1 Scope Statement State of North Carolina Office of Information Technology Services AWARDED VENDOR: SUNGARD RECOVERY SERVICES, INC. 6/18/2001 Scope Statement for Business Recovery Services BCRS Contract Attachment #1 #ITS October 20, 2000
2 Table of Contents A. Scope Statement Purpose...3 B. Description of Business Functions...3 C. Scope/Objectives...3 D. Recovery Requirements...4 E. Security Requirements...8 F. Testing Requirements...9 G. Length of Contract...9 H. Response Requirements...9 I. Offeror Proposal Costs J. Political or Business Environment K. Additional Vendor Qualifications L. Additional Contractual Terms M. Evaluation Criteria N. Administrative Items O. Execution of Scope Statement Appendix A - Channel to Channel Connections for the Mainframe Page 2
3 Department/Agency: Office of Information Technology Services Issue Date: October 20, 2000 Short Description: Due Date for Scope Statement Responses: BCRS Umbrella Contract Manager: Project Sponsor: Project Manager: ITS Business Recovery Services November 17, 2000, 2:00 p.m. Sherri Garte Ann Garrett, Chief Security Officer Julean Self (919) Deadline for Vendor Questions: November 2, 2000 Submit Questions to: Non-Mandatory Vendor Conference: November 1, :00 a.m Wake Forest Rd. Raleigh, NC Submit all vendor questions to the address indicated above. All questions will be answered and submitted to vendors by November 6, A. Scope Statement Purpose The purpose of this scope statement is to procure recovery services for the ITS Data Center. ITS and its customer agencies have recently completed a project to assess and document their recovery requirements. These requirements have been consolidated and are represented in this scope statement. B. Description of Business Functions ITS serves as the data center for many of the agencies in the state. ITS operates mainframe, mid-range, and server class machines, as well as a statewide network (TCP/IP and SNA) to support hundreds of applications. C. Scope/Objectives The recovery time objective is hours and the recovery point objective is 24 hours. Monthly full-volume back-ups are performed for the mainframe production environment, which establishes a baseline for applications and production data. Incremental backups are performed by the customer agencies, with tape back-ups being transported off-site nightly. In the UNIX environment, a full back-up is performed weekly with tapes taken offsite. Incremental backups are performed nightly. The recovery plan includes transport of the tape back-ups to the recovery facility by ITS personnel, restoration of all applications and production data, and network connection to the statewide WAN and SNA network. Page 3
4 D. Recovery Requirements A detailed description of the equipment is described below. Mainframe Environment The following minimum requirements are necessary to support mainframe operations at the recovery site immediately after declaration of a disaster. All proposed equipment must be specified for each category including model numbers and where appropriate, rated speeds. CPU Requirements LPAR MIPS Central Storage Expanded Storage A MB 1600 MB B MB 2624 MB N MB 0192 MB E MB 0480 MB S MB 0304 MB Totals: MB 5200 MB A minimum of 100 MIPS uni processors for the A, B, and N LPARs are required while E and S LPARs require a minimum of 60 MIPS uni processors. Note that the S LPAR is a secure LPAR. The LPARs run OS/ with associated support software such as CICS, IMS DB-DC, DB2, etc. Channel to Channel (CTC) connections are included in Appendix A. SCTC connections should be configured using the addresses in this table for communications between LPARs. Two (2) OSA/2 adapters are required for each of the N and S LPARs (4 total). Disk Storage Requirements All disk storage for the recovery site must be EMC. The reason for this is that ITS uses the Time Finder and BCV features of EMC DASD. In addition, future plans call for the use of EMC s SRDF for remote copy. ITS requires the following EMC usable Raid 1 capacity: 1,600 volumes (2838 MB each) for the Shared LPARs (A, B, N, E) 384 volumes (2838 MB each) for the Secure LPAR (S). S LPAR DASD can access all DASD. However, the shared LPARs (A,B,N, and E) cannot access S LPAR DASD. Connectivity for the Disk Storage depends upon the solution proposed. However, connectivity must be provided to ensure adequate I/O response. Expectations for response are 6-8 MS per I/O across a 24-hour day. Page 4
5 ESCON connections from the OS/390 mainframe systems noted above must also be provided to an EMC 5930 (or equivalent) DASD subsystem with approximately 748 GB of UNIX Storage that will also be connected to a SUN E Data will be moved from the MVS system to the SUN E10000 Unix system using EMC s Infomover and Open Enabler software. See the UNIX requirements for the Sun E10000 for more specific details. Magnetic Tape Requirements One of the following will be chosen as the tape recovery solution. Please provide individual pricing for each solution as described in Section I: SOLUTION #1: 112 IBM type 3490 E drives (or equivalent) with autoloaders 2 IBM type 3420 drives (or equivalent) with 1600/6250 BPI 4 IBM type 3480 drives (or equivalent) SOLUTION #2 Shared LPARs (A, B, E, N) Robotic Tape Support with 64 high speed 3490 E type drives and storage for 25,000 cartridges (ITS currently uses STK Silos for robotic tape support) 32 IBM type 3490 E drives (or equivalent) with autoloaders 2 IBM type 3420 drives (or equivalent) with 1600/6250 BPI 4 IBM type 3480 drives (or equivalent) Secure LPAR (S) Robotic Tape Support with 16 high speed 3490 E type drives and storage for 5,000 cartridges (ITS currently uses STK Silos for robotic tape support). SOLUTION #3 ITS currently utilizes robotic tape support similar to what is described in solution #2. Vendors are asked to respond with their recommendation for the most cost effective robotic solution. This should be consistent with industry trends, best practices, and common among other customers requirements. This must also include support for legacy tape systems, including the following: 32 IBM type 3490 E drives (or equivalent) with autoloaders 2 IBM type 3420 drives (or equivalent) with 1600/6250 BPI 4 IBM type 3480 drives (or equivalent) Optical Storage requirements 1 IBM 3995 C38(8X) unit with 258 slots, 4 inside drives, and 6 outside drives. Page 5
