PREVENTIVE MAINTENANCE & ROUTINE INSPECTION OF CONTACTORS

Size: px
Start display at page:

Download "PREVENTIVE MAINTENANCE & ROUTINE INSPECTION OF CONTACTORS"

Transcription

1 Page # 1/5 PREVENTIVE MAINTENANCE & ROUTINE INSPECTION OF CONTACTORS A. GENERAL INSPECTION: A.1. Check for loose, missing, broken or corroded hardware, pivot pins, cotter pins, springs and other mechanical parts. B. ARC BOXES: B.1. Check arc boxes for broken or eroded parts and Grid plates and also for excessive collection of contact material or other foreign conducting material on the surface of insulating parts. B.2. Replace broken or badly eroded parts. B.3. Clean or replace parts having excessive build of conducting material. C. CONTACTS: C.1. C.2. C.3. C.4. C.5. D. SHUNTS: D.1. D.2. Remove oxide or large beads of contact materials from the faces of contacts, using a fine file or sandpaper.(emery cloth should not be used for cleaning contacts.) Do not file or sand silver or alloy contact faces unless considerable foreign matter has collected on the surface of the contacts. When replacing contacts or other current-carrying parts, clean surfaces, which are to be bolted together. Realign contacts and set over travel if necessary. Do not substitute contact material without factory approval. Replace shunts having broken of frayed strands. Clean connection points if current-carrying parts are discolored. E. BLOWOUT COILS: E.1. Inspect blowout coils for discolored connections, shorted turns, and loose hardware. F. TERMINALS, CNTACT SUPPORTS, BUS BARS, AND CONNECTORS. F.1. Discolored connections usually indicate that overheating has occurred, probably because of loose connections. F.2. Clean connection points which are discolored and tighten all hardware.

2 Page # 2/5 G. INSULATORS. G.1. Remove dust and dirt from insulating parts. G.2. If carbonized tracks or cracked or broken insulators are found, replace the defective parts. G.3. As a last resort, carbonized tracks may be scraped clean and painted with insulating varnish. G.4. Before a repaired part is put into service give it an over voltage test. H. MAGNET ASSEMBLY. H.1. Check magnet for dirty or corroded pole faces, pivot points, and other moving parts. H.2. Check for loose, broken, or missing shading coils, residual shims, and hardware. H.3. Inspect operating coil for evidence of electrical or mechanical damage. H.4 Operate armature by hand and check for mechanical interference and friction. I. ELECTRICAL OPERATION. I.1. Operate the contactor electrically without load and observe magnet operation to be sure it opens and closes cleanly and that armature is fully sealed in the closed position. If an a-c magnet is used, check for abnormal Magnet noise. I.2. Test a sample of oil used with oil-immersed contactors and fill oil tank to the proper level with good oil. I.3. Megger insulation between phases, to ground, and to the control circuit. I.4. Operate the contactor under load and check for abnormal report and arcing both on opening and closing. A Loud report and arcing on closing is usually due to contact bounce. The magnitude of the report and arcing found on opening and closing will depend upon the type of contactor, operating load, and phase angle at which the contacts separate or touch. Since no absolute standard can be set for covering this detail, it will be necessary to judge performance on the basis of past experience with equipment when it was new or with other applications having similar equipment and operating conditions. J. ELECTRICAL OPERATION. The following table will be of great help in trouble shooting of contactors: Sl Trouble/Defect Cause What to do/remedy A. MAGNET. 01 Coil Burned out. Mechanical damage. Replace. Protective resistance or high resistance winding is not Inserted in series with d-c coil when armature seals in. Coil voltage is too high. Adjust, repair, or replace interlock and series resistance so that continuous rating of coil is not exceeded when armature is sealed. Correct coil voltage. Use higher-voltage coil.

