Low Carbon Data Centres without compromise
|
|
|
- Maurice Lang
- 10 years ago
- Views:
Transcription
1 Low Carbon Data Centres without compromise Thursday 16 th September 2010 Pip Squire, Engineering & Project Director delivered by: Ark Continuity - Continuously Delivering high integrity data centres
2 Introduction Since this conference last year we: have completed SQ17 Module 1 have demonstrated a PUE of 1.4 during IST testing* are now operational with a capacity of: 800 kw of IT Load 600m 2 of supported Data Suite space Tier III Security to IL4 This presentation will look at: Whole Life Cycle Data Centre Costs Our focus on reducing carbon through efficient operation by sustainable design The benefits arising from this approach
3 Definitions Data Centre A Facility that is dedicated to Data Centre operations Whole Life 26 years from start of design to decommissioning and disposal Whole Life Costing... the systematic consideration of all relevant costs associated with the development and ownership of an asset Whole Life Stages Design, Build, Operate, Refresh, Decommission.
4 Definitions Power Usage Effectiveness (PUE) This is a metric for characterising and reporting overall data centre infrastructure efficiency based on annual energy consumption data as follows: PUE = Total Data Centre energy consumption/it energy consumption. Total Data Centre Energy Consumption is measured in kwh and is the sum of the kwh recorded on the utility company bills IT Energy Consumption is measured in kwh. It is the sum of the kwh recorded at the PDUs supplying the IT load. PDU Power Distribution Unit UPS Uninterruptible Power Supply Autonomy Time the UPS can supply the technical load without an incoming supply.
5 Whole Life Cycle Data Centre Costs Only 44% of IT Managers see their Data Centre Energy Bills (Institute of Engineering and Technology, November 2009)
6 Whole Life Cycle Data Centre Costs
7 Implementation and Impact on Whole Life Cycle Data Centre Costs Focus on continuous improvement in terms of: - Design with sustainability at its core - Operations
8 The Cycle of Continuous Improvement The Virtual Circle Driven by our systems that are accredited to: - BS :2007, Business Continuity Management - ISO/IEC 27001:2005, Information Security Management - ISO 14001:2004, Environmental Management
9 Linking Carbon Impacts with Whole Life Cycle Costs In our SQ17 Facility we have: 1. Measured our Construction Carbon Footprint, where we can: Our M&E Suppliers are still working on their embedded carbon calculations Shell & Core has 1,111 tonnes of CO 2 equivalent Anticipate a total of 3,000 tonnes of CO 2 equivalent including the M&E data Embedded CO 2 is 3,000 t per MW of IT Load
10 Linking Carbon Impacts with Whole Life Cycle Costs In our SQ17 Facility we have: 2. Calculated our Operating Carbon Footprint: At full load With an annual operating PUE of between 1.4 and 1.5 Based on the total UK electricity mix of coal, nuclear, oil, gas and renewable generation mix and the 5 year rolling grid average of 0.54 t CO 2 equivalent per kwh. As 6,600 to 7,000 tonnes CO 2 equivalent per year This provides: a) A saving of 3,500 to 4,000 t CO 2 equivalent a year over a data centre with a PUE of 2.5 b) The basis on which to build a carbon accounting tool for compliance with: - the CRC Energy Efficiency Scheme - the EU Code of Conduct on Data Centres
11 Sustainable Design - local renewable energy and water conservation Sustainable Design - local renewable energy and water conservation
12 Sustainable Design - local renewable energy and water conservation We anticipate that this will enable the site to achieve a PUE of around 1.2 and provide an annual saving of around 6,000 t of CO 2 per MW per year over an equivalent data centre with a PUE of 2.5
13 Sustainable Design - Power Usage Efficiency (PUE) PUE presented so far has been to 1 decimal place because: It varies with IT load, time of day and time of year. PUEs quoted have been unqualified in terms of support systems. At low PUEs the UPS efficiency and ancillary loads have a significant impact:
14 Benefits of Efficient Operation by Sustainable Design Operations, Design, Implementation and Research are all linked in a virtual circle. Development effort is focussed at the appropriate stages in the project life cycle to obtain maximum benefit for cost incurred Sustainable design means we are focussed on minimising our impact on the planet Risk management and the use of incentivised contracts mean we deliver to cost and programme
15 Benefits to Government ICT Sustainable Operations on the Government Estate (SOGE), have the following targets: Reduce Carbon Emissions on 1999/2000 levels by 12.5% in 2010 and 30% in 2020 Increase energy efficiency per m 2 on 1999/2000 levels by 15% in 2010 and 30% in 2020 Reduce water consumption on 2004/5 levels by 25% in 2020 Reduce waste arisings on 2004/5 levels by 5% in 2010 and 25% in 2020 Increase recycling to 40% in 2010 and 75% in 2020 The Ark SQ17 Facility: With a PUE of reduces data centre carbon emissions, over a 1999/2000 facility by more than 30%, i.e target delivered in Sustainable design and operating practices mean that we are already delivering the water consumption and waste reduction targets identified above
16 Our mission is to continuously deliver scalable and predictable mission critical infrastructure that is the most secure, resilient & sustainable in Europe. Thank you
DATA CENTRE DESIGN AND
SPUSC 2008 SOUTH PACIFIC USER SERVICES CONFERENCE DATA CENTRE DESIGN AND ENERGY INITIATIVES Presented by Jarrad Clift Electrical Engineer Greenstar Accredited Presentation Content Data Centres General
An addendum for France & the UK to Cloud Computing the IT Solution for the 21 st Century
Carbon Disclosure Project Study 2011 An addendum for France & the UK to Cloud Computing the IT Solution for the 21 st Century Study produced for Carbon Disclosure Project by: 1 Introduction This report
Electric Utilities. Introduction to the module
Introduction to the module The electric utilities module is based on a reporting framework produced by the Institutional Investors Group on Climate Change (IIGCC), Ceres, and the Investor Group on Climate
CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers
CEMEP UPS The high environmental performance solution for power supply to high-availability data centers Exchanges of information and communication needs are growing at an exponential rate. That growth
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008
University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008 Contents Welcome and Introduction Chapter 1: Data centre energy recap Chapter 2: Co-generation Chapter 3: CTC case study
ALWAYS ON GLOBALSWITCH.COM
ALWAYS ON GLOBALSWITCH.COM Data Centre Design Considerations Kelvin Fong Managing Director, Hong Kong ALWAYS ON GLOBALSWITCH.COM Agenda 1. Introduction to Global Switch 2. Customer Requirements 3. Development
Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling
Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by
ICT and the Green Data Centre
ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by
Cody Park One of Ark s high integrity data centre campus sites
UKC COMMERCIAL Cody Park One of Ark s high integrity data centre campus sites Ark is a privately held company that design, build, operate and finance third party data centre solutions tailored to meet
Global Green Data Center Best Practices In Action
Global Green Data Center Best Practices In Action DOUG WASHBURN VICE PRESIDENT & RESEARCH DIRECTOR September 25, 2013 Four questions I will answer 1 Why is green important to your business? 2 Why is green
glyndwr.ac.uk/sustainability environmental sustainability strategy
glyndwr.ac.uk/sustainability environmental sustainability strategy 2012-2014 overview of the environmental sustainability strategy 2012-2014 Glyndŵr University s Environmental Sustainability Strategy 2012-2014
Data centre experts. Advanced power protection for data centres
