Best Practices Guide for Obvius Data Acquisition Products



Similar documents
Wireless Ethernet LAN (WLAN) General a/802.11b/802.11g FAQ

SmartDiagnostics Application Note Wireless Interference

WIRELESS INSTRUMENTATION TECHNOLOGY

Application Note: Monitoring Branch Circuit Loads in Critical Facilities

USB 3.0* Radio Frequency Interference Impact on 2.4 GHz Wireless Devices

EKT 331/4 COMMUNICATION NETWORK

Networks. The two main network types are: Peer networks

Environmental Monitoring: Guide to Selecting Wireless Communication Solutions

Introduction. Network Basics. Workstations. Server. Hub

Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.

WIRELESS REMOTE MONITORING OF CATHODIC PROTECTION SYSTEMS. John Hawkyard MICorr Deputy General Manager Rawabi Corrosion Technology Co Ltd Al-Khobar

Unidirectional Transmitter/ Receiver Units Introduction

communication over wireless link handling mobile user who changes point of attachment to network

The data can be transmitted through a variety of different communications platforms such as:

Demystifying Wireless for Real-World Measurement Applications

Installation Instructions. Wireless Adapter/Repeater. Introduction Rev C

Guide for Performing a Wireless Site Survey. 2.4 GHz IEEE g/802.11b/

Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka

SECTION 2 TECHNICAL DESCRIPTION OF BPL SYSTEMS

This Antenna Basics reference guide includes basic information about antenna types, how antennas work, gain, and some installation examples.

Introduction to Z-Wave. An Introductory Guide to Z-Wave Technology

Network Design. Yiannos Mylonas

M2M I/O Modules. To view all of Advantech s M2M I/O Modules, please visit

Understanding Range for RF Devices

Planning BACnet networks

For the purpose of setting up a home network, all you need to worry about are two major categories of components:

Understanding Device Level Connection Topologies

Cisco Integrated 4G Low-profile Outdoor Saucer Antenna (ANT-4G-SR-OUT-TNC)

Getting the Most Out of Your WirelessHART System

Cisco Outdoor Wireless Mesh Enables Alternative Broadband Access

Product Overview. Steve Erickson

FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK

General Camera Information and use for NuAire Biological Safety Cabinets (BSC) and Isolators

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Chapter 2 Wireless Settings and Security

How To Wire Wireline Cable To A Cell Phone (New Zealand)

How To Use A Ds340 (Dsp)

Ethernet Radio Configuration Guide

Chapter 9A. Network Definition. The Uses of a Network. Network Basics

C Spire Indoor Cell Zone FAQs

WEB log. Device connection plans

WIRELESS SOLUTIONS. The Right Connection for. Make the Right Connection for Industrial Wireless Solutions

Technology White Paper Capacity Constrained Smart Grid Design

Networking. Introduction. Types of Wireless Networks. A Build-It-Ourselves Guide to Wireless Mesh Networks

Computers Are Your Future Prentice-Hall, Inc.

NETWORKING TECHNOLOGIES

Wireless LAN Concepts

ProCurve Networking. Troubleshooting WLAN Connectivity. Technical White paper

Chapter 2 Configuring Your Wireless Network and Security Settings

Municipal Mesh Network Design

Chapter 4 Connecting to the Internet through an ISP

Wireless Feasibility Survey And Site Survey For Sandersville, GA. Jay Sexton and Jeffrey Lee Georgia Tech Research Institute

is the power reference: Specifically, power in db is represented by the following equation, where P0 P db = 10 log 10

EDI Distributor Control Interface Wiring and Setup Instructions

1 Which network type is a specifically designed configuration of computers and other devices located within a confined area? A Peer-to-peer network

Southern Utah Water SCADA Project and Dispelling Myths regarding 900MHz Spread Spectrum Technology:

Wireless The answer to all our communications needs?

Contents Chapter 1: Introduction... 3 Chapter 2: Ethernet (LAN)... 5 Chapter 3: ZigBee Wireless Connection Options... 7

Technology Spotlight on Cellular Data Networking for SCADA system networks. Presented by Teamwork Solutions, Inc.

Are apps available for Virtual Water Assistant? No. We use a mobile website.

Still Images or Video. Long Battery Life. Easy and Quick to Setup. How do they work?

