Transformer Based Voltage Sag Generator to test Renewable Energy Systems during Grid Faults in the Laboratory



Similar documents
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Analysis, Calculation and Reduction of Shaft Voltage in Induction Generators

WIND TURBINE TECHNOLOGY

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Advance Electronic Load Controller for Micro Hydro Power Plant

Solar Power Plant Design and Interconnection

Simulation and Analysis of Parameter Identification Techniques for Induction Motor Drive

300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal

Control Strategies of the Doubly Fed Induction Machine for Wind Energy Generation Applications

Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique

Simulation and Analysis of PWM Inverter Fed Induction Motor Drive

Dually Fed Permanent Magnet Synchronous Generator Condition Monitoring Using Stator Current

Renewable Energy Laboratory for Engineering Students

Principles of Adjustable Frequency Drives

THESIS FOR THE DEGREE OF DOCTOR OF PHILOSOPHY. Modeling of Wind Turbines for Power System Studies

Renewable Energy Applications: Photovoltaic and Wind Energy Conversion Systems (WECS)

Reactive Power Generation by DFIG Based Wind Farms with AC Grid

Performance Analysis of Grid connected Wind Energy Conversion System with a DFIG during Fault Condition

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Hybrid Power System with A Two-Input Power Converter

Control Development and Modeling for Flexible DC Grids in Modelica

Modeling and Simulation of a Large Chipper Drive

Understanding Delta Conversion Online "Power Regulation" - Part 2

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

Transient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

Control of a Three Phase Induction Motor using Single Phase Supply

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.

Modeling Grid Connection for Solar and Wind Energy

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems

AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

SYNCHRONOUS MACHINES

Modeling and Simulation of a Novel Switched Reluctance Motor Drive System with Power Factor Improvement

CONVENTIONALLY reduced order models are being

Equipment Performance Due to Voltage Sags Test Results for Contactor and Induction Motor

2012 San Francisco Colloquium

Power Quality. Uninterruptible Power Supply

How To Improve Power Quality

THIS paper reports some results of a research, which aims to investigate the

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors

Wind Turbine Operation in Power Systems and Grid Connection Requirements

POWER QUALITY ISSUES IN A STAND-ALONE MICROGRID BASED ON RENEWABLE ENERGY

Knowing the FACTS. FACTS that enhance power quality in rail feeder systems

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

High Intensify Interleaved Converter for Renewable Energy Resources

Power Quality & Custom Power

DC/DC BUCK Converter for Renewable Energy Applications Mr.C..Rajeshkumar M.E Power Electronic and Drives,

POWER TRANSMISSION FROM OFFSHORE WIND FARMS

The design and performance of Static Var Compensators for particle accelerators

MULTI-LEVEL INVERTER WITH DC LINK SWITCHES FOR RENEWABLE ENERGY SOURCES

How To Improve Power Quality

Data center energy efficiency and power quality: an alternative approach with solid state transformer

Advanced Protection of Distribution Networks with Distributed Generators

Verification of Short Circuit Test Results of Salient Poles Synchronous Generator

INDUCTION MOTOR PERFORMANCE TESTING WITH AN INVERTER POWER SUPPLY, PART 2

Simulation of Ungrounded Shipboard Power Systems in PSpice

Harmonic Reduction and Load Balancing of Three Phase Four Wire DSTATCOM using Three Leg VSC and a Zig Zag Transformer

Three phase circuits

Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters

Performance Enhancement of Wound Rotor Induction Motor by VSI with Dynamic Capacitor Controlled Rotor Circuit

Multilevel DC-AC Converter Interface with Solar Panels

Guidelines for Large Photovoltaic System Integration

Renewable Energy Grid Integration

PM734F - Technical Data Sheet Winding 28

Control of a Three Phase Inverter Feeding an Unbalanced Load and Operating in Parallel with Other Power Sources

Design and Development of Speed Control of Induction motor drive using Pulse-Width Modulation

FREQUENCY CONTROLLED AC MOTOR DRIVE

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

8 Speed control of Induction Machines

Cahier technique no. 196

A bidirectional DC-DC converter for renewable energy systems

The effect of inrush transients on PV inverter s grid impedance measurement based on inter-harmonic injection

Analysis of Space Vector Pulse Width Modulation VSI Induction Motor on various conditions

Droop Control Forhybrid Micro grids With Wind Energy Source

Closed Loop PWM Control for Induction Motor Drive Using Dual Output Three Phase Inverter

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Management of Low- and High-Frequency Power Components in Demand- Generation Fluctuations of a DFIG-Based Wind-Using Fuelcell

New Pulse Width Modulation Technique for Three Phase Induction Motor Drive Umesha K L, Sri Harsha J, Capt. L. Sanjeev Kumar

Design of Four Input Buck-Boost DC-DC Converter for Renewable Energy Application

Power Quality Standards for Electric Service

Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power

International Review of Grid Connection Requirements related with Voltage Dips for Wind Farms

What Is Regeneration?

