Fire Resisting Self Closing Doors

Size: px
Start display at page:

Download "Fire Resisting Self Closing Doors"

Transcription

1 Background This Note f Inspecting Officers provides guidance on the standards that are considered appropriate in respect to Fire Resisting Self-Closing Dos. The Note aims to set general principles and to provide the reader with infmation as to which approved document technical standard is considered by this Authity to be appropriate. Further infmation on the testing and assessment of fire resisting metal do sets (e.g. dos with swinging leaves) can be found in FS-NFG028 Fire Resisting Metal Dos. Definition of Fire Do The expression "fire do", "fire do assembly" and "fire do set" are synonymous f the purposes of this Note f Guidance and have the following definition: "A do shutter provided f the passage of persons, air things which, together with its frame and furniture as installed in a building, is intended when closed, to resist the passage of fire and/ gaseous products of combustion and is capable of meeting perfmance criteria to these ends". Functions of Fire Dos Fire dos have at least one of two functions to perfm and, in certain situations both i.e. 1. To protect escape routes from the effects of fire so that occupants can safely reach a final exit; and 2. To protect the contents and/ structure of a building by limiting the spread of fire. Consequently any particular fire do may have to perfm one both of these functions f the purposes of smoke control, protecting means of escape, compartmentation the segregation of special risk areas. Perfmance of Fire Dos Fire Protection Fire Resisting Self Closing Dos Issue/Revision Date 01/10/2010 Review Date 15/12/2016 Version 8.0 Procedure & Guidance Ref FS- NFG003 Fire Dos f Smoke Control Fire dos provided f smoke control purposes should be capable of withstanding smoke at medium temperatures Smoke control fire dos are provided f life safety purposes and play an imptant role in the vicinity of the fire in its early stages and in protecting escape routes me remote from a fully developed fire. Although smoke control dos are not required to meet any specific period of fire resistance, they should be of substantial construction. Flexible edge seals should be provided f the early control of smoke movement. Tests have shown that do stops (rebates) that have been increased to 25mm do not improve the smoke stopping perfmance of dos because a fire do will bow towards the fireexposed side. Page 1 of 7

2 Fire Dos to Protect Means of Escape Fire Dos provided to protect means of escape should be capable of achieving a minimum fire resistance f integrity of 30 minutes, when tested in accdance with an appropriate British, European International standard. The dos are required to keep escape routes sufficiently free from smoke long enough to allow occupants to reach a place of safety and to maintain integrity against the effects of fire long enough to fulfil that objective. To achieve this they may need smoke seals. NB: When other methods of smoke control are provided in buildings, e.g. pressurisation of escape routes, the ability of fire dos to withstand smoke may not be applicable. Fire Dos f Compartmentation and the Segregation of Special Risks Fire Dos provided f fire compartmentation and the segregation of special risk areas must be capable of achieving the period of fire resistance appropriate to the structure which is not less than 30 minutes and may be as much as 6 hours. To achieve this level of fire resistance, it may be necessary to provide two fire dos in series. The sum total of the fire resistance would be designed to meet the required standard. If such dos are also required to protect an escape route they will need also to have the smoke control capabilities described above. In some circumstances e.g. the protection of property, it may be necessary f them to be capable of withstanding high temperature smoke. Increasing the Fire Resistance of Existing Timber Dos Increasing the fire resistance of existing dos is not nmally acceptable and usually it will be me cost effective to install a new do. However, in certain instances it may be necessary to retain an existing do e.g. in a listed building and, where the reasons are considered valid by an enfcing authity it may be appropriate to modify the dos to provide an improved standard of fire resistance. Guidance on how to improve the fire resistance of existing timber dos can be found in: - Building Research Establishment Infmation Paper 8/82 "Increasing the fire resistance of existing timber dos" and the Timber Research and Development Association's Wood Infmation Sheet, Section 1, Sheet 32, "Fire Resisting Do sets by Upgrading". Fire Safety - Public Advice Note FS-PAN0025 "Dos - Upgrading the Fire Resistance of Existing Dos". NB: An existing timber do nmally can only have its fire resistance improved to a maximum of 30 minutes Designation of Fire Dos Fire dos should be designated by the initials FD followed by the perfmance in minutes that the do should achieve when tested in accdance with British Standard BS476: part 22 f integrity of not less than 30 minutes (i.e. 30 minutes fire resistance). Where the do should also resist the passage of smoke at ambient temperatures the suffix "S" should be added to the designation. Two illustrations of this are as follows; 1. The entrance do to a flat in a block of flats would be required to protect the means of escape, so that the crect designation would be FD 30s. 2. A fire do is a 60 minute compartment wall where there are no means of escape considerations would be designated FD 60. Page 2 of 7

