Service Life of Stator Winding Insulation as an Important Quality Feature of Large Hydro Generators
|
|
|
- Tiffany Jackson
- 9 years ago
- Views:
Transcription
1 Operating Experience Service Life of Stator Winding Insulation as an Important Quality Feature of Large Hydro Generators Wolf-Dietrich Blecken, Hartmut Meyer As central components of hydroelectric power plants, generators are subjected to operating stresses which influence the long-term performance of the winding insulation. Failure of the insulation can lead to lengthy downtimes. The unsurpassed reliability of products such as MICALASTIC insulation is therefore of great economic significance. The capacity of a hydroelectric power plant is determined by the available water flow and head. Both of these parameters vary widely, and generators can be dimensioned for any rating between 10 kw and 800 MW. The head determines the turbine type as well as the speed, which can lie between 50 and 1500 rpm. Additional parameters include the generator voltage, the rotor s moment of inertia, the runaway speed of the turbine, the physical design of the generator (horizontal or vertical) and various requirements imposed by the grid. Hydroelectric generators are therefore always customdesigned. Dimensions and weights can assume enormous proportions (Fig. 1): External diameters of up to nearly 23 meters are possible, and total weight can amount to as much as 3500 metric tons. Generators of this size cannot be assembled and tested at the factory. Nevertheless, the generators can be expected to operate well right after their initial installation at the power plant. It was once correctly stated that the construction of a hydroelectric generator can be compared to making a tailormade suit without trying it on. To date, Siemens has manufactured more than 1200 large hydroelectric generators with a combined capacity in excess of 80,000 MVA. Of these, 360 generators (over 50,000 MVA) have MICALASTIC windings. These machines are characterized by their outstanding reliability, which can be attributed in large measure to their highquality MICALASTIC insulation system. The MICALASTIC Insulation MICALASTIC is the registered trademark for Siemens insulation systems for high-voltage windings of rotating electrical machines. These systems use mica, a material capable of withstanding high electrical and thermal loads, together with curable, elastic epoxy resins as bonding material. Since the early days of electrical machine construction, the naturally occurring, inorganic mineral mica has been an indispensable constituent of highvoltage insulation systems. The most important criterion for the use of mica is its ability to durably withstand the partial electrical discharges which can occur inside the insulation due to high electrical stresses.
2 Fig. 1 Insertion of a rotor at the Itaipú hydroelectric power plant. Due to its diameter of 16 m and weight of 1960 t, assembly on site is the only practicable approach. Manufacturing and Design As early as 1957, Siemens- Dynamowerk in Berlin manufactured the first stator windings that made use of mica tape and a vacuum-pressure impregnation process. With this method, single coils and Roebel bars for hydroelectric generators are continuously wrapped with mica tape in the slot and end sections. The taped winding elements are then dried out and degassed in a vacuum impregnation tank, and flooded with low-viscosity, curable synthetic resin. High nitrogen pressure applied to the impregnating bath completely impregnates the mica tape. After being placed in accurately sized, portable pressing molds, the insulation is cured at high temperatures in large chamber ovens. Continued development of this insulation technology ultimately led to the use of a film of ground mica on mechanically strong glass fabric as the carrier material with epoxy resin as the impregnant, which produced a very durable (electrically, thermally and mechanically), modern insulation system. Longduration tests in a slot model were unnecessary, since the desired voltage endurance had already been achieved in the previous development stages (Fig. 2) using lower-quality carrier materials. Short-duration tests were performed, however, for verification. Fitting of Roebel Bars into Slots Fig. 2 Comparative functional testing using the stator slot model confirms the progress achieved in extending the service life of 13.8-kV insulation of varying compositions. Winding elements with cured MICALASTIC insulation are secured in the slots by filling up the tolerances between the slot wall and the conductive surface (coilside corona shielding) of the bar insulation. Initially, Siemens used graphite-treated paper as filler material. Since about 1969,
3 however, a special bar fitting procedure has been used for hydroelectric generators. The main features of this procedure are U-shaped slot liners made of polyester fleece impregnated with a conductive material, and a conductive, curable synthetic resin paste between the surface of the bar insulation and the slot liner (Fig. 3). Therefore, the insulation does not stick to the stator core, and the option of removing the bars, even though seldom required, is retained. In the radial direction, the slot portion of the winding elements is secured by means of various packing strips or ripple springs, and slot wedges. Bracing the end windings and jumpers by using glassfiberreinforced spacers and epoxy-resinimpregnated cording makes the winding resistant to electrodynamic forces during operation and to possible short-circuit faults. This resistance is also aided considerably by the mechanical stiffness of the MICALASTIC insulation, which is also cured within the end winding. Thermal Stability The MICALASTIC insulation system was developed strictly for a continuous load in accordance with temperature class F (155 C). Nevertheless, generator design engineers generally guarantee compliance with class B (130 C) temperature limits for nominal operating conditions, as is also required in most invitations to tender. In practice, the stator windings of hydroelectric generators are frequently dimensioned for even lower operating temperatures, because the stators will usually be optimized for good efficiency by adding electrically active material (winding copper and core