CITY OF LOS ANGELES CALIFORNIA



Similar documents
Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

Installation Guide Content for P250xV-240 microinverters

How To Plan Out An Array Of Solar Panels

AC Module Installation Guide Content

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

Doe Residence kw DC Roof Mounted Photovoltaic System

PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS

County of Riverside Building and Safety Department

Advantium 2 Plus Alarm

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

DC disconnects for solar photovoltaic installations. Connecting the. power of the sun

AC Module Installation Guide Content

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

City of Riverside Building & Safety Division Phone: (951)

D. Permits: A building permit is required for the structural support of all solar energy device installations.

Expedited Permit Process for PV Systems AC Module

Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations

Solar Photovoltaic (PV) Systems

RAY-MAX Integrated Solar Power Strip

Safety and Installation Instructions for AC Modules

Solar Panel Installations

Co-location Interconnect Power Panel (CIPP) Installation Guide

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

PV System Disconnect PV System Discon-

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

CHAPTER 2 EXAMPLES AND TABLES

Top Commercial / Residential Electrical Requirements *

Submittal Requirements for Solar Photovoltaic Installations 10 kw or Less in One and Two Family (Duplex) Dwellings

GUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS

Model Number Electrical Compatibility Module Connector Type. M LL-S22 60 cell PV module MC-4 Type 2 Locking

HM-W536 Install Guide

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance/Non-Service Entrance

Installation and Operation Guide for PD4000 Series Power Control Center

Chapter 9. Bonding and Grounding

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

VLT Series 300 Watt True Sine Wave Inverter

Ontario Electrical Safety Code 25 th Edition/ 2012

Solid State Timers Type F

City of San Diego Residential Photovoltaic Systems Inspection Guidelines

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

User Manual. Replus-250 Replus-250A Replus-250B. U.S.A Add: 301 Howard St, Suite 850, San Francisco, CA T:

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

ELECTRICAL INSPECTION BULLETIN (Effective )

NEC 2014 Code Changes

Photovoltaic System Grounding

Electrical Code Regulation

Capacitive Prox E2K-X

Operating Instructions. UL325 Compliant Non-monitored

How To Test A Power Distribution Unit

2 WAY (2/2) AND 3 WAY (3/2) BRASS AND STAINLESS STEEL SOLENOID VALVES

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures) Installation and User s Guide

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes

Enphase M215 Microinverter

AC Unison Installation Guide

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Electric Vehicle Charging Station Products EVoReel Charge Cable Management Solutions

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

TOP 10 CHANGES 2013 CALIFORNIA ELECTRICAL CODE 2013 CALIFORNIA ENERGY CODE (ELECTRICAL)

STREETLIGHT SYSTEM GROUNDING AND BONDING

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C

Specification Requirements DBL 700MX and 1000MX Series UPS

PLUGS & RECEPTACLES. INNOVATIVE EXPLOSION PROTECTION by R. STAHL

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

YINGLI SOLAR PV MODULES Installation and User Manual

Owner's Manual. Automatic Transfer Switch. This manual should remain with the unit.

MCR1900 Media Converter 19-Slot Chassis

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

ELECTRICAL SAFETY Information Bulletin

Title: Grounding and Bonding Rev-01

TC Grounding and Bonding for Telecommunications Systems

YINGLI SOLAR PV MODULES Installation and User Manual

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10

GUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS

Generator DoCKInG StatIonS

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

BUILDING CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION Based on the 2014 LACBC

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

RELOCATION OF BUILDINGS

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Installation Guide of Sunrise Solartech PV Modules. Term Contents. Purpose of this guide. General. Safety precaution for installing a solar

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

Transcription:

BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI MAYOR DEPARTMENT OF BUILDING AND SAFETY 201 NORTH FIGUEROA STREET LOS ANGELES, CA 90012 RAYMOND S. CHAN, C.E., S.E. GENERAL MANAGER FRANK BUSH Executive Officer ------- Power-One, Inc. 3201 E. Harbour Dr. Phoenix, AZ 85034 Attn: Robert White RESEARCH REPORT NO.: 930512 Approval Date: March 27, 2015 Expires: March 27, 2016 GENERAL APPROVAL - - Models MICRO-0.3-I-OUTD-US-208/240 and MICRO-0.25-I-OUTD-US-208/240 - Manufactured by Power-One, Inc. (Aurora) installed as part of the Photovoltaic (PV) system on a single family dwelling (SFD). CONDITIONS OF APPROVAL The installation of the above s are approved when the following conditions are met: 1. Only the following model designations are approved under this research report: Model Number Power Input DC Voltage Input DC Current Output 1Ph, 60HZ, 0.95pf MICRO-0.3-I-OUTD-US-208/240 300 W Nominal: 40 VDC Maximum: 65 VDC Full Power: 30-50 VDC MICRO-0.25-I-OUTD-US-208/240 250 W Nominal: 40 VDC Maximum: 65 VDC Full Power: 30-50 VDC 10.5 Amp 208 VAC, 1.44 Amp 240 VAC, 1.25 Amp 10.5 Amp 208 VAC, 1.2 Amp 240 VAC, 1.04 Amp 2. The Micro-inverters shall be plainly and permanently marked on a contrasting background where readily visible with the following: a. Manufacturer s Name, b. Model designation, c. Serial Number, d. Complete input and output direct current (DC) and alternating current (AC) in Volt, Amperes/Watts electrical ratings, e. Maximum branch circuit protection: 20A f. Maximum and minimum operating ambient temperatures, g. Current CSA listing information. 3. If the listing of this, under CSA File Number 173688 is no longer, the approval of this Research Report may be suspended or cancelled subject to Electrical Test Lab s evaluation. Page 1 of 5 LADBS G-5 (Rev.06/30/2013) AN EQUAL EMPLOYMENT OPPORTUNITY - AFFIRMATIVE ACTION EMPLOYER

4. Upon installation, the following marking shall be permanently printed on a weather proof tag and placed on each end of PV circuit run(s): The installation of this shall comply with City of Los Angeles Research Report (RR) number 930512. Not valid if the RR is expired. For a copy of RR visit www.ladbs.org or call 323-224-2168. 5. Micro-inverters shall be supplied from a dedicated 20 Ampere AC branch circuit without GFCI or AFCI protection 6. The Micro-inverters shall be installed and maintained by Qualified Person as defined in the Los Angeles Electrical Code and in strict compliance with manufacturer s instructions. 7. The maximum number of Micro-inverters in a 20 Amp circuits shall not exceed the following: Model Number Power Voltage Single Phase Max Number of Micro-inverters Max Length of Circuits (feet) MICRO-0.3-I-OUTD-US-208/240 300 W 208 VAC 11 90 MICRO-0.3-I-OUTD-US-208/240 300 W 240 VAC 12 96 MICRO-0.25-I-OUTD-US-208/240 250 W 208 VAC 13 103 MICRO-0.25-I-OUTD-US-208/240 250 W 240 VAC 15 116 Refer to manufacturer s installation instructions. 8. The Micro-inverter shall be provided with a DC grounding electrode fitting for the DC grounding electrode conductor (GEC). 9. The DC grounding electrode fitting shall be of approved stainless steel 300 series material, consisting of a clamp, No.10 machine screw, self clinching nut screw and ground washer. When assembled, the ground screw shall be torqued to 45 in-lb in accordance with the manufacturer s installation instructions. 10. Only No. 6 AWG or No. 8 AWG solid bare copper (CU) wire shall be used as the DC GEC under the DC grounding electrode terminal. This bare CU wire shall be installed in accordance with provisions of section 250.64 of the 2011 Los Angeles Electrical Code. 11. All interconnecting cable system associated with this Micro-inverter shall be listed by a Recognized Testing Agency. 12. The hardware used to mount the Micro-inverter to the racking system shall be of a corrosion resistant type. 13. The power source to the engage cable shall be de-energize prior to servicing. Page 2 of 5

