10 Gigabit Ethernet over copper: Unshielded, unprotected?



Similar documents
White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care?

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair

White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable

How To Plan A Data Center Network

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks

How To Get 40G Over Copper (Wired) And 40G On Coaxian (Wireless) Cable (Wired Coaxian) (Wired Cable) (Wireline) (Powerline) And 50G Over Coaxian Cable (Wire Coaxian

Network Design. Yiannos Mylonas

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)

Gigabit Ethernet on Copper Cabling Infrastructures

Data Communications Competence Center

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

The Next Generation of Cable Technology. A technology primer from NORDX/CDT By, Eric d Allmen

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware

with Component Rating A Simple Perspective

Cabling for 10GBASE-T and Beyond - A Tangled Web

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module

How to Choose the Right Cable Category

Networks. The two main network types are: Peer networks

Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER

White Paper. Power over Ethernet Plus Update and Cabling Considerations

Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8

SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS

ANSI/TIA/EIA A, Commercial Building Telecommunications Cabling Standard.

Accelerating Light. Copper Cabling Solutions. Category 6A

Cat. 6 A EL Incredibly fast Get more

Total Solutions Verification

Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel

Category 8 Cable Transmission Measurements Comparative Study between 4-port single wire measurements and 2-port balun measurements

Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka

White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

How To Get A Better Signal From A Fiber To A Coax Cable

Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk

Ethernet Patch Cord Wiring

Enhanced Category 5 Cabling System Engineering for Performance

Chapter 4 Connecting to the Internet through an ISP

The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings. Focus on the IBDN System 4800LX from NORDX/CDT

Things You Must Know About Gigabit Ethernet 1. Understanding Gigabit Ethernet

IT Cabling Solutions

Nexus Technology Review -- Exhibit A

Advantages of 4 th Generation CAT 6A UTP Cables. Antonio Cartagena Business Development - Caribbean Leviton Network Solutions

AMP NETCONNECT Data Center Cabling Solutions

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber

Data Transmission. Data Communications Model. CSE 3461 / 5461: Computer Networking & Internet Technologies. Presentation B

Security & Surveillance Cabling Systems

SICK AG WHITEPAPER. Information for cable manufacturers Note-2_03

High Speed Ethernet. Dr. Sanjay P. Ahuja, Ph.D. Professor School of Computing, UNF

Implementing Fast Ethernet

WHITEPAPER. Cable and Connector for Hiperface dsl motor drive applications

CATEGORY 8: UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE

Network Engineers Everywhere:

PANDUIT TX6 10GIG SHIELDED COPPER CABLING SYSTEM. Innovative Connectivity Solution for Maximum Performance and Security

Ethernet/IEEE evolution

2. What is the maximum value of each octet in an IP address? A. 128 B. 255 C. 256 D. None of the above

Discussion Paper Category 6 vs Category 5e Cabling Systems and Implications for Voice over IP Networks

A Simple Model of Relative Power vs. Reach

The Effect of Network Cabling on Bit Error Rate Performance. By Paul Kish NORDX/CDT

1000BASE-T: Gigabit Ethernet. over Category. 5 copper. cabling. Acronyms and abbreviations

Frequently Asked Questions

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

Local-Area Network -LAN

Transmission of High-Speed Serial Signals Over Common Cable Media

GigaSPEED X10D Solution How

MYTHBUSTING Takes on Shielded Cabling

Upgrading Path to High Speed Fiber Optic Networks

Specification SFTP CAT6 Network Cable 23AWG CU

Broadband 101: Installation and Testing

Innovative Connectivity Solution for Maximum Performance and Security

Category 6 UTP - Cabling System

Balanced vs. Unbalanced Audio Interconnections

Feasibility Study on High Speed Transmission over UTP Cables

SMARTen 24 UTP Patch Panels

SHEET 5 CABLE TELEVISION SYSTEM

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company

Introduction to Computer

Christopher Rathgeb ECE 453 Dr. Qi 9/19/2006. Task 1: Make an Ethernet cable yourself.

Cisco - Ethernet 100BaseTX and 10BaseT Cables: Guidelines and Specifications

Specifying an IT Cabling System

Cable Products HONEYWELL SECURITY & CUSTOM ELECTRONICS. Honeywell's Genesis Series provides a full range

The High Cost of a Low-Cost Cable Certification Tester

DATA CENTER NETWORK INFRASTRUCTURE. Cable and Connectivity for the Most Demanding Networks. BerkTekLevitonTechnologies.com

SECTION TELECOMMUNICATIONS ACCEPTANCE TESTING

AMP CO Plus Insert for Cat. 6 A Applications

Chapter 9A. Network Definition. The Uses of a Network. Network Basics

Upon completing this chapter, you will be able to: Describe the primary types and uses of twisted-pair cables Describe the primary types and uses of

Copper Cables CONNECTIVITY & CABLING SYSTEM

How To Make A Data Center More Efficient

R&S ENY81-CA6 Coupling Network For radio disturbance and immunity measurements

LMR16TC Mini 10BASE-T Repeater. Installation Guide

Trends and Standards in LAN Cabling Systems Intelligent Buildings

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications

CN1047 INTRODUCTION TO COMPUTER NETWORKING CHAPTER 1 BASIC CONCEPTS OF NETWORK

Transcription:

Technical Article 10 Gigabit Ethernet over copper: Unshielded, unprotected?