3 Ambient temperature is too high. Provide better ventilation. Relocate starter. Intermittent coil is energized too long. Re-adjust operating cycle. Check factory for special coil. Jogging duty is too severe. Readjust operating cycle. Check factory for special coil. Abnormal atmosphere. Relocate starter. Check factory for special coil. 02 Does not pick up. Defective coil. Replace. Low voltage. Correct coil voltage or system Voltage. Mechanical interference or friction Adjustments and/or repairs. Magnetic lockout. Use nonmagnetic-armature-stop details. Add nonmagnetic Shim between armature and armature stop. 03. Does not seal; hesitates at Contact touch; drops open Mechanical interference or friction. adjustments and/or repairs. to contact touch. (This condition may exist only Contact force too high. Replace springs. Remove friction from moving contact assembly. Adjust spring length if adjustment is provided. when operating coil is hot or line voltage is low.) Coil voltage too low. Correct coil Voltage or System Voltage. Use lower-voltage coil. Series protective resistance or high-resistance coil Adjust, repair, or replace interlock and/or series resistance. winding is inserted too early, or series resistance is too high (For DC Magnets). Coils of two-coil d-c magnet have bucking polarity. Reverse polarity of one coil and check operation with load disconnected. 04. Does not dropout, or Dirt or grease on pole faces. Clean. dropout is sluggish. Mechanical interference or friction. adjustments and/or repairs. Residual shim is pounded down or is missing. Replace residual shim or magnet assembly. Residual air gap is pounded down. Kick out spring is defective or missing. Replace (Kick out spring is not used on all contractors). Control relay does not open d-c side of rectifier. Control relay has long arcing time. Add contact in control circuit. Repair or replace relay. Repair or replace relay. Shorted coil turns. (DC Magnet) Replace coil. 05. Magnet chatter or Shading coil broken or out of place. Adjust or Replace.

4 pumping. PREVENTIVE MAINTENANCE & ROUTINE INSPECTION OF CONTACTORS: Series protective resistance or high-resistance coil Winding is inserted too early, or series resistance is too high or is open. (Applies to DC magnets having over voltage during Pickup.) Chattering contacts on control relay, control switch, Pressure switch, temperature switch, etc. Adjust, Repair or replace interlock and/or series resistance. Check over travel and contact force on control device. Replace control device. Move control device to a location having less vibration, or insulate control device from shock And vibration. Tighten connections. Loose connections. 06. Noisy a-c magnet. Armature does not seal in tight. Clean pole faces. Remove mechanical interference and/or friction. Pole faces rough. Replace magnet assembly. File pole faces as a last resort If new parts are not available. Magnet misaligned. Realign. Shading coil broken or out of place. Replace. Coil voltage is low. Correct coil voltage or system voltage. B. Contacts. 01. Overheating. Load current too high. Loose connections. Reduce load. Use larger contactor. Clean discolored or dirty Connections and retighten. Over travel and/or contact force too low. Adjust over travel, replace contacts, and replace contact Springs as required to correct defect. Collection of copper oxide or foreign matter on contact Faces. Clean with fine file or sandpaper. Use dust -tight enclosure for dusty atmosphere. Load is on in excess 8hr. Change operating procedure. Check factory for more Suitable contacts Ambient temperature is too high. Reduce load. Provide better ventilation. Relocate starter. Use larger contactor. Line and/or load cables are too small. Apply cable in line with existing load. 02. Welding of contacts. Over travel and/or contact force is too low. Adjust over travel, replace contacts, and replace contact spring Magnet stalls or hesitates at contact touch point. See Magnet, this table. Magnet drops open at contact touch due to voltage See Magnet, this table. dip. Magnet chatter. See Magnet this table. Contact bounce on closing. Correct coil over voltage condition. Correct mechanical defects.

