1 Branch Circuit Calculations by Gerald Newton October 31, A 20 ampere, 120 volt, 2-wire branch circuit has a maximum load capacity of watts or volt-amperes. Reference: Using the following for Single Phase Circuits: Watts = Volts x Amperes x Power Factor Volt-amperes = Volts x Amperes Power Factor is the cosine of the angle between volts and amperes and varies from 0 to 1.0, lagging or leading. Answer: Assuming that the voltage and current are in phase, the angle between the voltage and current is 0 degrees, and the Cosine of 0 is 1.0, then the power factor is 1.0. then Watts = 120 x 20 x 1.0 Watts = 2400 At a power factor of 1.0, Watts and Volt-amperes are equal and volt-amperes is also Answer: A 5-kilowatt clothes dryer has a full-load current of amperes when connected to a 120/240 volt, single phase 3-wire supply circuit. The minimum size of circuit (rating of the overcurrent device) that can be used on this circuit is amperes, with a minimum wire size of No. copper (assuming a 60 degrees C. ampacity and no listing for higher temperature devices and equipment.) Reference: Using the following for Single Phase Circuits: (1 of 10) [5/3/2004 3:46:56 PM]
2 Watts = Volts x Amperes x Power Factor Assume a power factor of 1.0 Amperes = Watts/Volts Answer: Amperes = 5,000 watts/240volts Amperes = 20.8 amperes The minimum size overcurrent device that can be used on this circuit is 25 amperes. (see 240-6) A minimum size No. 10 copper rated at 30 amperes is required. (Table ) Note: The 60 C. ampacity for No. 12 is 25 amperes, but Section 240-3(d) does not allow a No.12 conductor on a circuit breaker greater than 20 amperes. Answers: 20.8 amperes, 25 amperes, No The maximum continuous load permitted on a 20 ampere, 120 volt, 2-wire branch circuit supplying incandescent lighting that stays on for three hours or more is watts. (Assume that the circuit breaker is not listed for 100 percent continuous load at its rating) 120 Volts Reference: Section (a) The rating of the overcurrent device shall not be less than 125 percent of the continuous load. Answer: The solution to this problem and many Code calculations can be simplified by converting the language into mathematical terms. Then rules from algebra for inequalities can be used to solve the problems. Use ">=" to represent "greater than or equal to" Use "<=" to represent "less than or equal to" "shall not be less than" is the same as "greater than or equal to" represented by ">=" Then: Rating of Overcurrent Device >= 1.25 x Continuous load Continuous Load <= Rating of Overcurrent Device / 1.25 Continuous Load <= 20 amperes / 1.25 Continuous Load <= 16 amperes (2 of 10) [5/3/2004 3:46:56 PM]
3 Converting 16 amperes to Watts: Watts = 16 amperes x 120 volts Watts = 1920 watts Answer: 1920 watts 4. If the wattage of a single phase 120 volt appliance is given, then the full-load current can be found using the formula I =. Answer: I = Watts/120volts 5. An 800 watt 120-volt car heater will draw a load of amperes. Answer: I = Watts / Volts I= 800 watts / 120 volts I = 6.7 amperes 6. A 80 gallon 4500 watt 240 volt hot water heater has a load of amperes. This load is less than 20 amperes, but Section requires that fixed storage-type water heaters that have a capacity of 120 gallons or less shall have a branch circuit rating not less than 125 percent of the nameplate rating of the water heater. The branch circuit rating then must not be less than. Since the load for this appliance is more than 13.3 amperes and it is a nonmotor-operated appliance that does not have overcurrent protection marked on the appliance the overcurrent rating shall not exceed 150 percent of the appliance rated current by section (e)(3). In this case the rating of the circuit breaker shall not greater than. However, section (e)(3) states that if 150 percent of the appliance rating does not correspond to a standard size overcurrent device, the next larger standard size shall be permitted. So the overcurrent device shall be permitted to be amperes maximum size. The rules for selecting conductors are found in Section (a) and The conductors shall have an ampacity not less than the load to be served or amperes, and shall be protected in accordance with their ampacities as specified in Section 240-3(d) limits the overcurrent protection for a No. 10 copper conductor to 30 amperes. This assumes a 60 degree C. temperature rating. If the equipment, terminations, and overcurrent devices are listed for 75 degree C., then a No. 10 conductor would still be required since Section 240-3(d) does not allow a No. 12 with a 75 degree C. ampacity of 25 amperes to be used on a 30 ampere circuit breaker. A No. 10 copper conductor with a 25 ampere two-pole circuit breaker would also meet these rules. Answers: amperes, 23 amperes, 28 amperes, 30 amperes. 