Data Transmission. Data Communications Model. CSE 3461 / 5461: Computer Networking & Internet Technologies. Presentation B

Cisco Outdoor Wireless Network Serves Up Automatic Meter Reading

Wireless Medical Telemetry Laboratory

Wireless Links - Wireless communication relies on radio signals or infrared signals for transmitting data.

AIRAVE Frequently Asked Questions

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

Why WireFree: Wireless Gas Detection System Basics and Benefits

Crestron Best Practices for Installation and Setup of Crestron RF Products Reference Guide

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

Parking Guidance System

LoRaWAN. What is it? A technical overview of LoRa and LoRaWAN. Technical Marketing Workgroup 1.0

Guide for wireless environments

Applying Mesh Networking to Wireless Lighting Control

Defining the Smart Grid WAN

Contents. Section A Networking Basics Learning the Basics Section B Wired Ethernet Networking... 17

Documentation. M-Bus 130-mbx

PCMCIA Wireless LAN Card User s Manual

Understanding Device Level Connection Topologies

WiFi Antenna Installation Best Practices Design Guide

Basic Network Design

Security & Surveillance Cabling Systems

Internet-Accessible Power Monitoring & Control Systems

Process Control and Automation using Modbus Protocol

DSX Master Communications

Cellular Wireless Antennas

Communication Setup Application Note

Wireless Networking for Small Businesses, Branches and Home Offices

FIBRE TO THE BTS IMPROVING NETWORK FLEXIBILITY & ENERGY EFFICIENCY

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2

Wireless LANs vs. Wireless WANs

12. INDOOR INSTALLATION

Wireless Field Data Backhaul

AC1900, N900, and N450 WiFi Cable Data Gateways

New DuraFon-SIP Long-Range Cordless Phone System. Presented by Walter Navarro

How To Know If You Are Safe To Use An Antenna (Wired) Or Wireless (Wireless)

Tnet WIRELESS MESH SENSOR NETWORKS

cellularbooster.com THINGS YOU MUST KNOW BEFORE YOU 7BUY AND INSTALL A CELLULAR BOOSTER

Home Wi-Fi Gateway Instructions

CHAPTER 1 1 INTRODUCTION

Transcription:

Best Practices Guide for Obvius Data Acquisition Products Part I: Background/general information Obvius LLC provides industry-leading products for cost effective data gathering, storage and communications. The company's products fall into three major categories: 1. Data acquisition servers (DAS) Obvius provides several varieties of data acquisition servers that are designed gathering and storing interval data from a number of different meters. The DAS also provides options for communicating the interval data to local or remote database servers using LAN's, phone lines or cellular communications. This guide will focus on the company's AcquiSuite (model A8812-1, also A8810 AcquiSuite EMB) DAS with Modbus communications support. 2. Wireless mesh networking products the company's ModHopper line of radio transceivers is the industry's first designed specifically for wireless Modbus communications and provides wireless RS 485 communications for any Modbus master/slave network. 3. Input/output modules Obvius also provides support for a number of Modbus RTU input/output modules to allow connectivity of both new and existing meters and sensors that do not have Modbus capability. The AcquiSuite DAS (see Illustration 1, below) provides plug-and-play connectivity for gathering interval data from a variety of new and existing Modbus meters. The AcquiSuite automatically detects and loads drivers to gather interval information from a variety of meters, including the following meters (as of 9/16/2011): Obvius A8332-8F2D Flex IO Module Square-D Power Logic Enercept power meter class 3020 Obvius A8923-11 HD Pulse Module Square-D Power Logic Energy Meter with comm board Obvius A8923-4 IO Module (4A4P-M2) Square-D Power Logic PM710 Power Logic ION 6200 Obvius R9120 ModHopper Siemens ION 9200 Veris HXO/T-485M Siemens ION 9300, 9330, 9350 Veris Enercept H8035 and H8036 Siemens ION 9510, 9610 Veris H8163 Energy Meter with comm board E-Mon ProMon (modbus version), Class 3000, 3400, 5000 Veris H663 and H704 Branch Current Monitor E-Mon pulse output meters (all) Veris E30, E31, H8238 Multi Circuit Monitor GE kv2c with Modbus card Veris E50C, E51C, H8436, H8437 Power Meter Acromag 902MB, 10 channel relay output module Power Logic ION 6300 Advantech ADAM-4051, 16 channel digital input module Power Logic ION 7300, 7330, 7350 Advantech ADAM-4068, 8 channel relay output module Power Logic ION 7500, 7600 PDI BCMS Power Logic ION 8500 For the most current list, visit the Obvius website: http://obvius.com/pdfs/tn23-supporteddevicelist.pdf 3300 NW 211th Terrace, Hillsboro, OR 97124 Page 1