Scholars Research Library

Low Frequency AC Transmission System

LOSSELESS STARTING METHOD FOR THE WOUND ROTOR INDUCTION MOTOR

Transcription:

Transformer Based Voltage Sag Generator to test Renewable Energy Systems during Grid Faults in the Laboratory C. Wessels, T. Wehrend and F. W. Fuchs Institute of Power Electronics and Electrical Drives, Christian-Albrechts-University of Kiel, D-24143 Kiel, Germany, Tel.: +49 (0) 431-880-6105, E-Mail: chw@tf.uni-kiel.de Keywords Voltage sag generator, Grid codes, Low voltage ride through Abstract A transformer based voltage sag generator to test renewable energy systems is presented. Design considerations concerning overvoltages and overcurrents during switching action are adressed. Measurement results of a 30 kw laboratory prototype testing a line side PWM converter and a DFIG are presented. Both measurement results for investigations on the transformer based sag generator at the line side converter and the DFIG show the superb fuctionality of the sag generator. Voltage dips of variable depth, duration time and fault type can be generated without overvoltages or voltage interruptions. 1 Introduction With the increased amount of installed wind power transmission system operators are forced to tighten their grid connection requirements to guarantee a stable and safe operation of the energy network. A detailed review of international grid code requirements can be found in [1]. A fault ride through of voltage dips for renewable energy systems (RES) is required in the grid codes and in international standards as [2]. For research and development of RES voltage sag generators are needed to test the systems under defined, repeatable voltage sags of different voltage depth, fault duration and fault type. There are four main solutions to build a voltage sag generator, which are generator based [3], shunt impedance based [4], [5], transformer based [6], [7], [8] or full converter based as described in [9], [10], and [11]. In this paper design and testing of a 30 kw transformer-based voltage sag generator are described. It is easy to build in a laboratory and suitable to test renewable energy systems during voltage dips of variable depth, duration time and fault type. The paper is structured as follows. In section 2 requirements for renewable energy systems are highlighted concentrating on voltage dips. Section 3 gives an overview on four different solutions to realize a voltage sag generator. In section 4 the experimental setup of a 30 kw transformer based voltage sag generator prototype is described. Design issues concerning overvoltages and overcurrents are adressed. The laboratory equipment consisting of a line side PWM converter and a 22 kw doubly-fed induction generator (DFIG) that are tested by the sag generator are described in this section as well. Finally, in section 5 measurement results for the sag generator testing the line side converter and the DFIG are shown. A conclusion closes the paper. 2 Requirements for renewable energy systems Renewable energy systems have to fulfill international standards and grid codes to be connected to the energy network. Grid codes for wind turbines cover the steady state and transient state operation

as well as the communication and power dispatch. In steady state operation the wind turbine must provide active power to stabilize the grid frequency and reactive power to perform a grid voltage control. The main dynamic requirements concern the fault ride through capability of wind turbines. Transmission system operators have specified their recent requirements, so that wind turbines must offer ride through capability under abnormal conditions. Instead of disconnecting from the grid the turbines have to stay connected and supply reactive power to the grid continuously to support the voltage level. One Low Voltage Ride Through requirement from the german transmission code is shown in Fig. 1. A detailed review on international grid code requeirements can be found in [1]. Figure 1: LVRT in german VDN Transmission Code The International Electrotechnical Commission (IEC) developed and released the IEC-standard 61400-21 for testing and assessing power quality characteristics of grid-connected wind energy converters [2]. The standard stipulates the measurement of the turbine electrical behaviour under symmetrical three phase and asymmetrical 2 phase voltage dips of different amplitudes (90 %, 50 % and 20 %) and duration (0,2 ms to 0,5 ms). However, to predict the behavior of renewable energy systems under voltage dips and to fulfill international standards like the IEC 61400-21, voltage dip generators are needed. 3 Overview on voltage sag generators In summary there are four different types of voltage dip generators, which are 1) generator based, 2) shunt impedance based, 3) transformer based and 4) full converter based. An overview on the four voltage sag generator types is shown in Fig. 2. Figure 2: Overview on the four different types of voltage sag generators

