LEAK DETECTION ALARM SYSTEM GUIDELINES FOR TOXIC HAZARDOUS/MATERIALS STORAGE



Similar documents
Aboveground Indoor Tank Design Guidelines

Suffolk County Department of Health Services. Division of Environmental Quality

TOXIC/HAZARDOUS MATERIAL DOUBLE-WALLED UNDERGROUND TANK DESIGN GUIDELINES

SUFFOLK COUNTY DEPARTMENT OF HEALTH SERVICES TOXIC/HAZARDOUS MATERIAL TRANSFER FACILITY DESIGN GUIDELINES

~~~~ Brian L. Harper, M.D., M.P.H. Commissioner of Health. Vito Minei, P.E. Director of Environmental Quality

Pollution Prevention And Best Management Practices For Dry Cleaners Operating In Broward County

Spill Control Prevention Plan (SCPP)

New York State Department of Environmental Conservation 625 Broadway, Albany, NY Environmental Self Audit For Small Businesses

DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY. August 2012

Managing Floor Drains and Flammable Traps

MAINE DEPARTMENT OF ENVIRONMENTAL PROTECTION

SILICON VALLEY CLEAN WATER. May 2015

Petroleum Tanks at Municipal Facilities

Regulations and Recommended Practices. Introduction. American Petroleum Institute Recommended Practices 2350

The following definitions apply with regard to requirements specified in this document:

RULE DRY CLEANERS USING SOLVENT OTHER THAN PERCHLOROETHYLENE

Spill Prevention, Control and Countermeasure (SPCC) Rule

ENGINEERED DRAWINGS FOR PETROLEUM STORAGE TANKS

NDEP Bureau of Corrective Actions Secondary Containment Regulations Guidance Document April 7, 2010 (Revision)

Hazardous Waste Accumulation, Storage, & Labeling

The following definitions apply with regard to requirements specified in this document:

Industrial Strength Leak Detection

Improper storage of fuel on construction sites will increase the risk of water pollution that may occur as a result of leaks or spills.

CHAPTER PETROLEUM CONTACT WATER

Farm Fuel Tank Safety Guide

Waste Oil Collection / Storage

ACTIVITY NAME. Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas

Hazardous Waste Determination and Management Plan

This page left intentionally blank

5/3/2010. Article 500 address the requirements for hazardous locations: Wiring Equipment

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

OIL STORAGE REQUIREMENTS OF THE SPCC REGULATIONS. Christopher J. Ecsedy, P.E. Fuss & O'Neill, Inc. 146 Hartford Road Manchester, CT 06040

1. TANK OWNER INFORMATION TANK OWNER FIRST NAME LOCATION OF RECORDS:

PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT

Secondary Containment: Regulations & BMPs. Beth Powell Vice-President and General Manager New Pig Energy bethp@newpigenergy.com

UDOT SPILL PREVENTION and RESPONSE PLAN for CONSTRUCTION SITES

Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual

Alabama Air and Waste Regulatory Update

Here are some hazardous wastes commonly generated by the marina industry:

Underground Storage Tanks

PROCESS AUTOMATION. ALARM SYSTEMS FOR SEPARATORs PRODUCT OVERVIEW

GUIDANCE FOR DEVELOPMENT OF SPILL AND SLUG PREVENTION CONTROL PLANS AND FACILITIES FOR THE CITY OF ATTLEBORO SEWER USERS

Natural Resources Conservation Authority Guidelines for Secondary Containment of Hazardous Liquids stored Above-ground

Compliance Guidance for Motor Vehicle Waste Disposal Wells in Oregon September 2015

Contact Person Sarah Morris-Benavides Revision 1.1 Document Plan Effective Date 07/01/2014 Review Date 03/15/2017.

The Federal Spill Prevention, Control & Countermeasures (SPCC) Rule Overview

The Federal Spill Prevention, Control & Countermeasures (SPCC) Rule Overview

Hazardous Waste Management Procedures

SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN

Maryland Containment System Testing Protocol. The individual performing the inspection and testing as outlined in this protocol must be either:

SOP 4: Spill Response and Cleanup Procedures SOP 4: SPILL RESPONSE AND CLEANUP PROCEDURES

Brochure Designed by

Electrical Classification

A Guide to Hazardous Substance Storage Capacity

Hazardous Waste Compliance Awareness For Faculty and Staff

Steel Tank Institute AST Inspections. Dana Schmidt, PE STI/SPFA

2-Party Shared Well Users Agreement (If Applicable)

September 2008 AFC (2) Page 1 of 5. Maximum Size and Aggregate Capacities of Aboveground Storage Tank Systems at Fuel Dispensing Stations

Inspections Standard Operating Procedure 5 Aboveground Storage Tanks

UPDATE ON MAINE'S UNDERGROUND TANK LAWS

SECTION 807 PUMP STATION REHABILITATION

The Fuel Storage Tank Regulations 2009

THE CORPORATION OF THE CITY OF COURTENAY BYLAW NO A bylaw to amend Storm Sewer Bylaw No. 1402, 1986

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

HERNANDO COUNTY FIRE ALARM GUIDELINES

Outdoor Storage of Raw Materials SC-33

PLAN REVIEW GUIDE FOR FIRE ALARM

DRAFT REVISED Musts For USTs DRAFT. Printed on Recycled Paper. Updated June 2015

Welcome UST Owners & Operators!!