lamination). Particularly low operating temperatures can be expected in the case of stator windings with direct water cooling. With an appropriately dimensioned demineralized-water cooling Fig. 3 Fixing Roebel bars in a stator core using Ushaped slot liners and conductive curable synthetic resin paste. This method ensures a particularly tight fit and rules out slot corona discharges. system, the maximum winding temperature can be reduced to 70 C and lower. Thermal aging of the insulation is therefore essentially eliminated, and thermomechanical stresses are also substantially reduced. The resulting increase in operational reliability makes a real difference in the case of hydroelectric generators which are essential to safe grid operation. Selected References Since 1984, the world s largest hydroelectric power plant Itaipú on the Brazil/Paraguay border has given problem-free operation using MICALASTIC windings with direct water cooling in nine generators with a combined capacity of nearly 7200 MVA. Another fifteen MICALASTIC stator windings with water cooling have yielded excellent results in pumped-storage and peak-load machines with a combined capacity of 4800 MVA. The demineralized-water cooling systems with built-in redundancy are easy to maintain. Siemens experience in more than 150 years of operation has shown that the reliability of generators with direct water cooling, as opposed to air cooling, is not affected in the slightest by these plant components. In fact, when life-limiting effects are are minimized in this way a longer service life is anticipated for the respective ground wall insulation. The MICALASTIC stator windings installed at the Grand Coulee hydroelectric plant in the U.S. (see article on page 40) represent a highlight in terms of the development and fabrication of Roebel bars with direct water cooling. Due to negative experience with the originally installed windings, the new request for proposals issued by the power plant operator, the United States Bureau of Reclamation, included strict quality requirements that are likely unprecedented. The Roebel bars developed and fabricated for these generators have set new standards in terms of the quality and reliability of stator windings with direct water cooling (Fig. 4). Rated Voltage Level MICALASTIC-insulated stator windings can be manufactured with a rated voltage of up to 40 kv for large turbogenerators operating in a hydrogen atmosphere. Hydroelectric generators, on the other hand,
4 always operate in air, which is why the ionization processes caused by the high electrical field strengths are of higher significance. To obtain an optimum generator design, the design engineer should be given the latitude to select the best rated voltage-particularly with respect to slot ampereturn limits. At power output levels above about 400 MVA, however, 18 kv has proven to be a good compromise between the costs of the generator and the bus ducts. The world s highest voltage rating for hydroelectric applications is 23 kv, at which the pumped-storage units at Raccoon Mountain in the U.S. have been operating since Operating Stresses During operation, the insulation is subjected to electrical stresses due to field strength, and to thermal stresses due to the temperature of the winding copper and core teeth (slot walls). As a result of differences in temperature and coefficients of thermal expansion, forces develop within the winding elements which are superimposed on the electrodynamic stresses caused by the live Roebel bars. Added to the electrical and thermal stresses-which occur similarly in the stator windings of turbogenerators and hydroelectric generators-is a thermomechanica stress element which occurs in hydroelectric generators, particularly in peak-load generators and even more in pumped-storage units. Although the operating times in this case lie within a range of only 1500 to 5000 hours per year, up to 80 load cycles per day can occur in extreme circumstances. It often takes only ten seconds to go from a no-load, synchronous condenser mode to full-load operation, and the load service duration can range from one minute to several hours. The stator windings in particular are subjected to extreme mechanical stresses imposed by load cycles of this kind. This factor is taken into consideration in the abovementioned fitting procedure, Fig. 4 End-winding section of the Grand Coulee stator winding with its characteristic insulating caps. which guarantees a particularly tight fit of the Roebel bars in the slots. And finally, the effects of the operating environment must be taken into consideration. Air quality is a function of the geographical location and the design of the power plant, and plant elevation and relative humidity are the most important natural parameters. Oil vapor escaping from bearings within the generator enclosure is extremely damaging too. The oil vapor precipitates out on the stator winding, among other components, and in combination with brake dust forms a deposit which can lead to corona damage. Operating Experience A comprehensive series of comparative functional tests is required in order to assess the expected service life of new or redesigned insulation systems before they are used in practice. In order to evaluate MICALASTIC insulation at its various development stages, operating conditions were simulated using slot models, and accelerated tests were performed by applying increased stress levels. The actual performance capability of an insulation system can only be measured in terms of its service life under true operating conditions. For that reason, Siemens sent questionnaires to plant operators in 1984 and 1994 to obtain data on their operating experience. Both questionnaires pertained to stator windings with MICALASTIC insulation which had been applied using the fitting procedure introduced in Generator output ranges from 35 to 823 MVA, and rated voltage lies between 10.5 and 23 kv [1,2]. The first hydroelectric generators with MICALASTIC insulation were commissioned in 1958, and are still in operation today. At present (as of March 1997), the 360 generators with MICALASTIC windings have amassed a total of 4700 years of on-line operating time. Of these, 39 generators have fed power into the grid for more than 25 years.