6 Printer Requirements 1 IBM Line Printer at 4000 LPM (or equivalent). 1 IBM Printing subsystem (229 PPM) with AFP(or equivalent). Roll-feed desirable but not required. Note: Vendor must also provide as a separate cost quotation, the cost of MICR encoding capability on the noted above, as well as the cost for an additional printer (or equivalent), in order to provide duplex printing. Consoles and TSO Terminals Minimum of two 2 consoles for each LPAR with one in the control room and one in the tape library. Minimum of 10 additional TSO terminals. Sysplex Timers 2 IBM Sysplex Timers. Coupling Facilities C04s with 512 MB of Storage Each Coupling Facility Links on the CPU(s) must be provided to connect each Shared LPAR (A,B, E, and N) to each coupler twice each ( S LPAR is not included). Coupling Facility Links must be provided on each C04 to support the connectivity specified above. Network Environment Response must address how network communication will be established between the recovery center and the users in North Carolina. The statewide network has points of presence in Charlotte, Greensboro, and Raleigh. ITS intends to establish 2 DS3 lines between one of these points of presence and the vendor s presence in the same vicinity. In the event of a declared disaster, the capacity requirements would be as follows: 20 T1 circuits, or channelized equivalent for SNA, WAN, and channel extenders 20 MB capacity to support WAN traffic Note: 2 T1 circuits are required within the first 12 hours after a declaration. The remaining capacity is required within hours of a declaration. All network capacity may be on active reserve. During a test, the capacity requirements are as follows: 2 T1 circuits, or channelized equivalent for SNA, WAN, and channel extenders Below is a detailed inventory of the required network equipment: Page 6
7 NETWORK HARDWARE w/900 frame Communications Controller 2 16MB storage, tokenring TIC Communications Controller 2 16MB storage, tokenring TIC Lease Line CSU/DSU 317 ATTM24 DPC Adtran OCU-DP Card or compatible 317 ATTM24D4 000 ATT Compatible D4 Channel Bank 14 ATTLX2000 LCU ATT 8820 Channel Extender/Local 1 ATT3611B3 003 ATT K R3 DSU w/6prt TDM 1 ATT3611B3 005 ATT 14.4 DBM-V Multpt DBU R/M 1 CI7000 Base Cisco 5-Slot 7000 Router 4 CI7000-CX CIP2 w/single ESCON Interface 1 CI7000-CX EIP6 6-Port Ethernet I/F Card 2 CI7000-CX MIP2 Multichannel Dual I/F Proc. 2 CI7000-CX SIP8 8-Port Fast Serial Card 2 CI7000-CX TRP4 4-Port Token Ring I/F Card 5 CI7513 Base Cisco 11-Slot 7513 Router 1 CNT5110 PTP CNT Channel Extender Configuration 1 NETWORK LINES ISDN/GBG BRI ISDN BRI 56-62KB Channel 1 Line 000 Analog Dial Line 40 Line/GBG T3 AT&T Accunet Reserve Line 2 UNIX Environment RS/6000 R30 CPUs: 8 x 604 Memory: 1.5gb Disk: 4 x 2gb, 2.2gb disk internal; 102gb disk with RAID configuration external Tape: 2 x 8mm 5gb tape units E10000 (includes SSP) CPUs: 24 (2 domains of 8 CPUs and 8gb each, 2 domains of 4 CPUs and 4gb each) Memory: 24gb total Disk: EMC 5930 type (or equivalent) disk access with configuration capacity on first domain of 640gb, second domain of 90gb, third domain of 18gb, and fourth domain of 18gb. Operating system 18gb disks for each of the 4 domains. Each domain needs networking. The Sun E10000 is to be connected to the EMC 5930 type DASD as follows: The 2 small domains are to be connected to the DASD via Ultra Fast Wide Differential SCSI. The two large domains are to be connected the same way. A separate cost quotation is requested for connecting the two large domains to the EMC DASD using JCOR Cards(4) from JNI Corporation as an alternative. Page 7
8 Note: Disk storage must be EMC 5930 type (or equivalent) that will be connected via ESCON channels to the OS/390 mainframe(s) in addition to the connection to the SUN E These connections will permit transfer of data from the OS/390 mainframe systems to the E10000 system using EMC's Infomover and Open Enabler software. E4500 CPUs: 2 Memory: 1gb Disk: 6 x 9gb disk in a D1000 Array E450 CPUs: 2 Memory: 2gb Disk: 7 x 4.5gb disk E450 CPUs: 2 Memory: 2gb Disk: 9 x 4.5gb disk Tape: DLT 4700 Jukebox, 1 x 8mm 20gb (Mammoth) tape drive Ultra 1 (Quantity 2) CPUs: 1 x 200mh Memory: 256mb Disk: 1 x 4.5gb disk internal, 4 x 4.2 gb disk external Tape: DLT 4000 tape drive E. Security Requirements Vendor must be, and remain, compliant with all state and federal regulations for processing information, including but not limited to IRS 1075, HIPAA (Health Information Portability and Accountability Act), and any future regulations imposed upon ITS, or by ITS pursuant to future statutory or regulatory requirements. U.S. Department of Defense level C2 security is preferred. Response must specify all security and facility protection (e.g. back-up power supply) measures that are in place in each proposed recovery site. Compliance with federal or state statutory and regulatory requirements shall be determined by the State in its sole discretion. Preference will be given to vendors who are able to provide data encryption between the in-state point of presence and the recovery center. Encryption standards may be subject to federal or state statutory and regulatory requirements, and shall be determined by the State in its sole discretion. Preference will be given to vendors who are able to provide separate physical partitions of DASD and separate processors (to be used for LPAR S). Page 8