3 Marking Of Fire Dos Table 1 All fire dos should be permanently marked with their designation (as above). A convenient and recommended method is by use of a colourcoded plug, inserted in the edge of the hanging stile, and confming to the table given on the right. Ce Colour Background colour Integrity Mins Colour Interpretation Code Red White 20 Intumescent seals Yellow 30 require to be fitted at the time of iginal Pink 45 installation Blue 60 Brown 90 Black 120 Green White 20 No additional Yellow 30 intumescent seals need to be fitted at Pink 45 the time of installation Blue 60 Brown 90 Black 120 Blue White 20 With no intumescent seals fitted. White 30 With intumescent seals fitted in either do edge frame Intumescent and Smoke Seals F do assemblies designed to achieve 20 min 30 min integrity, test experience shows that a 10mm wide strip of intumescent material which has satisfied the test described in BS476: Part 23 f the relevant period, fitted centrally into the leaf frame rebate of a conventional sized, latched, single leaf, single swing assembly will nmally be adequate. The seal strip may be interrupted at ironmongery positions. F similar dos designed to provide periods of 60 minutes fire resistance greater, the intumescent seal specification will be at least twice that required f 30 min applications and with at least part of the seal by-passing all ironmongery fixings. F double leaf assemblies the quantity of intumescent seal will be that established by test and will be dependent upon the behaviour of the do leaves. Where separate smoke and intumescent seals are to be fitted, they should be placed with one in the do leaf and one in the frame. Compression type smoke seals should be used on latched dos only (Blade and brush types do not rely on latches). Page 3 of 7

4 Frame to wall junction The junction between a do frame and wall should be dealt with in accdance with tables 2 and 3. Fit of do leaf Leaf to frame gaps should not exceed those as tested to BS 476: Part 22. Gaps exceeding 4mm are not likely to be acceptable even when intumescent material is present. Smoke seals should make continuous contact. Gaps should allow f some settlement and shrinkage. Threshold sealing Intumescent sealing is not nmally necessary and gaps of up to 8mm can nmally be tolerated. If the gap exceeds 3mm and total smoke control is required, a seal must be provided. Glazing apertures Apertures f glazing any other purpose should be provided by the manufacturer. Evidence of manufacturer's approval would nmally be required f post fming of apertures. (See Letter-plates below). Glass and glazing beads should be in accdance with the manufacturer's specifications. Timber beads are likely to be suitable only if of substantial dimensions and in conjunction with intumescent bedding mastics. See also FS-NFG014 Fire Resisting Glass". Maintenance Fire and Smoke Seals should be examined at six monthly intervals and replaced if necessary. Do gaps should be examined at the same time and should receive attention if they have increased to me than 5mm become so tight as to over compress the smoke seals. Replacement of glazing should be in accdance with manufacturer's recommendations. Hardware should be appropriately lubricated. Replacement of hardware should be with identical components, ones approved by the manufacturer and any gaps resulting should be filled with suitable intumescent material. Self-closing devices and latches should be checked at six monthly intervals to ensure they are wking fully and effectively. Self Closing Devices A fire do (except to a cupboard service duct) should nmally be fitted with a self closing device (other than rising butt hinges) that: 1. Should be of a type that cannot readily be disconnected immobilised and does not embody a stand-open action; 2. Should override any latches fitted to the do(s); in the absence of a suitable latch other positive device f holding the do shut in its frame, should be of a type that has been shown by test to be capable of holding the do closed in the frame f a sufficient period of time f the closing role to be taken over by a thermally activated sealing device (such as an intumescent seal), throughout the full period of exposure if such seals are not incpated. Page 4 of 7

5 Letter-plates (Letterboxes) The provision of letter-plates in fire resisting dos should be avoided where possible and approval should be obtained from any enfcing authity befe they are installed. Letter-plates are not acceptable in any do required to give a fire resistance greater than 30 minutes. An acceptable alternative to the provision of letter-plates is separate mail boxes that can be protected me easily from the effects of fire. The following criteria should apply befe the Fire Authity will consider giving approval f the provision of a letter-plate in a fire-resisting do: - 1. The do must be of suitable construction and the aperture cut in the do must be in an area of solid timber. 2. The size of the aperture cut in the do must not exceed the size of that in the letter-plate. 3. The letter-plate should be sited 900mm up from the flo as this is where the neutral pressure axis is expected to be in a fire situation. 4. The letter-plate must be constructed from metal and have a positive spring closer fitted to it. 5. A stainless steel inner flap with a positive spring closer must be provided. It should have a generous overlap which must not be less than 10mm and it must be independently screwed to the do and not be reliant on the bolt fixings from the back of the letter-plate to hold it in position. 6. A combined smoke and intumescent seal must be provided around the aperture cut in the do and the inner flap must close onto this seal. Notices Fire dos should be marked "FIRE DOOR - KEEP SHUT" on each face unless it is a do to a ste room, service duct etc, in which case it should be marked "FIRE DOOR KEEP LOCKED" on the outer face. The size, shape and colouring of the notice should comply with BS 5499: Part 1: 1990, Appendix B.3 "Mandaty Signs". Page 5 of 7