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

ABC CIRCUITS 10 Circuit Drive Circuit Town, IN SLUG CONTROL PLAN

Morrison Bros. Co. General Product Specifications

DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY

Civil Engineering Sector Labour-Management Health and Safety Committee

FLORIDA HAZARDOUS WASTE MANAGEMENT REGULATIONS THAT DIFFER FROM FEDERAL REQUIREMENTS

Tanks: What's in store?

Fire Pump Plan Review March 2010

Laboratory Hazardous Waste Disposal Guidelines

Kurt Wilson Louisiana Dept. of Environmental Quality Business & Community Outreach Division Small Business/Small Community Assistance Program

A Code Review for Emergency Generators and Indoor Use of Portable Generators

Florida Department of Environmental Protection

UltraTech International, Inc. Canadian Secondary Containment Requirements

Used Oil Guidance. Tank and Secondary Containment Requirements For Used Oil Processors

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS DEPARTMENT OF ENVIRONMENTAL MANAGEMENT OFFICE OF COMPLIANCE & INSPECTION

SPILL PREVENTION, CONTROL, AND COUNTER MEASURES PLAN (SPCC)

AUTOMATIC TANK GAUGING SYSTEMS Achieving Compliance. John D. Sieger, Tanknology

POLLUTION PREVENTION FACT SHEET: AUTOMOBILE MAINTENANCE

ON-SITE WASTEWATER TREATMENT SYSTEMS ACT

Septic Tank Use & Maintenance Tips

APPENDIX G Materials Storage and Handling Guidelines

Aboveground Storage Tank Rules

Citgo Service Station (Former Gulf Oil/Chevron) Jarrettsville Pike Baltimore County Jacksonville, Maryland Open Case No.

General Fire Code Requirements Within Commercial Tenant Spaces

Hazardous Materials Storage Tanks Management. Procedure Date of Issue: Table of Contents. UBC.EMS Advisory Committee.ENV.Procedure.

IAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1

Safety Manual Title: Spill Prevention & Response Review Date: 6/1/2014

PLAN APPLICATION HAZARDOUS MATERIALS USE AND SPILL PREVENTION CONTROL (HMPC) PLAN

City of Bettendorf Fire Alarm System Requirements

Good Housekeeping Practices for DPW/Fleet Maintenance Facilities

Petroleum Storage Tank Compliance 101

Transcription:

Suffolk County Department of Health Services Division of Environmental Quality LEAK DETECTION ALARM SYSTEM GUIDELINES FOR TOXIC HAZARDOUS/MATERIALS STORAGE ~~~~ Mary E. Hibberd, M.D., M.P.H. Suffolk County Commissioner of Health Services Joseph H. Baier, P.E. Director of Environmental Quality SEAL

Suffolk County Department of Health Services Leak Detection Alarm System Guidelines For Toxic/Hazardous Materials Storage ~~~~ 1.0 General 1.1 Article 12 of the Suffolk County Sanitary Code requires that toxic/hazardous materials storage facilities be equipped with a positive means of detecting leakage. This system must detect leakage from the tank, piping, or as a result of spill during material transfer. The detection system must include, but is not limited to, both audible and visual alarms. 1.2 Exemptions - storage facilities which meet the following criteria shall be exempt from the provisions of this guideline:! storage facilities located on a residential parcel with total on-site capacity less than 1,100 gallons, storing #2, #4 or #6 fuel oil, diesel oil or kerosene used solely for on-site hearing or intermittent power production.! aboveground tanks with a containment area approved by the commissioner where any leakage would be clearly visible to the owner/operator or! aboveground piping whose containment system drains to an aboveground containment structure, approved by the commissioner, where any leakage would be clearly visible to the owner/operator or 1.3 Retrofit of existing single-walled, noncorrodible tanks, must include a tank leak detection system utilizing either monitoring wells or U-tube(s) as specified by the Standards for the Administration of Article 12, Single Walled Underground Tank Design Standards, or other system acceptable to the commissioner. 1.4 Replacement of existing single-walled underground piping, with double-walled piping and leak detection, must conform with the time frame set forth by Article 12. 1.5 Submittals must include manufacturer and model number of the proposed alarm systems and must be approved by the commissioner. 2.0 Definitions 2.1 Aboveground - when referring to tanks, means more than 90 percent exposed above the final ground or finished floor elevation.