5 Contacts rebound to contact touch when opening. Correct mechanical defects in stop assembly. Correct Mechanical defects in latch if one is used. Poor contact alignment. Adjust contacts to touch simultaneously within 1/32 in. Jogging duty is too severe. Reduce jogging cycle. Check factory for more weld-resistant contact material. Use larger contactor. Excessive inrush current. Readjust accelerating time or operating sequence. Use larger contactor. Check factory for more weld-resistant contact material. Vibration in starter mounting. Move starter to location having less shock and vibration. Insulate starter from shock and vibration. Provide more rigid Support for starter. Jogging cycle is too severe. Reduce jogging cycle. Check factory for more durable contact material. Use larger contactor. Oil-immersed contactor is used where an air break Contactor could be used. Air break contactors may have 10 to 20 times longer contact life than oil-immersed contactors of equal ratings C. ARC INTERRUPTION Poor arc interruption. Arc box not in place. Install arc box in line with instruction-leaflet data. Arc box damaged. Replace broken or eroded insulating parts, arc horns, and grid plates. Clean or replace insulating parts having a heavy Coating of foreign conducting material. Dirt or paint on arc horns or steel grid plates. Remove insulating materials, which may have accumulated on arc horns and steel grid plates. Magnetic hardware substituted for nonmagnetic Replace with correct hardware. hardware in arc box and blowout assemblies. Blowout coil reversed or short-circuited. Replace coil. Correct defect. Magnet opening is sluggish. See Magnet, this Table.

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C 41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers

More information

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number

More information

(3) Explosion proof. Designed to prevent ignition of any explosive gases or dust and dirt which may surround the motor.

(3) Explosion proof. Designed to prevent ignition of any explosive gases or dust and dirt which may surround the motor. ELECTRIC MOTORS Enclosures for Motors Types of motor enclosures generally used in farm applications: (1) Open type; drip proof or splash-proof. A general purpose motor for use in dry locations which are

More information

Directions for use : Dosing chutes type DSX.

Directions for use : Dosing chutes type DSX. Pag. 1-10 Directions for use : Dosing chutes type DSX. Introduction The linear vibrations of STILETTO consist of a drive part and a movable part which are connected to leave springs. The purpose of the

More information

AZ420 MINIATURE GENERAL PURPOSE RELAY

AZ420 MINIATURE GENERAL PURPOSE RELAY MINIATURE GENERAL PURPOSE RELAY FEATURES Rugged construction for high reliability Life expectancy greater than 0 million operations DC coils to 11 V Power consumption as low as 2 mw per pole available

More information

DC MOTOR ANALYSIS & TROUBLESHOOTING

DC MOTOR ANALYSIS & TROUBLESHOOTING DC MOTOR ANALYSIS & TROUBLESHOOTING By Don Shaw Condition assessment of DC motors requires a basic understanding of the design and operating characteristics of the various types available: the series motor,

More information

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line

More information

Chapter 7 Hydraulic System Troubleshooting

Chapter 7 Hydraulic System Troubleshooting Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic

More information

Single Phase Soft Starter

Single Phase Soft Starter Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

ELECTRICAL SAFETY RISK ASSESSMENT

ELECTRICAL SAFETY RISK ASSESSMENT ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures

More information

12. Inspection and Maintenance

12. Inspection and Maintenance 12. and Maintenance Mandatory Be sure to inspect the inverter regularly and periodically to prevent it from breaking down because of the environment of use, such as temperature, humidity, dust and vibration,

More information

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table Z. Troubleshooting Chart for Air Conditioners. Cause Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SF 6 Gas Insulated Switchgear Type SDF for 170 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment

More information

Type MG-6 Multi-Contact Auxiliary Relay

Type MG-6 Multi-Contact Auxiliary Relay Type MG-6 Multi-Contact Auxiliary Relay Instruction Leaflet: 41-753.1 N Effective: August 2008 Supersedes 41-753.1 M, Dated December 1999 ( ) Denotes Change Since Previous Issue Device Number: 94X, Y,

More information

Hydraulic Trouble Shooting

Hydraulic Trouble Shooting Hydraulic Trouble Shooting Hydraulic systems can be very simple, such as a hand pump pumping up a small hydraulic jack, or very complex, with several pumps, complex valving, accumulators, and many cylinders

More information

IA Renewal Seminar 2014

IA Renewal Seminar 2014 IA Renewal Seminar 2014 Introductions Introductions Scott Durham President, Co-Owner Overview of FAA / EASA Certified Repair Station Instrument & Accessory Overhaul Location: McClellan CA (Sacramento)

More information

Single-Phase AC Synchronous Generator

Single-Phase AC Synchronous Generator ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description