6 Table 2 RECOMMENDATIONS FOR THE JOINT BETWEEN TIMBER DOOR FRAMES AND WALLS TO PROVIDE 30 MIN FIRE RESISTANCE Wall Construction Maximum Frame to Wall Gap Width Architrave Condition Additional Protection Non-load bearing walls unlikely to exhibit significant disttion during fire exposure e.g. timber stud walls and masonry walls without fair face > Load bearing walls likely to exhibit disttion during fie exposure e.g. steel stud walls > Load bearing nonload bearing walls. Fair faced masonry walls > Up to 10mm > Me than 10mm > All gap sizes > Me than 10mm > Up to 10mm > Intimately fitted soft of hard wood architraves at least 15mm thick with a 15 mm overlap onto the wall and do frame > Imperfectly fitting architraves > All architrave conditions > Fit of architrave cannot be guaranteed due to likely disttion of the wall > All architrave conditions > Immediately fitted 19mm hardwood quadrant bead > Nil 2mm x 10 mm of intumescent material as a pre-fmed strip seal mineral glass wool packed to a depth of at least 10mm A bed of intumescent mastic Nil NOTE: There is a risk that wall finishes with a surface spread of flame rating of Class 3, as defined in BS476:Part 7, may contribute to ignition and flaming of the architrave on the unexposed face due to leakage of hot gases. F smoke control do sets frame to wall gaps should always be packed with mineral glass wool sealed with a bead of intumescent paste mastic. Page 6 of 7

7 Table 3 RECOMMENDATIONS FOR THE JOINT BETWEEN TIMBER DOOR FRAMES AND WALLS TO PROVIDE 60 MIN FIRE RESISTANCE Wall construction Non-load bearing walls unlikely to exhibit significant disttion during fire exposure e.g. timber stud walls and masonry walls without fair face > Load bearing walls likely to exhibit during fire exposure e.g. steel stud walls > Load bearing nonload bearing walls. Fair faced masonry walls > Maximum Frame to Wall Gap Width Up to 10mm > Me than 10mm > All Gap sizes > All Gap sizes > Architrave Condition Intimately fitted soft hard wood architraves at least 15mm thick with a 15mm overlap onto the wall and do frame > Imperfectly fitting architraves > All architrave conditions > Fit of architrave cannot be guaranteed due to likely disttion of the wall > All architrave conditions > Additional Protection 2mm x 10mm of intumescent material as a pre-fmed stop seal mineral glass wool packed to a depth of at least 10mm A bead of intumescent mastic 2mm x 20mm of intumescent material as a pre-fmed strip seal mineral glass wool packed to a depth of at least 10mm A bead of intumescent mastic NOTE: There is a risk that wall finishes with a surface spread of flame rating of Class 3, as defined in BS476:Part 7, may contribute to ignition and flaming of the architrave on the unexposed face due to leakage of hot gases. F smoke control do sets frame to wall gaps should always be packed with mineral glass wool sealed with a bead of intumescent paste mastic. Page 7 of 7

Fire Doors Basic Guidance & Checklist

Fire Doors Basic Guidance & Checklist Fire Doors Basic Guidance & Checklist Introduction Fire doors and all passive fire protection products play a unique role in fire safety by containing a fire to a single compartment of a building and therefore

More information

The Role of Fire Doors. BWF-Certifire Fire Door and Doorset Scheme

The Role of Fire Doors. BWF-Certifire Fire Door and Doorset Scheme The Role of Fire Doors BWF-Certifire Fire Door and Doorset Scheme Fire doors today s agenda 1. Fire doors are essential in passive fire protection A requirement in compartmenting a building Protecting

More information

Code of Practice for fire resisting metal doorsets

Code of Practice for fire resisting metal doorsets COP 1005 Code of Practice for fire resisting metal doorsets Scope The aim of this document is to provide guidance on the best practice for, and a better understanding of, hinged or pivoted fire resisting

More information

GENERAL FIRE SAFETY TERMS & DEFINITIONS

GENERAL FIRE SAFETY TERMS & DEFINITIONS UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:

More information

FIRE DOORS - GENERAL SPECIFICATIONS / EMPLOYERS REQUIREMENTS (ERs) & QUICK OVERVIEW

FIRE DOORS - GENERAL SPECIFICATIONS / EMPLOYERS REQUIREMENTS (ERs) & QUICK OVERVIEW Fire Safety Technical Guide FIRE DOORS - GENERAL SPECIFICATIONS / EMPLOYERS REQUIREMENTS (ERs) & QUICK OVERVIEW Fire Door Provision In UCL Buildings - what you need to know: Not Acceptable Opening direction

More information

CERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED

CERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED CERTIFICATE OF APPROVAL No CF 291 This is to certify that, in accordance with TS General Requirements for Certification of Fire Protection Products The undermentioned products of Drummond Road, Stafford.

