Small PV Systems Performance Evaluation at NREL's Outdoor Test Facility Using the PVUSA Power Rating Method



Similar documents
Regional Field Verification Operational Results from Four Small Wind Turbines in the Pacific Northwest

Optical Blade Position Tracking System Test

A New Empirical Relationship between Thrust Coefficient and Induction Factor for the Turbulent Windmill State

Elastomer Compatibility Testing of Renewable Diesel Fuels

Computer Simulations of Edge Effects in a Small-Area Mesa N-P Junction Diode

Rate Analysis of Two Photovoltaic Systems in San Diego

Method to Calculate Uncertainties in Measuring Shortwave Solar Irradiance Using Thermopile and Semiconductor Solar Radiometers

Wind Energy and Production of Hydrogen and Electricity Opportunities for Renewable Hydrogen

Early Fuel Cell Market Deployments: ARRA and Combined (IAA, DLA, ARRA)

Comparison of Photovoltaic Models in the System Advisor Model

Using HOMER Software, NREL s Micropower Optimization Model, to Explore the Role of Gen-sets in Small Solar Power Systems

Wind Forecasting stlljectives for Utility Schedule and Energy Traders

Application Note: String sizing Conext CL Series

WET BULB GLOBE TEMPERATURE MEASUREMENT AT THE Y-12 NATIONAL SECURITY COMPLEX

Financing Projects That Use Clean-Energy Technologies: An Overview of Barriers and Opportunities

Monitoring System Performance

Measurement of BET Surface Area on Silica Nanosprings

System Advisor Model, SAM : General Description

Energy Systems Integration

Second Line of Defense Virtual Private Network Guidance for Deployed and New CAS Systems

Solar Energy Feasibility Study

Collaboration on Renewable Energy Standards, Testing, and Certification under the U.S. China Renewable Energy Partnership

Technology Advantage

Corona Department of Water & Power (DWP) Solar Partnership Program Guidelines and Application

Amorphous Transparent Conducting Oxides (TCOs) Deposited at T 100 C

NREL Job Task Analysis: Crew Leader

Solar America Board for Codes and Standards

Dynamic Vulnerability Assessment

Auburn University s Solar Photovoltaic Array Tilt Angle and Tracking Performance Experiment

Weather-Corrected Performance Ratio

Procedure for Measuring and Reporting the Performance of Photovoltaic Systems in Buildings

DARK CURRENT-VOLTAGE MEASUREMENTS ON PHOTOVOLTAIC MODULES AS A DIAGNOSTIC OR MANUFACTURING TOOL

Laser Safety Audit and Inventory System Database

Solar Energy Systems. Matt Aldeman Senior Energy Analyst Center for Renewable Energy Illinois State University

Solar Power at Vernier Software & Technology

Validation of Multiple Tools for Flat Plate Photovoltaic Modeling Against Measured Data

Grid Interconnection and Performance Testing Procedures for Vehicle-To-Grid (V2G) Power Electronics

Penetration Testing of Industrial Control Systems

Potential of Photovoltaics (PV) and CPV/CSP in Cyprus. University of Cyprus. Photovoltaic Technology, University of Cyprus

EFFICIENT EAST-WEST ORIENTATED PV SYSTEMS WITH ONE MPP TRACKER

Automated Transportation Management System

How To Use The Csi Ebpp Calculator

Overview of BNL s Solar Energy Research Plans. March 2011

Electrical Collection and Transmission Systems for Offshore Wind Power

Design of Grid Connect PV systems. Palau Workshop 8 th -12 th April

Irradiance. Solar Fundamentals Solar power investment decision making

Photovoltaic Systems II EE 446/646

IDC Reengineering Phase 2 & 3 US Industry Standard Cost Estimate Summary

Analysis of Photovoltaic System Energy Performance Evaluation Method

Solar Energy. Airports Going Green Aimee Fenlon

Situated Usability Testing for Security Systems

SUNPOWER CORPORATION Document # Rev *B Title: Page 1 of 8 Initial release: 17-Aug-09

measurements at varying irradiance spectrum, intensity and module temperature

Design of a Photovoltaic Data Monitoring System and Performance Analysis of the 56 kw the Murdoch University Library Photovoltaic System

SHARP SOLAR Frequently Asked Questions for PV Integrators Revised 05/04/2010

Solar Energy Commercial Applications. Agenda. Venture Catalyst Inc. Intro. Opportunity. Applications. Financing. How to start

Improving a Gripper End Effector

MORE POWER. A BETTER INVESTMENT.