3.1 Generator based voltage sag generators In [3] a diesel powered 15 kw synchronous generator is presented as sag generator for testing electrical equipment. The synchronous generator has been modified to give controlled symmetrical voltage sags by changing the field excitation. The hardware expense is high due to the weight and scale of the diesel engine and the synchronous generator. Only symmetrical voltage sags can be emulated with this topology. Field tests show symmetrical voltage sags with a rather slow decrease of voltage within several grid periods. To emulate more realistic transient grid faults symmetrical and asymmetrical 1- and 2-phase dips or even phase voltage shifts and harmonics as well as a more dynamic decrease in the voltage within milliseconds is desirable. 3.2 Shunt impedance based voltage sag generators A voltage dip can also be created by switching an impedance in parallel to the line. The current flow in the additional path causes a voltage drop across the impedance, that leads to the voltage dip. In [4] a thyristor controlled reactance consisting of an inductance, a bidirectional thyristor and a step-down transformer is presented. The step-down transformer is used to reduce the voltage rating of the thyristors. The current through the impedance, and though the voltage dip depth, can be controlled by the method of firing delay angle control. This kind of control causes significant undesired harmonics that must be reduced by additional harmonic filters, increasing the hardware expense of the system. A voltage sag generator consisting of one shunt and one series impedance to test wind turbines up to the 5 MW range is presented in [5]. The shunt impedance is used to decrease the line voltage while the series impedance immunizes the grid from the fault. The depth of the voltage dip can be adjusted by changing the value of the impedance. Though an impedance bank is necessary. A switch to connect the line directly to ground is included to produce voltage dips down to 0 % voltage. Summarizing the shunt impedance voltage sag generator solution allows the generation of one to three phase voltage sags of variable depth. No controllable generation of harmonics is possible. For the thyristor controlled reactor solution the undesired harmonics must be reduced by filters. 3.3 Transformer based voltage sag generators A transformer in combination with appropriate switching devices can also be used to generate different voltage sags. The switch changes the output voltage from nominal to sag voltage by connecting another transformer output level to the load. In [6] a low cost single phase transformer-based voltage sag generator as laboratory prototype is presented. In [7] three single phase variacs with adjustable output voltage are used to generate symmetrical and unsymmetrical voltage dips. The duration of the voltage decrease is approximately 100 milliseconds which is a rather slow performance for a voltage dip. Thus, a step transformer combined with switches should be used to generate dynamic, transient voltage dips. The transformer based solution is suitable for building a low cost laboratory type voltage sag generator because standard components like a step transformer and power electronic switching devices as well as a simple control scheme can be used and the grid pertubation like harmonics or overcurrents is low. 3.4 Full converter based voltage sag generator A fourth solution to build a voltage sag generator is a full converter setup. A back-to-back converter is connected in between the grid and the load. By controlling the load-side output voltage all kinds of grid faults can be emulated. In [9], [10], and [11] such devices are described. The hardware is expensive and the control algorithm is complicated compared to the other sag generator solutions. A comparison between a full converter based and a transformer based sag generator can be found in [8]. It is concluded, that the full converter setup is powerful in creating all kinds of grid faults,

