SECTION 02612 NONREINFORCED CONCRETE SEWER PIPE



Similar documents
Wastewater Capital Projects Management Standard Construction Specification

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

SECTION CEMENT-MORTAR LINED AND COATED STEEL PIPE

SECTION SANITARY SEWER AND STORM DRAIN SYSTEMS

SECTION REINFORCED CONCRETE PIPE. A. The following is a list of SPECIFICATIONS, which may be related to this section:

Section SEWER PIPE INSTALLATION AND TESTING

DIVISION 4300 STORM DRAINAGE

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

SECTION PRECAST CONCRETE UTILITY STRUCTURES

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.

725-R-599 PIPE LINING. (Revised ) SECTION 725, BEGIN LINE 1, INSERT AS FOLLOWS: SECTION 725 SLIP LINING OF EXISTING PIPE

San Antonio Water System Standard Specifications for Construction ITEM NO SLIP-LINING SANITARY SEWERS

SECTION POLYVINYL CHLORIDE (PVC) PIPE

PRE INSTALLATION MANUAL

CCU Engineering Specifications. Section PRECAST CONCRETE PRODUCTS

SECTION POLYVINYL CHLORIDE (PVC) PIPE

SECTION STORM DRAINAGE SYSTEM

SECTION 3 SANITARY SEWER DESIGN

SECTION PRECAST CONCRETE STRUCTURES

SECTION STORM DRAIN SYSTEM

A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.

ENGINEERED SOLUTIONS. A2 Liner Pipe for Trenchless Technology

Manufacturing Standards for Precast Concrete Products. March 2009

INDEX. Sec. No. Items Page Nos.

STANDARD SPECIFICATIONS SECTION INSTALLATION OF GRAVITY SEWER PIPELINES. 1. Trenching, Backfilling and Compacting: 02223

CHAPTER 6 - SANITARY SEWER

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

Guide Specification Precast Concrete Products

STANDARD SPECIFICATIONS & CONSTRUCTION DETAILS MANUAL SECTION 5 - STORM DRAINAGE Design

GUIDE SPECIFICATIONS FOR PRECAST CONCRETE PRODUCTS

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

Specification for Pipe Bursting Gravity Sewer Mains with HDPE Pipe

SECTION PRESTRESSED CONCRETE CYLINDER PIPE

SECTION 9.02 BUILDING SUBSURFACE DRAINS (PERIMETER, ETC.)

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

Meeting the Challenge of Pipeline Emergency Repair

SECTION STORM DRAINAGE TABLE OF CONTENTS

Native InDesign 2890 SaniTite Brochure 1/8" CMYK April 17, 07

Flowtite Jacking Pipe

City of West Linn Public Works Standard Construction Specifications. Table of Contents

NAPCA BULLETIN APPLICATION PROCEDURES FOR CONCRETE WEIGHT COATING APPLIED BY THE COMPRESSION METHOD TO STEEL PIPE

The Most Advanced Name in Drainage Systems. Sanitary Sewer Pipe

PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS

Inspection Manual for Precast Concrete Pipe and Structures

The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.

Prequalification Requirements For Precast Concrete Drainage Products

DMS REINFORCED CONCRETE PIPE AND MACHINE-MADE PRECAST CONCRETE BOX CULVERT FABRICATION AND PLANT QUALIFICATION

TABLE OF CONTENTS SECTION 500 SANITARY SEWER AND FORCE MAIN

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 21

SECTION 6A STORM DRAIN DESIGN Mar S E C T I O N 6A STORM DRAIN - DESIGN

SECTION 9. All sewer laterals shall tie into the sewer main lines unless approved by the City Engineer.

Use of Corrugated HDPE Products

TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE

BEST PRACTICE GUIDELINES FOR CULVERT LINER SELECTION

Section 2100-Trenching and Tunneling

900 SEWERAGE WORK ITEM PIPE SEWERS COMPLETE IN PLACE

Royal Seal Gasketed Sewer Pipe

ASTM C76, Class III, Wall B, except as modified herein. Clean natural sand, ASTM C33. Artificial or manufactured sand will not be permitted.