7. If a 277 volt fluorescent lighting fixture has a ballast with a nameplate rating of.9 amperes, the number of such fixtures that can be connected to a 2 wire 277 volt circuit (3 of 10) [5/3/2004 3:46:56 PM]
4 protected by a 20 ampere circuit breaker is if the fixtures are used in an office building where they will be on for 8 hours continuously each day. Answer: The maximum allowed continuous ampacity for the 20 ampere circuit breaker is 16 amperes. 16/.9 = 17 fixtures. Answer: The maximum number of 100 watt incandescent light bulbs that can be installed on a 20 ampere 120 volt 2 wire circuit where the lights will be on for 10 hours a day is. Answer: Amperes for each light bulb = 100 watts / 120 volts Amperes = x.8 = 1.0 amperes (Multiply by 1.25 for the continuous load.) 20 amperes / 1.0 amperes = 20 light bulbs Answer: Section 220-3(b)(9) requires that receptacles in other than dwelling units be computed at 180 voltamperes each. The maximum number of receptacles that can be installed on a 20 ampere 120 volt circuit in a store is. The maximum number of receptacles that can be installed on a 15 ampere 120 volt circuit in a school is. Answer: Number of receptacles on a 20 ampere circuit = 120 volts x 20 amperes / 180 voltamperes Number of receptacles on a 20 ampere circuit = 13 Number of receptacles on a 15 ampere circuit = 120 volts x 15 amperes / 180 voltamperes Number of receptacles on a 15 ampere circuit = In dwelling units and in guest rooms of hotels and motels all receptacles used for general-use on 20 ampere rating or less circuits including the small appliance receptacles, laundry room receptacle and bathroom receptacle(s) are included in the general lighting load calculations of Section 220-3(a). These receptacles shall not be required to calculated at 180 voltamperes per receptacle. True False Answer: False The small appliance circuits are not included in the the general lighting load calculation. See Section 220-3(b)(9) and (10) 11. In the sketch below if SW-1 is closed how many amperes will L1 and the grounded conductor draw? (4 of 10) [5/3/2004 3:46:56 PM]
5 SKETCH 3 Answer: Load = 1800 watts Amperes = watts / volts Amperes = 1800 watts / 120 volts Amperes = 15 amperes Answer: 15 amperes 12. In Sketch 3, the resistance of the 1800 watt load is. The resistance of the 200 watt load is. Answer: E=IR by ohms law. R=E/I, Then the resistance is 120 volts / 15 amperes Resistance of the 1800 watt load is 8 ohms For the 200 watt load, first find the amperes. Amperes = 200 watts / 120 volts, Amperes = 1.7 amperes. Resistance = 120 volts / 1.7 amperes Resistance of the 200 watt load is 70.6 ohms 13. In sketch 3 if the grounded conductor were open and both the 1800 watt load and the 200 watt load were turned on what would the voltage be across the 200 watt load? Answer: If the grounded conductor were open the two loads would be in series. The 8 ohm and 70.6 ohm resistances in series add to 78.6 ohms. The amperes through both loads would be 240 volts / 78.6 ohms or 3 amperes. The voltage across the 200 watt load would be 70.6 ohms x 3 amperes or volts. Answer: volts (5 of 10) [5/3/2004 3:46:56 PM]
6 14. In the diagram below Ia, Ib, and Ic can be found using? A. I = Watts / (277 volts x 1.732) B. I = watts / 3 C. I = watts / (480 volts x x power factor) Answer: C "The Single Phase Professor" (6 of 10) [5/3/2004 3:46:56 PM]