5 The individual service life record is 31.5 years. Not a single operator of a hydroelectric generator equipped with MICALASTIC stator windings (with a total of more than a quarter of a million Roebel bars installed) reported winding damage or evidence of electrical or thermal aging. None of the MICALASTIC stator windings showed evidence of slot discharges. Some incidents of damage were reported, however these were without exception attributable to foreign particles, loose core tooth lamination or inadequate maintenance. Limit-rating machines or units requiring high utilization factors (e.g., high-speed pumpedstorage sets) are natural design candidates for the application of proven direct water cooling with its low operating temperatures. Regular inspections and a good main-tenance program are important factors in getting a high reliability from an insulation system and achieving a practically unlimited service life. The use of sophisticated Siemens monitoring systems (see article on page 26) allows step-by-step transition from periodical to condition-oriented inspection intervals, which significantly decreases maintenance effort and expense. References [1] H. Meyer, W. Schmatloch: Reliability of Stator Winding Insulation in Hydro Generators. Water Power and Dam Construction, Dec. 1984, pp [2] H. Meyer, W.-D. Blecken: Trial and Error. Water Power and Dam Construction, Feb. 1995, pp Outlook Due to its practically unlimited service life as well as its outstanding insulating properties, the MICALASTIC insulation system can be regarded as the standard for the reliability of rotating electrical machines. Despite its already high operational reliability, development of the MICALASTIC insulation system continues step by step. Reduction of the ground wall insulation thickness is still possible in small increments and can increase the utilization of electrical machines. Although curable synthetic resins with a much higher long-term resistance to high temperatures are available for vacuumpressure impregnation, their use in standard hydroelectric generators would have no technical or economic benefit due to their conservative thermal design.
6
Micalastic insulation for high voltage hydro generators
Micalastic insulation for high voltage hydro generators Voith Hydro is a global leader in hydro power equipment and services for both new and modernization. For more than 140 years, our name has been synonymous
Wound Rotor Induction Motors 4-12 poles, up to 8000 kw, 11500 HP
Wound Rotor Induction Motors 4-12 poles, up to 8000 kw, 11500 HP ABB The Preferred Partner Egypt Cement Corporation, a major cement manufacturer, has chosen ABB wound rotor motors for all key applications
Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission
Power transformers Generator step-up and system intertie power transformers Securing high-quality AC transmission Generator step-up transformers Built to withstand continuous full load Generator step-up
GE Power Conversion. Generators. 2,500 to 80,000 kva Up to 22,000 Volts
GE Power Conversion Generators 2,500 to 80,000 kva Up to 22,000 Volts 2 GE I Power Conversion GE has been setting the standard in generator manufacturing for over 130 years. GE created and implemented
Powerformer chosen for Swedish combined heat and power plant
Powerformer chosen for Swedish combined heat and power plant Powerformer, a radically new type of generator developed by ABB, has been chosen for a combined heat and power plant in Eskilstuna, Sweden.
MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003
MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU
Turbo generators Best quality for thermal power plants
Turbo generators Best quality for thermal power plants www.andritz.com ANDRITZ HYDRO Turbo generators International technology Group ANDRITZ is a globally leading supplier of plants, equipment, and services
CONTINUOUS AUTOMATED FLUX MONITORING FOR TURBINE GENERATOR ROTOR CONDITION ASSESSMENT
CONTINUOUS AUTOMATED FLUX MONITORING FOR TURBINE GENERATOR ROTOR CONDITION ASSESSMENT Abstract J. Kapler, S. Campbell, M. Credland Iris Power Engineering Inc. Toronto, Canada Flux monitoring via permanently
Generators TEM. for small hydroelectric power stations. Electric Machines
Generators for small hydroelectric power stations TEM Electric Machines Advanced solutions for the cleanest energy Reputable manufacturer of generators for small hydroelectric power stations TED Electric
Power-factor testing of rotating machinery is another valuable test
Feature Power-Factor Testing of Stator Winding Insulation: Understanding the Test Technique and Interpretation of Results Power-factor testing of rotating machinery is another valuable test technique providing
Solid-Cast Versus Resin-Encapsulated Transformers
Data Bulletin 7300DB0402 12/2004 Monroe, NC USA Replaces 7300PD9202, 02/1992 Solid-Cast Versus Resin-Encapsulated Transformers Class 7300 Retain for future use. OVERVIEW The continuing development of dry-type
Excitation. www.andritz.com/neptun
Excitation www.andritz.com/neptun 02 NEPTUN Excitation Excitation 3 x 150 MW, Kopswerke II, Austria Dynamics with brain power The excitation system of a synchronous generator makes it possible to supply
Green Thread Product Data
Green Thread Product Data Applications Dilute Acids Caustics Produced Water Industrial Waste Hot Water Condensate Return Materials and Construction All pipe manufactured by filament winding process using
Replacement Generators to Modernize and Uprate Power Trains Limited by the Generator
Replacement Generators to Modernize and Uprate Power Trains Limited by the Generator Dr. Thorsten Krol (presenter, [email protected] ), Kai-Uwe Paeselt (author, [email protected] ), Fabian
KINETIC ENERGY RECOVERY SYSTEM BY MEANS OF FLYWHEEL ENERGY STORAGE
ADVANCED ENGINEERING 3(2009)1, ISSN 1846-5900 KINETIC ENERGY RECOVERY SYSTEM BY MEANS OF FLYWHEEL ENERGY STORAGE Cibulka, J. Abstract: This paper deals with the design of Kinetic Energy Recovery Systems
Reducing Maintenance Costs Replacement of Small Fossil Generators in Russia
siemens.com/energy Reducing Maintenance Costs Replacement of Small Fossil Generators in Russia Russia Power 2014 4-6 March, 2014 Moscow, Russia Authors: Fabian Bremer Maren Stockhausen Dusan Jovic Siemens
Impregnating Machine
Impregnating Machine Dasan Engineering manufactured Resin Coating & Laminating Machine for composite material and insulating material in addition to Impregnating & drying machine by means of high efficiency
A S Y N C H R O N O U S M O T O R S
ASYNCHRONOUS M O T O R S S E R I E S INDAR ASYNCHRONOUS MOTORS S E R I E S WHO WE ARE Indar Electric s trajectory is endorsed by the construction of thousands of motors for the different industrial sectors.
3. Three phase winding technology
3. Three phase winding technology VATech Hydro, Austria Prof. A. Binder 3/1 Single layer winding Per slot only one coil side is placed. Coils manufactured as: a) Coils with identical coil span: W = τ p
Raising the waters. Lift irrigation is getting a boost from ABB s synchronous motors
Raising the waters Lift irrigation is getting a boost from ABB s synchronous motors JARI LINDSTRÖM, TAPIO RAUHALA, MAGNUS REJSTRÖM In India, the scarcity of water is unfortunately a harsh reality. Still,
Basics of Electricity
Basics of Electricity Generator Theory PJM State & Member Training Dept. PJM 2014 8/6/2013 Objectives The student will be able to: Describe the process of electromagnetic induction Identify the major components
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
DC MOTOR ANALYSIS & TROUBLESHOOTING
DC MOTOR ANALYSIS & TROUBLESHOOTING By Don Shaw Condition assessment of DC motors requires a basic understanding of the design and operating characteristics of the various types available: the series motor,
Top Technology for Industry, Agriculture, Business and Communities
Top Technology for Industry, Agriculture, Business and Communities CHP The Technology with a Potential for Saving Energy Combined Heat and Power (CHP) is a highly efficient technology for the conversion
BRUSHHOLDERS AND THE PERFORMANCE OF CARBON BRUSHES
Tech Note No. 22 TECH NOTE NO. 22 Brushholders and the Performance of Carbon Brushes Reliable Solutions Today! EA SA ELECTRICAL SERVICE APPARATUS ASSOCIATION BRUSHHOLDERS AND THE PERFORMANCE OF CARBON
CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR
47 CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR 4.1 INTRODUCTION This chapter deals with the design of 24 slots 8 poles, 48 slots 16 poles and 60 slots 16 poles brushless dc
Lab 14: 3-phase alternator.