9 F. Testing Requirements Due to audit findings recommending that tests be scheduled outside of hurricane season, preference will be given to vendors who can provide testing dates in May and November each year, avoiding holidays such as Mother s Day weekend and Memorial Day weekend in May and Veteran s Day and Thanksgiving week in November. May tests will require 60 hours to start on a Thursday evening and conclude on a Sunday morning. November tests will require 84 hours to start on a Monday evening and conclude on a Friday morning. The weekend test in May is necessary in order to test the SNA network outside of normal business hours. Response must include the total test time associated with the subscription as well as the cost and availability of additional test time. Additionally, response must state the test dates for the next 3 years, starting in May Acceptable test start dates for May 2001 include May 3 rd, May 17 th, and May 31 st. Acceptable test start dates for November 2001 include October 29 th, November 5 th, November 26 th, and December 3 rd. If these dates are unavailable due to schedule conflicts, suggest reasonable alternatives for consideration. Within 45 days of contract award, the successful Vendor must develop a test plan. During the month of March 2001, or such other time as determined by the State, a minitest and structured walkthrough must be conducted to confirm procedures and evaluate the test plan. Response should describe both processes. Additionally, on occasion ITS plans to have vendor personnel perform the test procedures with only limited participation on the part of ITS personnel. This first test of this type could happen as early as November The response should describe this process and include the associated cost. G. Length of Contract Responses must be submitted for a contract term of three (3) years, with the option of extending for a fourth year and a fifth year. This contract will begin when an award is made. The anticipated beginning date is on or about January 1, H. Response Requirements Response must address the following points: A detailed description of your proposed solution The location of your proposed primary and secondary recovery sites, both of which must meet all equipment and capacity requirements Any networking capability for interconnection of recovery sites Number of technical staff, by function, supporting each relevant platform and telecommunications at primary and secondary site Support provided during testing and a declared disaster Testing dates as described in Section G, scheduled for Security measures in place at each proposed recovery center; any security ratings such as C2 Page 9
10 Facility protection measures in place at each proposed recovery center Description of the declaration process, including a step-by-step description of actions and a timeline for access to the recovery center Policy and ability to handle multiple declarations Contract management process Description and proposed location of coldsite facility (20,000 sq. feet), preferably within 50 miles of Raleigh, NC Any applicable Service Level Agreements I. Offeror Proposal Costs Each piece of equipment or service must be priced independently. Costs must cover all requirements set forth in this document, unless otherwise noted. All costs for items listed in Section D must be presented using the following table format: Item Quantity Requested by ITS Quantity Primary Site # of Current Subscriptions for Item Max # of Subscriptions Allowed for Item Total Cost Additionally, a separate table must also be presented in the above format for the following (use N/A for any columns that are not applicable): Declaration fee schedule and all costs associated with occupancy of the recovery center during a disaster Additional testing time by the hour Vendor operated test, as described in Section F Cold Site Facility UNIX servers with the following specifications: RS/6000 H50 CPUs: 4 Memory: 2gb Disk: 2 x 9gb, 5 banks of SSA DASD with 8 x 9gb disk per bank Tape: 2 x 3570-B12 tape units (4 drives, 40 slots) Page 10
11 RS/6000 F50 CPUs: 2 Memory: 512 mb Disk: 2 x 9gb internal, 3 banks of SSA DASD with 8 x 9gb disk per bank Tape: 1 x 3570-B12 tape unit RS/6000 F40 CPUs: 1 Memory: 128 mb Disk: 4 x 9gb internal Tape: 8mm 5gb tape unit E450 CPUs: 1 Memory: 256mb Disk: 4 x 9gb disks Tape: 1 x 8mm 5gb DX NT servers with the following specifications: Compaq Proliant 5500R (Quantity 3) CPUs: (1) Pentium III Xeon 550mhz Memory: 512mb EDO Disk: (3) 9gb Ultra SCSI2 with 3200 Smart Array Controller Tape: (1) 35/70 DLT tape drive Compaq Proliant 5500R CPUs: (2) Pentium III Xeon 550mhz Memory: 768mb EDO Disk: (7) 9gb Ultra SCSI2 with 3200 Smart Array Controller Tape: (1) 35/70 DLT tape drive J. Political or Business Environment ITS is a receipts supported agency and provides its services to other governmental entities. For this reason, ITS is subject to the same stringent federal and state statutes and regulations as the agencies for which it provides services. This includes IRS 1075, HIPAA, etc. The relationship between ITS and its customer agencies allows agencies to participate in business recovery tests. Such tests must be scheduled and conducted in such a way as to encourage agency participation. Vendors are encouraged to propose services, business recovery models, incentives or other measures designed to achieve and maximize agency participation. Page 11
12 K. Additional Vendor Qualifications Mandatory Qualifications include: Ability to meet all mainframe, network, and UNIX requirements included in Section D of this document, excluding those specifically stated as optional or preferable. Compliance with all security requirements as described in Section E of this document, excluding those specifically stated as optional or preferable. Failure to meet these qualifications in the judgment of the evaluators will disqualify the vendor. L. Additional Contractual Terms If data communication is established between North Carolina and the primary hotsite facility, and during a declaration ITS is directed to the secondary hotsite facility, the vendor will bear the cost of re-routing communications. Additionally, the ITS team must be physically located in the same location for both testing and in the case of a declaration. All equipment and services must be priced independently, allowing ITS the ability to modify individually by line item as needed. The response should specifically state the contract change management process. Due to the constantly changing technical environment at ITS, it is expected that the detailed technical requirements contained in this document will change between the issue date and when the contract is awarded. The changes are not expected to be material, however the awarded vendor is expected to include the changes when the initial contract is established. Page 12
