Lower Energy Costs with Rooftop Air-Conditioning Package Units



Similar documents
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc

HVAC Efficiency Definitions

Glossary of Heating, Ventilation and Air Conditioning Terms

Dehumidification Frequently Asked Questions

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

HVAC Basic Science - System Capacity

3/29/2012 INTRODUCTION HVAC BASICS

Get the FACTS about SEER and Deliver Better Customer Value

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM

Energy Efficiency in Industrial HVAC Systems

1932 Lexington Houston, Texas (713) Recommendations for installation of cooling systems

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

How To Buy A Lennox Power System

SECTION HEAT PUMPS

Creating Efficient HVAC Systems

HIGH EFFICIENCY RTU. HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons

Bring the fresh in. Dedicated Outside Air Systems

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

HVAC Systems: Overview

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Air-Conditioning Buying Guide

How To Design A Building In New Delhi

Defining Quality. Building Comfort. Precision. Air Conditioning

Energy Efficiency. Energy Efficient Home Cooling:

Heating, Ventilation & Air Conditioning Equipment

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Air Conditioning Contractors of America

air conditioners how to choose a cooling system

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes

Heating, Ventilation & Air Conditioning Equipment

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA

Characteristics of Evaporators

Massachusetts COOL SMART. RESIDENTIAL CENTRAL AC/DUCTED AIR SOURCE HEAT PUMP Rebate Application

Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

Energy Efficient Homes: Air Conditioning 1

Preventive Maintenance Strategies and Technologies Can Pave the Path for Next Generation Rooftop HVAC systems

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

Commercial Packaged Rooftop Units 3- to 50-Ton LC/LG Models. Up to 17.0 SEER, Up to 12.8 EER

Mechanical Rooftop Custom Capabilities

Certified HVAC Audit Report Key Takeaways and Implications. Created for: Pets On the Go 445 Logging Road, Building 3 Yardley, PA-19034

Evaporative Cooling for Residential and Light-Commercial

MAC-120HE-01 Air-Cooled Chiller

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

Strategy Guideline: HVAC Equipment Sizing

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

Heating & Cooling Efficiency

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

TWE+TTA TWE+TWA T.R.

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

Packaged Gas/Electric Rooftop Units

HSX19 Air Conditioner Up to SEER. Home Comfort Systems HSX19. The most quiet and efficient central air conditioner you can buy.

DOAS UNITS. MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR. Kitchens Hotel Corridors Laboratories. Paint Booths. Capacities Tons MBH

Introduction. Motor Types

By Tom Brooke PE, CEM

ENERGY STAR Program Requirements for Residential Air Source Heat Pump (ASHPs) and Central Air Conditioner Equipment. Partner Commitments.

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Dehumidification Design

CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)

Energy Efficient Homes: Air Conditioning

Laboratory Performance Testing of Residential Window Mounted Air Conditioners

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

SECTION MORTUARY REFRIGERATORS

AND SIMPLE HVAC SYSTEMS

Packaged Cooling with Electric Heat Rooftop Units

ARMSTRONG AIR HEAT PUMPS

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

85 F 80 F 50% 75 F 70 F 73.0/ F 10% Figure 1

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

Todd M. Rossi, Ph.D. President

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.

Ground Source Heat Pumps The Fundamentals. Southington, Connecticut John F. Sima III P.E.

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT

Commercial Packaged Rooftop Units. Designed to achieve the lowest lifecycle cost. *

Glossary of HVAC Terms

Pool Dehumidification Basics

1/15/2013. HVAC Maintenance Repair or Replace & Planned Replace Initiative. Reduce Operating Costs. Improve Comfort / Process Conditions

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity

HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.

Transcription:

Lower Energy Costs with Rooftop Air-Conditioning Package Units Sponsored by Mike West, PhD, PE Advantek Consulting, Inc

Package Unit Efficiency Factors Sensible and latent performance ratings Unit efficiency ratings (IPLV, SEER, or EER) Fan motor drive and efficiency rating Fan is 10 to 20% of unit power draw [kw] Fan is 20% to 50% of unit energy usage [kwh] Number of stages / capacity control Geographical location / climate Likelihood of maintenance Total life-cycle installed and operating costs including options

EER Rating Specification

Efficiency Ratings EER Energy Efficiency Ratio MBH per kw SEER Seasonal EER MBTU per kwh IPLV Integrated Part-load Value MBH per kw Energy Star light commercial HVAC equipment uses 7 10% less energy than standard equipment. Energy Star package units can save $3 to $4 per square foot over the life of the equipment. For example, a 12,000 square foot building using an ENERGY STAR qualified HVAC product, could save $36,000 to $48,000 over 15 years, more than enough to justify the upgrade cost.