Copyright 2005 Reichle & De-Massari AG (R&M). All rights reserved. Transmission and reproduction of this publication or parts thereof for whatever purpose and in whatever form is not permitted without the express written permission of Reichle & De-Massari AG. Information contained in this publication is subject to change without prior notice. This document was prepared with the greatest possible care and represents the technical status current at the time of its preparation. Subject to technical changes. Technical article: 10 GbE over Copper: Unshielded, unprotected? Version 6 en 01.08.2005 Regina Good-Engelhardt Page 2 / 9

10 Gigabit Ethernet over copper: Unshielded, unprotected? 10 Gigabit Ethernet over horizontal twisted pair copper cables right to the desktop a dream for many users, a nightmare for some planners and IT managers. If you need to invest in your LAN infrastructure now, you can t wait until the relevant IEEE Standard has been finalized. You have to decide: Cat. 6 shielded or unshielded? Or Cat. 7? Application: Technology: Format: Subjects: Goal: Target group: Authors: Enterprise cabling Copper cabling Technical article 10 Gigabit Ethernet over copper, standardization status, technical status, discussion about shielded and unshielded cabling, investment protection Introduction of the 10 GbE STAR Real10 range in the R&Mfreenet system with shielded and unshielded solutions, explanation of the current background conditions for 10 GbE Decision-makers, planners, R&M sales & distribution Regina Good-Engelhardt, Burkhard Braach Published: September 2005 IEEE 802.3ae, the standard for 10 Gigabit Ethernet over optical fiber, was passed in 2002. Since then, the most prolific LAN protocol has penetrated the WAN market. Complementing this, the optical fiber transmission medium has moved from wide area networks into MAN and campus networks and on through to backbone cabling in buildings. But, as far as price and handling are concerned, copper is still the winner when it comes to horizontal cabling. Planners and IT managers are therefore hoping for the final approval of the standard for 10 Gigabit Ethernet over copper, IEEE 802.3an (10GBASE-T), due in July 2006. The application is clear. 10GBASE-T will be the most economical way of building server clusters in data centers, keeping fiber optic solutions out of the picture in the mid-term. The alternative protocol, 10GBASE- CX4, is unlikely to succeed because of the limitation of its 15 meter range. 10GBASE-T will also move into horizontal-structured building cabling. Future-oriented planners, who set a high priority on investment security, are convinced that higher bandwidths and bandwidth reserves are necessary. The need is there, without considering visible, highly demanding applications like multimedia streaming or real-time image processing. Those that are aware of the invisible applications working in the background, such as VoIP, virus scanning, and software updates, don t need convincing that the bandwidth requirement is increasing. Moreover, the installation of a cabling infrastructure is an investment that must last for several generations of computers and software. A confusion of cables If you have to decide on an installation now, you face a dilemma. As long as IEEE 802.3an has not been approved, the ISO/IEC and EIA/TIA workgroups concerned with the necessary cabling properties remain unable to issue any definitive recommendations. The confusion for planners is made complete by EIA/TIA discussions about an augmented or extended Cat. 6/Class E specification, and the New Class E from the ISO/IEC. Nevertheless, this confusion can be largely untangled by careful consideration. The political solution If the IEEE 802.3an standard is to be successful, it must work with as much existing cabling as possible. All the manufacturers of equipment, components and software involved are interested in this. As a result, Technical article: 10 GbE over Copper: Unshielded, unprotected? Version 6 en 01.08.2005 Regina Good-Engelhardt Page 3 / 9