2.2 Commissioner - Commissioner of Suffolk County Department of Health Services. 2.3 Double-walled - constructed with more than one containment layer with space between the layers sufficient to allow monitoring of any leakage into or out of the space. 2.4 Residential Parcel - a single body of land or single building plot zoned for single-family residential use. 2.5 Single-walled - constructed with walls made of but one thickness of material. Laminated, coated or clad materials shall be considered as single-walled. 2.6 Storage Facility - tanks, pipes, vaults, buildings, yards, pavements, or fixed containers used, or designed to be used, either singly or in any combination thereof, for the storage and/or transmission of toxic/hazardous materials. 2.7 Toxic or Hazardous Materials - any substance, solution or mixture which, because of its quality, quantity, concentration, physical, chemical or infectious characteristics, or any combination of the foregoing, presents, or may present, an actual or potential hazard to human health, or to the drinking water supply, if such substance, solution, mixture or combination thereof is discharged to the land or waters of the County of Suffolk. Toxic or hazardous materials shall include: a. each and every substance, material, waste found listed in either or both Part 116 and Part 261, Title 40 of the Codes of Federal Regulations; or Title 6, Part 371 of the New York State Codes, Rules and Regulations. b. acid and alkalies beyond the ph range of 4 to 10. c. heavy metal sludges, mixtures and solutions in excess of the allowable concentrations listed in Title 6, Part 703.6 of the New York State Codes, Rules and Regulations. d. petroleum products, including fuels and waste oils. e. organic solvents, including petroleum solvents, halogenated and nonhalogenated hydrocarbons. f. any material listed in Schedule I, Part 703.6 of the Official Compilation of New York Codes, Rules and Regulations, in excess of the concentration standards thereof, except of iron, manganese, foaming agents and ph, unless otherwise provided in Article 12 of the Suffolk County Sanitary Code. g. any substance not included within subdivisions a through f above, subsequently declared to be a toxic or hazardous material by the commissioner. Page #2

h. any solid or semi-solid material which, if left to stand, or if exposed to water, will leach out, or wholly or partially dissolve, forming a toxic or hazardous material as defined in subdivisions a through g above. 2.8 Underground - when referring to tanks, means 10 percent or more below the final ground or finished floor elevation. 3.0 Components 3.1 The leak alarm system shall consist of, but not be limited to, a sensing unit and alarm panel. 3.2 Sensing unit. 3.2.1. The sensing probe may be of any type, i.e., mechanical, float, optical, ultrasonic, capacitance, or conductance, which is compatible with the material being stored, and is easily testable. 3.2.2 The sensing unit may operate on the principal of either liquid, vapor, positive pressure or loss of vacuum sensing. 3.2.3 The sensing unit must be capable of differentiating water from the material store or conveyed, except for positive pressure and vacuum systems which monitor both walls of a double-walled storage facility. 3.3 Alarm Panel 3.3.1 The alarm panel must be equipped with both audible and visual warning devices. 3.3.2 The audible element must be a horn or bell which can be heard by the storage facility operator, or 3.3.3 The visual element must be a steady burning light which is visible to the storage facility operator or 3.3.4 The alarm panel must visually annunciate each sensing unit separately, i.e., an individual set of lights for each sensing unit. 3.3.5 The alarm panel must be equipped with a manual reset button which will silence the audible alarm after annunciation. The visual alarm must remain on until the alarm condition is properly addressed. Subsequent alarm conditions must activate both the audible and visual alarms. 3.3.6 The alarm panel must be equipped with a self-checking system capable of monitoring the circuitry, as well as the working condition of the audible/visual alarms and the sensing unit. This selfchecking feature may be either an automatic or manual operation. Should malfunction be detected by this check system, the alarm panel must clearly indicate the failure. 3.3.7 The alarm panel must be located where it will be seen and heard by the storage facility operator, or Page #3

3.3.8 The alarm panel must have differentiating lights to distinguish water from the material being stored or conveyed. 4.0 Electrical 4.1 All electrical wiring and components must conform to all applicable building and electrical codes. 4.2 All wiring must be run within conduit. 4.3 Electrical enclosures mounted at the tank must be explosion proof where dictated by the tank contents. 4.4 Outdoor electrical enclosures must be weather proof. 4.5 Power on/off switches on the sensing unit, alarm panel, or any other component of the leak detection system is prohibited. 4.6 All components must be hardwired; plug-in type cords are not acceptable. effective: 2/15/87 amended: 05/89 amended: 11/95 Page #4