ENERGY YIELD PREDICTION OF AMORPHOUS SILICON PV MODULES USING FULL TIME DATA SERIES OF IRRADIANCE AND TEMPERATURE FOR DIFFERENT GEOGRAPHICAL LOCATIONS

Overview Presented by: Boyd L. Summers

Yield Reduction due to Shading:

Photovoltaic Incentive Program

Running the Electric Meter Backwards: Real-Life Experience with a Residential Solar Power System

REQUEST FOR PROPOSALS SOLAR POWER PURCHASE AGREEMENT (PPA)

Gross/Active PV Surface Area: ,40 / ,29 m². Energy Produced by PV Array (AC):

Bigger is Better: Sizing Solar Modules for Microinverters

Dynamic Programming Applied to Investigate Energy Management Strategies for a Plug-in HEV

Understanding Tracker Accuracy and its Effects on CPV

Own Your Power! A Consumer Guide to Solar Electricity for the Home

ADDENDUM #1(BID PACKAGE # 3)

The Planning and Design of Photovoltaic Energy Systems: Engineering and Economic Aspects. William Nichols Georgia Southern University Atlanta, GA

Investigation of Performance For Fixed-Inclined, One Axis and Two-Axis Tracking Photovoltaic System in Different Parts of Turkey

Drupal Automated Testing: Using Behat and Gherkin

Central Inverter Planning of a PV Generator

Cost and Performance Assumptions for Modeling Electricity Generation Technologies

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

DEFENSE CONTRACT AUDIT AGENCY

Transcription:

National Renewable Energy Laboratory Innovation for Our Energy Future A national laboratory of the U.S. Department of Energy Office of Energy Efficiency & Renewable Energy Small PV Systems Performance Evaluation at NREL's Outdoor Test Facility Using the PVUSA Power Rating Method Conference Paper November 2005 Presented at the 2005 DOE Solar Energy Technologies Program Review Meeting November 7 10, 2005 Denver, Colorado NREL is operated by Midwest Research Institute Battelle Contract No. DE-AC36-99-GO10337

NOTICE The submitted manuscript has been offered by an employee of the Midwest Research Institute (MRI), a contractor of the US Government under Contract No. DE-AC36-99GO10337. Accordingly, the US Government and MRI retain a nonexclusive royalty-free license to publish or reproduce the published form of this contribution, or allow others to do so, for US Government purposes. This report was prepared as an account of work sponsored by an agency of the United States government. Neither the United States government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States government or any agency thereof. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States government or any agency thereof. Available electronically at http://www.osti.gov/bridge Available for a processing fee to U.S. Department of Energy and its contractors, in paper, from: U.S. Department of Energy Office of Scientific and Technical Information P.O. Box 62 Oak Ridge, TN 37831-0062 phone: 865.576.8401 fax: 865.576.5728 email: mailto:reports@adonis.osti.gov Available for sale to the public, in paper, from: U.S. Department of Commerce National Technical Information Service 5285 Port Royal Road Springfield, VA 22161 phone: 800.553.6847 fax: 703.605.6900 email: orders@ntis.fedworld.gov online ordering: http://www.ntis.gov/ordering.htm Printed on paper containing at least 50% wastepaper, including 20% postconsumer waste