13 M. Evaluation Criteria The selection criteria will not be based on lowest cost but on the best value concept. Source selection will be in accordance with the trade off method as described in the North Carolina Administrative Code, Title 4, Chapter 21B For this scope statement, the evaluation criteria shall be: Criteria # Criteria Description Percentage Weight 1 Equipment brand and model proposed 20 2 Ability to meet testing dates and requirements as 20 described in Section F 3 Total cost of ownership (contract costs plus costs 20 associated with conducting tests) 4 Ability to provide separate physical partitions of 10 DASD and separate processors 5 Ability to provide data encryption between the 10 vendor s in-state PoP and the recovery center 6 Capacity from the vendor s in-state PoP to the 10 recovery center 7 Availability and cost of items outlined in Section 5 I 8 Business processes and approach, including declaration policy and process, contract management process, etc. 5 The evaluation committee may request written clarifications of any offer received. However, the State may, at its sole discretion, refuse to accept in full or partially the response to a clarification request given by any vendor. Vendor is cautioned that the evaluators are not required to request clarification; nor is the State required to conduct negotiations, therefore, all offers should be complete and reflect the most favorable terms. The State may, in its sole discretion, conduct negotiations with one or more offerors after the bid opening. Any aspect of a vendor s bid, including price, may be subject to negotiation. The State may request Vendors to revise either or both their technical and price responses for resubmission during negotiations. This request, if made, may be made in the form of requesting a Best and Final Offer setting forth the result of the negotiations. Final ranking of responses and award of the contract will be made after the State reviews all bids and completes its evaluation, or if negotiations are conducted, after all rounds of Best and Final Offers have concluded. Award will be made to the vendor with the most advantageous overall score. The State reserves the right to reject any bid failing to meet the required evaluation criteria. Page 13
14 Note: Those vendors who do not satisfy the Vendor Qualifications specified in Section K will not be considered in the evaluation process. N. Administrative Items A non-mandatory vendor conference will be held on Wednesday, November 1 st at 10:00 am at the IT Procurement facility at 3900 Wake Forest Rd. Raleigh, NC. Important: One (1) hardcopy original and four (4) copies of your response, signed by an authorized officer of the corporation shall be submitted. In addition, an electronic PDF version of your response is required either on diskette or CD-ROM. Response should be clearly labeled as a Response to the ITS Business Recovery Services Scope Statement #ITS All responses are due on Friday, November 17, 2000 by 2:00 pm to the following address: NC Office of Information Technology Services IT Procurement 3900 Wake Forest Rd. Raleigh, NC Attention: Sherri Garte Any responses not received by that time will not be considered. O. Execution of Scope Statement Responding vendors must include the signed Execution of Scope Statement form provided on the following page: Page 14
15 EXECUTION OF SCOPE STATEMENT By signing below, the Offeror certifies that: This scope statement response was signed by an authorized representative of the Offeror This scope statement response was not derived through any acts of collusion as stated in NCGS 143B The Offeror agrees to all the mandatory terms and conditions and agrees to pay the 2% administrative fee to ITS per Section I, Paragraph B of the ITS Business Continuity and Recovery Services Contract Therefore in compliance with the foregoing Scope Statement and subject to all terms and conditions of the ITS Business Continuity and Recovery Services Contract, including all exhibits, the undersigned offers and agrees to furnish the services set forth in the Scope Statement if the Scope Statement Response is accepted by the State. Failure to execute/sign scope statement prior to submittal shall render it invalid. Late bids are not acceptable. BIDDER: FEDERAL ID OR SOCIAL SECURITY NO.: STREET ADDRESS: CITY, STATE, AND ZIP: TELEPHONE (TOLL-FREE IF AVAILABLE): FAX NUMBER: TYPE OR PRINT NAME & TITLE OF PERSON SIGNING ADDRESS: AUTHORIZED SIGNATURE: DATE: Acceptance by Agency is contingent upon ITS approval of the Agency s recommendation of award. This contract award was approved by ITS on, 20, as indicated by attached certification letter from ITS. ACCEPTANCE OF SCOPE STATEMENT RESPONSE If any or all parts of this scope are accepted, an authorized representative of Using Agency shall affix their signature hereto and this document along with the provision of the Umbrella Contract shall then constitute the written agreement between the parties. A copy of this acceptance will be forwarded to the successful offeror(s). FOR CONTRACTING AGENCY USE ONLY Offer accepted this day of, 20, as indicated on attached certification or purchase order, by (Authorized representative of Contracting Agency) Page 15