Energy Star efficiency rating Units rated at 65,000 to 135,000 Btuh 11.0 EER or higher -and- 11.4 IPLV or higher Units rated at 135,000 to 250,000 Btuh 10.8 EER or higher -and- 11.2 IPLV or higher Three-phase equipment rated below 65,000 Btuh SEER 13.0 or higher Air conditioner EER ratings are measured at outdoor temperature of 95 F, indoor 80ºF db 67ºF WB or 50% Relative Humidity. IPLV takes into account the higher efficiency of air conditioning units at part load. IPLV is measured using ARI Standard weightings and provides more of an apples to apples comparison than EER alone. SEER was intended to rate efficiency over an entire cooling season, not a single outdoor temperature. In theory, SEER is calculated by total amount of cooling (Btu) over the entire season divided by the total Watt-hours it will consume. SEER is used only for units 5-tons and less.

SEER ratings In some cases manufacturer s simply rate SEER as 0.875 x EER at 82 F outdoor (instead of ARI 95 F) The SEER of a system is determined by multiplying the steady state energy efficiency ratio (EER) measured at conditions of 82 F outdoor temperature, 80 F db and 67 F wb indoor entering air temperature by the Part Load Factor (PLF) of the system. (The PLF is supplied by the government.) The PLF is a measure of the cyclic performance (CD) of a system and is calculated as follows, where CD is Cyclical Data: PLF = 1.00 - (CD x 0.5) "The cyclic performance (CD) value in the above equation has been determined by the government to be 0.25." The government contends that the PLF should equal: 1.00 - (.25 x.5) 1.00 -.125 = 0.875, which yields: PLF of 0.875

Rating Specifications

Savings Estimates / Quick Need estimated annual operating hours, cost of electricity. MBH unit size = Tons x 12 EER 1 = rating of standard efficiency unit EER 2 = rating of high efficiency Energy Star unit Hours = annual operating hours ~ 1.3 x CDD Rate = $ cost of electricity, demand and tax per kwh MBH EER 1 MBH EER 2 Savings = ( - ) x Hours x Rate

Capacity selection Avoid Oversizing Performance Ratings are at steady-state Larger units costs more & use more power Example: compare power of 2 units at full load 15 ton: 15.7 kw 17½ ton: 18.9 kw added cost of $1500 Added electric demand of 3.2 kw ~ $400 per year Documented sizing calculations should be performed using accepted ACCA or ASHRAE procedures. ACCA methods have sufficient built-in safety factors. Use ASHRAE design conditions. Don t exaggerate outdoor design temperatures by using the AHR 95 F test point, or an unrealistically low indoor space condition such as 70 or 72 F.

Load-calc Lessons Learned Perform an accurate hourly load calculation Use the correct project location weather data 1. Peak Sensible Load 2. Maximum Latent Load 3. Lowest SHR Reasonably estimate infiltration airflow ACH Or, if an hourly load calc is not feasible, calculate the cooling load at three design conditions: ASHRAE Fundamentals 2003 Chapter 27, Miami 0.4% F.2005 Chapter 28 data available on CD-ROM 1. Cooling: 91db / 78wb / 125 grains 2. Dehumidification: 83db / 79 wb / 145 grains 3. Latent-Part-Load: 75db / 72 wb / 116 grains

Equipment Specification Tips Use manufacturer s performance software or tables to determine actual unit capacity (don t use nominal) Select the model closest in capacity to the load Specify that TAB shall include supply air CFM, fan RPM, External SP, and EAT LAT OA CFM must meet ASHRAE 62, provide exhaust makeup, and pressurize the building 0.02 to 0.04 in.wg [5 to 10 Pa] Request prices - be able to support and defend your equipment specification with hard economics.

The importance of carefully selecting the design airflow The SHR of a DX package unit will try to follow it s capacity curve to match the SHR of the space load. Load SHR drops as the space humidity drops, yet equipment SHR increases as entering wet bulb drops. If airflow is too low, temperature may rise and energy is wasted. If airflow is too high, humidity may be excessive at times. Higher airflow increases fan kw, but cooling capacity also increases, so EER usually goes up at the higher fan speeds. However, too high a fan speed means the latent load will not be met at times and fan energy use will be excessive.