7 15. In the diagram for question 14, if each leg serves 1/3 of a balanced load of 10,000 voltamperes then what is the current in each leg? Assume that the power factor is 1.0. Answer: I = 10,000 voltamperes / (480 volts x 1.732) I = 12 amperes 16. The minimum number of 20 ampere 120 volt branch circuits required to serve the general lighting load for a 3,000 square foot one family dwelling unit is circuits. Answer: General Lighting load = 3 voltamperes x 3,000 square ft. General Lighting Load = 9,000 voltamperes. A 20 ampere circuit supplies 120 volts x 20 voltamperes or 2400 voltamperes. 9,000 voltamperes / 2400 voltamperes = 3.75 Round up to 4 circuits Answer: 4 circuits 16. In a dwelling unit at least two 20 ampere, 120 volt circuits must be provided for laundry outlets. True False Answer: False See Section (f) 17. The receptacles installed to serve countertop surfaces in dwelling unit kitchens shall be supplied by two each small appliance circuits. True False Answer: True See (b)(3) Note: One small appliance circuit cannot be used to supply all the receptacles for countertops while another small appliance circuit is used to supply the other required outlets in the dining room, pantry, kitchen, breakfast room, or similar area in a dwelling unit. (7 of 10) [5/3/2004 3:46:56 PM]
8 18. In the diagram below the 120 volt loads are computer loads. If the line current in each phase is 40 amperes, the approximate current in the neutral is. Answer: 80 amperes Discussion: The switching in the computer power supplies cause the current in the neutral to be approximately double the current in the phase conductors. Special cables and "K" rated transformers are designed to supply such loads. 19. In the diagram below for derating purposes the neutral is a current carrying conductor. True False Answer: True See Section (b)(4)(c) Discussion: When the major load is nonlinear the neutral carries third harmonic currents that are approximately equal to the line currents. (8 of 10) [5/3/2004 3:46:56 PM]
9 20. In the diagram below if Ia, Ib, and Ic are equal to 50 amperes the current in the neutral is approximately amperes. (9 of 10) [5/3/2004 3:46:56 PM]
10 Answer: 0 amperes Return to electrician.com (10 of 10) [5/3/2004 3:46:56 PM]
Section 3: Load Planning Bill Brown, P.E., Square D Engineering Services
Section 3: Load Planning Bill Brown, P.E., Square D Engineering Services Basic Principles The most vital, but often the last to be acquired, pieces of information for power system design are the load details.
BRANCH CIRCUIT AND FEEDER REQUIREMENTS
CHAPTER 36 BRANCH CIRCUIT AND FEEDER REQUIREMENTS SECTION E3601 GENERAL E3601.1 Scope. This chapter covers branch circuits and feeders and specifies the minimum required branch circuits, the allowable
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical
GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta
GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for
CHAPTER 2 EXAMPLES AND TABLES
CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of
Line Loss WSDOT Winter 2008 BZA
Electrical Design Training Class Line Loss WSDOT Winter 2008 BZA Presented by: Keith Calais 1 OHM S LAW P = Watts (Power) I = CURRENT (AMPERES) R = RESISTANCE (OHMS) E = ELECTROMOTIVE FORCE (VOLTS) P =
GENERAL ELECTRICAL REQUIREMENTS
GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of
Department of Labor and Industry Electrical Licensing
Department of Labor and Industry Electrical Licensing License Examination Guide The information in this guide is provided by the Licensing Unit of the Department of Labor and Industry to ensure that applicants
Voltage Drop (Single-Phase)
Voltage Drop (Single-Phase) To Find: To Find Voltage Drop Formula: 2 x K x L x I V.D. = ------------------- C.M. Variables: C.M. = Circular Mill Area (Chapter 9, Table 8) To Find Voltage Drop Percentage
NEC 2014 Code Changes
NEC 2014 Code Changes Articles 400-408.55 CHANGES FROM 2011 TO 2014 CODE ARE IN RED Chapter 4 Equipment for General Use ARTICLE 400 Flexible Cords and Cables 400.4 Types Flexible cords and flexible cables
ELECTRICAL CIRCUITS. Electrical Circuits
Electrical Circuits A complete path, or circuit, is needed before voltage can cause a current flow through resistances to perform work. There are several types of circuits, but all require the same basic
COUNTY OF LOS ANGELES BUILDING AND SAFETY DIVISION ELECTRICAL CODE FEE SCHEDULE (Title 27 of the County of Los Angeles Code, Ord No.