More information

Fire Doors The Role of a Fire Door

Fire Doors The Role of a Fire Door Fire Doors The Role of a Fire Door BWF-Certifire Fire Door and Doorset Scheme Presented by John Fletcher John Fletcher Consulting Ltd. Fire doors main messages 1. Fire doors are essential in passive fire

More information

Fire Doors Explained. Presented by - Peter Barker

Fire Doors Explained. Presented by - Peter Barker Fire Doors Explained Presented by - Peter Barker Objectives and Outline 1. The role of fire resisting doors 2. Proving the performance of fire resisting doors 3. Common problems and solutions The Role

More information

5.1. Smoke Sealing. General: The test procedure for smoke sealed doorsets is given by reference to BS476 Section 31.1.

5.1. Smoke Sealing. General: The test procedure for smoke sealed doorsets is given by reference to BS476 Section 31.1. v8 5.1 General: The test procedure for smoke sealed doorsets is given by reference to BS476 Section 31.1. The performance criteria for smoke sealed doorsets is given by reference to BS5588 (and BS9999)

More information

Fire doors guidance. Safety and Health Services. Document control information. Date issued: January 2011. Version: 2. Previous review dates: 2011

Fire doors guidance. Safety and Health Services. Document control information. Date issued: January 2011. Version: 2. Previous review dates: 2011 Document control information Fire doors guidance Published document name: Firedoors-gn.pdf Date issued: January 2011 Version: 2 Previous review dates: 2011 Next review date: Related documents: Governing

More information

Approved Document Q: Security

Approved Document Q: Security Approved Document Q: Security Requirement Q1 Unauthorised access Consultation draft September 2014 1 The approved documents What is an approved document? The Secretary of State has approved a series of

More information

Basic Fire Door Requirements

Basic Fire Door Requirements TECHNICAL DATA SERIES S D I 118-01 Basic Fire Door Requirements 2001 Steel Door Institute STEEL DOOR INSTITUTE 30200 DETROIT ROAD - CLEVELAND, OHIO 44145 Technical Data Series SDI 118-2001 Basic Fire Door

More information

Gordon Cooke BSc PhD CEng MICE MIMechE FIFireE

Gordon Cooke BSc PhD CEng MICE MIMechE FIFireE International Symposium on Protection of Cultural Heritage Buildings from Fire, Kyoto, April 6-7, 2003 Upgrading the fire resistance of floors and doors in heritage buildings Gordon Cooke BSc PhD CEng

More information

Relevant British, European and International standards

Relevant British, European and International standards Relevant British, European and International standards BS 1245:1975 Specification for metal door frames (steel) BS 3621:2007 + A1:2009 Thief resistant lock assemblies - Key egress BS 476-20:1987 Fire tests

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you

More information

Passive Fire Protection Guidance for the Fire Risk Assessor. Niall Rowan Technical Officer Association for Specialist Fire Protection

Passive Fire Protection Guidance for the Fire Risk Assessor. Niall Rowan Technical Officer Association for Specialist Fire Protection Passive Fire Protection Guidance for the Fire Risk Assessor Niall Rowan Technical Officer Association for Specialist Fire Protection ASFP has just completed a guide on what to look for when undertaking

More information

Composite Panel Firewall Systems

Composite Panel Firewall Systems Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.

More information

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in REV 1-12.12.11/TB002 Technical Bulletin Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in conjunction with TRADA Technology and is intended to provide the reader with introductory

More information

Tremco Fire Protection Systems Group Technical Bulletin

Tremco Fire Protection Systems Group Technical Bulletin Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,

More information

Office of the State Fire Marshal. Fire Rated Doors

Office of the State Fire Marshal. Fire Rated Doors Office of the State Fire Marshal Fire Rated Doors Fire Rated Doors These doors serve a purpose. They are manufactured in a way that is to help reduce the spread of fire and smoke. Fire rated doors allow

More information

Standard Door Specification

Standard Door Specification Element General Requirement To be defined in the project brief but should meet Building Regulations. All doors to be a minimum of 30 minute fire rated and must comply with all relevant UK legislation and

More information

Technical data sheet PVC Bi-fold doors

Technical data sheet PVC Bi-fold doors Standard Specifications White internally beaded, Deceuninck 3000 series profile 28mm Low-e toughened sealed units with argon gas Open in doors with white handles and hinges Tracks are fitted to the top

More information

Guidance on loft conversions in two-storey houses

Guidance on loft conversions in two-storey houses Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for

More information

ModuSec. Secure and efficient IT room solutions. Turnkey Modular Construction Fast clean build to any size or shape