More information

DiscPlus DX195 and DX225 Air Disc Brakes

DiscPlus DX195 and DX225 Air Disc Brakes Revised 11-04 Technical Bulletin Revised 1 Technical 11-04 Bulletin DiscPlus DX195 and DX225 Air Disc Brakes Inspection, Installation and Diagnostics Air Disc Brake Inspection Intervals and Procedures

More information

SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor

SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor INSTALLATION, OPERATION AND MAINTENANCE MANUAL For SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor Yeomans Chicago Corporation 3905 Enterprise Court P.O. Box 6620 Aurora, IL 60598-0620 Phone:

More information

Preview of Period 16: Motors and Generators

Preview of Period 16: Motors and Generators Preview of Period 16: Motors and Generators 16.1 DC Electric Motors What causes the rotor of a motor to spin? 16.2 Simple DC Motors What causes a changing magnetic field in the simple coil motor? 16.3

More information

Installation and Operating Instructions (for chargers shown below)

Installation and Operating Instructions (for chargers shown below) Installation and Operating Instructions (for chargers shown below) For additional information please call our Technical Support Group 800.742.2740 PRO CHARGING SYSTEMS, LLC 1551 Heil Quaker Boulevard,

More information

Explosion proof enclosures

Explosion proof enclosures 1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without

More information

SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT

SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT Overview In all drying out of electrical windings, the regulation of temperature should be controlled carefully. Maximum drying temperatures on windings should

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

ELECTRIC MOTOR TEFC OPERATION & MAINTENANCE. meps Approved

ELECTRIC MOTOR TEFC OPERATION & MAINTENANCE. meps Approved SOUTH AUSTRALIA HEAD OFFICE (Accounts / Payments) 34-36 Kinkaid Avenue NORTH PLYMPTON SA 5037 Ph: (08) 8295 5566 Fax: (08) 8295 5533 VICTORIA 23 James Street CLAYTON SOUTH VIC 3169 Ph: (03) 9544 2324 Fax:

More information

SOLAR PV SYSTEM MAINTENANCE GUIDE

SOLAR PV SYSTEM MAINTENANCE GUIDE SOLAR PV SYSTEM MAINTENANCE GUIDE GUYANA HINTERLANDS STAND-ALONE SOLAR PV INSTALLATIONS IMPROVING HEALTH FACILITY INFRASTRUCTURE (IHFI) GUYANA CONTRACT NO. EPP-I-00-03-00008-00, TASK ORDER 07 APRIL 2013

More information

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions: The Charging System Charging System The charging system has two essential functions: Generate electrical power to run the vehicle s electrical systems Generate current to recharge the vehicle s battery

More information

Chapter 5 - Aircraft Welding

Chapter 5 - Aircraft Welding Chapter 5 - Aircraft Welding Chapter 5 Section A Study Aid Questions Fill in the Blanks 1. There are 3 types of welding:, and, welding. 2. The oxy acetylene flame, with a temperature of Fahrenheit is produced

More information

TQ SMD RELAYS TQ SMD LOW-PROFILE SURFACE-MOUNT RELAY FEATURES SPECIFICATIONS

TQ SMD RELAYS TQ SMD LOW-PROFILE SURFACE-MOUNT RELAY FEATURES SPECIFICATIONS LOW-PROFILE SURFACE-MOUNT RELAY RELAYS.55 5.6. FEATURES Low-profile: 6 mm.36 inch (Tape height: max. 6.5 mm.56 inch) Tape and reel package is available as standard packing style Surge withstand between

More information

PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual

PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual A Regal Brand TABLE OF CONTENTS INTRODUCTION 2 General Data 2 Initial Inspection 2 SAFETY 2 INSTALLATION 3 Location / Environment

More information

Installation Guide of Sunrise Solartech PV Modules. Term 2013. Contents. Purpose of this guide. General. Safety precaution for installing a solar

Installation Guide of Sunrise Solartech PV Modules. Term 2013. Contents. Purpose of this guide. General. Safety precaution for installing a solar Installation Guide of Sunrise Solartech PV Modules Term 2013 Contents Purpose of this guide General Safety precaution for installing a solar Photovoltaic system Product Identification Mechanical Installation