CW GRAVITY SEWERS TABLE OF CONTENTS

San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS

PRECAST CONCRETE MANHOLES

SECTION HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS FOR WATER DISTRIBUTION AND TRANSMISSION

City of Lincoln, Nebraska STEVENS CREEK BASIN TRUNK SEWER TECHNICAL MEMORANDUM NO. 5 PIPE MATERIAL SELECTION TABLE OF CONTENTS

SPR PE Steel Reinforced Liner

HDPE PRODUCTS QUALITY, PERFORMANCE AND ECONOMY COMBINED

TECHNICAL SPECIFICATIONS GRAVITY AND PRESSURE SEWER LINE AND MATERIALS

Storm Sewer Trenchless Upgrade Alternatives and Recommendations

PIPE REHABILITATION. Industrial Wastewater Municipal Wastewater Drinking Water Pressure Pipes

STANDARD SPECIFICATIONS SECTION PRECAST REINFORCED CONCRETE MANHOLES AND MANHOLE BASES. 1. Structure Earthwork: 02200

SECTION DUCTILE IRON PIPE AND FITTINGS

SECTION STEEL PIPE, MORTAR LINED AND COATED

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES SITE UTILITIES

SECTION DUCTILE IRON PIPE AND FITTINGS

CITY OF BEVERLY RULES AND REGULATIONS - SEWER SYSTEM TESTING. General

SECTION GRAVITY SANITARY SEWERS

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

SECTION 200: STORM SEWER CONSTRUCTION STANDARDS

SECTION POINT REPAIRS TO SANITARY SEWERS. A. Repairs to existing sewer lines by replacing short lengths of failed pipe.

MATERIALS DIVISION MEMORANDUM

STORM DRAIN DESIGN AND CONSTRUCTION STANDARDS & SPECIFICATIONS 400 SERIES

SECTION 603 SANITARY SEWER FORCE MAINS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION ASBESTOS CEMENT PIPE REPAIRS, DEMOLITION, AND DISPOSAL

SECTION SANITARY SEWER PIPE

SECTION 7- STORM SEWER

550 PIPE CULVERTS, SEWERS AND DRAINS

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing

PIPE INSPECTION AND REPAIR. Larry Ritchie

SANITARY SEWER SPECIFICATIONS

ITEM # OSTERBERG CELL LOAD TESTING OF DRILLED SHAFT

LS 2540 SEWER LATERALS AND INSPECTION TEES

Section 402. STORM SEWERS

Section Four: Linings and Coatings

SECTION ABANDONMENT OF SEWER MAINS

SECTION BUILDING SEWERS. B. Connection of building sanitary drainage system to municipal sewers.

APPENDIX K PIPE INSPECTION

SECTION DUCTILE-IRON PIPE AND FITTINGS

Transcription:

SECTION 02612 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: Furnishing and installing nonreinforced concrete sewer pipe. Provide concrete sewer pipe less than 12 inches in diameter, and in other sizes when specifically called for, to be nonreinforced concrete pipe. B. Related Work Specified in Other Sections Includes: 1. Section 02650 - Laying and Jointing Buried Pipelines 2. Section 02676 - Leakage Tests 1.2 REFERENCES A. Codes and standards referred to in this Section are: 1. ASTM C 14 - Specification for Concrete Sewer, Storm Drain, and Culvert Pipe 2. ASTM C 443 - Specification for Joints for Circular Concrete Sewer and Culvert Pipe, Using Rubber Gaskets 3. ASTM C 497 - Test Methods for Concrete Pipe, Manhole Sections, or Tile 1.3 SUBMITTALS A. General: Provide all submittals, including the following, as specified in Division 1. B. Shop Drawings: Submit complete shop drawings of all plastic liner, details of installation and joints between pipes and structures, between other pipes and all other joints for approval. C. Samples: Submit samples of the type of sheet and strip plastic liner plate for approval, together with a list of ingredients from which the sheets and strips are to be compounded. Submit the list to show the Page 1 of 6

percentage of each ingredient used in the formulation. No changes in formulation are permitted without prior approval. D. Quality Control: Submit certified test results of all shop tests for approval. 1.4 QUALITY ASSURANCE A. General: Provide concrete sewer pipe that is precast or machine made and of the product of a concern that can demonstrate by tests and installation records satisfactory experience in manufacturing concrete pipe of the quality and type specified. B. Provide nonreinforced concrete pipe meeting the requirements of ASTM C 14 for Class 2 or Class 3 nonreinforced concrete pipe. C. Classes: Provide the classes of concrete sewer pipe for the various pipelines as shown or specified. 1.5 DELIVERY, STORAGE AND HANDLING A. Deliver, store and handle all products and materials as specified in Division 1 (and as follows:) PART 2 PRODUCTS 2.1 MATERIALS A. Concrete Pipe: Manufacture all nonreinforced concrete pipe in the longest lengths normally available except where shorter lengths are required for pipeline curves or at junctions with structures whose location cannot be adjusted. 1. Design: Cure all pipe by steam or membrane curing. Water curing is not permitted. a. Do not deliver pipe to the site of the work until it has attained an age of at least 12 days. B. Specials, Fittings and Accessories: Provide specials, fittings, and accessories where shown, specified or required, and manufactured in accordance with the applicable sections of the respective standard of the adjoining pipe. Provide joints the same as in the adjoining pipe. Page 2 of 6