ModuSec. Secure and efficient IT room solutions. Turnkey Modular Construction Fast clean build to any size or shape ModuSec Secure and efficient IT room solutions Turnkey Modular Construction Fast clean build to any size or shape Room in room Standalone external build Transportable Modusec SR Options Modusec SR Options

More information

FIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England

FIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England FIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England Fire is a life-threatening and destructive force, which if unchecked, can spread rapidly through a building. Every year,

More information

>active antimicrobial wall cladding for hygienic environments

>active antimicrobial wall cladding for hygienic environments >active antimicrobial wall cladding for hygienic environments Activ:ion makes hygiene-critical areas safer than ever. >04 Food >06 Leisure >08 Healthcare >10 About Activ:ion >12 Lab tests >13 Technical

More information

Security steel door dw 52-1 Teckentrup DF WK 2 optionally with glazing/ventilation grille

Security steel door dw 52-1 Teckentrup DF WK 2 optionally with glazing/ventilation grille Security steel door dw 52-1 Teckentrup DF WK 2 optionally with glazing/ventilation grille Text example Compile and tender according to requirements. Please refer to technical data below for respective

More information

Services Enclosures and Protected Shafts - Maintaining Compartmentation

Services Enclosures and Protected Shafts - Maintaining Compartmentation Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping

More information

Intumescent Fire Seals

Intumescent Fire Seals Intumescent Fire Seals Trade Name: ASTRO STRIP Intumescent Strip - Fire Only Astrostrip FO - fire only seals. Intumescent seals for use where no smoke sealing is required. CERTIFIRE Approval CF276 Passed

More information

White Paper FIRE DOOR INSPECTIONS, REPAIRS AND LABELING

White Paper FIRE DOOR INSPECTIONS, REPAIRS AND LABELING INTRODUCTION When the 2012 edition of the Life Safety Code is adopted by the Centers for Medicare Services (CMS) the following accreditation organizations The Joint Commission, AOA Healthcare Facilities

More information

ABLOY EXIT. Functional and technical descriptions Single and double leaf doors. An ASSA ABLOY Group brand

ABLOY EXIT. Functional and technical descriptions Single and double leaf doors. An ASSA ABLOY Group brand SSFN 014/2 2 ABLOY EXIT Functional and technical descriptions Single and double leaf doors An ASSA ABLOY Group brand ABLOY EXIT - EXIT PRODUCTS It is time to take the exit safety standards to a new level.

More information

Fire safety in timber buildings

Fire safety in timber buildings Fire safety in timber buildings Introduction Fire spread in buildings is a risk to life safety for which the Building Regulations (for England and Wales 1,2, Scotland 3 and Northern Ireland 4 ) aims to

More information

TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER

TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER PSUM These technical specifications determinate a range of manufactured sizes and models of fire shutters (further only shutters)

More information

Narrow stile lock 1314

Narrow stile lock 1314 3 2 4 6 6 1 3 2 4 4 5 3 2 4 3 5.... ( (. ). ) 11 12 5 3 5 4 8 1 6 20 8.5 6.5 19 Backset 15 3 5 2 1 5 2 5 5 0 8 9 2 8 1 1 21-1mm 12 8 24 1 6 8 1 ( 9 2 5 ) ) ). ) Narrow stile lock 1314 CE EN 12209 2 4 5

More information

Energy Company Obligation (ECO): Technical Monitoring Questions

Energy Company Obligation (ECO): Technical Monitoring Questions Energy Company Obligation (ECO) Technical Monitoring Questions v1 30/05/2013 Energy Company Obligation (ECO): Technical Monitoring Questions Under ECO suppliers are required to instruct suitably qualified

More information

A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS

A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard : ISSUE 3.0 Requirements for the LPCB Approval and Listing of Companies Undertaking the Maintenance and Repair of Doorsets, Shutters, and Active Smoke/Fire Barriers This standard

More information

- 5 - Table1. Maximum Compartment Volumes

- 5 - Table1. Maximum Compartment Volumes - 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,

More information

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations

More information

FIRE RATED GLAZING System Guide

FIRE RATED GLAZING System Guide SYSTEM GUIDE Issue date: 05-05-2015 Expiry date: 31-12-2016 System Guide Introduction Pyropanel Developments are specialists in fire rated glazing solutions, and our systems are designed for easy installation

More information

IMPORTANT INFORMATION

IMPORTANT INFORMATION Curved Quadrant Instruction Manual CQ IMPORTANT INFORMATION Toughened glass is completely safe for use in our shower enclosures and bath screens; providing our products are installed according to our guidelines.

