SECTION 33 05 16.13 PRECAST CONCRETE UTILITY STRUCTURES



Similar documents
SECTION PRECAST CONCRETE STRUCTURES

CCU Engineering Specifications. Section PRECAST CONCRETE PRODUCTS

Wastewater Capital Projects Management Standard Construction Specification

DIVISION 4300 STORM DRAINAGE

SECTION STORM DRAINAGE SYSTEM

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

Section 2100-Trenching and Tunneling

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

September 2012 Brunswick County Engineering Department Revision 1.0. Technical Specification GRAVITY SANITARY SEWER SYSTEM

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

C. Section TESTING LABORATORY SERVICE.

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

Section SEWER PIPE INSTALLATION AND TESTING

SECTION 200: STORM SEWER CONSTRUCTION STANDARDS

SECTION 9.02 BUILDING SUBSURFACE DRAINS (PERIMETER, ETC.)

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

STANDARD SPECIFICATIONS SECTION PRECAST REINFORCED CONCRETE MANHOLES AND MANHOLE BASES. 1. Structure Earthwork: 02200

SECTION STORM DRAINAGE TABLE OF CONTENTS

CHAPTER 6 - SANITARY SEWER

SECTION CEMENT-MORTAR LINED AND COATED STEEL PIPE

SECTION NONREINFORCED CONCRETE SEWER PIPE

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

INDEX. Sec. No. Items Page Nos.

LS 2540 SEWER LATERALS AND INSPECTION TEES

Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.

SECTION SANITARY SEWER PIPE

SECTION REINFORCED CONCRETE PIPE. A. The following is a list of SPECIFICATIONS, which may be related to this section:

FY11 Sanitary Sewer Main Rehab and Point Repair Bid Tabulation

SECTION STORM DRAINAGE STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.

Guide Specification Precast Concrete Products

Beacon Hill Sewer District Standard Specifications

SECTION BUILDING SEWERS. B. Connection of building sanitary drainage system to municipal sewers.

SECTION POINT REPAIRS TO SANITARY SEWERS. A. Repairs to existing sewer lines by replacing short lengths of failed pipe.

SECTION IV - TESTS AND INSPECTIONS PART 1 - GENERAL Testing - General

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 21

SECTION STORM DRAIN SYSTEM

TABLE OF CONTENTS. Manhole, Frame, and Cover Installation (includes Drop Manhole) Additional Manhole Depth

CLEANING, INSPECTION, AND TESTING OF SEWERS

MATERIALS DIVISION MEMORANDUM

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

SECTION SANITARY SEWER AND STORM DRAIN SYSTEMS

San Antonio Water System Standard Specifications for Construction ITEM NO SLIP-LINING SANITARY SEWERS

GUIDE SPECIFICATIONS FOR PRECAST CONCRETE PRODUCTS

PRE INSTALLATION MANUAL

FY08 SEWER POINT REPAIRS BID TABULATION

SECTION 724 PIPE CULVERTS

Specification for Pipe Bursting Gravity Sewer Mains with HDPE Pipe

SECTION 3 SANITARY SEWER DESIGN

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13)

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES SITE UTILITIES

Stormwater/Wetland Pond Construction Inspection Checklist

ITEM II - SANITARY GRAVITY SEWER PIPE, FITTINGS, & ACCESSORIES

DMS REINFORCED CONCRETE PIPE AND MACHINE-MADE PRECAST CONCRETE BOX CULVERT FABRICATION AND PLANT QUALIFICATION

Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL

SECTION POLYVINYL CHLORIDE (PVC) PIPE

PRECAST CONCRETE MANHOLES

A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.

Section 402. STORM SEWERS

SECTION GRAVITY SANITARY SEWERS

SECTION ABANDONMENT OF SEWER MAINS

SANITARY SEWER SPECIFICATIONS

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

SECTION XXXXXX TECHNICAL SPECIFICATIONS FOR INSTALLATION OF PROTECTIVE COATINGS FOR MANHOLES, WETWELLS, AND OTHER SANITARY SEWER STRUCTURES

SECTION POLYVINYL CHLORIDE (PVC) PIPE

SECTION 9. All sewer laterals shall tie into the sewer main lines unless approved by the City Engineer.