Modbus devices are connected to the AcquiSuite by daisy-chaining a two-conductor twisted wire to each of the meters and then to the RS 485 connection on the DAS. As each device is connected, the AcquiSuite will determine the device type, load the appropriate drivers and begin logging interval data. All interface with the AcquiSuite is accomplished using any web browser connected to the network port on the AcquiSuite using a straight-through (or crossover) cable or hub for local connection or the local area network if available. For more information on the AcquiSuite, including installation manuals and technical specifications, visit the Products section of the Obvius website: http://www.obvius.com Power USB LAN Modem RS 485 Pulse and Analog Inputs Illustration 1 AcquiSuite A8812-1 connections 3300 NW 211th Terrace, Hillsboro, OR 97124 Page 2

The ModHopper (model R9120-x) wireless transceiver provides mesh communications in a Modbus format to support ease of connectivity to any Modbus master/slave network. Used in conjunction with the AcquiSuite, the ModHoppers provide a complete wireless data acquisition system for installation in existing facilities with minimal wiring requirements. A typical ModHopper network is shown in Illustration 2 below. Each of the ModHoppers forms an integral part of the self-configuring and self-healing network that does not require software or a PC for configuration. Each of the devices can also function as a repeater with no connected Modbus devices in the event there are dead spaces within the building where communications are difficult. The ModHopper uses an FCC approved unlicensed 900 Mhz radio using frequency hopping spread spectrum (FHSS) radios to transmit Modbus data between meters and the AcquiSuite. In a standard application, up to 32 Modbus devices can be connected to each ModHopper and typical transmit distances are up to 1500 ft indoors. The FHSS radios in the ModHoppers minimize (but do not eliminate) interference from outside radio sources such as cell phone repeaters or other ISM band radio devices. Best practices in installation (see below) will serve to greatly improve the success rate for wireless transmission of meter data. For more information about the ModHopper, see the Products section of the website: http://www.obvius.com 3300 NW 211th Terrace, Hillsboro, OR 97124 Page 3

Part II: General best practices guidelines The following are general guidelines that will help in planning and set up of a ModHopper and AcquiSuite wireless data acquisition network. Separate sections following will address specific recommendations for site surveys, installation and commissioning. This guide assumes that the user has a general working knowledge of the installation and wiring of Modbus RTU devices, so the primary focus will be on the wireless RS 485 installation. Less emphasis will be placed on the AcquiSuite and its functionality other than some best practices for locating the AcquiSuite(s) and troubleshooting installations. For each of the sections in this guide, the best practices will be in the format BP #x: with the practices listed in order of importance whenever practical. BP #1: The single most important contributor to a successful installation is to always remember that the ModHopper is a radio and that the installer should be aware of environmental factors that would be likely to impair radio signals. These factors include other sources of radio signals, large metal objects (e.g., electrical panels) and any obstructed locations. BP #2: When installing ModHoppers, always allow at least 10 feet of separation between each radio. Although the ModHoppers are using FHSS to avoid interference, signals transmitted in frequencies close to the 900 Mhz signals of the ModHopper will be seen by the antennas and will likely result in reduced throughput. BP #3: The ModHopper functions as a Modbus device on the network, therefore each ModHopper MUST have a unique Modbus address from all other devices on your Modbus network. Since the ModHopper is a communications node with multiple connected devices, address conflicts with other devices will seriously impair the overall network operation. It is advisable to designate a range of Modbus addresses exclusively for the ModHoppers as this will minimize the likelihood of conflicts and make troubleshooting much easier. BP #4: Avoid placing ModHoppers in and around heavy steel work or very thick concrete walls. There are unique ways to work around areas like this. For example in a deep sub basement or below grade parking structure, an easy solution would be to install one ModHopper at the below grade location. Then run a hardwire from it back to another ModHopper located above grade and which is 'connected' to other ModHoppers. In this implementation, you are adding a hop to the overall comms channel, but the overall impact will allow better and more reliable comms. Another option is to hardwire the basement ModHopper directly to the AcquiSuite, providing a solid line of communication. BP #5: Avoid placing ModHoppers in/on/around electrical conduits or near sources of high electrical 'noise' - generators, powerful antennas, VFD drive electric motors, or other sources which might introduce ambient interference. BP #6: Adding more ModHoppers to facilitate long wiring runs should only be done after careful consideration of the number of hops that may be added. In general, the best way to avoid delays in data delivery is to minimize the number of hops that the data must make to reach the AcquiSuite. In many cases it is more practical (and costeffective) to add a hard-wired twisted pair connection if possible to eliminate long linear runs. 3300 NW 211th Terrace, Hillsboro, OR 97124 Page 4