More information

Rutland 913 Windcharger Fault Finding Guide

Rutland 913 Windcharger Fault Finding Guide Rutland 913 Windcharger Fault Finding Guide Document No. SM-133 Issue A LOW VOLTAGE CHARGE CURRENT? TE 4 REGULATOR TE 5 REG RETURN REG TO MANUFACTURER CHARGE CURRENT INTERMITTENT CHARGE CURRENT SUFFICIENT

More information

HIGH REPEATABILITY, BROADBAND TO-5 RELAYS DPDT

HIGH REPEATABILITY, BROADBAND TO-5 RELAYS DPDT HIGH REPEATABILITY, BROADBAND TO-5 RELAYS DPDT SERIES RF00 RF00D RF00DD RF0 RF0D RF0DD RELAY TYPE Repeatable, RF relay Repeatable, RF relay with internal diode for coil transient suppression Repeatable,

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

AC Electric Motors best practice

AC Electric Motors best practice If you want to learn more about best practice machinery maintenance, or world class mechanical equipment maintenance and installation practices, follow the link to our Online Store and see the Training

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

16. APTA PR-IM-S-016-02 Standard for Pantograph Current Collection Equipment Periodic Inspection and Maintenance

16. APTA PR-IM-S-016-02 Standard for Pantograph Current Collection Equipment Periodic Inspection and Maintenance 16. APTA PR-IM-S-016-02 Standard for Pantograph Current Collection Equipment Periodic Inspection and Maintenance Approved October 30, 2002 APTA Passenger Rail Equipment Safety Standards Task Force Authorized

More information

Adjustment functions for both span and shift have been incorporated

Adjustment functions for both span and shift have been incorporated SENSORS FOR SERIES LED Type Wafer Alignment Sensor FX-0-F FT-F9 FD-F7 EX-F70/F60 M SH-7 FD-L4 M-DW The use of a safe LED light beam now allows for high precision detection with a resolution of 0!m (.8

More information

CHARGING SYSTEMS INTERNATIONAL

CHARGING SYSTEMS INTERNATIONAL CHARGING SYSTEMS INTERNATIONAL INSTALLATION AND OPERATING INSTRUCTIONS FOR THE FOLLOWING BATTERY CHARGING SYSTEMS: MODELS MAX AMPS/BANK NO. OF BANKS BATTERY SYSTEM PRO XL 6 1 12 DUAL PRO XL 6 2 12/24 PRO

More information

Transfer Equipment Controls

Transfer Equipment Controls Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

RAY-MAX Integrated Solar Power Strip

RAY-MAX Integrated Solar Power Strip RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...

More information

Installation and Operating Instructions (for chargers shown below)

Installation and Operating Instructions (for chargers shown below) Installation and Operating Instructions (for chargers shown below) For additional information please call our Technical Support Group 800.742.2740 PRO CHARGING SYSTEMS, LLC 1551 Heil Quaker Boulevard,

More information

PARTS LIST (G-2536GP) (Automotive Start Unit )

PARTS LIST (G-2536GP) (Automotive Start Unit ) PART NO. 0014-AGM-1050 G-4918 G-4052-A 1-336 5-56 G-47 Y-110 0-24 B-436 G-292 -A H-469 A-606-A I-684-14T 1-706 D-8 1-781 G-4919 EE- 120 EE-133 AM-88 G-4923 EE- 156 EE-654 EE-939 EE-940 EE-1334 EE-2136

More information

Micro Contactors. Micro Contactor Relays. Micro Contactors With Solder Pins. Coil voltages. Micro Reversing Contactor. Technical Data.

Micro Contactors. Micro Contactor Relays. Micro Contactors With Solder Pins. Coil voltages. Micro Reversing Contactor. Technical Data. Micro Contactors Micro Contactor Relays 0 Micro Contactors Micro Contactors With Solder Pins Coil voltages Micro Reversing Contactor 3 Technical Data 4 Dimensions 8 9 Micro Contactor Relays 4pole C Operated

More information

Hydraulic Troubleshooting PRESENTED BY

Hydraulic Troubleshooting PRESENTED BY Hydraulic Troubleshooting PRESENTED BY NORMAN KRONOWITZ Introduction Welcome to the CMA/Flodyne/Hydradyne s Hydraulic Troubleshooting presentation. We will introduce many aspects of troubleshooting hydraulic