COUNTY OF LOS ANGELES BUILDING AND SAFETY DIVISION ELECTRICAL CODE FEE SCHEDULE (Title 27 of the County of Los Angeles Code, Ord No. 2013-0049) Effective July 1, 2014, Electrical Permit Fees in the unincorporated
An Electrical Lab Exercise on Voltage Drop
An Electrical Lab Exercise on Voltage Drop Mark C. Tatum, P.E. Auburn University Auburn, AL Lab exercises are an excellent way to give students hands on experiences. Practice by doing has been demonstrated
7. What is the current in a circuit if 15 coulombs of electric charge move past a given point in 3 seconds? (1) 5 A (3) 18 A (2) 12 A (4) 45 A
1. Compared to the number of free electrons in a conductor, the number of free electrons in an insulator of the same volume is less the same greater 2. Most metals are good electrical conductors because
SINGLE FAMILY DWELLING ELECTRICAL SERVICES RATED 225 TO 600 AMPS
SINGLE FAMILY DWELLING ELECTRICAL SERVICES RATED 225 TO 600 AMPS A. PURPOSE 1. The following information includes the basic permit application requirements for a 120/240 volt single phase Electrical Service
Electrical Design TABLE OF CONTENTS FOREWORD... 1. BASIC ELEMENTS OF ELECTRICITY... 2 Electricity works much like water Ohm s Law
TABLE OF CONTENTS Electrical Design TABLE OF CONTENTS FOREWORD.......................................................................... 1 BASIC ELEMENTS OF ELECTRICITY..................................................
Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA
Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA presented by: Keith Calais 1 What is it? Ampacity is the current, in Amperes, that a conductor can carry continuously under the conditions
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
Electrician s Math and Basic Electrical Formulas
UNIT 1 Electrician s Math and Basic Electrical Formulas INTRODUCTION TO UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS In order to construct a building that will last into the future, a strong
Definition AC Power Distribution
COMMON AC POWER DISTRIBUTION CONFIGURATIONS The input voltage needed to power electronic equipment is provided by the manufacture in the product specifications. Matching this requirement to the facility
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
Description. Lesson Outcomes. Assumptions. Terminology. Electrician
Description Successfully performing electrical work requires the ability to read and interpret many different types of drawings and diagrams. Understanding circuit symbols and components is another one
City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines
Western Riverside County Code Uniformity Program City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines PHONE (951) 826-5697 3900 Main Street, Riverside, CA 92522
I = V/r P = VI. I = P/V = 100 W / 6 V = 16.66 amps. What would happen if you use a 12-volt battery and a 12-volt light bulb to get 100 watts of power?
Volts, Amps and Ohms Measuring Electricity The three most basic units in electricity are voltage (V), current (I) and resistance (r). Voltage is measured in volts, current is measured in amps and resistance
Parallel Circuits. Objectives After studying this chapter, you will be able to answer these questions: 1. How are electrical components connected
This sample chapter is for review purposes only. Copyright The Goodheart-Willcox Co., Inc. All rights reserved. Electricity Objectives After studying this chapter, you will be able to answer these questions:.