but due to the disadvantages of the complex control, high cost and less reliability due to the limited overvoltage and overcurrent capabilities of the IGBT s the transformer based sag generator with bidirectional switches is the preferred solution for laboratory type application. A series connected FACTS (flexible AC transmission system) converter also known as dynamic voltage restorer is normally used to mitigate voltage dips in power systems. By generating an appropriate voltage this device can also be used to generate voltage sags and swells. Note, that as a fifth class of voltage sag generators a waveform generator can also be used to create output voltages with desirable charactersics as varying magnitude, frequency, duration and harmonics but they are not available or very expensive in the comparable power rating of renewable energy systems and thus not included here. 4 Experimental setup design and description 4.1 Transformer based voltage sag generator According to the advantages of the transformer based voltage sag generator topology highlighted in the previous section, such as simple realization and relative low cost a 30 kw laboratory type sag generator was built and is described in this section. The one phase equivalent circuit is shown in Fig. 3. Figure 3: One phase equivalent of transformer based voltage sag generator topology A 30 kw 3-phase delta-star connected, variable ratio, isolating transformer (primary side: V N = 400V/I = 43A) was used that allows the adjustment of five different output voltages which are 12.5 %V N = 50 V, 37.5 %V N = 150 V, 62.5 %V N = 250 V, 80 %V N = 320 V and 100 %V N = 400 V. By using appropriate switching devices a voltage dip can be emulated by switching another output level to the load by switching on switch 2 and switching off switch 1 (see Fig. 3). To conduct current in both directions bidirectional switches have to be chosen. There are three different possibilities to realize a switch as described in [8], which are a relay, bidirectional thyristors or bidirectional IGBT s. A high power rating can be achieved using a relay but due to the inherent physical conditions it is difficult to control precisely the action time of the relay which will cause short-term voltage interruptions and high peak voltages, which is unfavorable when testing sensible electronic equipment precisely. Compared to a relay, a bidirectional switch composed of thyristors has many advantages such as fast switch speed, noise-free action, no spark, long life, vibration resistance and high reliability. But the thyristor is a half-controlled device and switching can only occur at the zero-crossing point of the current. Thus, for a three phase system two- or three-phase-faults will not occur simultaneously. This problem can be solved using full-controllable IGBT switches in bidirectional topology that allow fast turn-on and turn-off and precise phase control of one- to three-phase voltage sags. In the laboratory prototype twelve (four per phase) Toshiba MG500Q1US1 devices are used that have a maximum rating of V CE = 1200V and I C = 500A, which is quite overrated for the 30kW power rating of the sag generator but eventually occuring peak voltages or currents can be studied safely. The voltage sag duration and the gate signals for switch 1 and 2 are emulated by an ATMEL 8 bit microcontroller. Simultaneous switching from switch 1 to switch 2 must be avoided due to the short circuit peak current in the IGBT s. Thus, switch 2 is turned on after a given delay time. The delay time must be designed precisely to avoid overcurrents. In the laboratory setup it was designed experimentally.an overvoltage at the output of the transformer can be caused by switching off large

load currents if the load contains inductances like machines that have an inductive characteristic or converters that are typically connected by line filters to the grid. To avoid a fast decrease of the current di dt slow switching of the IGBT s was implemented by choosing large gate series resistances. Note that during the slow switching of the device high power losses are produced that may decrease its lifetime. Thus an overrating of the power modules is necessary. To protect the IGBT s from overvoltages additional varistors are installed across each device. The described transformer based sag generator was built in the laboratory and shown in Fig. 4. Figure 4: Picture of transformer based voltage sag generator laboratory prototype For laboratory tests it is connected to a wind energy test system comprising a 22 kw doubly-fed induction generator. The rotor of the machine is fed by a back-to-back converter via slip rings. Investigations using the sag generator have been done separately on the line side converter of the back-to-back converter and on the stator of the DFIG. Both systems are described in the following subsections. 4.2 Test devices 4.2.1 Line side converter The experimental setup of the sag generator connected to the line side converter is shown in Fig. 5. Figure 5: Experimental setup with sag generator connected to line side converter nected to Figure 6: Experimental setup with sag generator con- DFIG The line side converter is a 2-level PWM converter with a DC link capacitance of C DC = 8mF. The six pack module is an Infineon BSM100GD120DN2 with a maximum rating of V CE = 1200V and I C = 100A. The converter is connected to the grid by a line filter consisting of a three phase inductance of L = 3mH. To control the line side converter a standard voltage oriented control with an outer DC voltage PI controller and inner PI current controllers as described in [12] is applied and implemented on a dspace 1104 board. The DC voltage is controlled to 320 V and limited to 375 V by a DC-chopper for security reasons. Tests are performed at a line-to-line voltage of V N = 160V. The voltage level is chosen to adapt the converter to the low rotor voltages of the doubly