More information

The Starting System. Section 4. Starting System Overview. Starter. The starting system:

The Starting System. Section 4. Starting System Overview. Starter. The starting system: The Starting System Starter The starter motor drives the engine through a pinion gear that engages the ring gear on the flywheel. Fig. 4-01 TL623f401c Starting System Overview The starting system: Uses

More information

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is

More information

Electromechanical Relays - Frequently Asked Questions

Electromechanical Relays - Frequently Asked Questions Electromechanical Relays - Frequently Asked Questions Q: What is the contact carry rating? A: Our EMR are capable of hot switching 28W load plus 100 cycles of overload condition at 56W. Therefore at a

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

AerAtron. Ceiling fans

AerAtron. Ceiling fans AerAtron Ceiling fans User Manual & Technical Specifications Models: e502 & e503 Electricians PLEASE FOLLOW THESES INSTRUCTIONS CAREFULLY & PAY SPECIAL ATTENTION TO THE NOTES NOTES WILL ASSIST WITH AN

More information

Operating Manual. Los Angeles Abrasion Machine HM-70A & HM-70AF

Operating Manual. Los Angeles Abrasion Machine HM-70A & HM-70AF Operating Manual Los Angeles Abrasion Machine HM-70A & HM-70AF Rev: 07/19/2012 PHONE: 800-444-1508 P.O. Box 200, Lewis Center, Ohio 43035-0200 FAX: 800-255-5314 740-548-7298 E-mail: customerservice@gilsonco.com

More information

Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules

Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules CHIEF EN TERPRISES INC. M a s t e r I n t e r n a t i o n a l D i s t r i b u t o r Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules M AS TER IN

More information

Diagnosing and Understanding Starting Problems on the ZR-1 Marc Haibeck 28-Sep-13

Diagnosing and Understanding Starting Problems on the ZR-1 Marc Haibeck 28-Sep-13 Diagnosing and Understanding Starting Problems on the ZR-1 Marc Haibeck 28-Sep-13 There are three basic failure conditions: - A VATS security system lockout - A click from the starter solenoid but no engine

More information

BRAKE DRUM AND ROTOR SERVICE INFORMATION

BRAKE DRUM AND ROTOR SERVICE INFORMATION SERVICE INFORMATION To achieve maximum drum life and optimum performance, proper brake maintenance and brake balance are essential. Consult your truck or trailer manufacturer s maintenance manual for proper

More information

12-Volt Negative Ground Installation Instructions

12-Volt Negative Ground Installation Instructions 12-Volt Negative Ground Installation Instructions For Part Number: 1141, 1164, 1165, 1181 CAUTION!!! Before installing, please read the following important information... 1. The Ignitor is designed for

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Electrical Domestic Appliances (EDA)

Electrical Domestic Appliances (EDA) 14 Electrical Domestic Appliances (EDA) Paper-I Theory 40 Practical - 60 Unit. I : Current Electricity: Electricity as a source of energy, definition of resistance, voltage, current, power, energy and

More information

HL-5000. Economical, Miniature Limit Switch Boasting Rigid Construction. General-purpose Limit Switch. Model Number Structure.

HL-5000. Economical, Miniature Limit Switch Boasting Rigid Construction. General-purpose Limit Switch. Model Number Structure. General-purpose Limit Switch CSM DS_E_3_ Economical, Miniature Limit Switch Boasting Rigid Construction The Head, Box, and Cover mate with ridged surfaces to maintain strength. A unique Head structure

More information

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,

More information

Quartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters

Quartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters Quartzone Owner s Manual File E97759 COMFORT S for INDOOR* and OUTDOOR** USE *Excluding Residences ** With Quartz Elements and when mounted Underneath an Overhang by means of brackets out of the reach

More information

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless

More information

Power Supply Cables and Connectors

Power Supply Cables and Connectors Power Supply Cables and Connectors Often during the excitement of designing a challenging new system, some of the more mundane engineering aspects get overlooked. This is especially true of connections

More information

EPSOLAR LS0512R / LS0524R. Solar Light Controller INSTRUCTION MANUAL. Please read this manual carefully before using the product!