16 Appendix A - Channel to Channel Connections for the Mainframe SCTC X3X SYSE TO SYSB "OK F320 SCTC X3X D SYSE TO SYSB "OK F820 SCTC X3X SYSE TO SYSA "OK 2430 SCTC X3X D SYSE TO SYSA "OK C250 SCTC X3X SYSE TO SYSS "OK 5500 SCTC X3X D SYSE TO SYSS "OK D200 SCTC X3X SYSE TO SYSN "OK F320 SCTC X3X D SYSE TO SYSN "OK F720 SCTC X3X SYSS TO SYSE "OK 5420 SCTC X3X D SYSS TO SYSE "OK D320 SCTC X3X SYSS TO SYSB "OK F440 SCTC X3X D SYSS TO SYSB "OK F740 SCTC X3X SYSS TO SYSA "OK 2450 SCTC X3X D SYSS TO SYSA "OK C270 SCTC X3X SYSS TO SYSN "OK F340 SCTC X3X SYSS TO SYSN "OK F440 SCTC X3X F SYSB TO SYSE "OK 6420 SCTC X3X F SYSB TO SYSE "OK D240 SCTC X3X F SYSB TO SYSA "OK 3420 SCTC X3X F SYSB TO SYSA "OK C240 SCTC X3X F SYSB TO SYSS "OK 7420 SCTC X3X F SYSB TO SYSS "OK D340 SCTC X3X F SYSB TO SYSN "OK F140 SCTC X3X F SYSB TO SYSN "OK F150 SCTC X3X SYSA TO SYSE "OK 7440 SCTC X3X C SYSA TO SYSE "OK D360 SCTC X3X SYSA TO SYSB "OK F410 SCTC X3X C SYSA TO SYSB "OK F810 SCTC X3X SYSA TO SYSS "OK 7440 SCTC X3X C SYSA TO SYSS "OK D360 SCTC X3X SYSA TO SYSN "OK F310 SCTC X3X C SYSA TO SYSN "OK F810 SCTC X3X F SYSN TO SYSA "OK 2440 SCTC X3X F SYSN TO SYSA "OK C260 SCTC X3X F SYSN TO SYSB "OK F130 SCTC X3X F SYSN TO SYSB "OK F220 SCTC X3X F SYSN TO SYSE "OK 6430 SCTC X3X F SYSN TO SYSE "OK D350 SCTC X3X F SYSN TO SYSS "OK 6430 SCTC X3X F SYSN TO SYSS "OK 7430 Page 16
Scope Statement for DST IT Disaster Recovery Services
Scope Statement Administrative Services Division Information Technology Section AUTHORIZATION TO AWARD 3/23/01 VENDOR: IBM BUSINESS CONTINUITY AND RECOVERY SERVICES Scope Statement for DST IT Disaster
Scope Statement for North Carolina State University. Administrative Computing Services. Disaster Recovery Services
Authorization to Award to Vendor: Inflow Group, Inc. February 18, 2002 Scope Statement for North Carolina State University Disaster Recovery Services BCRS Contract Attachment #3 #ITS-000826 December 14,
Response to Bidder Questions and Amendment 2 to Request for Proposal 11 01 Disaster Recovery Services
STATE OF NEW YORK DEPARTMENT OF TAXATION AND FINANCE Office of Budget & Management Analysis Bureau of Fiscal Services Building 9, Room 234 W.A. Harriman Campus Albany, NY 12227 Eric Mostert, Chief Financial
SAN TECHNICAL - DETAILS/ SPECIFICATIONS
SAN TECHNICAL - DETAILS/ SPECIFICATIONS Technical Details / Specifications for 25 -TB Usable capacity SAN Solution Item 1) SAN STORAGE HARDWARE : One No. S.N. Features Description Technical Compliance
E-Business Technologies
E-Business Technologies Craig Van Slyke and France Bélanger John Wiley & Sons, Inc. Slides by Fred Niederman 7-1 Client/Server Technologies for E-Business Chapter 7 7-2 Key Ideas E-commerce applications
TECHNICAL SPECIFICATIONS For DISASTER RECOVERY SERVICES TKG 15001 02/09/2015
TECHNICAL SPECIFICATIONS For DISASTER RECOVERY SERVICES TKG 15001 02/09/2015 Index I. General Requirements II. Central Computer Recovery Requirements III. Network Recovery Requirements 1 TECHNICAL SPECIFICATIONS
Data Storage Solutions
Data Storage Solutions Module 1.2 2006 EMC Corporation. All rights reserved. Data Storage Solutions - 1 Data Storage Solutions Upon completion of this module, you will be able to: List the common storage
secure Agent Secure Enterprise Solutions
secure Agent Secure Enterprise Solutions SecureAgent Software The Secure Data Solution U.S. Patent 7,293,179; European Patent 1669872; and Others Pending Midrange Systems SecureAgent Software 2448 E 81
Request for Proposal Managed IT Services 7 December 2009
Request for Proposal Managed IT Services 7 December 2009 BuzzBack, LLC 25 West 45 th Street Suite 202 New York, NY 10036 Table of Contents 1 Summary... 1 2 Proposal Guidelines and Requirements... 1 2.1
About Backing Up a Cisco Unity System
CHAPTER 4 Introduction This chapter describes in general terms backing up a Cisco Unity system. When you back up a Cisco Unity server (and one or more Exchange servers) you need to consider the same issues
MDL 100S Product Description
Product Description Data Library 100S Delivers a Complete Virtual Tape Library for the IBM Data Library 100S (MDL-100S) provides everything you need to deploy a virtual tape library into your existing
zframe: a technical overview for
ES : A Bottom Up View of High Tech Mainframe Options zframe: a technical overview for Mike Hammock Cornerstone Systems Inc. IBM zseries Enablement Solutions [email protected] Cornerstone's zframe Objectives:
REQUEST FOR PROPOSAL (RFP) FOR SERVER VIRTUALIZATION HARDWARE, SOFTWARE AND IMPLEMENTATION
REQUEST FOR PROPOSAL (RFP) FOR SERVER VIRTUALIZATION HARDWARE, SOFTWARE AND IMPLEMENTATION RFP Circulation Date: February 20 th, 2009 Proposal Submission Deadline: March 13 th, 2009 1 Table of Contents
Independent School District No. 9 (Union Public Schools) Tulsa County, Oklahoma
May 7, 2015 Addendum No. 1 Solicitation No. 2015-RFP-12 Independent School District No. 9 (Union Public Schools) Tulsa County, Oklahoma Bidders: Please note the following changes, additions, modifications,
ClearPath Storage Update Data Domain on ClearPath MCP
ClearPath Storage Update Data Domain on ClearPath MCP Ray Blanchette Unisys Storage Portfolio Management Jose Macias Unisys TCIS Engineering September 10, 2013 Agenda VNX Update Customer Challenges and
How To Move From Iseries To Iseries Content Manager On A Microsoft Computer (For A Non-Profit)
Enterprise Content Management Request For Information Issue Date: October 18, 2013 Table of Contents Request for Information: Purpose, Scope, and Objectives 4 Louisiana State Employees Retirement System
Hosted VoIP RFP. Throughout this document, the word System refers to The Jackson Hinds Library System
Hosted VoIP RFP Throughout this document, the word System refers to The Jackson Hinds Library System Subject RFP-For a 3 year contract with the option for a 2 year voluntary extension, the System desires
BACKUP AND RECOVERY PLAN MS SQL SERVER
BUREAU OF INFORMATION & TELECOMMUNICATIONS BACKUP AND RECOVERY PLAN MS SQL SERVER Page 1 of 5 Revisions & Addendums Log: Instructions: Changes and Addendum can be sent to: James R. Douglas, Technical Analyst
Improving disaster recovery with Virtual Tape Libraries in Mainframe Environments By Deni Connor Principal Analyst, Storage Strategies NOW
Improving disaster recovery with Virtual Tape Libraries in Mainframe Environments By Deni Connor Principal Analyst, Storage Strategies NOW Recovering from disasters is an arduous process for mainframe
When EP terminates the use of Hosting CC OG, EP is required to erase the content of CC OG application at its own cost.