6/14/02 Chapter 2: Basic Electrical Power Fundamentals 1/6
Basic Electrical Power Fundamentals LOAD REFERENCE Kilowatts Kilovolt amps Power Factor PF Motors KW KVA USE NEC 430-148 KW < KVA.6-.95 and 430-150 to find current for given HP Indancescant Lighting USE
Section B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
Commercial/Industrial Electricity
1 ELC 210 Commercial/Industrial Electricity Course Package Presented and Approved July 31, 2008 2 Contact person(s) DAVE WHITE Date of proposal to JULY 31, 2008 Curriculum Committee NEW COURSE PACKAGE
Commercial Energy Savings Guide. www.touchstoneenergy.coop
Commercial Energy Savings Guide www.touchstoneenergy.coop NRECA Pocket Savings Guide Pag.indd 1-3 2/7/05 4:19:07 PM Commercial Energy Saving Tips Notes: This guide provides basic hints on ways to reduce
Electric Vehicle Charging Station Installation Guidelines: Residential and Commercial Locations
Electric Vehicle Charging Station Installation Guidelines: Residential and Commercial Locations Streamlining Permitting and Inspection of Residential and Commercial Electric Vehicle Charging Station Installations
Determining the Cause of AFCI Tripping Branch/Feeder and Combination Arc Fault Circuit Interrupters Class 760
Data Bulletin Determining the Cause of AFCI Tripping Branch/Feeder and Combination Arc Fault Circuit Interrupters Class 760 Retain for future use. 0760DB0204 Replaces 0760DB0204 R09/07 Precautions DANGER
Buck - Boost Transformers
Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
Electrical Wiring Guide
Electrical Wiring Guide In order to wire your own home, you must comply with the requirements of the 2011 edition of the National Electrical Code (NEC). NEC code articles are indicated by brackets ([ ]),
Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port
Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port Code-Wide Code Change Section 90.5(C). Fine Print Notes are now referred to as "Informational Notes." The purpose, intent,
Current Programs available to Limited Income Customers. Residential and Multifamily
Current Programs available to Limited Income Customers Residential and Multifamily CAP Program- Residential and Multifamily The City of Austin offers programs to help customers facing temporary and long-term
Objectives 200 CHAPTER 4 RESISTANCE
Objectives Explain the differences among conductors, insulators, and semiconductors. Define electrical resistance. Solve problems using resistance, voltage, and current. Describe a material that obeys
INSPECTION GUDELINES
GENERAL REQUIREMENTS Building permit and approved set of plans Building permit on the card is the same as on the route "If this is not the first inspection, read inspection records and notes on permit
INSTALLATION GUIDE LOW VOLTAGE TRANSFORMER
INSTALLATION GUIDE LOW VOLTAGE TRANSFORMER 300W 600W 900W 1200W ATTENTION: Please read and understand thoroughly this installation guide to ensure safe and efficient operation of this Power Module 1 Open
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
Voltage Loss Formula s
www.litz-wire.com HM Wire International Inc. Phone: 330-244-8501 Fax: 330-244-8561 Voltage Loss Formula s www.hmwire.com Voltage loss in a wire is synonymous to pressure loss in a pipe. Electric current
Residential Electrical Inspection Checklist
Residential Electrical Inspection Checklist Based on the 2008 National Electrical Code Generally, Minnesota law requires all electrical work to be performed by licensed, bonded and insured electrical contractors
OHM S LAW AND RESISTANCE
OHM S LAW AND RESISTANCE Resistance is one of the basic principles of Ohm s law, and can be found in virtually any device used to conduct electricity. Georg Simon Ohm was a German physicist who conducted
BASIC NEC CODE RULES AND DESIGN PRACTICE
BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,
LED Retro Fit the next generation in energy efficiency. Converting existing 12v systems to LED
Benefits and Features of Retro Fitting with LED- LED Retro Fit the next generation in energy efficiency Converting existing 12v systems to LED Between 1960 and 1990, landscape lighting was still in the
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared
Voltage Drop. Voltage Drop 1
Voltage Drop The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences. Qualified person is defi ned in Article 100 of
A kilowatt-hour (kwh) is a unit for measuring energy. It is, as its name suggests, one kilowatt of power used over a period of one hour.