EPSOLAR LS0512R / LS0524R. Solar Light Controller INSTRUCTION MANUAL. Please read this manual carefully before using the product! EPSOLAR LS0512R / LS0524R Solar Light Controller INSTRUCTION MANUAL Please read this manual carefully before using the product! LandStar LS0512R / LS0524R Solar Light Controller Nominal system voltage

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

Standard for an Electrical Preventive Maintenance (EPM) Program

Standard for an Electrical Preventive Maintenance (EPM) Program Recommended Maintenance Practices for Electrical Distribution System Equipment Hartford Steam Boiler One State Street P.O. Box 5024 Hartford, CT 06102-5024 Tel: (800) 472-1866 www.hsb.com April 2013 Introduction

More information

SINGLE PHASE MOTORS. INSTALLATION AND MAINTENANCE MANUAL March 21, 2006

SINGLE PHASE MOTORS. INSTALLATION AND MAINTENANCE MANUAL March 21, 2006 SINGLE PHASE MOTORS INSTALLATION AND MAINTENANCE MANUAL March 21, 2006 Irvine, California (800) 474-0520 Indianapolis, Indiana (800) 866-7973 Hamilton, Ontario (800) 809-0330 e-mail: sales@sterlingelectric.com

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

DO NOT attempt to repair hub and wheel bearing assembly.

DO NOT attempt to repair hub and wheel bearing assembly. Page 1 of 6 HUB & WHEEL BEARINGS (WITH PULSE VACUUM HUBLOCK) DO NOT attempt to repair hub and wheel bearing assembly. Removal DO NOT remove hub lock assembly by prying on hub lock legs. This can crack

More information

This chapter is devided into two sections:

This chapter is devided into two sections: This chapter is devided into two sections: Page Installation requirements........................................................................ 127 The installation process..........................................................................

More information

CHAIN CARE & TROUBLE SHOOTING

CHAIN CARE & TROUBLE SHOOTING Fatigue Failure Bushing Fatigue Stress Corrosion Stress Corrosion and Hydrogen Embrittlement These closely related failures are similar in appearance and nature. They appear as cracks which initiate at

More information

How To Build A Germany Power Plant

How To Build A Germany Power Plant Medium Voltage Air Insulated Motor Control Featuring AdvanceTM Technology. Medium Voltage Motor Control Center Product Description Contemporary Design Advance TM medium voltage motor control center (MVMCC)

More information

SERVICE GUIDE For WARN PULLZALL 120v AC &100v AC P/N 685000 & 685001

SERVICE GUIDE For WARN PULLZALL 120v AC &100v AC P/N 685000 & 685001 SERVICE GUIDE For WARN PULLZALL 120v AC &100v AC P/N 685000 & 685001 REPAIR / REPLACEMENT INSTRUCTIONS TROUBLE SHOOTING GUIDE 986765A2.doc Page 1 of 50 WARNING This guide identifies potential hazards and

More information

DIRECT CURRENT GENERATORS

DIRECT CURRENT GENERATORS DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle

More information

AerAtron. Ceiling fans

AerAtron. Ceiling fans AerAtron Ceiling fans User Manual & Technical Specifications Models: e502 & e503 Australian edition 2011 Instructions...3 General precautions...3 Location and installation requirements for your fan...3

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) Matthew Theriault Designer Hindle Power Inc. Easton, PA SCOPE AND PURPOSE OF THE PAPER Why do we bother to monitor

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Global Water Instrumentation, Inc. 11390 Amalgam Way Gold River, CA 95670 T: 800-876-1172 Int l: (916) 638-3429, F: (916) 638-3270 Solar Panels 2 Watt Solar Panel: SP101 5 Watt Solar Panel: SP102 01-752

More information

Amps Per Bank. Total Output. Battery System. Model Name. 6 amps 12 amps 10 amps 20 amps 30 amps 40 amps 15 amps 30 amps 45 amps