Small PV Systems Performance Evaluation at NREL s Outdoor Test Facility Using the PVUSA Power Rating Method National Renewable Energy Laboratory, 1617 Cole Blvd. Golden, CO 80401 jill_adelstein@nrel.gov ABSTRACT The PV Systems Performance and Reliability R & D group currently has seven grid-tied 1-2 kilowatt PV systems deployed at NREL s Outdoor Test Facility (OTF) and two 6 kilowatt systems mounted on the roof of NREL s Solar Energy Research Facility (SERF). The systems, which employ several PV module technologies including crystalline silicon (c-si), amorphous silicon (a-si), cadmium telluride (CdTe), and copper indium diselenide (CIS), are being monitored to determine the long-term performance and reliability of the modules and arrays under actual field conditions. The length of observation ranges from 2 months for our newest system to 11 years for our oldest systems. The annual degradation and seasonal fluctuation of the systems power output are calculated using the PV for Utility-Scale Applications (PVUSA) power rating regression model. 1. System Descriptions A typical 1kW system consists of anywhere between 5 modules for larger and/or high efficiency c-si modules and 53 for smaller and/or lower efficiency a- Si modules. Strings of series wired modules are combined in parallel and both held at the system maximum power point and connected to the utility grid through an inverter. System voltages range from 35V to ~250V while system currents range from 2.5A to 17A. All of the OTF systems face true south and are mounted at a (latitude) tilt of 40 degrees with the exception of one system, which is mounted at a 30 degree tilt. Mounting systems at the OTF include Uni- Strut rack mounts, pole mounts and a simulated roof mount for an array of combination shingle/modules (see Figure 1). Fig. 1. Typical OTF rack mounted PV system. The two SERF systems are mounted on the SERF roof and face 158 o (22 o east of south) with a tilt angle from the horizontal equal to 45 due to building constraints. Kipp and Zonen CM11 thermopile pyranometers and Campbell Scientific 107 thermistor temperature probe are mounted in the plane-of-array of each system to measure POA irradiance and ambient temperature, respectively. Campbell Scientific or National Instruments data acquisition systems (DAS) record in-situ data for the PV systems, which are is instrumented with sensors to measure various system parameters (see Figure 2). Parameters measured and recorded for the PV systems include: plane-of-array (POA) irradiance, DC voltage, DC current, AC power, and ambient temperature. DC power is calculated by the DAS by multiplying the DC voltage and DC current. Wind speeds are recorded with a Campbell Scientific DAS from NREL s Reference Meteorological and Irradiance System (RMIS), also located at the OTF, just north of most of the systems. Measurements are made every 5 s and stored as 15-min averages for the PV systems and 1-min averages for the RMIS wind speed data. Fig. 2. Typical DAS using Campbell Scientific data logger. 2. PVUSA power rating analysis The annual degradation and seasonal fluctuation of the PV system power output are calculated using the PVUSA power rating regression model. The PVUSA rating system is based on the assumption that array current primarily depends on irradiance and that array voltage primarily depends on array temperature which, in turn, depends on irradiance, ambient temperature, and wind speed [2]. Measured data can be used to calculate a best-fit correlation to the following equation: 1

P = I POA (a + bi POA + ct amb + dw), where: P = power (AC or DC), kw I POA = POA irradiance, W/m 2 T amb = ambient temperature, o C W = wind speed, m/s a,b,c,d = regression coefficients derived from operational data One-month blocks of 15-min average system performance and meteorological observations are used to obtain the regression coefficients above. Because the PVUSA model performance is poor at low irradiances, the POA irradiance inputs to the regression equation are restricted to I POA > 800 W/m 2. The measured power is restricted to P DC > ~0.75 P DCmax to eliminate data points where the array may be snow covered while the pyranometer is not. After determining the regression coefficients, we find the PVUSA power rating for the system for each one month block by normalizing to PVUSA test conditions (PTC), where PTC conditions are defined as 1000 W/m 2 POA irradiance, 20 o C ambient temperature, and 1 m/s wind speed. National Instrument s LabVIEW programs, originally developed at NREL by Keith Emery and modified for this paper, are used to combine the USSC data with the RMIS wind speed data and to perform the linear regression. LabVIEW s general linear-fit function was used to determine the set of linear coefficients using the least chi-square method. Monthly power ratings are then plotted to show the system performance vs. time. 3. Results and Accomplishments Figure 3 depicts a typical a-si system plot of PVUSA DC power rating vs. from September 1999 through July 2005 for irradiances greater than 800 W/m 2 and system power greater than 1100 W DC. The analysis clearly shows the initial six months to one year of rapid degradation (-7.25% from September 1999 to August 2000 in this case) characteristic of a-si modules, followed by the typical seasonal oscillating power output also characteristic of a-si modules, i.e. higher power output in the warmer summer months. The yearly maximum and minimum power ratings for this system varied by +6.6% and -3.8%, respectively, from the yearly mean power rating. In a paper summarizing performance characterization of a-si modules from several manufacturers, Sandia National Laboratories found that previously unexposed a-si modules showed an initial rapid degradation in power over the first 6 months and reached a stabilized power level, about 20% below the initial (1 st day) power after about one year. Seasonal oscillation is usually ±4% from the stabilized level [1]. Through the PVUSA analysis described in this paper, we have observed annual degradations of between 1 and 3 percent per year. The photovoltaic (PV) industry wants a module technology that will last 30 years in the field. A PV module fails to provide service if its power output decreases by more than 30% after 30 years in its use environment. 2 Through careful measurement and analysis by the methods described above, we can identify possible failure mechanisms and help to determine solutions to these problems. REFERENCES 1. D. King, J. Kratochvil, and W. Boyson,. Stabilization and Performance Characteristics of Commercial Amorphous-Silicon PV Modules, Proc. 28 th IEEE PVSC, 2000, p1446-1449. 2. T. J. McMahon, G. J. Jorgensen, and R. L. Hulstrom, Module 30 Year Life: What Does it Mean and Is it Predictable/Achievable?, Proc of the IEEE PV Spec. Conf. (2000). 1550.0 1500.0 1450.0-7.25% (first year) Power Rating (W) 1400.0 1350.0 1300.0-1.73% (-23.2 W) per year 1250.0 1200.0 1150.0 Aug-99 Feb-00 Aug-00 Feb-01 Aug-01 Feb-02 Aug-02 Feb-03 Aug-03 Feb-04 Aug-04 Feb-05 Time Fig. 3. PVUSA power rating vs. time plot for typical a- Si system. 2