Air Delivery Considerations Air leakage and heat gain from ducts significantly reduce air-conditioning system efficiency. The insulation level of traditional ducting is typically only R-4 to R-6 (1.5 to 2.2 inches). Specify R-8 (2¾ to 3 inches) Larger ducts typically mean lower static pressure, less leakage and higher system efficiency, if well insulated. With no attention, duct leakage rates can be 10% to 15% of total system airflow, sometimes higher. Specify ASHRAE Leakage Class-3 on the design drawings Test and Balance the Unit and Duct System

Test and Balance Package Units are not Plug-and-Play Engineering observation of startup is a must. Set fan speed and airflow according to design engineers specifications. Verify rotation direction of fan. Check and adjust refrigerant charge according to manufacturer s procedure. Adjust and calibrate fresh air damper and linkage to obtain design amounts of fresh air. Properly install high-efficiency filters.

Commissioning Example: Motorized Fresh-air damper with Economizer

Commissioning Some problems can be identified in the design phase: sizing, supply and outside airflows, controls Most problems can be identified at the project site: 1. Leak-test curb and ducts under pressure 2. Calibrate thermostats and sensors 3. Check ceiling diffusers for short-circuits 4. Functional performance test in all modes 5. Operations and maintenance training 6. Checkup visits at 30 and 90 days

Equipment Selection Factory Equipment Options Select evaporative condenser option wherever available Motorized fresh-air damper with Economizer Dehumidification enhancements needed below SHR ~ 0.65 Face and bypass damper, heat pipes, liquid reheat, hot gas reheat Filter pressure drop sensor so filter losses remain low BACNET Communications interface Avoid High Static Drive Use static regain duct design, and VFD or staged air-volume with SP or LAT control DCV - Demand Controlled Ventilation based on return air CO 2 Field Installed LPA liquid pressure amplification for low ambient conditions EER-Plus desuperheater / subcooler for the adventurous Auxiliary Condenser - increased heat rejection is a plus

Stages and Capacity Control This unit has 1- compressor, thus 1 refrigerant circuit Single scroll compressor Digital Scroll TM provides variable capacity control

Stages and Capacity Control This unit has 2 compressors, but only 1 refrigerant circuit 1 2

Stages and Capacity Control This unit has 4 compressors and 4 refrigerant circuits, but only 2 control stages. Modification to 4 stages is simple. 1 2 3 4

Model Selection This unit has a Thermostatic Expansion Valve (TXV) Evaporator coil TXV

Evaporative Condenser Wet condenser coil uses evaporative cooling like a cooling tower, except refrigerant flows inside copper tubes. Less condenser fan HP Energy savings are typically 20% - 30%, up to 40% in dry climates Highly climate dependent Near-peak versus off-peak operating hours and MC wet-bulb temperatures wb 10 to 30 degrees cooler than db Integrated water treatment system, chemical and/or ozone Stainless steel, copper, PVC, FRP Desuperheater coils not wetted

Evaporative Condenser - AAON

Savings Estimates / Calculator http://www1.eere.energy.gov/femp/procurement/eep_unitary_ac_calc.html

Savings Estimates / Calculator http://www1.eere.energy.gov/femp/procurement/eep_unitary_ac_calc.html Range is still 8.9 to 13.5 Estimate based on location and type Billed rate including kw demand and tax

Savings Estimates / Calculator Annual Hours of Operation http://www.accuratehvac.com/accurate_residential/estimator/2/hvac_costest.htm 1 600 to 900 hours 2 900 to 1400 hours 3 1400 to 2000 hours 4 2000 to 2800 hours 5 2800 to 4000 hours

Savings Estimates / Calculator Hours of Operation = 1.3 x CDD http://lwf.ncdc.noaa.gov/img/documentlibrary/clim81supp3/annualcoolingdd_hires.jpg

Savings Estimates / Calculator http://www1.eere.energy.gov/femp/procurement/eep_unitary_ac_calc.html $4194 - $3200 = $994 savings per year Cost of 10-ton high efficiency (EER 13.5) unit: $7,000 Cost of a standard (EER 10.3) typical unit: $5,000 Upgrade cost for a high-efficiency unit: $7,000 - $5,000 = $2,000 Payback period = $2,000 / $994 = 2 years to recover higher price Return on investment = $994 / $2000 = 49% every year for life of equipment

