral board sending between 0 V and 2.5 V correlating between dry and wet. A Non-Disclosure agreement with the manufacturer prohibits further detailed explanation of the sensor interface.

SOFTWARE DESCRIPTION The software flowchart is as shown in Figure 10. It describes in detail, how the data from the moisture sensors is taken into the 8051 controller, averaged, compared & depending Start Get Data Get Data SENSOR 1 SENSOR 2 Average Data Average Average Data Average Database Compare Average Database Difference Total Avg Emergency Turn on or off Modifying default watering time Difference Turn On Servo 1 Turn On Servo 2 Start timer 2 Start timer 1 Soaker System 1 Turn off system 1 Soaker System 2 Wait till next check Turn off system 2 Time Check Time Check Figure 10. Software Flowchart for Moisture Regulation on the value of the result, the respective servo motors are turned on or turned off [8-9].

CONCLUSION The prototype of ACCF using two watering zones performed successfully during the project demonstration. Certain precautions were required both in hardware as well as the software in order to ensure no damage occurred to the sensors. Initial troubles with plumbing were resolved through re-plumbing with added attention to complete seals. Potential follow-on projects which could be on the project are, further investigation into water emitter systems. Many products are out in the market for drip irrigation systems. Using such a system in place of the PVC pipe with holes would allow for more precise control of water flow and pressure regulation. Several models are available which allow for variable flow rates in addition to self cleaning features. Other potential follow-on projects could include a data logger system to allow users the ability to download and track moisture trends of the soil. REFERENCES [1] "Maintenance and Monitoring Program," Mr. Foundation, http://www.foundationrepairs.com/foundation_watering.htm?src=, [Accessed July 15, 2008] [2] "Foundations and Water," Advanced Foundation Repairs, http://www.foundationrepairs.com/foundation_watering.htm?src=, see the FAQ section, [Accessed July 15, 2008] [3] http://www.specmeters.com/soil_moisture/watermark_soil_moisture_sensors_and_met er.html [Accessed July 15, 2008] [4] http://www.bipom.com/documents/boards/minimax51c2.pdf [Accessed July 15, 2008] [5] http://www.bipom.com/documents/peripherals/tb1.pdf [Accessed July 15, 2008] [6] http://www.bipom.com/documents/peripherals/relay4.pdf [Accessed July 15, 2008] [7] Scott MacKenzie, and Raphael Chung-Wei Phan, "The 8051 Microcontroller," 4 th. Edition, Prentice-Hall, 2006. [8] Thomas W. Schultz, "C And The 8051," 3 rd. Edition, Pagefree Publishing, 2004. [9] Michael J Pont, "Embedded C," Addison-Wesley Professional, 2002