Lab 14: 3-phase alternator. Objective: to obtain the no-load saturation curve of the alternator; to determine the voltage regulation characteristic of the alternator with resistive, capacitive, and inductive
WIND TURBINE TECHNOLOGY
Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems
1150 hp motor design, electromagnetic and thermal analysis
115 hp motor design, electromagnetic and thermal analysis Qasim Al Akayshee 1, and David A Staton 2 1 Mawdsley s Ltd., The Perry Centre, Davey Close, Waterwells, Gloucester GL2 4AD phone: +44 1452 888311
An Overview of Lapp Insulator High Voltage Bushing Design
An Overview of Lapp Insulator High Voltage Bushing Design W.A. Young Lapp Insulator Company LeRoy, NY 14482 USA INTRODUCTION High voltage bushings are devices designed to transmit electric energy through
This section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
DIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
Electrical Maintenance Workshop
Electrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003 Transformer Maintenance & Testing Purpose This presentation provides an overview of the major considerations
Lead & Magnet Wire Connection Methods Using the Tin Fusing Method Joyal A Division of AWE, Inc.
Lead & Magnet Wire Connection Methods Using the Tin Fusing Method Joyal A Division of AWE, Inc. Abstract The technology for connecting lead and magnet wires for electric motors and electro mechanical devices
The DC Motor/Generator Commutation Mystery. Commutation and Brushes. DC Machine Basics
The DC Motor/Generator Commutation Mystery One small, yet vital piece of the DC electric motor puzzle is the carbon brush. Using the correct carbon brush is a key component for outstanding motor life,
*ADVANCED ELECTRIC GENERATOR & CONTROL FOR HIGH SPEED MICRO/MINI TURBINE BASED POWER SYSTEMS
*ADVANCED ELECTRIC GENERATOR & CONTROL FOR HIGH SPEED MICRO/MINI TURBINE BASED POWER SYSTEMS Jay Vaidya, President Electrodynamics Associates, Inc. 409 Eastbridge Drive, Oviedo, FL 32765 and Earl Gregory,
WIRE AND CABLE ENGINEERING GUIDE
DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a
Presentation of the France Transfo factories
Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Shape the future of energy with innovative electrical steel for the energy industry. voestalpine Steel Division www.voestalpine.
ISOVAC your FUTURE! Shape the future of energy with innovative electrical steel for the energy industry. Tereza Schöberl, Key Account Manager voestalpine Steel Division www.voestalpine.com/stahl ISOVAC
Calculation of Temperature in a Large Turbine Generator with Multilayer Roebel Transposition Coils
Calculation of Temperature in a Large Turbine Generator with Multilayer Roebel Transposition Coils Kenichi Hattori *, Kazuhiko Takahashi, Kazumasa Ide, Keiji Kobashi, Hiroshi Okabe, and Takashi Watanabe
Power chip resistor size 2512 PRC221 5%; 2% FEATURES Reduced size of final equipment Low assembly costs Higher component and equipment reliability.