BP #7: Use shielded twisted-pair 2 conductor wire for hardwired installations, Belden 1120A is a recommended product for this. Make sure that the color-coding is consistent between + and -. Illustration 3 AcquiSuite EMB A8810 connections BP #8: Since one key element in overall throughput is the number of Modbus devices attached to a single wireless node (ModHopper), load balancing the networks can be beneficial. For example, if you have 50+ high data rate Modbus meters, sometimes using 2 or 3 ModHoppers can help even out the routing sequence data being collected and sent back to the AcquiSuite. BP #9: More power (or more gain) does not necessarily translate to better network performance. In areas where you have difficulty attaining good signal integrity, the use of high gain Yagi or Dipole antennas may help considerably. It is important, however, to keep in mind that the overall network looks for the optimum (i.e., most reliable) path, so adding a higher power antenna at one location may actually hinder performance if other ModHoppers in the adjacent network route higher levels of traffic through the ModHopper with the higher gain antenna. In general, it is a good practice to contact Obvius for assistance in using high gain antennas mixed with standard antennas. 3300 NW 211th Terrace, Hillsboro, OR 97124 Page 5

Part III: Site survey best practices Note: This section deals primarily with issues related to surveying sites for wireless networks, but it assumes that the user is familiar with the following: Part I: Background/general information of this guide Part II: General best practices of this guide AcquiSuite installation manual ModHopper installation manual BP #1: Start with with a layout map of the building or site showing the physical locations and quantities of new and existing Modbus devices that need to be connected to the ModHopper network. This information will be critical in determining the proper load balancing of the network for optimal throughput. BP #2: Once the quantities of Modbus devices for each location is determined, add one or more ModHoppers to each physical location (e.g., meter bank) as a starting point. In many cases, this step will provide a quick look at logical communications sub-networks based on the proximity of ModHoppers to each other. BP #3: One of the most important elements to remember is that a good layout generally minimizes the number of hops that a particular device needs to use to get to the AcquiSuite. While each ModHopper can function as a repeater, adding additional ModHoppers should be only one of the options considered in designing an optimum layout as each ModHopper in most cases adds an additional hop for the data. BP #4: Once you have established the locations for the meters and ModHoppers, map out the building locations. Mark the ModHopper address numbers on the map for reference by the installer to minimize the likelihood of duplicate addresses once the network is installed. 3300 NW 211th Terrace, Hillsboro, OR 97124 Page 6

BP #5: Try to arrange the modbus Master unit in the center of the network, to minimize the average number of hops to any node location. In many applications, it will be advantageous to have ModHoppers that are hardwired to an AcquiSuite in areas where radio comms may be difficult. Balance the cost of running a twisted pair RS 485 loop with the number of additional ModHoppers required to get the data back to the AcquiSuite. BP #6: Arrange units in a star or cluster, and not in a linear configuration. Place the Modbus master device near the center of the cluster if possible. BP # 7: Radio traffic is hindered by metal, including metal studs located on interior walls. Locations near outdoor walls are usually best. BP #8: Large clusters of modbus devices will require lots of modbus traffic. Keep the number of hops to these locations at 3 or fewer. BP #9: Since the ModHopper operates on a 900 MHz FHSS radio, its performance is very similar to a cell phone operating in the same range. If your cell phone does not work inside the building, it is a good indication that you are in a challenging environment and you should look carefully at the design in areas where cell coverage is marginal. This includes transformer vaults, concrete lined basements, below grade parking garages, etc. 3300 NW 211th Terrace, Hillsboro, OR 97124 Ph: +1-503-601-2099 Fax: +1-503-601-6878 Page 7 Revised April 2, 2012

BP #10: Verify with local facilities personnel the presence of cellular repeaters or wi-fi networks. These installations will often transmit at very high power levels and may serve to limit the ability of the ModHopper radio signal in certain areas. 3300 NW 211th Terrace, Hillsboro, OR 97124 Page 8