even Cat. 5e / Class D was briefly considered as a possible medium by the IEEE. This idea had to be abandoned for technical reasons. For the standard development IEEE assumed four cabling models with different ranges (Table 1). Model Cable type Range 1 Class F 100 m 2 Class E UTP 55 m 3 Class E shielded 100 m 4 Class E UTP, NEXT optimized 55 m to 100 m Table 1: Cabling models in IEEE 802.3an, as of July 2004 So, using Class E is feasible, and it does not have to be shielded. In fact, STP (shielded twisted pair) is only widespread in German-speaking countries, known for their thoroughness and high safety standards. Normally individually shielded S/FTP cabling is used, where the twisted pairs are shielded with foil (F) and the four pairs together are shielded again with a tin-coated copper braid (S). The French generally use U/FTP, dispensing with the common outer shielding. But the rest of the world, by far the majority, uses UTP (unshielded twisted pair) or, more precisely, U/UTP. In principle, this type of cabling should also be sufficient for 10GBASE-T. The technical solution Of course, a real effort has been made to squeeze the 10 Gbit/s into a 500 MHz bandwidth for 10GBASE-T. This is to be accomplished by distributing the data stream across all four wire pairs, using a clever encoding procedure (DSQ Double Square using 128 points from 16 x 16 / 2 bits) and multilevel pulse amplitude modulation (PAM16, i.e. 16 amplitude levels). Nevertheless, 500 MHz is difficult to realize in part because of the high attenuation of twisted pair data cables. The received signal becomes so small as to be virtually indistinguishable from noise. No wonder, then, that developers are doing all they can to reduce all likely sources of interference as much as possible. Noise within the cable and, as such, within a 10GBASE-T link, can be suppressed using intelligent DSP circuits, which is a huge high-tech effort to enable copper cable to carry 10 Gbits of data. But, this system is powerless against disturbances from outside the cable. It can only compensate for noise it knows about. This problem is particularly acute for Alien NEXT (ANEXT), crosstalk between neighboring cables and connector modules (figure 1). It is negligible for STP. In the case of UTP, however, it not only depends on the cable, but also on the way the cables are laid out. This additional complication is particularly unpleasant, because it means that the transmitted power level also depends on the way the components are installed, not just on the components themselves. Technical article: 10 GbE over Copper: Unshielded, unprotected? Version 6 en 01.08.2005 Regina Good-Engelhardt Page 4 / 9

ANEXT optimization by standardization? For 10GBASE-T, the specification of cables and components needs to be extended from the current 250 MHz up to 500 MHz. This is where views start to differ. ISO/IEC envisages a linear extrapolation of NEXT for its new Class E. TIA s Cat. 6 augmented requirement is more moderate, while the IEEE has a more relaxed limit for the values from 330 MHz upwards, which are seen as being adequate (figure 2). Let s be clear about this: It is the specifications that are new or improved, not necessarily the cables. Existing cabling can be quite capable of meeting the requirements for 10 Gigabit. Cables and modules that were good up to 250 MHz don t have to be bad up to 500 MHz. That is particularly true of highquality STP installations. As stated, the biggest uncertainty is not NEXT but Alien NEXT. There are no compulsory, reproducible test procedures for measuring this. To determine suitable test scenarios, you need to know the distances over which the cables run parallel in the real installation, and how close they are together. Paradoxically, ANEXT is more of a problem with neat installations than with the much-maligned spaghetti style of cabling. An experiment with conventional UTP cables performed in the test laboratory at Reichle & De- Massari showed differences in ANEXT of 10 db between cables laid strictly parallel to each other and those tied together only every 30 cm. ANEXT optimization by design Manufacturers of cables and components are therefore trying to build in reliability. The easiest way to reduce NEXT is to increase the spacing between the wire pairs within the cable. ANEXT and other spurious disturbances can be combated by a larger external cable diameter and a shorter twist length for the twisted pairs. This results in some optimized UTP cables having diameters of up to 10 mm! For these solutions new patch panels and outlets with greater distances between connectors are also needed. A more sophisticated approach is to use the principles of shielding and apply them to unshielded components. Swiss cabling manufacturer Reichle & De-Massari and Norwegian cable manufacturer Draka have worked together on a solution which uses foil segments to protect the cable. These segments are completely isolated from one another and from the outside, and they are short enough not to carry loop currents or act as antennas (figure 4). The matching connector modules are equipped with a metal housing. This results in improved ANEXT values without the need to ground any shielding. All about grounding No shielding grounding, so no problem with grounding? Actually, the opposite is the case. If the cables are laid in metallic, grounded frames or trunking, the (common-mode) coupling becomes a significant factor. High-quality shielded cabling typically has a common-mode suppression ratio to ground of 40 db, whereas unshielded cables barely achieve 10 db. So while STP can tolerate spurious voltages of 2.5 V at 100 MHz in the surrounding ground system, UTP can tolerate just 0.05 V at 100 MHz! A good, consistent grounding concept conforming to EN 50174-2 and EN 50310 is therefore vital, particularly for UTP systems. Technical article: 10 GbE over Copper: Unshielded, unprotected? Version 6 en 01.08.2005 Regina Good-Engelhardt Page 5 / 9