Explanatory Note 1 (Hosting CC OG - For Trading) Section A Notes to the Application a. China Connect Open Gateway (CC OG) : CC OG is a hardware and software component operated by the Exchange Participant,
Module 5 Introduction to Processes and Controls
IT Terminology 1. General IT Environment The general IT environment is the umbrella over the following IT processes: 1. Operating Systems 2. Physical and Logical Security 3. Program Changes 4. System Development
STATE OF MAINE REQUEST FOR PROPOSALS AMENDMENT
STATE OF MAINE REQUEST FOR PROPOSALS AMENDMENT 201405744 - Off-Site Electronic Media Storage and Transport RFP NUMBER AND TITLE: Services RFP AMENDMENT NUMBER: #1 Amendments and Submitted Questions & Answers
Addendum No. 1 to Packet No. 28-13 Enterprise Data Storage Solution and Strategy for the Ingham County MIS Department
Addendum No. 1 to Packet No. 28-13 Enterprise Data Storage Solution and Strategy for the Ingham County MIS Department The following clarifications, modifications and/or revisions to the above project shall
Symantec NetBackup 5220
A single-vendor enterprise backup appliance that installs in minutes Data Sheet: Data Protection Overview is a single-vendor enterprise backup appliance that installs in minutes, with expandable storage
Big Data Storage in the Cloud
Big Data Storage in the Cloud Russell Witt Scott Arnett CA Technologies Tuesday, March 11 Session Number 15288 Tuesday, March 11Tuesday, March 11 Abstract Need to reduce the cost of managing storage while
Department of Technology Services UNIX SERVICE OFFERING
Department of Technology Services UNIX SERVICE OFFERING BACKGROUND The Department of Technology Services (DTS) operates dozens of UNIX-based systems to meet the business needs of its customers. The services
Appendix C to DIR Contract Number DIR-TSO-2736 SunGard Availability Services Discount Level: 25% Managed Data Center Services - Cloud Hosting
Resource Pool for ECS/Managed Cloud. Order in 2GB increments. Storage added separately Level: 25% Min RAM Max RAM Cloud Resource Pool (1 GB RAM /.5 vcpu) 1 2 32 26% 2 33 64 26% 3 65 128 26% 4 129 N/A 26%
iseries Server Cloud Migration Frequently Asked Questions
iseries Server Cloud Migration Frequently Asked Questions 1. What are the advantages of the iseries cloud-hosted environment? Elimination of LEA s costs associated with power, cooling and floor space Elimination
Sizing the Compaq StorageWorks Enterprise Backup Solution
White Paper March 1999 Prepared by ECG Technology Communications Group Compaq Computer Corporation Contents The Compaq StorageWorks Enterprise Backup Solution (EBS)...3 EBS Architecture...3 EBS Components
CARMEL UNIFIED SCHOOL DISTRICT REQUEST FOR PROPOSALS - VOIP SYSTEMS
CARMEL UNIFIED SCHOOL DISTRICT REQUEST FOR PROPOSALS - VOIP SYSTEMS Carmel Unified School District ( District ) hereby invites qualified telecommunication specialists to submit proposals ( Proposals )
IBM TSM DISASTER RECOVERY BEST PRACTICES WITH EMC DATA DOMAIN DEDUPLICATION STORAGE
White Paper IBM TSM DISASTER RECOVERY BEST PRACTICES WITH EMC DATA DOMAIN DEDUPLICATION STORAGE Abstract This white paper focuses on recovery of an IBM Tivoli Storage Manager (TSM) server and explores
Best in Class Storage Solutions for BS2000/OSD
Best in Class Storage Solutions for BS2000/OSD March 2012 Product overview Agenda Online Storage Systems ETERNUS DX400 and DX8000 SHC-OSD SAN infrastructure Nearline Storage Systems ETERNUS CS and powerful
NOTICE ADDENDUM NO. TWO (2) JULY 8, 2011 CITY OF RIVIERA BEACH BID NO 308-11 SERVER VIRTULIZATION/SAN PROJECT
NOTICE ADDENDUM NO. TWO (2) JULY 8, 2011 CITY OF RIVIERA BEACH BID NO 308-11 SERVER VIRTULIZATION/SAN PROJECT TO ALL PROPOSERS ON THE ABOVE PROJECT: PLEASE NOTE CONTENTS HEREIN AND AFFIX (PASTE OR STAPLE)
C. La Plata County is exempt from all state taxation including state sales and use tax.
Informal Bid (Request for Quotes) Drupal Hosting and Development Service Project Number 12-062-2201 Let Date: August 17, 2012 Bid Deadline: 2:00 p.m. August 30, 2012 I. Administrative Information A. La
REQUEST FOR PROPOSAL E-RATE Funding Year 2015 HOSTED VOICE OVER IP (VOIP) for Tunica County School District
REQUEST FOR PROPOSAL E-RATE Funding Year 2015 HOSTED VOICE OVER IP (VOIP) for Tunica County School District Tunica County School District Technology Department 744 School Street P. O. Box 758 Tunica, MS
Backup and Recovery 1
Backup and Recovery What is a Backup? Backup is an additional copy of data that can be used for restore and recovery purposes. The Backup copy is used when the primary copy is lost or corrupted. This Backup
Virtual Tape Systems for IBM Mainframes A comparative analysis
Virtual Tape Systems for IBM Mainframes A comparative analysis Virtual Tape concepts for IBM Mainframes Mainframe Virtual Tape is typically defined as magnetic tape file images stored on disk. In reality
Disaster Recovery Checklist Disaster Recovery Plan for <System One>
Disaster Recovery Plan for SYSTEM OVERVIEW PRODUCTION SERVER HOT SITE SERVER APPLICATIONS (Use bold for Hot Site) ASSOCIATED SERVERS KEY CONTACTS Hardware Vendor System Owners Database Owner
JOLIET JUNIOR COLLEGE REQUEST FOR PROPOSAL PC & LAPTOP PURCHASE PROGRAM RFP
JOLIET JUNIOR COLLEGE REQUEST FOR PROPOSAL PC & LAPTOP PURCHASE PROGRAM Proposal Due Date: 03/20/2008 @ 2:00 P.M. CDT Please direct bid questions to: [email protected] Questions will be compiled and answers
L2F Case Study Overview
LF Case Study Overview Introduction This case study describes how one Internet service provider (ISP) plans, designs, and implements an access virtual private network (VPN) by using Layer Forwarding (LF)
APPENDIX 7 TO SCHEDULE 3.3 TO THE COMPREHENSIVE INFRASTRUCTURE AGREEMENT MAINFRAME & SERVER SERVICES SOW EXHIBIT P TO AMENDMENT NO.