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

Safety Storage Cabinets

Safety Storage Cabinets Safety Storage Cabinets Safe storage of flammables? The workplace without a fire resistant Safety Storage Cabinet Dangers, risks and your disadvantages... STORAGE ROOM Transport/working time - Increased

More information

How To Write A Fire Risk Assessment

How To Write A Fire Risk Assessment Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes

More information

BASIC FIRE DOOR REQUIREMENTS TECHNICAL DATA SHEET NO. 401

BASIC FIRE DOOR REQUIREMENTS TECHNICAL DATA SHEET NO. 401 BASIC FIRE DOOR REQUIREMENTS SHEET NO. 401 Fire door openings are classified by their locations in the building. The location determines the length of exposure protection required, based on the potential

More information

Glass partitions SFB 3074

Glass partitions SFB 3074 Glass partitions SFB 3074 Our facade system SFB 3074 is innovative in its design. We have made a great effort to obtain an energy effective system. The future requirements regarding the economical use

More information

Important Information

Important Information Single Door Quadrant Instruction Manual ESQ Important Information Toughened glass is completely safe for use in our shower enclosures and bath screens; providing our products are installed according to

More information

A1 Example fire safety maintenance checklist

A1 Example fire safety maintenance checklist Appendix A A1 Example fire safety maintenance checklist A fire safety maintenance checklist can be used as a means of supporting your fire safety policy. This list is not intended to be comprehensive and

More information

ISSUE 2. Installation Guide

ISSUE 2. Installation Guide ISSUE 2 Installation Guide Here at Slide and Fold, we LOVE our Bi-Fold Plus range of folding-sliding doors. We want to ensure that your customers love them too. So we have created a new, detailed installation

More information

REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012

REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012 TEST REPORT REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Fire Door Caulk LLC.

More information

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct

More information

Installation Instructions and Ordering Information

Installation Instructions and Ordering Information The Flush Finish Trimless Door Frame Installation Instructions and Ordering Information CLEAN LINES! The Flush Finish Door Jamb System Manufactured by STUDCO Building Systems Step 1 Verify if you are using

More information

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

Installation Window Building In Details

Installation Window Building In Details Installation Window Building In Details INSTALLATION Photo courtesy of Rowe Aluminium DATE: NOVEMBER 2009 REPLACES: AUGUST 2003 INSTALLATION Installation Replaces: Scale: NOT TO SCALE Vantage snap-on couplers

More information

RADAR. 227 www.ncdirect.co.uk

RADAR. 227 www.ncdirect.co.uk RADAR solutions RADAR RADAR Key System 228 RADAR Lockset 229 RADAR Cover Plate 229 RADAR Padlock 230 RADAR Automatic Toilet Entry System 231 RADAR Ramp 231 RADAR Ramp Sign 231 227 www.ncdirect.co.uk RADAR

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

Fiberglas, Exterior Wall Thermal Insulation

Fiberglas, Exterior Wall Thermal Insulation PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

Fire Barriers & Fire Stopping

Fire Barriers & Fire Stopping Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com Environmental Part 2 Life Safety Code Chapter 8 Fire Barriers & Fire Stopping 1 Fire

More information

Tested to BS 6375: Part 1: 1989 and achieved a weathertightness classification of 2000 Pa (Special)

Tested to BS 6375: Part 1: 1989 and achieved a weathertightness classification of 2000 Pa (Special) THE B6 GLAZING SYSTEM GLAZING SYSTEMS FOR SEPTEMBER 2013 THE B6 HEEL BEAD SEAL SECURITY GLAZING SYSTEM Page 1 DESCRIPTION The B6 Heel Bead Seal Security Glazing System is suitable for installing all types

More information

BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010

BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010 Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance

More information

Panic & emergency exit devices

Panic & emergency exit devices CFPA-E Guideline CFPA-E No 2:2007 - Appendix Appendix No: 1 Panic & emergency exit devices FOREWORD This Appendix offers technical solutions according to table 8.1 in the European Guide Line ""Panic &

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard LPS 1581: Issue 2.1 Requirements and tests for LPCB approval of nonload This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information

More information

Fire-Rated Doors and Hardware. A Guide to Field Inspection

Fire-Rated Doors and Hardware. A Guide to Field Inspection Fire-Rated Doors and Hardware A Guide to Field Inspection Foundation s Mission To promote secure and safe openings that enhance life safety Awareness To be a source of information through awareness campaign

More information

Installation Instructions

Installation Instructions Installation Instructions 1. Position the unit onto bridging packers. These keep the unit away from any water sitting inside the frame. 2. Centralise the unit within the frame and pack the edges with appropriate

More information

LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market

LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market Ian Stewart Passive installer scheme manager September 2011 Introduction to BRE Global Research,

More information

TRADITIONAL CASEMENT WINDOWS

TRADITIONAL CASEMENT WINDOWS TRADITIONAL CASEMENT WINDOWS Design Guide Timber casement windows succeeded the stone mullioned window, to become the most common window type by the second half of the eighteenth century. The traditional