Data centre experts Advanced power protection for data centres A robust power protection strategy is critical to successful data centre operations. Uninterruptible Power Supplies Limited (UPSL), a Kohler
BS EN 16001 Energy Management Systems VICTORIA BARRON, PRODUCT MARKETING MANAGER, BSI
BS EN 16001 Energy Management Systems VICTORIA BARRON, PRODUCT MARKETING MANAGER, BSI Agenda Energy Management in context Why Energy Management? Business Needs How BS EN 16001 helps organisations meet
Domestic Customer Tariff Breakdown - RoI Note this is approximate due to tariff and consumption variations
Guide to Electricity price formation in Ireland and Northern Ireland The numbers The average household consumes 4,300 kwh 1 of electricity per annum in Ireland and 4,100 in Northern Ireland. At an average
ENERGY EFFICIENT DATA CENTRES AND STORAGE. Peter James University of Bradford
ENERGY EFFICIENT DATA CENTRES AND STORAGE Peter James University of Bradford ABOUT US 1998 Co-founded world s first NGO on GreenIT EU Expert Advisors/Project Managers on ICT & Energy Efficiency; Environmental
Green Data Centers. Energy Efficiency Data Centers. André ROUYER Director of Standardization & Environment. The importance of standardization
Green Data Centers GOING FORWARD ENERGY EFFICIENCY TRENDS André ROUYER Director of Standardization & Environment All content in this presentation is protected 2008 American Power Conversion Corporation
Domestic energy bills and costs of implementing environmental measures
Domestic energy bills and costs of implementing environmental measures The Sustainable Development Commission has analysed household electricity and gas bills to show the contribution of the additional
GREEN ICT DELL, OUR SUPPLIERS AND CUSTOMERS
GREEN ICT DELL, OUR SUPPLIERS AND CUSTOMERS Victor C. Smith Senior Strategic Technologist Dell Corporation Ltd. GROWTH EVERY SECOND IN THE CONNECTED AGE 2 new blogs created 4 cell phones purchased 7 personal
Sustainability Policy and Targets to 2015
Sustainability Policy and Targets to 2015 1 Here at Asda our approach to sustainability is based on the belief that protecting the environment and saving people money go hand in hand. This belief is backed
Green ICT Strategy 2010-2014
Department of Transformation Information & Communication Technology Author: Quentin McPhee - Lead for Green ICT Date: February 2010 Version: 00_05 Green ICT Strategy 2010-2014 Table of Contents 1.Summary...2
LTES Environmental Management System (EMS) Compliance
LTES Environmental Management System (EMS) Compliance 0 TABLE OF CONTENTS Introduction... 2 Compliance... 2 Requirement #1:... 2 Requirement #2:... 2 Requirement #3:... 3 Requirement #4:... 4 Requirement
Zen Internet Case Study
Zen Internet Case Study About Zen Internet Zen Internet is an independent Internet Service Provider (ISP) that offers a full range of data, voice, and hosting services to businesses and residential users
Capita Symonds Real Estate Sustainability Report 2012 Royal London Asset Management Portfolio
Capita Symonds Real Estate Sustainability Report 2012 Royal London Asset Management Portfolio Highlights Over 10,000 tonnes CO2 equivalent saved from entering the atmosphere Carbon Saver Gold Standard
A REScoop manifesto. REScoop policy priorities for the European Parliament elections 2014
A REScoop manifesto REScoop policy priorities for the European Parliament elections 2014 Renewable Energy: citizens take the initiative at grassroots level REScoop.eu is the federation of groups and cooperatives
Contact: Environment and Green Technologies Department Phone: 01-7272480 Email: [email protected] www.envirocentre.
Contact: Environment and Green Technologies Department Phone: 01-7272480 Email: [email protected] www.envirocentre.ie Enterprise Ireland August 08 (152) Eco-labels GreenTech Support Eco-labels
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations
Introducing Gazprom Energy Stable, secure, reliable energy from one of the world s biggest names. With deals tailored around your needs, not ours.