Cat. 6 shielded or unshielded? If you already have a Cat. 6 UTP installation which you want to use for 10GBASE-T, you will need to make new measurements and improvements where necessary. ISO/IEC TR 24750 and TIA TSB 155 describe installation practice and improvement methods for ANEXT optimization. But, more often than not, these may not be feasible for certain installations or parts of them. If you want 10GBASE-T capability on all links with 100% certainty, you will have to use a UTP solution that is specially designed for this, or better still, use a STP solution from the start. This will mean that you are not dependent on the installation factors described above. It is not just the material costs that have to be considered, but also the total cost including risk analysis. Cabling using Cat. 6 STP components provides 10 Gigabit capability by its very nature, whereas channels with optimized UTP components will only have this capability if they have been installed perfectly. Why not Cat. 7? Without question, due to reduced attenuation and improved shielding characteristics Cat. 7 cables provide performance for the future, and the additional cost is minimal compared with the overall costs. The problem is with the Cat. 7 connectors. Two standardized but mutually incompatible systems are available: either IEC 60603-7-7 which is based on RJ45, or IEC 61076-3-104 based on a completely new design. This means that you have to decide on one system or the other, both of which are standardized but which also have all the disadvantages of a proprietary solution. And, as long as the terminal equipment is not fitted with the corresponding Cat. 7 connectors, hybrid cables will be needed. And at the very least, the end with the RJ45 plug will downgrade the channel back to Cat 6 again. The authors: Regina Good-Engelhardt, Product Marketing Manager, Reichle & De-Massari AG (R&M). R&M is a member of the ISO/IEC Workgroup JTC 1/SC 25 WG3, in which it is actively involved in the cabling specification process. Burkhard Braach is a freelance technical editor for communications and network technology. Technical article: 10 GbE over Copper: Unshielded, unprotected? Version 6 en 01.08.2005 Regina Good-Engelhardt Page 6 / 9

Figure 1. Alien NEXT, crosstalk from neighboring cables in a cable bundle. It is strongest between same colored pairs (shown in green with red arrows) because of their common twist length. IEEE802.3an vs. ISO/IEC vs. CENELEC vs. TIA Channel NEXT values (March 2005) NEXT (db) -20.00-25.00-30.00 IEEE 802.3an, TIA TSB-155, ISO/IEC TR, CENELEC TR TIA Cat 6 Augmented ISO/IEC New Class E -35.00-40.00 100 1000 Frequency (MHz) Figure 2. Channel NEXT limit values as envisaged by various standardization bodies (as of March 2005). Technical article: 10 GbE over Copper: Unshielded, unprotected? Version 6 en 01.08.2005 Regina Good-Engelhardt Page 7 / 9

Figure 3. Alien NEXT becomes a critical factor when a lot of unshielded cables run parallel to each other over long distances, as in this riser zone. Figure 4. A new solution: discontinuous shielding of UTP cables. (Photo: R&M) 100.0 PS ANEXT Global Rack 8 Victims Around 1 UTP 90.0 80.0 70.0 [db] 60.0 50.0 40.0 PSANEXT PSANEXT 12 PSANEXT 36 PSANEXT 45 PSANEXT 78 30.0 20.0 10.0 0.0 1.00 10.00 100.00 1000.00 Frequency [MHz] Figure 5. Conventional Cat. 6 UTP cables and UTP modules cannot cope with PS (power sum) ANEXT, the sum of crosstalk power levels from neighboring channels and modules. Technical article: 10 GbE over Copper: Unshielded, unprotected? Version 6 en 01.08.2005 Regina Good-Engelhardt Page 8 / 9

PS ANEXT Global Rack 8 Victims Around 1 Real10 UTP 100.0 90.0 80.0 70.0 [db] 60.0 50.0 40.0 PSANEXT PSANEXT 12 PSANEXT 36 PSANEXT 45 PSANEXT 78 30.0 20.0 10.0 0.0 1.00 10.00 100.00 1000.00 Frequency [MHz] Figure 6. Cat. 6 UTP cables and modules optimized by means of innovative shielding keep within the limit values. 100.0 PS ANEXT Global Rack 8 Victims Around 1 Real10 STP 90.0 80.0 70.0 [db] 60.0 50.0 40.0 PSANEXT PSANEXT 12 PSANEXT 36 PSANEXT 45 PSANEXT 78 30.0 20.0 10.0 0.0 1.00 10.00 100.00 1000.00 Frequency [MHz] Figure 7. High-quality Cat. 6 S/FTP cables and modules have the most margin compared with all other solutions. All graphics: R&M Figure 8. RJ45 connector modules: Cat. 6 Real10 UTP and Cat. 6 Real10 STP Technical article: 10 GbE over Copper: Unshielded, unprotected? Version 6 en 01.08.2005 Regina Good-Engelhardt Page 9 / 9