Provide the interior surface of bends of the same smoothness and diameter as the adjoining pipe. Provide the center line radius of curvature to be equal, in dimension, to the inside diameter of the pipe. 1. Strength: Design all specials, fittings, and accessories to have the same strength as the class of the adjoining pipe. Submit working drawings in conjunction with those submitted for the entire pipeline. C. Joints: Have nonreinforced concrete pipe manufactured with bell and spigot ends suitable for use with a rubber gasket joint. 1. Gaskets: Provide pipe ends for use with rubber gaskets that are suitably reinforced or of sufficient thickness to withstand the stresses caused by the compression of the gasket without cracking or fracturing, and provide surfaces that are smooth and free from spalls, cracks, fractures, and imperfections that would adversely affect the performance of the joint. 2. Gasket Design: Provide rubber gaskets of the 0-ring type. Provide the composition and physical requirements of the gasket for joints not normally subjected to internal pressure meeting the requirements of ASTM C 443. Do not stretch the gasket more than 20 percent when placed on the spigot of the pipe. Provide the gasket of such size that when the joint is off center sufficiently to cause the outer surface of the spigot end of the pipe and the inner surface of the bell end of the adjacent pipe to come into contact at some portion of their periphery, the deformation of the stretched rubber gasket is not more than 50 percent at the point of contact nor less than 20 percent at any point of the normal diameter or thickness of the gasket before deformation. Provide the gasket to be the sole element depended upon to make the joint watertight. 3. Bell and Spigot: Provide inside surfaces of the bell and outside surfaces of the spigot to be parallel with each other within one degree and, unless otherwise permitted, with an angle of not more than 2 degrees with the longitudinal axis of the pipe. Angles greater than 2 degrees will be approved only if plant or field hydrostatic tests show that the adjacent pipes can be properly joined and that the joint will not leak under a deflection sufficient to open one side of the joint 1/2-inch wider than the fully compressed position. In no case are angles of greater than 5 degrees Page 3 of 6

approved. Provide the spigot with a preformed groove of sufficient depth to hold the gasket securely in place and produce the proper compression in the gasket. 4. Grout: Fill the interior annular space of each joint, for pipe sizes 30 inches and larger in diameter, with cement grout as specified in Section 02650. 2.2 SOURCE QUALITY CONTROL A. Tests: Test concrete sewer pipe in accordance with the applicable provisions of ASTM C 497 as required by the ASTM Specification for the pipe. Test not less than three sections of each size and class of pipe. B. Basis of Acceptance: Conform the basis of acceptance for nonreinforced concrete pipe with Section 5.1 of ASTM C 14. C. Results: Have the manufacturer submit certified test results of these tests for approval. Provide the number of pipe tested equal to one percent of the number of pipe manufactured in any one size and class, except that not less than three pipes are to be tested unless otherwise approved. PART 3 EXECUTION 3.1 INSTALLATION A. General: Install all nonconcrete sewer pipe in accordance with the manufacturer's recommendations and approved shop drawings and as specified in Division 1. B. Install nonreinforced concrete sewer pipe in accordance with the requirements of Section 02650. 3.2 FIELD QUALITY CONTROL A. Tests: After installation of the nonreinforced concrete pipe and all appurtenances, subject the pipeline to a field running test, as specified in Division 1, under actual operating conditions. B. Leakage Tests: Test the nonreinforced concrete pipelines for leakage after completion in accordance with Section 02676. Page 4 of 6

3.3 SCHEDULES A. Refer to the schedules contained in Section 02650 Laying and Jointing Buried Pipelines for information on the piping that is to be constructed using the pipe materials and methods specified herein. END OF SECTION Page 5 of 6

(NO TEXT FOR THIS PAGE) Page 6 of 6