Introducing Gazprom Energy Stable, secure, reliable energy from one of the world s biggest names. With deals tailored around your needs, not ours. About us Gazprom Energy customers receive a long lasting
THE UK CLIMATE CHANGE PROGRAMME AND EXAMPLES OF BEST PRACTICE. Gabrielle Edwards United Kingdom
Workshop on Best Practices in Policies and Measures, 11 13 April 2000, Copenhagen THE UK CLIMATE CHANGE PROGRAMME AND EXAMPLES OF BEST PRACTICE Gabrielle Edwards United Kingdom Abstract: The UK published
CIPS Sustainable procurement review
CIPS Sustainable procurement review Chartered Institute of Purchasing & Supply September 2011 Contents Content What is sustainable procurement? Relevance and impact Links with other standards and models
How sustainability standards can drive business performance
How sustainability standards can drive business performance How sustainability standards can drive business performance How can standards bring consistency and scalability to sustainability programmes?
Energy Management Strategy
Energy Management Strategy Gloucester s Energy Management Strategy sets out the way for the organisation to measure and manage all the energy and water resources it uses. The main areas it looks at are
NetSuite Offers Green Alternative to Traditional On-Premise ERP and CRM Solutions
Offers Green Alternative to Traditional On-Premise ERP and CRM Solutions July 2009 Presented by www.greenspacesupply.com Offers Green Alternative to Traditional On-Premise ERP and CRM Solutions Executive
Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire. http://rare-idc.herts.ac.
Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire http://rare-idc.herts.ac.uk Making Existing Server Rooms More Efficient Reduction and Re-use
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance. Chapter 8: 8 Guide for assessing GHG emissions of Data Centers
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance Chapter : Guide for assessing GHG emissions of Data Centers DRAFT March 0 Table of Contents GHG Protocol ICT Sector
Fact sheet. Conversion factors. Energy and carbon conversions 2011 update
Fact sheet Conversion factors Energy and carbon conversions 2011 update 1 Introduction This leaflet provides a number of useful conversion factors to help you calculate energy consumption in common units
Working with. Carbon Management Board (CMP) 18 September 2009. William Stephens. Cranfield Executive
Working with Carbon Management Plan (CMP) Date: Version: 18 September 2009 2.2 Owner: Approval route: Approval status: John Street William Stephens Carbon Management Board Cranfield Executive Approved
Agent-Based Micro-Storage Management for the Smart Grid
Agent-Based Micro-Storage Management for the Smart Grid Perukrishnen Vytelingum, Thomas D. Voice, Sarvapali D. Ramchurn, Alex Rogers and Nicholas R. Jennings University of Southampton Outline Energy Domain
Fuel cell microchp: Greener and cheaper energy for all
Fuel cell microchp: Greener and cheaper energy for all Paddy Thompson General Manager Business Development Ceramic Fuel Cells Ltd. May 2013 1 What does our generation mix look like today? 2 Will the lights
Energy Storage for Demand Charge Management
Energy Storage for Demand Charge Management Wednesday, June 24, 2015 Seth Mullendore Program Associate Clean Energy Group Housekeeping Who We Are www.cleanegroup.org www.resilient-power.org 3 Resilient
CarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense
CarbonDecisions The green data centre Why becoming a green data centre makes good business sense Contents What is a green data centre? Why being a green data centre makes good business sense 5 steps to
Carbon Path to 2020. Alan Aldridge Executive Director Energy Services and Technology Association
Carbon Path to 2020 Alan Aldridge Executive Director Energy Services and Technology Association ESTA PO Box 77 Benfleet Essex SS7 5EX T: 01268 569010 F: 01268 569737 E: [email protected] W: www.esta.org.uk
The Energy Saving Trust s community solar programme How your community can benefit from discounted solar panels and Feed-in Tariffs
The Energy Saving Trust s community solar programme How your community can benefit from discounted solar panels and Feed-in Tariffs 1 Introduction Feed-in Tariffs have arrived, which means there has never
World s Greenest High Performance Data Center
World s Greenest High Performance Data Center EcoDataCenter Sustainability for future generations Our Services Colocation Data Center for Mission Critical Requirements Lockable racks, cages, private rooms
Data Centre Harbour Exchange Square Campus, London Access to unrivalled connectivity.