FEATURES Reduced size of final equipment Low assembly costs Higher component and equipment reliability. APPLICATIONS Power supplies Printers Computers Battery chargers Automotive Converters CD-ROM. QUICK
Power Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
Force Measurement Systems. Force Measurement Systems
Force Measurement Systems Force Measurement Systems Force Measurement Systems from IMS Your Guarantee of Quality Modern production equipment is designed for high productivity and quality. To achieve these
The Three Heat Transfer Modes in Reflow Soldering
Section 5: Reflow Oven Heat Transfer The Three Heat Transfer Modes in Reflow Soldering There are three different heating modes involved with most SMT reflow processes: conduction, convection, and infrared
PREFAULT MONITOR FOR AIR COOLED GENERATORS
PREFAULT MONITOR FOR AIR COOLED GENERATORS Steve Kilmartin Utility Products Specialist Environment One Corporation 2773 Balltown Road Schenectady, NY 129 518 346-6161 George F. Skala Senior Engineer Environment
Transformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
ELECTROPUTERE ROTATING ELECTRICAL MACHINES DIVISION
ELECTROPUTERE ROTATING ELECTRICAL MACHINES DIVISION SC ELECTROPUTERE SA SC ELECTROPUTERE SA 1. Vision, Mission, Values SC ELECTROPUTERE SA 2. LOCATION Craiova: Located in the South West of the country,
525-MVA Generator-motor and Thyristor Starter Put into Service at the Tokyo Electric Power Co., Inc. s Kannagawa Hydroelectric Power Station
525-MVA Generator-motor and Thyristor Starter Put into Service at the Tokyo Electric Power Co., Inc. s Kannagawa Hydroelectric Power Station 114 525-MVA Generator-motor and Thyristor Starter Put into Service
EXPERIMENTAL RESEARCH ON FLOW IN A 5-STAGE HIGH PRESSURE ROTOR OF 1000 MW STEAM TURBINE
Proceedings of 11 th European Conference on Turbomachinery Fluid dynamics & Thermodynamics ETC11, March 23-27, 2015, Madrid, Spain EXPERIMENTAL RESEARCH ON FLOW IN A 5-STAGE HIGH PRESSURE ROTOR OF 1000
PMG vs. DFIG the big generator technology debate
PMG The Switch challenges the industry on the superior total life cycle cost efficiency and reliability of PMG-FPC drive train solutions. gear DFIG PMG vs. DFIG the big generator technology debate In the
Technical catalogue About KOLEKTOR ETRA has been acting as transformer manufacturer over more than 75 years. Specializing in the manufacturing of power transformers rating up to 500 MVA and 420 kv the
CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2
WASTE HEAT BOILERS CONTENTS 1 INTRODUCTION... 3 2 CONCEPTION OF WASTE HEAT BOILERS... 4 2.1 Complex Solution...4 2.2 Kind of Heat Exchange...5 2.3 Heat Recovery Units and Their Usage...5 2.4 Materials
Extreme Temperature Reed Switch Operation
Application Note ANA Extreme Temperature Reed Switch Operation Hamlin reed switches are normally specified to operate in a temperature range of -4 C to +1 C. This application note will explain the reasons
VD4. Vacuum circuit-breaker
VD4 Vacuum circuit-breaker VD4. The economical solution in power distribution. Applications: Power stations Transformer stations Chemicals industry Steel industry Automotive industry Airport power supply
Who is VENPOWER? Since November 1, we have been striving to fulfill the above-stated mission under our new company name VENPOWER GmbH
Who is VENPOWER? VENPOWER GmbH began life as PM-Generators GmbH, which was founded by three shareholders in August 2009. From the beginning, our mission has been to design and manufacture excellent generator
Brochure. Generators for wind power Proven generators reliable power
Brochure Generators for wind power Proven generators reliable power We provide motors, generators and mechanical power transmission products, services and expertise to save energy and improve customers
1x90 TONS TENSIONERS TECHNICAL PROPOSAL. 1 X 90 Tons 30 m/min Tensioners TECHNICAL PROPOSAL JOB 08/059. 0 19/02/2008 Basic proposal PP GM SB
Pagina N.: 1 of 19 1 X 90 Tons 30 m/min Tensioners JOB 08/059 0 19/02/2008 Basic proposal PP GM SB Rev N Date Issue Description Prepared by Checked by Approved by Pagina N.: 2 of 19 TABLE OF CONTENTS:
Vacuum Evaporation Recap
Sputtering Vacuum Evaporation Recap Use high temperatures at high vacuum to evaporate (eject) atoms or molecules off a material surface. Use ballistic flow to transport them to a substrate and deposit.