Part IV: Installation best practices Note: This section deals primarily with issues related to installation of wireless networks, but it assumes that the user is familiar with the following: Part I: Background/general information of this guide Part II: General best practices of this guide AcquiSuite installation manual ModHopper installation manual BP #1: Mount the ModHopper a minimum of 10 feet away from any other radio device including other ModHoppers, cordless phones, and wifi access points. Cellular transmitters and grid arrays require a greater distance depending on their transmission power. BP # 2: Do not mount the ModHopper on metal objects. The antenna of the ModHopper must be free and clear of metal beams, conduit, pipe, ducts, etc. BP #3: Be aware of what is located on the opposite side of the wall the ModHopper is mounted on. The ModHopper with the standard antenna broadcasts equally in all directions. If the other side of the wall has, for example, a large metal enclosure, that metal will severely limit the range of the ModHopper. 3300 NW 211th Terrace, Hillsboro, OR 97124 Page 9

BP #4: Do not run cable or conduit on top of the ModHopper as it will likely cause a reduction in the ability of the ModHopper to communicate. BP #5: Whenever possible, mount the ModHoppers at the highest location on the wall. Even a few feet of elevation can have a very significant effect on the quality of the data throughput. BP #6: Whenever possible, mount all the ModHoppers at the same elevation (see BP #5). Having all the antennas on the same plane will greatly improve the signal quality in most instances. This, however may have to be balanced with the other practices (for example, it is generally better to have a ModHopper at a slightly different elevation if that location avoids large metal enclosures that would have an adverse impact. BP #7: It is always good practice to assign a cluster of contiguous Modbus addresses to the ModHoppers that is distinct from the meters. One option is to assign the ModHoppers with addresses between 200 and 247 as many meters have software configurable modbus addresses that default to low numbers (address 1, 15, etc). Others such as the ion 73xx, 75xx, 62xx meters default to 100-199. The actual address allocation is up to the installer, but should be designed to avoid default Modbus meter addresses. Following this practice will greatly improve any troubleshooting problems that may arise after installation. 3300 NW 211th Terrace, Hillsboro, OR 97124 Page 10

Part V: Commissioning best practices Note: This section deals primarily with issues related to commissioning sites for wireless networks, but it assumes that the user is familiar with the following: Part I: Background/general information of this guide; Part II: General best practices of this guide; AcquiSuite installation manual; ModHopper installation manual; BP #1: The biggest single mistake in commissioning and troubleshooting is to attempt to bring the entire network online all at once. This practice makes it extremely difficult to isolate different issues and will virtually insure a significant amount of wasted time and effort trying to isolate problems. Bringing the overall network up one piece at a time will provide a solid foundation for wringing out problems as they arise. BP #2: It is strongly recommended that the AcquiSuite and ModHopper network be established prior to connecting any devices. This allows the comms network to settle out and also provides a much simpler troubleshooting protocol. Use the AcquiSuite to review the routing information for the ModHoppers. If the AcquiSuite is not available on VPN, one option is to use a GSM AcquiSuite that does not require network comms to troubleshoot the initial installation. BP #3: Once the comms and data acquisition network functionality is established (see BP #2 above), audit your Modbus addresses. Make absolutely certain that there are no duplicate addresses. It is particularly important that there is no duplication of addresses between ModHoppers and meters as this will greatly hinder troubleshooting of the network once everything is brought on line. BP #4: Bring the meter banks on line one at a time by connecting the RS 485 wire to the comms port on the ModHopper. Bringing the banks on one at a time will provide an indication of wiring problems, malfunctioning meters or duplicate addresses that can be isolated to a single location. Allow several minutes for the network to settle out and resolve all the routing for the designated bank before moving on to other locations. BP #5: As each new bank comes on line, the network will require time to settle out and adjust to the additional devices on the network. After each new meter location is brought on line, use a laptop connected to the AcquiSuite to verify signal quality of the node and to verify that the appropriate number of devices can be seen by the network as a whole. 3300 NW 211th Terrace, Hillsboro, OR 97124 Page 11

BP #6: If link quality drops dramatically when a meter bank is brought on line, review the Modbus addresses and wiring to confirm that the installation and setup of the devices is correct. If this is all correct and there are a large number of meters on the loop, it may be necessary to add an additional ModHopper to balance the load on the system. 3300 NW 211th Terrace, Hillsboro, OR 97124 Page 12