Data Centre Harbour Exchange Square Campus, London Access to unrivalled connectivity. TelecityGroup 6/7 Harbour Exchange London E14 9GE United Kingdom Tel: +44 (0)20 7001 0101 [email protected] www.telecitygroup.com
How one simple step can halve a carbon footprint
How one simple step can halve a carbon footprint Overview How businesses disclose their greenhouse gas emissions has changed and in a big way. It follows on from new guidance issued by the World Resources
Ark Data Centre Information Pack
Ark Data Centre Information Pack Our Commitment Welcome to Ark Data Centre s information pack. As the CEO of Ark I welcome the opportunity to work with you either full of the details you need to support
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
Module 1: Introduction to Industrial Energy Management
Module 1: Introduction to Industrial Energy Management Organisations that successfully manage energy have business processes to plan, monitor, and control energy use, just as they do for other corporate
Green ICT: Consistent Actions to Reduce Energy Consumption
/ Martin Chaloupek Vienna, 2010 02 22 Green ICT: Consistent Actions to Reduce Energy Consumption Input to Conference Energy Efficiency Chances of Green ICT and Electronics Vienna, 2010 03 05 20010 IBM
Big Yellow Group PLC Basis of Reporting 1st April 2012 31st March 2014 Corporate Social Responsibility
Big Yellow Group PLC Basis of Reporting 1st April 2012 31st March 2014 Corporate Social Responsibility Deloitte LLP provides independent and limited assurance of selected subject matters in our annual
red zone management white paper Making the most of Distribution Use of System (DUoS) Charges
red zone management white paper Making the most of Distribution Use of System (DUoS) Charges 1. Distribution charges 2. Measuring usage 3. Component parts 4. Time is of the essence 5. Solution provider
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. [email protected]
Enhancing Competitiveness through Sustainable Supply Chain. Clearstream Solutions. Greener Business
Enhancing Competitiveness through Sustainable Supply Chain Clearstream Solutions Greener Business Agenda Understanding Sustainability : Competitive advantage or disadvantage for Ireland? Why focus on sustainable
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
Data Center Life Cycle Analysis. Christophe Garnier EMEA Technical Work Group Member Schneider Electric
Data Center Life Cycle Analysis Christophe Garnier EMEA Technical Work Group Member Schneider Electric V3 The 3 Pillars of Sustainability Sustainability = meet the needs of the present without compromising
GUIDE TO PRODUCTS AND SERVICES HELPING YOU GET MORE VALUE OUT OF YOUR ENERGY CONTRACT, REDUCE YOUR ENERGY CONSUMPTION AND LOWER YOUR CARBON FOOTPRINT
GUIDE TO PRODUCTS AND SERVICES HELPING YOU GET MORE VALUE OUT OF YOUR ENERGY CONTRACT, REDUCE YOUR ENERGY CONSUMPTION AND LOWER YOUR CARBON FOOTPRINT CARBON ZERO FOR ENERGY ENERGY HEALTH CHECK WHAT WE
Environmental Policy. JRI Orthopaedics Limited
JRI Orthopaedics Limited October 2014 Contents Clause 1. Policy Statement 1 2. Who is covered by the policy? 2 3. Organisation and Responsibilities 2 4. Training and Communication 3 5. Suppliers and Customers
San Francisco Chapter. Deborah Grove, Principal Grove-Associates
Deborah Grove, Principal Grove-Associates Why Green IT is Important 1. The energy consumed by servers in the US (and associated air -conditioning) is equivalent to the annual output of about 20 new coal-fired
SOLAR PV SYSTEM INFORMATION PACK
SOLAR PV SYSTEM INFORMATION PACK Apollo Solar the solar pv professionals If you are considering going green and earning money from solar energy, look no further than Apollo Solar we are fully qualified
Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics
On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations
Code of Conduct on Data Centre Energy Efficiency. Endorser Guidelines and Registration Form. Version 3.0.0