THE VALUE OF POWER FACTOR TESTING
THE VALUE OF POWER FACTOR TESTING Nov 1, 2005 12:00 PM by John Bleyer and Phillip Prout, National Grid NATIONAL GRID DISCOVERED A HIGH POWER FACTOR DURING ACCEPTANCE TESTING of a new 40-MVA transformer
ŠKODA MACHINE TOOL HORIZONTAL MILLING AND BORING MACHINES ŠKODA HCW
ŠKODA MACHINE TOOL HORIZONTAL MILLING AND BORING MACHINES ŠKODA HCW KODA HCW TRADITION AND EXPERIENCE The ŠKODA machine tools of different types and design have been present in the world market since the
CHARACTERIZATION OF POLYMERS BY TMA. W.J. Sichina, National Marketing Manager
PERKIN ELMER Polymers technical note CHARACTERIZATION OF POLYMERS BY W.J. Sichina, National Marketing Manager Thermomechanical analysis () is one of the important characterization techniques in the field
Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
The stable way. Synchronous condenser solutions. siemens.com/energy/facts
The stable way Synchronous condenser solutions siemens.com/energy/facts Bringing grids in line with new requirements Global climate change poses new challenges for power generation and transmission. Innovative
Accurate Air Flow Measurement in Electronics Cooling
Accurate Air Flow Measurement in Electronics Cooling Joachim Preiss, Raouf Ismail Cambridge AccuSense, Inc. E-mail: [email protected] Air is the most commonly used medium to remove heat from electronics
2013 RESIBLOC transformers Product presentation. ABB Group October 2, 2013 Slide 1
2013 RESIBLOC transformers Product presentation October 2, 2013 Slide 1 Dry-type transformers For customers with high requirements Does your transformer application requires one of the following characteristic?
1 DESCRIPTION OF THE APPLIANCE
1 DESCRIPTION OF THE APPLIANCE 1.1 INTRODUCTION The cast iron SF boilers are a valid solution for the present energetic problems, since they can run with solid fuels: wood and coal. These series of boilers
ABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:
OPERATING LIMITS Flows up to: m /h* Heads up to: m C Max operating pressure: bars Temperature range: - à + C Max ambient temperature: + C ND of orifices: à * m /h: parallel operation SIRIUX SINGLE AND
High-ohmic/high-voltage resistors
FEATURES High pulse loading capability Small size. APPLICATIONS Where high resistance, high stability and high reliability at high voltage are required High humidity environment White goods Power supplies.
4.1.1 Generator Owner 4.1.2 Transmission Owner that owns synchronous condenser(s)
A. Introduction 1. Title: Verification and Data Reporting of Generator Real and Reactive Power Capability and Synchronous Condenser Reactive Power Capability 2. Number: MOD-025-2 3. Purpose: To ensure
L.I. Chubraeva. Corr. Member of RAS
STATE-OF OF-THE-ART AND NEW DEVELOPMENTS IN HIGH-TEMPERATURE CUPERCONDUCTIVITY IN RUSSIA L.I. Chubraeva Corr. Member of RAS Director of Research Institute of Innovative Technologies in Electromechanics
EXPERIENCE AND BENEFIT OF USING EL-CID FOR TURBINE-GENERATORS
EXPERIENCE AND BENEFIT OF USING EL-CID FOR TURBINE-GENERATORS Electric Power Research Institute Motor & Generator Predictive Maintenance & Refurbishment Conference Orlando, Florida November 28-30, 1995
PTC-Resistor Temperature-Sensors MINIKA to DIN 44 081 and DIN 44 082
PTC-Resistor Temperature-Sensors MINIKA to DIN 44 081 and DIN 44 082 General PTC-resistor temperature sensors (also called PTC-resistors or thermistors) are temperatur dependent semiconductor resistors
Commissioning of 87,000-kW Kaplan Turbine and Generator for Otori Power Station
Commissioning of 87,000-kW Kaplan Turbine and Generator for Otori Power Station 126 Commissioning of 87,000-kW Kaplan Turbine and Generator for Otori Power Station Asami Sato Keiichi Goto OVERVIEW: The
Single-Phase AC Synchronous Generator
ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description
Flowserve - Edward Valves Development of the Flowserve Edward Equiwedge Gate Valve
Flowserve - Edward Valves Development of the Flowserve Edward Equiwedge Gate Valve Problem Gate valves in severe service applications that experience premature trim wear from seat guided discs or leakage
North American Stainless
North American Stainless Long Products Stainless Steel Grade Sheet 2205 UNS S2205 EN 1.4462 2304 UNS S2304 EN 1.4362 INTRODUCTION Types 2205 and 2304 are duplex stainless steel grades with a microstructure,
Compliant Terminal Technology Summary Test Report
Engineering Report ER04100 October 5th, 2004 Revision A Copyright Autosplice Inc., September 2004 Table of Contents Summary Overview 3 Compliant Terminal Specifications 3 Test Plan 4 Test Conditions 4