EHIBIT P TO AMENDMENT NO. 60 APPENDI 7 TO SCHEDULE 3.3 TO THE COMPREHENSIVE INFRASTRUCTURE AGREEMENT APPENDI 7 TO SCHEDULE 3.3 TO THE COMPREHENSIVE INFRASTRUCTURE AGREEMENT EHIBIT P TO AMENDMENT NO. 60
UN 4013 V - Virtual Tape Libraries solutions update...
UN 4013 V - Virtual Tape Libraries solutions update... - a Unisys storage partner Key issues when considering virtual tape Connectivity is my platform supported by whom? (for Unisys environments, MCP,
The Advantages of Multi-Port Network Adapters in an SWsoft Virtual Environment
The Advantages of Multi-Port Network Adapters in an SWsoft Virtual Environment Introduction... 2 Virtualization addresses key challenges facing IT today... 2 Introducing Virtuozzo... 2 A virtualized environment
JOHNSON COUNTY COMMUNITY COLLEGE 12345 College Blvd., Overland Park, KS 66210 Ph. 913-469-3812 Fax 913-469-4429
JOHNSON COUNTY COMMUNITY COLLEGE 12345 College Blvd., Overland Park, KS 66210 Ph. 913-469-3812 Fax 913-469-4429 ADDENDUM #1 September 21, 2015 REQUEST FOR PROPOSALS #16-033 FOR CLOUD BASED BACKUP & RECOVERY
RFP SB01-PO1516 Taos Regional Landfill Data Collection and Point of Sale System Page 1
Town of Taos Request for Proposal (RFP) Taos Regional Landfill Data Collection and Point of Sale System September 21, 2015 SB01-PO15-16 1.0 PROJECT DESCRIPTION 1.1 Taos Regional Landfill Board is seeking
DO NOT REMOVE ANY PAGES FROM THIS REQUEST FOR QUOTATION DOCUMENT. FAILURE TO RETURN ALL PAGES WITH YOUR REQUEST FOR QUOTATION MAY INVALIDATE YOUR BID.
Page 1 of 10 April 7, 2015 Name of Firm or Individual Address City Province Postal Code Telephone No. Fax No. Name of Person Signing for Firm (Please Print) Position of Person Signing for Firm DO NOT REMOVE
CITY OF OAK CREEK VoIP Telephone System Addendum
CITY OF OAK CREEK VoIP Telephone System Addendum Important Dates: RFP Documents available April 24 th, 2015 Pre Bid Walkthrough None Last Day for Questions May 6th, 2015 4:00 p.m. CST Last Addendum Issued
IT SERVICES MANAGEMENT Service Level Agreements
IT SERVICES MANAGEMENT Service Level Agreements Sample Agreements, Reports, and Checklists White Paper PREPARED BY: RICK LEOPOLDI May 25, 2002 Copyright 2002. All rights reserved. Duplication of this document
EHR Implementation: What you need to know to have a successful project: Part 2. Bruce Kleaveland President Kleaveland Consulting, Inc.
EHR Implementation: What you need to know to have a successful project: Part 2. Bruce Kleaveland President Kleaveland Consulting, Inc. Learning Objectives: Recognize key EHR hardware & network components
THE CASE FOR ACTIVE DATA ARCHIVING
THE CASE FOR ACTIVE DATA ARCHIVING Written by Ray Quattromini 3 rd September 2007 Contact details Tel: 01256 782030 / 08704 286 186 Fax: 08704 286 187 Email: [email protected] Web: www.data-storage.co.uk
SAN Conceptual and Design Basics
TECHNICAL NOTE VMware Infrastructure 3 SAN Conceptual and Design Basics VMware ESX Server can be used in conjunction with a SAN (storage area network), a specialized high speed network that connects computer
M.Sc. IT Semester III VIRTUALIZATION QUESTION BANK 2014 2015 Unit 1 1. What is virtualization? Explain the five stage virtualization process. 2.
M.Sc. IT Semester III VIRTUALIZATION QUESTION BANK 2014 2015 Unit 1 1. What is virtualization? Explain the five stage virtualization process. 2. What are the different types of virtualization? Explain
IBM Mainframe Services. 10 April 2014. G-Cloud. service definitions
IBM Mainframe Services 10 April 2014 G-Cloud service definitions TABLE OF CONTENTS Definitions and Interpretation... 4 The Services... 6 Core Services... 6 Optional Services... 8 Additional Services...