More information

Thanks go to the following officers who have produced this guide:

Thanks go to the following officers who have produced this guide: London Fire Safety Guidance for Houses in Multiple Occupation Introduction Part 1 of the Housing Act 2004 introduced the Housing Health and Safety Rating System (HHSRS). Statutory Operating Guidance provides

More information

Architectural Nylon. Architectural. Nylon

Architectural Nylon. Architectural. Nylon Architectural Nylon Architectural Nylon Contents Paris Series 273-279 Pull Handles and Accessories 281-292 269 Architectural Nylon HOPPE nylon levers and pull handles are manufactured to exacting standards

More information

Technical Information

Technical Information Technical Information This section of the catalogue provides technical information that will help specify, install and maintain Surelock McGill devices and components. The topics are listed below: Blast

More information

CERTIFICATE OF APPROVAL No CF 5055 ARABIAN VERMICULITE INDUSTRIES

CERTIFICATE OF APPROVAL No CF 5055 ARABIAN VERMICULITE INDUSTRIES CERTIFICATE OF APPROVAL No CF 5055 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 1 st Industrial Area,

More information

(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark

(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark Spectrum Laboratories Ltd is accredited by International Accreditation New Zealand (formerly Telarc). The tests reported herein have been performed in accordance with the terms of our accreditation. This

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test

More information

CLEAR-DIVISIONS CENTERFOLD

CLEAR-DIVISIONS CENTERFOLD CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in

More information

Lift-off hinge. Rising hinge. Standard hinge. Heavy duty hinge. Parliament hinge. Spring hinge. Double action spring hinge. Concealed mortise hinge...

Lift-off hinge. Rising hinge. Standard hinge. Heavy duty hinge. Parliament hinge. Spring hinge. Double action spring hinge. Concealed mortise hinge... Door Hinges Contents Butt hinges Lift-off hinge Rising hinge Standard hinge Heavy duty hinge Parliament hinge Spring hinge Double action spring hinge Concealed hinges Concealed mortise hinge... Pivot

More information

NRG 75 CRF NRG GREENBOARD WALL SYSTEM

NRG 75 CRF NRG GREENBOARD WALL SYSTEM NRG GREENBOARD WALL SYSTEM NRG Energy Efficient Building Systems is pleased to announce a revolution in lightweight cladding systems. NRG Building Systems is the first and only company to achieve CodeMark

More information

PHA 2000 PHB 3000 EXIT PAD

PHA 2000 PHB 3000 EXIT PAD PHA 2000 PHB 000 EXIT PAD Panic Hardware in Contur Design PHA 2000 PHB 000 EXIT PAD THE MODULAR PANIC HARDWARE-SSTEM IN CONTUR DESIGN Prior knowledge of how to open the escape door is not expected. DANGER

More information

Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing

Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing Substrate, structural panel, bonded waterproofing The universal substrate for tiles Perfect covering No matter whether you work with mosaics or large format tiles, an absolutely level substrate with straight

More information

ARCHITECTURAL. FritsJurgens Pivot Door System Product Range Brochure

ARCHITECTURAL. FritsJurgens Pivot Door System Product Range Brochure ARCHITECTURAL FritsJurgens Pivot Door System Product Range Brochure About Bellevue and FritJurgens -90 0 90 For over 30 years, the name Bellevue Architectural (formerly Bellevue Imports) has always been

More information

HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663)

HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663) HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663) Fire-Retardant-Treated Wood Framed Wall Assemblies GENERAL INFORMATION Fire-resistant construction

More information

Sliding and Folding Door Fittings Sliding Door Accessories

Sliding and Folding Door Fittings Sliding Door Accessories Sliding door lock Toplock For 1- and 2-leaf sliding doors Suitable for toughened safty glass and laminated sheet glass Suitable for DIN left and DIN right Max. weight per door leaf 120 kg For glass thickness:

More information

Steel Door Institute. Fire Rated Doors and Frames

Steel Door Institute. Fire Rated Doors and Frames Steel Door Institute Fire Rated Doors and Frames 1 1. Nomenclature and Overview 2. Fire Rated Frames 3. SDI 118 4. Fire Rated Doors 5. Fire Rated Hardware 6. Specialty Products Table of Contents 2 Fire

More information

FireWall. High performance fireresistant. FireWall. www.british-gypsum.com

FireWall. High performance fireresistant. FireWall. www.british-gypsum.com FireWall FireWall High performance fireresistant wall system FireWall is a non-loadbearing wall which provides up to 240 minutes fire resistance. It is used in certain ground floor basement situations

More information

A Guide to Best Practice in the Specification and Use of Fire-Resistant Glazed Systems