Savings Estimates / Calculator http://www1.eere.energy.gov/femp/procurement/eep_unitary_ac_calc.html Lifetime savings for 5 units: $82,370 in today s dollars (15 years) assuming a 4.1% annual increase in electricity Cost of 5 units: 5 x $7,000 = $35,000 Benefit / Cost Ratio = 83,370 / 35,000 = 2.4

Market Availability ENERGY STAR Partner List Results Look for Product Manufacturers in a different Country and State: New Search Refine Search Results 1-7 of 7 All Countries All States All # A B C D E F G H I J K L M N O P Q R S T U V W X Y Z Name Product Type Location Award Category (Year) Carrier Central ACs and Air-Source Heat Connecticut Corporation Pumps, Furnaces, Geothermal Heat Pumps, Light Commercial HVAC, Programmable Thermostats, Room Air Conditioners Daikin U.S. Light Commercial HVAC New York Corporation Goodman Manufacturing Company, L.P. Lennox Industries Incorporated Rheem-Ruud Manufacturing Central ACs and Air-Source Heat Pumps, Furnaces, Light Commercial HVAC, Room Air Conditioners Central ACs and Air-Source Heat Pumps, Furnaces, Light Commercial HVAC, Programmable Thermostats Central ACs and Air-Source Heat Pumps, Furnaces, Light Commercial HVAC, Programmable Thermostats Texas Texas Arkansas Trane Company Light Commercial HVAC Tennessee York International Central ACs and Air-Source Heat Oklahoma Corp. UPG Pumps, Furnaces, Light Commercial HVAC Go Excellence in Efficient Products(2003,2004,2005,2007) 1. Carrier 2. Daikin 3. Goodman 4. Lennox 5. Rheem-Ruud 6. Trane 7. York

Market Availability Carrier Centurion EER 11.5-12.5, SEER 14.1-15.0, to 5-tons Centurion EER 11.0-12.7, IPLV 12.0-13.7, 6 to 25-tons WeatherMaster EER 11.8 to 25-tons Goodman SEER 13 to 5-tons EER 11.5 to 7.5-tons Lennox Strategos EER 12.5-14.3, IPLV 13.5-16.4, to 20-tons L-Series EER 12.2 to 30-tons T-Class EER 11.0 to 25-tons S-Class EER 10.8 to 50-tons Trane Precedent SEER 15 to 5-tons, EER 11.5 to 10-tons Voyager Hi-E EER 10.4-11.5 to 25-tons York Affinity SEER 13-16.5 to 5-tons Predator EER 11.5 to 12½-tons

Savings Example / Quick MBH unit size = 20-Tons x 12 = 240 MBH EER 1 = rating of Lennox T-Class = 10.8 EER 2 = rating of Lennox Strategos = 12.6 Hours = annual operating hours ~ 1.3 x CDD = 3000 Rate = cost of electricity = $0.12 per kwh billed MBH EER 1 MBH EER 2 Savings = ( - ) x Hours x Rate 240 10.8 240 12.6 Savings = ( - ) x 3000 x 0.12 $1,143 per year savings

Design-in Maintainability Numerous energy surveys clearly show that lack of preventative maintenance is by far the major cause of air conditioning performance degradation. Common and costly problems include: clogged, corroded cooling and condenser coils sizeable duct leaks and cabinet air leaks low refrigerant, even in brand-new units maladjusted or stuck air dampers un-calibrated or nonfunctioning controls or sensors Design for Easy Access Provide Manuals and Training

Model Selection Likelihood of maintenance is important. VS.

Model Selection filter compartment access door Ease of Maintenance Fiberglass pre-filters MERV-11 final filters Filter rack was specified to fit 2-inch pre-filters and 2-inch final filters. Angled position of top filters improves flow.

Refrigerant Charge Both Over- and Under-charging are common Even a 5% adjustment is worthwhile the air conditioning system can be performing below its capacity because of poor maintenance and maintain comfort while energy use increases. I don t see anyone really checking charge right, most technicians only do a touch method. I have even found 8 ounces overcharge on brand new units. [total charge is 5 to 8 pounds]

Preventative maintenance program critical to realizing rated performance for the life of the unit.

Lower Energy Costs with Rooftop Air-Conditioning Package Units Thank you! Mike West, PhD, PE Advantek Consulting Engineering, Inc. mwest@advantekinc.com