Priority Pro v17: Hardware and Supporting Systems
Introduction Priority Pro v17: Hardware and Supporting Systems The following provides minimal system configuration requirements for Priority with respect to three types of installations: On-premise Priority
Request for Proposal - Business Telephone System
Request for Proposal - Business Telephone System Return Bid No Later Than: August 1 at 10:00 am Return Bid To: Town of Weaverville PO Box 338 Weaverville, NC 28787 Attn: Michael Boaz Description: Purchase,
Request for Proposals Erate Category 1 Hosted VoIP Service Hinds County School District
Request for Proposals Erate Category 1 Hosted VoIP Service Hinds County School District Notice to Bidders Notice is hereby given to interested bidders that the Hinds County School District will receive
REQUEST FOR PROPOSAL
CITY OF MUKILTEO 11930 Cyrus Way Mukilteo, Washington 98275 425-263-8030 www.ci.mukilteo.wa.us REQUEST FOR PROPOSAL IT SERVICES ACQUISTION SCHEDULE The Acquisition Schedule is as follows, with all times
City of Woodinville, Washington
City of Woodinville, Washington Telecommunications Analysis and Options Report Request for Proposal Issue Date: December 22nd, 2014 Due Date: January 22nd, 2015 Due Time: 4:00 PM Page 1 of 10 TABLE OF
Hosted VoIP RFP. Throughout this document, the word District refers to Smith County School District
Hosted VoIP RFP Throughout this document, the word District refers to Smith County School District Subject RFP-For a 3, 5, and 7 year contract, the District desires implement hosted VoIP services. The
MedInformatix System Requirements
MedInformatix System Requirements Acentec, Inc. A MedInformatix installation requires a workstation for each user who will access the system and a central server to store and process the data. A large
Virtualization, Business Continuation Plan & Disaster Recovery for EMS -By Ramanj Pamidi San Diego Gas & Electric
Virtualization, Business Continuation Plan & Disaster Recovery for EMS -By Ramanj Pamidi San Diego Gas & Electric 2001 San Diego Gas and Electric. All copyright and trademark rights reserved. Importance
Exam: 070-215 QUESTION 1 QUESTION 2 QUESTION 3 QUESTION 4
Exam: 070-215 QUESTION 1 You want to provide complete redundancy for all data stored on your hardware RAID-5 disk array. You install a second hardware RAID-5 disk array. You want to create a mirror of
LAN/Server Free* Backup Experiences
LAN/Server Free* Backup Experiences Senior Consultant, TSM Specialist Solution Technology Inc * Beware ambiguous terminology Who is Solution Technology IBM Premier Business Partner $70M+ in Sales 80+ Employees
Performance Navigator Installation
Midrange Performance Group / Performance Navigator Business Partner Installation / SOS / Capacity Planning Guide Aug 1, 2011 Overview Performance Navigator provides three main functions for the IBM i platform:
FDRSOS (Safeguard Open Storage)
Introducing FDRSOS (Safeguard Open Storage) FDRSOS (Safeguard Open Storage) provides high-speed, reliable backups of Open Systems (SCSI) data to an MVS or OS/390 System. FDRSOS and the SYMMETRIX 3000 and
CounselorMax and ORS Managed Hosting RFP 15-NW-0016
CounselorMax and ORS Managed Hosting RFP 15-NW-0016 Posting Date 4/22/2015 Proposal submission deadline 5/15/2015, 5:00 PM ET Purpose of the RFP NeighborWorks America has a requirement for managed hosting
Distribution One Server Requirements
Distribution One Server Requirements Introduction Welcome to the Hardware Configuration Guide. The goal of this guide is to provide a practical approach to sizing your Distribution One application and
Data Center Colocation - SLA
1 General Overview This is a Service Level Agreement ( SLA ) between and Data Center Colocation to document: The technology services Data Center Colocation provides to the customer The targets for response
STATE OF NEW HAMPSHIRE Department of Administrative Services DAS RFB 787-07 Communications Network Services VENDOR QUESTIONS WITH RESPONSES
STATE OF NEW HAMPSHIRE Department of Administrative Services DAS RFB 787-07 Communications Network Services VENDOR QUESTIONS WITH RESPONSES Q1. Will the State consider extending the bid response due date
How To Run A Hosted Physical Server On A Server At Redcentric
REDCENTRIC HOSTED PHYSICAL SERVER SERVICE DEFINITION SD027 V1.6 Issue Date 01 July 2014 1) OVERVIEW The Hosted Physical Server service (HPS) offers dedicated off-site server resource located within an
REQUEST FOR PROPOSAL FOR: ENTERPRISE BACKUP SOLUTION
REQUEST FOR PROPOSAL FOR: ENTERPRISE BACKUP SOLUTION DIRECT QUESTIONS TO: SUBMIT PROPOSALS TO: Samuel Samara Enterprise Backup Project Network Infrastructure Supervisor Scott County Purchasing Information
SCSI device drivers are provided for the following operating systems: Microsoft Windows NT Server 4.0 Novell NetWare 5.1
This section describes how to install and configure the Dell small computer system interface (SCSI) device drivers included with your Dell PowerEdge 1400 computer system. These device drivers are designed
BACKUP SECURITY GUIDELINE
Section: Information Security Revised: December 2004 Guideline: Description: Backup Security Guidelines: are recommended processes, models, or actions to assist with implementing procedures with respect
IBM TotalStorage Network Attached Storage 100
1U low-profile IBM NAS solution for central management of remote and distributed locations IBM TotalStorage Network Attached Storage 100 Model R12 Ease of use and ease of management Web-browser interface
Chapter 12 Network Administration and Support
Chapter 12 Network Administration and Support Objectives Manage networked accounts Monitor network performance Protect your servers from data loss Guide to Networking Essentials, Fifth Edition 2 Managing
Data Protection with IBM TotalStorage NAS and NSI Double- Take Data Replication Software
Data Protection with IBM TotalStorage NAS and NSI Double- Take Data Replication September 2002 IBM Storage Products Division Raleigh, NC http://www.storage.ibm.com Table of contents Introduction... 3 Key
IBM ^ xseries ServeRAID Technology
IBM ^ xseries ServeRAID Technology Reliability through RAID technology Executive Summary: t long ago, business-critical computing on industry-standard platforms was unheard of. Proprietary systems were
Enterprise Backup Solution for Legato NetWorker
White Paper December 1999 Prepared by: Multi-Vendor Solutions Storage Products Division Compaq Computer Corporation Contents Introduction...3 Platforms and Operating Systems...4 Storage Area Network Components...4
Adonis Technical Requirements
Information Sheet Adonis Technical Requirements CONTENTS Contents... 1 Adonis Project Implementation... 1 Host Installation / Onboard Installation Full replication (LARGER Vessels):... 1 Onboard installation
Enabling Technologies for Distributed Computing
Enabling Technologies for Distributed Computing Dr. Sanjay P. Ahuja, Ph.D. Fidelity National Financial Distinguished Professor of CIS School of Computing, UNF Multi-core CPUs and Multithreading Technologies
Systemverwaltung 2009 AIX / LPAR
Systemverwaltung 2009 AIX / LPAR Course materials may not be reproduced in whole or in part without the prior written permission of IBM. 4.0.1 Integrated Virtualization Manager (IVM) (1 of 2) Provides