Figure 7: Symmetrical voltage sag Figure 8: 2-phase voltage sag at line Figure 9: 1-phase voltage sag at line at line side converter 35 % 200 ms side converter 35 % 200 ms; upper) side converter 35 % 200 ms ; up; upper) line voltages, middle) DC line voltages, middle) DC voltage, per) line voltages, middle) DC voltvoltage, lower) line currents lower) line currents age, lower) line currents fed induction generator that loads the converter. For this purpose the DC link is connected to the rotor side converter of the DFIG. Experimental results are taken at a DC link power of 3 kw. 4.2.2 Doubly-fed induction generator (DFIG) The experimental setup of the sag generator connected to the stator of the doubly-fed induction generator is shown in Fig. 6. The DFIG is a 22 kw machine connected via slip rings to a back-to back-converter. The line side converter is described in the previous subsection and connected to a faultless grid and not connected to the sag generator. The rotor side converter has the same topology but is controlled by a separate dspace 1006 board. The DFIG shaft is powered by an inverter fed 18,5 kw squirrel cage induction machine (SCIM) modelling a wind turbine. The DFIG topology for wind turbine applications is described in [13] and [14], whereas the dynamic behavior of the DFIG is presented in [15] during three phase voltage dips and in [16] during asymmetrical voltage dips. Experimental results are taken at an apparent stator power of S = 12, 5kVA, a line-to-line stator voltage of VN = 400V and a slip of 10% subsynchronous which results in a mechanical speed of 1350r/min. 5 Measurement results Measurement results using the transformer based voltage sag generator have been performed at the research laboratory for power electronic generator systems in wind turbines described in [17]. The sag generator was tested at a 22 kw DFIG and a line side converter described in the previous section. Results are recorded using a Dewetron data acquisition device. It will be shown, that the transformer based voltage sag generator allows testing power electronic equipment under voltage sags of variable duration, amplitude and faulted line. 5.1 Line side converter The results shown in Fig. 7-9 show a three, two and one phase voltage sag for the duration of 200 ms. There are no voltage interruptions or spikes. The output voltage decreases from nominal voltage to sag voltage within less than one millisecond. By regulating the ratio of the transformer and controlling the IGBTs, the required voltage sag depth, duration time and fault types can be changed. To show the reaction of the line side converter to the different voltage sags the DC link voltage and the line currents are shown as well. The active load is the rotor side of the DFIG, generating a power of 3 kw. Due to the voltage sag the power cannot be fed into the grid immediatly which leads to an increasing DC voltage. The DC voltage controller adjusts the voltage by increasing the line currents. The converter is overrated, so no curent limitations have to be activated. To decrease the DC voltage ripple due to the negative sequence voltage during unsymmetrical grid faults the control can be improved significantly as shown in [18] and [19] but is not scope of this paper.

5.2 Doubly-fed induction generator Measurement results for DFIG operation under nominal and single phase 67% voltage sag are shown in Fig. 10 and 11 respectively. The three phase stator voltages, stator and rotor currents of phase a and the accordant current spectra are shown. During nominal operation the apparent power of 12,5 kva is generated. The rotor current oscillates at 10% slip frequency. Both frequency components are shown in the lower graph. During one phase voltage dip a (2 s)ω s = 95Hz (as theoretically analyzed in [16]) frequency component is superimposed on the rotor current (see Fig. 11). Figure 10: DFIG during nominal operation; upper) Figure 11: DFIG during 1 phase 67 % voltage sag 200 grid voltages, middle) stator current (red) and rotor ms; upper) grid voltages middle), stator current (red) current (blue), lower) FFT of currents and rotor current (blue), lower) FFT of currents 6 Conclusion The design of a transformer based voltage sag generator to test renewable energy systems is described. Design considerations concerning overvoltages and overcurrents during switching action are adressed. Measurement results of a 30 kw laboratory prototype testing a line side PWM converter and a DFIG are presented. Both measurement results for investigations of the transformer based sag generator at the line side PWM converter and the DFIG show the superb fuctionality of the sag generator. Voltage dips of variable depth, duration time and fault type can be generated without overvoltages or voltage interruptions.