Amps Per Bank. Total Output. Battery System. Model Name. 6 amps 12 amps 10 amps 20 amps 30 amps 40 amps 15 amps 30 amps 45 amps Model Name Total Output Amps Per Bank Battery System Pro XL Dual Pro XL Pro SE Dual Pro SE Three Bank Pro SE Four Bank Pro SE Pro Charger Dual Pro Charger Three Bank Pro Charger 6 amps 12 amps 10 amps

More information

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear. OVERCURRENT & EARTH FAULT RELAYS Objective: To study the protection of equipment and system by relays in conjunction with switchgear. Theory: The function of a relay is to detect abnormal conditions in

More information

4 A CAPACITY, THE VARIETY OF CONTACT ARRANGEMENTS FEATURES

4 A CAPACITY, THE VARIETY OF CONTACT ARRANGEMENTS FEATURES 4 A CAPACITY, THE VARIETY OF CONTACT ARRANEMENTS S RELAYS FEATURES 28. 1.12 12..472 1.4.49 The variety of contact arrangements 2 Form A 2 Form B, 3 Form A 1 Form B, 4 Form A Latching types available High

More information

Rotary Phase Converters

Rotary Phase Converters FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON

More information

employed to ensure the continuing reliability of critical systems.

employed to ensure the continuing reliability of critical systems. 4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective

More information

INSTALLATION AND OPERATION MANUAL FOR STEREO-HEAT ELECTRICALLY TRACED PIPING SYSTEM

INSTALLATION AND OPERATION MANUAL FOR STEREO-HEAT ELECTRICALLY TRACED PIPING SYSTEM Installation and Operation Manual Stereo-Heat Electrically Traced Piping System INSTALLATION AND OPERATION MANUAL FOR STEREO-HEAT ELECTRICALLY TRACED PIPING SYSTEM Stereo-Heat Electrically Traced Piping

More information

Mechanical Installation

Mechanical Installation Page -1-1. INTRODUCTION AND PURPOSE 1.1. This specification covers the installation, testing and precommissioning of mechanical equipment. Work is to be performed in conjunction with the manufacturer s

More information

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION: Revision Level: 01 Revision Date: 07/07/2011 Please read all instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Air Purifier. Failure to do

More information

Hydraulics Trouble Shooting Guide. TS-Guide_R.doc

Hydraulics Trouble Shooting Guide. TS-Guide_R.doc Hydraulics Trouble Shooting Guide TS-Guide_R.doc Table of Contents Condensed Table... 1 Valves... 3 Cylinders... 3 Boosters... 4 Fluid Motors... 5 Vane Pumps... 6 Radial Piston Pumps... 9 Hydraulic Systems...

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before

More information

Ordering Information. Latching Relay G2AK. Model Number Legend G2AK-@@@@@ 1 2 3 4 5. Magnetic Latching Version of G2A Ideal for Sequence Control

Ordering Information. Latching Relay G2AK. Model Number Legend G2AK-@@@@@ 1 2 3 4 5. Magnetic Latching Version of G2A Ideal for Sequence Control Latching Relay CSM DS_E_4_1 Magnetic Latching Version of G2A Ideal for Sequence Control Double-winding latch system with continuous rating. Terminals pulled from the respective junctions between the built-in

More information

101 BASICS SERIES LEARNING MODULE 19: STARTERS AND CONTACTORS. Cutler-Hammer

101 BASICS SERIES LEARNING MODULE 19: STARTERS AND CONTACTORS. Cutler-Hammer 101 BASICS SERIES LEARNING MODULE 19: STARTERS AND CONTACTORS Cutler-Hammer WELCOME Welcome to Module 19, which is about starters, devices that control the use of electrical power to equipment, usually

More information

WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS

WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS CONDUCTORS Conductors are needed to complete the path for electrical current to flow from the power source to the working devices and back to the power source. Special wiring is needed for battery cables

More information

Armature Actuated Brakes

Armature Actuated Brakes Armature Actuated s P/N 8-078-890-05 effective 05/02/14 Installation and Service Instructions Series AAB Armature Actuated s Sizes 72 through 170 Model Numbers 33[ ]-1, 33[ ]-2, 33[ ]-3, 33[ ]-4, 33[ ]-5

More information

Utility Distribution Systems

Utility Distribution Systems Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date

More information