A Guide to Best Practice in the Specification and Use of Fire-Resistant Glazed Systems Cl/SfB Ro Summer 2011 A Guide to Best Practice in the Specification and Use of Fire-Resistant Glazed Systems Issue 3 Introduction Introduction Table of Contents Introduction by Chairman 7 Terms used in

More information

Fire-resistance test on fire collars protecting a concrete slab penetrated by services

Fire-resistance test on fire collars protecting a concrete slab penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Mario Lara Report number: FSP 1614 Date: 14 February 2014 Client:

More information

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004]

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Case Study [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Requirement Intent Page 1 of 14 The primary intent behind the requirement for a vestibule is to reduce infiltration

More information

Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings

Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings BUILDING ENVELOPE DESIGN BY ROXUL Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB Exterior

More information

Contents. APA Construction Details. Full fill cavity walls 2-13. Partial fill cavity walls 14-25. Solid externally insulated walls 26-37

Contents. APA Construction Details. Full fill cavity walls 2-13. Partial fill cavity walls 14-25. Solid externally insulated walls 26-37 Contents Pages Full fill cavity walls 2-13 Partial fill cavity walls 14-25 Solid externally insulated walls 26-37 Appendix (BRE confirmation of Ψ and y-values) 38-40 Page 1 of 40 APA Construction Details

More information

WHI 90-Minute Rated Veneered Door Frame Installation Instructions

WHI 90-Minute Rated Veneered Door Frame Installation Instructions No. 940-03-10 INSTALLATION INSTRUCTIONS 90 MINUTE RATED VENEERED DOOR FRAME DOOR REQUIREMENTS: Consult the door manufacturer to make sure that the doors are qualified for the hardware to be installed,

More information

K17.12 Door closers K17. Doors 01.09.2013

K17.12 Door closers K17. Doors 01.09.2013 K17 Doors K17.12 01.09.2013 Waregemstraat 5-9870 Zulte - Belgium - T. +32 9 388 88 81 - F. +32 9 388 88 21 - commercial@sobinco.com - www.sobinco.com Contents 1. OPTIC door closer TS40(V) with scissor

More information

ARCHITECTURAL. CEAM INVISIBLE HINGES new adjustable 3D concealed hinge products for swing doors 100% made in Italy

ARCHITECTURAL. CEAM INVISIBLE HINGES new adjustable 3D concealed hinge products for swing doors 100% made in Italy RHITETURL EM INVISILE HINGES new adjustable 3D concealed hinge products for swing doors 1% made in Italy eam oncealed Hinges by ellevue - Smart rchitectural Products bout ellevue and eam For over 3 years,

More information

Financial Services Authority

Financial Services Authority Financial Services Authity Notice of undertaking Introduction As a qualifying body, we, the Financial Services Authity (the FSA), can challenge firms using terms which we view as unfair under the Unfair

More information

Vitraflex Classic Modular Combination Shower and Changeroom Cubicles (c/w Telescopic Stainless Steel Leg Anchors)

Vitraflex Classic Modular Combination Shower and Changeroom Cubicles (c/w Telescopic Stainless Steel Leg Anchors) GENERAL PRODUCT SPECIFICATIONS Vitraflex Classic Modular Combination Shower and Changeroom Cubicles (c/w Telescopic Stainless Steel Leg Anchors) (Document Reference CC/GPS/CUBE/03 Rev. 1 April 2010) (E&OE

More information

Safe Method: Gas Safety in Catering Establishments

Safe Method: Gas Safety in Catering Establishments Safe Method: Gas Safety in Catering Establishments Safety Point Why? What do you do? Gas equipment and services must only be installed, maintained and repaired by a Gas Safe registered installer. Check

More information

Dubai Municipality Standard DMS 1: Part 5: 2004

Dubai Municipality Standard DMS 1: Part 5: 2004 Specification for precast concrete blocks Part 5: Normal-weight concrete-polystyrene sandwich masonry blocks Issue Date Revision Revision Description Prepared by Approved by Authorized by 19/12/2004 Issue

More information

Building Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings

Building Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings Building Envelope Design using ROXUL Building Envelope Design using ROXUL (BEDR ) FIREWALL and ROXUL PLUS MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB

More information

Security Dwellings. The Building Regulations 2010. 2015 edition for use in England* ONLINE VERSION APPROVED DOCUMENT ONLINE VERSION

Security Dwellings. The Building Regulations 2010. 2015 edition for use in England* ONLINE VERSION APPROVED DOCUMENT ONLINE VERSION The Building Regulations 2010 Security Dwellings APPROVED DOCUMENT Q Q1 Unauthorised access 2015 edition for use in England* The 2015 Edition This approved document supports requirement Q1 of Schedule

More information

What locks do I have Timber Doors

What locks do I have Timber Doors What locks do I have Timber Doors Introduction Locking mechanisms on doors are varied and it can be difficult to judge whether what you have is good, bad or indifferent. This information takes you through

More information