References [1] M. Tsili and S. Papathanassiou, A review of grid code technical requirements for wind farms, Renewable Power Generation, IET, vol. 3, no. 3, pp. 308 332, Sept. 2009. [2] IEC 61400-21: Wind turbines - Part 21: Measurement and assessment of power quality characteristics of grid connected wind turbines, Aug. [3] J. Collins, E.R. and R. Morgan, A three-phase sag generator for testing industrial equipment, Power Delivery, IEEE Transactions on, vol. 11, no. 1, pp. 526 532, Jan 1996. [4] Y. Chung, G. Kwon, T. Park, and G. Lim, Voltage sag and swell generator with thyristor controlled reactor, in Power System Technology, 2002. Proceedings. PowerCon 2002. International Conference on, vol. 3, 2002, pp. 1933 1937 vol.3. [5] M. García-Gracia, M. P. Comech, J. Sallán, D. López-Andía, and O. Alonso, Voltage dip generator for wind energy systems up to 5mw, Applied Energy, vol. 86, no. 4, pp. 565 574, 2009. [Online]. Available: http://www.sciencedirect.com/science/article/b6v1t-4tbhndg- 3/2/dbb763b2880debdd9b79eb02ae152ad1 [6] Y. Ma and G. Karady, A single-phase voltage sag generator for testing electrical equipments, in Transmission and Distribution Conference and Exposition, 2008. T&D. IEEE/PES, April 2008, pp. 1 5. [7] A. O. Ibrahim, T. H. Nguyen, D.-C. Lee, and S.-C. Kim, Ride-through strategy for dfig wind turbine systems using dynamic voltage restorers, in Energy Conversion Congress and Exposition, 2009. ECCE. IEEE, Sept. 2009, pp. 1611 1618. [8] S. Hu, J. Li, and H. Xu, Comparison of voltage sag generators for wind power system, in Power and Energy Engineering Conference, 2009. APPEEC 2009. Asia-Pacific, March 2009, pp. 1 4. [9] R. Lohde and F. W. Fuchs, Laboratory type pwm grid emulator for generating disturbed voltages for testing grid connected devices, in Power Electronics and Applications, 2009. EPE 09. 13th European Conference on, Sept. 2009, pp. 1 9. [10] S. Richter, J. von Bloh, C. Dick, D. Hirschmann, and R. De Doncker, Control of a medium-voltage test generator, in Power Electronics Specialists Conference, 2008. PESC 2008. IEEE, June 2008, pp. 3787 3793. [11] C. Saniter and J. Janning, Test bench for grid code simulations for multi-mw wind turbines, design and control, Power Electronics, IEEE Transactions on, vol. 23, no. 4, pp. 1707 1715, July 2008. [12] K. R. Kazmierkowski, Marian P. and F. Blaabjerg, Control in power electronics: selected problems, ser. Academic Press series in engineering, 2002. [13] R. Pena, J. Clare, and G. Asher, Doubly fed induction generator using back-to-back pwm converters and its application to variable-speed wind-energy generation, Electric Power Applications, IEE Proceedings -, vol. 143, no. 3, pp. 231 241, May 1996. [14] S. Muller, M. Deicke, and R. De Doncker, Doubly fed induction generator systems for wind turbines, Industry Applications Magazine, IEEE, vol. 8, no. 3, pp. 26 33, May/Jun 2002. [15] J. Lopez, P. Sanchis, X. Roboam, and L. Marroyo, Dynamic behavior of the doubly fed induction generator during three-phase voltage dips, Energy Conversion, IEEE Transactions on, vol. 22, no. 3, pp. 709 717, Sept. 2007. [16] J. Lopez, E. Gubia, P. Sanchis, X. Roboam, and L. Marroyo, Wind turbines based on doubly fed induction generator under asymmetrical voltage dips, Energy Conversion, IEEE Transactions on, vol. 23, no. 1, pp. 321 330, March 2008. [17] F. Fuchs, J. Dannehl, R. Lohde, V. Dinkhauser, S. Jensen, A. Knop, K. Rothenhagen, S. Thomsen, and C. Wessels, Research laboratory for power electronic generator systems in wind turbines comprising converters, generators, interaction and grid interaction, in Power Electronics and Applications, 2009. EPE 09. 13th European Conference on, Sept. 2009, pp. 1 15. [18] F. Magueed, A. Sannino, and J. Svensson, Transient performance of voltage source converter under unbalanced voltage dips, vol. 2, June 2004, pp. 1163 1168 Vol.2. [19] P. Rodriguez, A. Timbus, R. Teodorescu, M. Liserre, and F. Blaabjerg, Flexible active power control of distributed power generation systems during grid faults, Industrial Electronics, IEEE Transactions on, vol. 54, no. 5, pp. 2583 2592, Oct. 2007.