REPORT DOCUMENTATION PAGE Form Approved OMB No. 0704-0188 The public reporting burden for this collection of information is estimated to average 1 hour per response, including the time for reviewing instructions, searching existing data sources, gathering and maintaining the data needed, and completing and reviewing the collection of information. Send comments regarding this burden estimate or any other aspect of this collection of information, including suggestions for reducing the burden, to Department of Defense, Executive Services and Communications Directorate (0704-0188). Respondents should be aware that notwithstanding any other provision of law, no person shall be subject to any penalty for failing to comply with a collection of information if it does not display a currently valid OMB control number. PLEASE DO NOT RETURN YOUR FORM TO THE ABOVE ORGANIZATION. 1. REPORT DATE (DD-MM-YYYY) November 2005 2. REPORT TYPE Conference Paper 4. TITLE AND SUBTITLE Small PV Systems Performance Evaluation at NREL's Outdoor Test Facility Using the PVUSA Power Rating Method 3. DATES COVERED (From - To) 5a. CONTRACT NUMBER DE-AC36-99-GO10337 5b. GRANT NUMBER 5c. PROGRAM ELEMENT NUMBER 6. AUTHOR(S) 5d. PROJECT NUMBER 5e. TASK NUMBER PVB6.7101 5f. WORK UNIT NUMBER 7. PERFORMING ORGANIZATION NAME(S) AND ADDRESS(ES) National Renewable Energy Laboratory 1617 Cole Blvd. Golden, CO 80401-3393 8. PERFORMING ORGANIZATION REPORT NUMBER 9. SPONSORING/MONITORING AGENCY NAME(S) AND ADDRESS(ES) 10. SPONSOR/MONITOR'S ACRONYM(S) NREL 11. SPONSORING/MONITORING AGENCY REPORT NUMBER 12. DISTRIBUTION AVAILABILITY STATEMENT National Technical Information Service U.S. Department of Commerce 5285 Port Royal Road Springfield, VA 22161 13. SUPPLEMENTARY NOTES 14. ABSTRACT (Maximum 200 Words) The PV Systems Performance and Reliability R & D group currently has seven grid-tied 1-2 kilowatt PV systems deployed at NREL s Outdoor Test Facility (OTF) and two 6 kilowatt systems mounted on the roof of NREL s Solar Energy Research Facility (SERF). The systems, which employ several PV module technologies including crystalline silicon (c-si), amorphous silicon (a-si), cadmium telluride (CdTe), and copper indium diselenide (CIS), are being monitored to determine the long-term performance and reliability of the modules and arrays under actual field conditions. The length of observation ranges from 2 months for our newest system to 11 years for our oldest systems. The annual degradation and seasonal fluctuation of the systems power output are calculated using the PV for Utility-Scale Applications (PVUSA) power rating regression model. 15. SUBJECT TERMS Photovoltaics; solar; small PV systems; PVUSA power rating; PV; NREL 16. SECURITY CLASSIFICATION OF: 17. LIMITATION 18. NUMBER 19a. NAME OF RESPONSIBLE PERSON OF ABSTRACT OF PAGES a. REPORT b. ABSTRACT c. THIS PAGE Unclassified Unclassified Unclassified UL 19b. TELEPONE NUMBER (Include area code) Standard Form 298 (Rev. 8/98) Prescribed by ANSI Std. Z39.18