How Much Electricity Does a Light Bulb Use and What will it Cost Me? We (the Village of Paw Paw) are often asked How do I know how much electricity a home appliance or device is using and what is the charge
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
Student Exploration: Circuits
Name: Date: Student Exploration: Circuits Vocabulary: ammeter, circuit, current, ohmmeter, Ohm s law, parallel circuit, resistance, resistor, series circuit, voltage Prior Knowledge Questions (Do these
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
CHAPTER 10: APPLIANCES AND LIGHTING
Chapter 10: Appliances and Lighting 151 CHAPTER 10: APPLIANCES AND LIGHTING According to the U.S. Environmental Protection Agency, appliances and home electronics account for 20% of energy bills in the
GENERAL WIRING RULES FOR HOUSES
GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat
Unit 4: Electricity (Part 2)
Unit 4: Electricity (Part 2) Learning Outcomes Students should be able to: 1. Explain what is meant by power and state its units 2. Discuss the importance of reducing electrical energy wastage 3. State
Services. Three Phase Service
Services Primary Service vs Secondary Service Overhead vs Underground Common Service Types Three Phase Wye Closed Open Delta Corner Grounded Center Tapped Open Single Phase Three Phase Service Wye Delta
Homeowner Information Guide Electrical Safety. British Columbia Safety Authority
Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in
Residential Electrical Inspection. Checklist
443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us Residential Electrical Inspection (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5743 TTY: (651) 297-4198 Checklist Generally, Minnesota
Chapter 24. Three-Phase Voltage Generation
Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal
Series and Parallel Circuits
Series and Parallel Circuits Direct-Current Series Circuits A series circuit is a circuit in which the components are connected in a line, one after the other, like railroad cars on a single track. There
Series and Parallel Circuits
Series and Parallel Circuits Components in a circuit can be connected in series or parallel. A series arrangement of components is where they are inline with each other, i.e. connected end-to-end. A parallel
LOS 2500 SUPER CEILING SENSOR. Installation Manual
LOS 2500 SUPER CEILING SENSOR Installation Manual How Do RAB Occupancy Sensors Work? Selecting A Location: The L0S2500 sensor sees infrared heat changes caused by the motion of people within its detection
Tristan s Guide to: Solving Series Circuits. Version: 1.0 Written in 2006. Written By: Tristan Miller [email protected]
Tristan s Guide to: Solving Series Circuits. Version: 1.0 Written in 2006 Written By: Tristan Miller [email protected] Series Circuits. A Series circuit, in my opinion, is the simplest circuit
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
7-41 POWER FACTOR CORRECTION
POWER FTOR CORRECTION INTRODUCTION Modern electronic equipment can create noise that will cause problems with other equipment on the same supply system. To reduce system disturbances it is therefore essential
STUDY GUIDE: ELECTRICITY AND MAGNETISM
319 S. Naperville Road Wheaton, IL 60187 www.questionsgalore.net Phone: (630) 580-5735 E-Mail: [email protected] Fax: (630) 580-5765 STUDY GUIDE: ELECTRICITY AND MAGNETISM An atom is made of three
How To Wire A Three Phase, Single Phase, Wye Transformer
Three-Phase Transformers When more power is needed - three transformers can be tied together. This is called three-phase. Here s a simple way of comparing single-phase to threephase power. Single-Phase
Ohm s Law. George Simon Ohm
Ohm s Law George Simon Ohm The law which governs most simple and many complex electrical phenomena is known as Ohm s Law. It is the most important law in electricity. In 1827, a German locksmith and mathematician
Ducoterra Radiant Heating Panel Installation Manual
Ducoterra Radiant Heating Panel Installation Manual 1. Introduction Your new radiant heating panels are designed to heat living and working spaces rapidly and efficiently by radiant heating. Like the sun,