THE COMPOSITE DISC - A NEW JOINT FOR HIGH POWER DRIVESHAFTS
THE COMPOSITE DISC - A NEW JOINT FOR HIGH POWER DRIVESHAFTS Dr Andrew Pollard Principal Engineer GKN Technology UK INTRODUCTION There is a wide choice of flexible couplings for power transmission applications,
3M Thermal Bonding Film AF42
Technical Data August 2015 3M Thermal Bonding Film AF42 Product Description 3M Thermal Bonding Film AF42 is an epoxy, thermoset film adhesive developed for structural bonding of metal, glass and other
NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR
INDEX NO. : M-142 TECHNICAL MANUAL FOR NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR Manufactured by : PREMIER TRADING CORPORATION (An ISO 9001:2000 Certified Company) 212/1, Mansarover Civil
REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)
SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY
Vehicle Design Summit Electric Hub Motor (V2) Eric Conner Harvey Tang Matthew Peddie
Vehicle Design Summit Electric Hub Motor (V2) Eric Conner Harvey Tang Matthew Peddie Motivation The AHPV from VDS 1.0 used an expensive, NGM electric hub motor, costing roughly $8000. (picture on right)
Power Transformers 10 to 100 MVA
Power Transformers 10 to 100 MVA Transformer technology at a glance An extensive transmission system with efficient transformers is indispensable to ensure a reliable supply of power. Consequently Siemens
3M Electrically Conductive Adhesive Transfer Tape 9703
Technical Data April 2011 M Electrically Conductive Adhesive Transfer Tape 970 Product Description M Electrically Conductive Adhesive Transfer Tape 970 is a pressure sensitive adhesive (PSA) transfer tape
High-ohmic/high-voltage resistors
FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS
S Y N C H R O N O U S G E N E R A T O R S
S E R I E S SYNCHRONOUS G E N E R A T O R S INDAR SYNCHRONOUS GENERATORS S E R I E S BZK INDAR ELECTRIC INDAR, EXPERIENCE AND COOPERATION INDAR Electric develops and manufactures electrical rotating machines
Flux Conference 2012. High Efficiency Motor Design for Electric Vehicles
Flux Conference 2012 High Efficiency Motor Design for Electric Vehicles L. Chen, J. Wang, P. Lombard, P. Lazari and V. Leconte University of Sheffield, Date CEDRAT : 18 October 2012 Presented by: P. Lazari
ROTARY SCREW COMPRESSOR. RMD 30-37 - 45-55 kw
ROTARY SCREW COMPRESSOR RMD - - - 55 kw EN The RMD Coaxial Rotary Compressor high reliability high performance low maintenance is the result of decades of experience in manufacturing design and construction
POLARIS AIR COMPRESSOR SERIES. engineering. excellence. stellar. performance. A World Leader for Centrifugal Compressors
POLARIS AIR COMPRESSOR SERIES engineering excellence stellar performance P - 3 0 0 RELIABLE 100% OIL-FREE ENGINEERED AIR A World Leader for Centrifugal Compressors It s simple: The Polaris Air Compressor
Belt Drives and Chain Drives. Power Train. Power Train
Belt Drives and Chain Drives Material comes for Mott, 2002 and Kurtz, 1999 Power Train A power train transmits power from an engine or motor to the load. Some of the most common power trains include: Flexible
Data sheet Radiator Thermostats type RA 2000 Valve bodies type RA-FN and RA-G
Data sheet Radiator Thermostats type RA 2000 Valve bodies type RA-FN and RA-G EN 215-1 HD 1215-2 Application RA 2910 built-in sensor RA 2920 tamperproof RA 5062 remote sensor temperature adjuster RA-FN
Typical values for a Kapton Polyimide tape wrapped sample, according to NEMA Specifications
DACRON DACRON GLASS FIBER COVERED MAGNET WIRE CLASS 200 INSULATION DACRON Glass Fiber-covered Magnet Wire is manufactured by serving a combination of glass and Dacron fibers over a bare or film-coated
QUALITY OF WIND POWER. How does quality affect the cost of electricity generation from wind power?
QUALITY OF WIND POWER How does quality affect the cost of electricity generation from wind power? QUALITY OF WIND POWER Wind power is a cornerstone in the green transition of the power sector, and onshore
SECTION 13. Multipliers. Outline of Multiplier Design Process:
SECTION 13 Multipliers VMI manufactures many high voltage multipliers, most of which are custom designed for specific requirements. The following information provides general information and basic guidance
Derakane epoxy vinyl ester resins: The Evolution of Corrosion Resistant FRP
A Brief History on Corrosion Derakane epoxy vinyl ester resins: The Evolution of Corrosion Resistant FRP Corrosion in industrial processes has always threatened pipes, ducting, process equipment, scrubbers