CW GRAVITY SEWERS TABLE OF CONTENTS

SANITARY GRAVITY SEWER LINE TESTING. B. Section CCTV Inspection of Gravity Sewer Lines

Meeting the Challenge of Pipeline Emergency Repair

Georgia Department of Transportation. Office of Materials and Research. Standard Operating Procedure (SOP) 19

City of Regina Standard Construction Specification SECTION 1320 SEWERMAIN TESTING

SECTION 1 GENERAL REQUIREMENTS

STANDARD SPECIFICATIONS SECTION INSTALLATION OF GRAVITY SEWER PIPELINES. 1. Trenching, Backfilling and Compacting: 02223

SECTION PRECAST CONCRETE STRUCTURES

San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS

53.03 MATERIALS FOR SEWER LINER PIPE AND FITTINGS: The following materials are approved for installation in sanitary sewer lines:

Construction Specifications for Keyhole Pavement Coring and Reinstatement

Exhibit A. Rules and Regulations for House Connections and Sewer Extensions

CITY OF BEVERLY RULES AND REGULATIONS - SEWER SYSTEM TESTING. General

City of Virginia Beach Public Utilities HRPDC Regional Construction Standards, 5 TH Edition Amendments May 19, 2014

Section Installation of pipe and casing for sanitary sewer by methods of augering.

SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS

NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS

INSTALLATION OF INSITUFORM LINER

Integrated Manhole Ladder System

SECTION GROUND WATER STORAGE TANKS

SEDIMENT/STORMWATER MANAGEMENT BASIN CONSTRUCTION CHECKLIST

900 SEWERAGE WORK ITEM PIPE SEWERS COMPLETE IN PLACE

STANDARD CONSTRUCTION SPECIFICATIONS FOR SANITARY SEWERS DIVISION 50 INDEX

UNIFIED FACILITIES GUIDE SPECIFICATIONS

STORM DRAIN DESIGN AND CONSTRUCTION STANDARDS & SPECIFICATIONS 400 SERIES

SECTION 7- STORM SEWER

Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer

Transcription:

SECTION 33 05 16.13 PRECAST CONCRETE PART 1 - GENERAL 1.01 SECTION INCLUDES A. This item shall consist of the construction of both sanitary and storm sewer precast concrete manholes in accordance with these specifications, at the specified location and conforming to the lines, grades, and dimensions shown on the plans or required by the Construction Manager. B. Appurtenances 1.02 RELATED SECTIONS A. Section 013523.13 - Project Safety Requirements B. Section 013301 Submittals C. Section 014516 Field Quality Control Procedures D. Section 312316 Excavation E. Section 312333 Trenching and Backfilling F. Section 321123 Aggregate Base Courses G. Section 312319 Dewatering 1.03 REFERENCES A. ASTM A185 - Steel Welded Wire Fabric for Concrete Reinforcement B. ASTM C33 - Concrete Aggregates C. B. ASTM C39 Compressive Strength Cylinder Specimens D. ASTM C478 Precast Reinforced Concrete Manhole Sections E. ASTM C497 Testing of Manhole Sections 330516.13-1 PRECAST CONCRETE

F. ASTM C990 Joints for Concrete Pipe, Manholes, and Precast Box Sections Using Preformed Flexible Joint Sealants G. ASTM C 1244 Standard Test Method for Concrete Sewer Manholes by the Negative Air Pressure (Vacuum) Test H. AASHTO M55- Steel Welded Wire Fabric for Concrete Reinforcement I. AASHTO M199 Precast Reinforced Concrete Manhole Sections J. AASHTO M198 Joints for Concrete Pipe, Manholes and Precast Box Sections Using Preformed Flexible Joint Sealants K. Standard Construction Specification for Sewers and Drainage Facilities 2000 by the Metropolitan St. Louis Sewer District 1.04 SUBMITTALS A. Refer to Section 01 33 01 - Submittals. B. Quality Control Submittals: Submit manufacturers certification indicating compliance with specified performance and design requirements. 1.05 SUBMITTALS FOR CONTRACT CLOSEOUT A. In accordance with Section 01 77 19 - Contract Closeout and Section 01 78 01 - Warranties and Bonds, Procedures for submittals. B. Manufacturer's Certificate: Certify that products meet or exceed specified requirements. C. Record actual locations of the manhole and the invert elevations. D. Identify and describe unexpected variations to subsoil conditions or discovery of uncharted utilities. 1.06 QUALITY ASSURANCE A. Perform all work in accordance with referenced standards, Section 01 45 16 Quality Control 1.07 DELIVERY, STORAGE, AND HANDLING A. Deliver, store, protect and handle products to site under provisions of Section 01 35 02 - Material and Equipment. 330516.13-2 PRECAST CONCRETE