14. The maximum available symmetrical line to ground fault current at the Micro-inverter shall not exceed 5,000 amperes. 15. To limit the maximum ground fault current, the minimum number of Micro-inverters in a circuit shall not be less than 4. 16. For installations in a single family dwelling in the City of Los Angeles, The minimum distance between the service equipment to the first Micro-inverter in a circuit shall comply to the following: Single Family Dwelling, Size of Service Available Fault Current At the Service Size of Circuit Between Service & Micro-inverter Minimum Distance From Service to Closest Micro-inverter 100A to 225A 10,000 Amp #12 AWG 10 Feet 100A to 225A 10,000 Amp #10 AWG 15 Feet 226A to 400A 22,000 Amp #12 AWG 15 Feet 226A to 400A 22,000 Amp #10 AWG 20 Feet 17. Only the following UL Listed AC, Engage Cable shall be used with this Micro-inverter: a. Type TC-ER, b. THWN-2, c. 4C, d. 10AWG, e. 90EC - Dry or Wet, f. 600V, g. SUN RES, h. OIL RES I / OIL RES II. 18. The PV racking system shall be provided with grounding means (ie. ground lug) for termination of the equipment grounding conductor that is independent form the Micro-inverter. The WEEB connector shall not be relied upon as an approved equipment bonding jumper or EGC. 19. The inverter s mounting screws shall not be used as a bonding jumper or as a part of the equipment grounding path between the Micro-inverter and the PV racking system. 20. The AC cable connector shall be of polarized nonstandard configuration, locking type with a grounding member, where all live parts are guarded against inadvertent contact by a person. The connector shall be rated for interrupting normal current without hazard to the operator. The grounding member shall be the first to make and the last to break contact with the mating connector. 21. The installation of the Micro-inverter shall comply with applicable provisions of the Los Angeles City Electrical Codes (Building, Electrical, and Fire Codes). Page 3 of 5

22. Except as permitted under this research report, the installed Micro-inverters and the engage cables, when replaced, shall be of the identical original manufacturer s part that was approved by the Los Angeles City Electrical Testing Laboratory. 23. The manufacturer shall supply either hard copies of, or downloadable web links for Installation Instructions, Operation Manual, Quick Install Guide and a copy of this approval letter to the installer. 24. The Micro-inverter shall be installed according to the provisions of this approval and the manufacturer s installation instructions. When the manufacturer installation instructions conflict with this approval letter, the conditions specified in this approval letter shall prevail. 25. The installation of this Micro-inverter is not approved for Hazardous (Classified) locations as defined in 2014 Los Angeles Electrical Code. 26. This Micro-inverter is only evaluated for fire, shock and personal hazard. Its performance or efficiency has not been investigated. 27. If a Micro-inverter is no longer in service, it shall be disconnected and removed in accordance with the manufacturer s installation instructions. 28. An electrical permit shall be obtained prior to installation or relocation of a photovoltaic system in the City of Los Angeles. DISCUSSION The products covered under this Research Report are grounded, non-linear, 208 or 240 volts, single phase, utility-interactive, s, Models MICRO-0.3-I-OUTD-US-208/240 and MICRO- 0.25-I-OUTD-US-208/240, Manufactured by Power-One, Inc. (Aurora) for use with Photovoltaic (PV) modules not exceeding 65 VDC output. This Micro-inverter is intended to connect to a single PV module using individual single pin connectors. The inverter s positive DC line is connected to its metal enclosure through the built in ground fault circuit detection and interrupter and the grounding electrode termination fitting. The AC neutral is not bonded to the DC grounded positive conductor or the inverter metal enclosure. The inverter metal inclosure is connected to the AC ground through the approved cable connector and the equipment grounding conductor within the AC cable. The PV modules, racking system, and associated hardware are not part of this approval. The Power-One Micro-inverter consists of a NEMA 4X aluminum corrosion resistant metal enclosure, built-in DC ground fault circuit detector and interrupter, a positive and negative DC cable and connectors, an AC cable and connector, and a stainless steel DC grounding electrode conductor fitting. Page 4 of 5

When this system is installed in accordance with the provisions of this General Approval, it should meet the minimum safety standards of the Los Angeles City Electrical Code. For this General Approval to be valid on any installation in the City of Los Angeles, an engineer or inspector of the Department of Building and Safety must make a determination that all conditions of the General Approval required to provide equivalency have been met. This General Approval is in accordance with Section 93.0303 of the Electrical Code pertaining to "New Materials and Methods of Construction" and does not waive the requirements of the City of Los Angeles Building Code. This General Approval is neither a product endorsement nor a certification of accuracy or function of the approved item. Power-One Micro-inverter APPROVED BY: Behrooz Hooriani, P.E. Electrical Engineer Electrical Testing Laboratory 2319 Dorris Place Los Angeles, CA 90031 (323) 224-2168 Tel (323) 224-2161 Fax www.ladbs.org Page 5 of 5 LADBS G-5 (Rev. 7/06) AN EQUAL EMPLOYMENT OPPORTUNITY - AFFIRMATIVE ACTION EMPLOYER