1 EUROPEAN COMMISSION DIRECTORATE-GENERAL JRC JOINT RESEARCH CENTRE Institute for Energy Renewable Energies Unit Ispra, 1 st January 2015 Code of Conduct on Data Centre Energy Efficiency Endorser Guidelines
Fixed + Protect Electricity supply contracts explained for large business customers
Fixed + Protect Electricity supply contracts explained for large business customers 2/7 Fixed + Protect explained We fix your unit price, with a generous tolerance on how much your electricity use can
Sustainability Portfolio. Keeping Business Sustainable
Sustainability Portfolio Keeping Business Sustainable Sustainable practice is the path to success now and for the long term. In 1800, the world s population was 1 billion people, by 1900 it was 2 billion
Formulating an energy management action plan
Formulating an energy management action plan Eskom Energy Management Information Pack: Brochure 1 Index Formulating an energy management action plan 1 Structuring an energy management action plan Sample:
Prudential plc. Basis of Reporting: GHG emissions data and other environmental metrics.
Prudential plc. Basis of Reporting: GHG emissions data and other environmental metrics. This Basis of Reporting document supports the preparation and reporting of GHG emissions data and other environmental
Carbon Management Plan
E-2015-02-02 Addendum Carbon Management Plan Date: 14 May 2014 Owners: Approval: K.W.Bullimore & M.Sackett A.Burrell Executive Summary This document sets out the Carbon Management Plan (CMP) for The Open
Measuring Power in your Data Center
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There
Green Data Centers. Jay Taylor Director Global Standards, Codes and Environment (512) 818-2073
Green Data Centers Jay Taylor Director Global Standards, Codes and Environment (512) 818-2073 The energy dilemma: With Me, Without Me The facts The need Energy demand By 2050 Electricity by 2030 Source:
Organizational Change Management for Sustainability Pearson Inc www.pearson.com
Organizational Change Management for Sustainability Pearson Inc www.pearson.com Kate McCarthy [email protected] Project Lead Green Teams Pearson North America Sustainability Specialist 1 About
WHEN AN EFFECTIVE EU ENERGY POLICY?
WHEN AN EFFECTIVE EU ENERGY POLICY? A. Clerici ABB Italy Honorary Chairman of WEC Italy Chairman of WEC WG The future role of nuclear in Europe 1 INDEX 1. General Comments 2. Vulnerability 3. Transmission
Metrics for Data Centre Efficiency
Technology Paper 004 Metrics for Data Centre Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Equinix Telecity Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 [email protected] www.telecitygroup.se
Capgemini UK Infrastructure Outsourcing
Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,
ICT Remanufacturing in the European B2B market. Questions + Answers. www.bitkom.org
ICT Remanufacturing in the European B2B market www.bitkom.org 2 ICT Remanufacturing in the European B2B market Global ICT»Original Equipment Manufacturers«(OEMs) are actively engaged in the effective reuse
Gas Absorption Heat Pumps. Future proofing your heating and hot water
Gas Absorption Heat Pumps Future proofing your heating and hot water Gas Absorption Heat Pumps 1 Contents Gas Absorption Heat Pumps (GAHPs) The heating solution What is a Gas Absorption Heat Pump? How
A new direction in energy?
A new direction in energy? 5 October Britain 'to be hit by 70s-style blackouts within three years' Daily Mail Blackouts possible as coal power stations go offline early, warns Ofgem Guardian 19 October
ENA Submission to the Parliamentary Renewable and Sustainable Energy Group Inquiry into the access and management of renewables and the Grid
1 ENA Submission to the Parliamentary Renewable and Sustainable Energy Group Inquiry into the access and management of renewables and the Grid 1.0 Introduction 1.1 Energy Networks Association (ENA) is