B. Store units in an upright position. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Precast Manholes: Klueter Brothers, Edwardsville, IL (618) 656 2581 or approved equivalent. B. Manholes Frames and Covers: Neenah Foundry or approved equivalent. 2.02 MATERIALS A. Manhole Bases: Bases shall have a monolithic base slab with riser barrel conforming to ASTM C478, AASHTO M199, and designed for AASHTO HS-20 loading. B. Manhole Risers: Riser sections shall have a minimum 4.5" wall for 42" diameter and conform to ASTM C478 and AASHTO M199. C. Manhole Top Slabs: Top Slabs (if required) shall have a minimum thickness of 8" and conform to ASTM C478 and designed for AASHTO HS- 20 loading. D. Manhole Steps: Manhole steps shall be 1 /2" diameter steel reinforced copolymer polypropylene conforming to ASTM C478, AASHTO M-199 and OSHA 29 CFR 1910.27. Steps shall be placed in vertical alignment in preformed holes as per step manufactures instructions. The steps shall resist a pullout force of over 1500 lbs. Eng lugs shall have a reflecting material insert. The steps shall not exceed spacing greater than 16" on center. E. Concrete: Concrete shall be air entrained in accordance with IDOT specifications and have a minimum concrete compressive strength of 4,000 PSI at 28 days. Concrete shall be placed in forms and vibrated in such a manner to make a dense uniform product. F. Coating: Exterior surfaces of manholes shall have two coats of an approved asphalt coating applied according to manufactures recommendations. An alternate to the exterior coating shall be a concrete admixture that is applied to the concrete with batching and demonstrates a reduction in water absorption below five percent. G. Pipe Connections: Pipes shall be connected to the manhole walls using an approved flexible sleeve. Approved connections shall be A-Lok 330516.13-3 PRECAST CONCRETE

or ZLok by A-Lok Products, or approved equal conforming to ASTM C990. H. Joint Sealant: Joint sealant shall be an approved butyl rubber conforming to ASTM C478 and ASTM C990. PART 3 - EXECUTION 3.01 REJECTION A. Precast units shall be subject to rejection for failure to conform to any of the specified requirements. In addition, individual sections may be rejected because of any of the following: 1. Fractures or cracks passing through the wall, except for a single end crack that does not exceed the depth of the joint. 2. Defects that indicate imperfect proportioning, mixing, and molding. 3. Surface defects indicating honeycombed or open texture. 4. Damaged or cracked ends where such damage would prevent making a satisfactory joint. 5. Any continuous crack having a surface width of 0.01 inch (0.3 mm) or more and extending a length of 12 inches (300 mm) or more, regardless of position in the section wall. 3.02 INSTALLATION A. Place the Precast base units on an aggregate base course with a minimum thickness of eight inches after compaction. The granular sub base shall be checked for level prior to setting. B. After setting of precast base section, the joint shall be clean free of dirt or other unsuitable materials. A butyl joint sealant conforming to ASTM C990 shall be applied to the joint area and then the next precast section installed. Set all sections in plum. When setting sections ensure that the manhole steps are set in vertical alignment. After two sections are joined together. The interior and exterior of the joints shall be grouted. C. Joining Pipe to Manholes: If manhole base sections are equipped with flexible sleeves, slide pipe through sleeve until the end of the pipe is flush with the inside wall of manhole. Install and secure sleeve to pipe 330516.13-4 PRECAST CONCRETE

with stainless steel clamp is required. If flexible sleeve is a compression type, such as A-Lok type, no external stainless steel clamp is required. D. Plug holes, in the concrete sections made for handling with a non-shrink grout and/or the rubber plugs. 3.03 FIELD TESTING A. Refer to the Standard Construction Specification for Sewers and Drainage Facilities, 2000, by the Metropolitan St. Louis Sewer District and the following specifications, whichever gives the greatest effect. B. Inspection: All units shall be inspected to be sound. There shall be no visible leakage through the walls or pipe connections. C. Testing: Testing on Sanitary Precast Concrete Manholes shall be by Vacuum Testing in accordance with ASTM C 1244. All vacuum testing shall be performed prior to backfilling of manhole. The test procedure shall be as follows: 1. Plug, seal, and brace all pipes entering the manhole to prevent them from dislodging during the test. Pipe plugs shall be installed beyond boot seals. 2. Firmly secure vacuum testing equipment to manhole as per recommendations. 3. Start vacuum and seal and necessary leaks around the testing equipment bladder. 4. Attain a vacuum of 10" Hg. 5. Time pressure drop to 9" Hg. Record time. If time to drop 1" Hg is less than 1 minute, manhole shall be passed. If manhole does not pass, the Contractor shall locate leak(s) and repair and retest until satisfactory. 6. Release Vacuum and backfill manhole in accordance with specifications herein. D. Repair: Any defect found shall be repaired as approved by the Construction Manager. The repair method shall be of sound principle to ensure compliance with this specification. END OF SECTION 33 05 16.13 330516.13-5 PRECAST CONCRETE