Motor Protection Voltage Unbalance and Single-Phasing
Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
Electrical Contractors. and the. New Jersey. Rehabilitation Code
Electrical Contractors and the New Jersey Rehabilitation Code Alan Chech Electrical Seminars 609-890-7072 www.alanchech.com Information is based on the presently adopted electrical subcode NEC 2005. Current
rpsa FIRE PROTECTION ENGINEERS
R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Sample Fire Alarm System Calculations 1. A fire alarm manufacturer specifies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
TECH TIP # 37 SOLVING SERIES/PARALLEL CIRCUITS THREE LAWS --- SERIES CIRCUITS LAW # 1 --- THE SAME CURRENT FLOWS THROUGH ALL PARTS OF THE CIRCUIT
TECH TIP # 37 SOLVING SERIES/PARALLEL CIRCUITS Please study this Tech Tip along with assignment 4 in Basic Electricity. Parallel circuits differ from series circuits in that the current divides into a
Electrical Drawings - Table of Contents
Electrical Drawings - Table of Contents E1.0 Lighting Plan E1.1 Power Plan E2.0 Electrical Specifications E2.1 Electrical Specifications E3.0 Panel Schedule E3.1 Load Summary 1 2 1 Panel Schedule LP1
Electrical Resistance Resistance (R)
Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed
Solutions to Bulb questions
Solutions to Bulb questions Note: We did some basic circuits with bulbs in fact three main ones I can think of I have summarized our results below. For the final exam, you must have an understanding of
Installation Instructions
H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.
Construction Electrical Terminology. Electricians
Construction Electrical Terminology Electricians Acknowledgments Winnipeg Technical College and the Department of Labour and Immigration of Manitoba wish to express sincere appreciation to all contributors.
Conductor Sizing and the National Electrical Code
Conductor Sizing and the National Electrical Code The National Electrical Code requirements for conductor sizing and overcurrent protection have always been confusing and complex. Factors that must be
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes
2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes 1) Tamper resistant receptacles. 2009 CEC Required in dwelling units 2012 CEC Expanded to child care facilities First introduced in the 2009
Unit: Charge Differentiated Task Light it Up!
The following instructional plan is part of a GaDOE collection of Unit Frameworks, Performance Tasks, examples of Student Work, and Teacher Commentary. Many more GaDOE approved instructional plans are
Photovoltaic Cell: Converting Light to Electricity
Photovoltaic Cell: Converting Light to Electricity Outcomes: 1. Understand that a photovoltaic cell produces DC voltage when light shines on its surface. 2. Understand that the electrical voltage produced
Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1
Experiment no 1 Power measurement in balanced 3 phase circuits and power factor improvement 1 Power in Single Phase Circuits Let v = m cos(ωt) = cos(ωt) is the voltage applied to a R-L circuit and i =
Ontario Electrical Safety Code 25 th Edition/ 2012
Ontario Electrical Safety Code 25 th Edition/ 2012 Ted Olechna Director, Codes and Standard Chief Engineer 1 What I Will Cover ESA s role is as the regulator Highlight of 2012 Code changes The Code and
Energy Efficiency. Energy Efficient Water Heating: Purchasing a new electric water heater. Hot water use has a significant impact on your bill.
Energy Efficiency Energy Efficient Water Heating: Purchasing a new electric water heater. Water heating accounts for about 18 percent of your home energy bill. Only space heating and cooling account for
AP Physics Electricity and Magnetism #4 Electrical Circuits, Kirchoff s Rules
Name Period AP Physics Electricity and Magnetism #4 Electrical Circuits, Kirchoff s Rules Dr. Campbell 1. Four 240 Ω light bulbs are connected in series. What is the total resistance of the circuit? What
Electric Potential Difference
Name: Electric Potential Difference Read from Lesson 1 of the Current Electricity chapter at The Physics Classroom: http://www.physicsclassroom.com/class/circuits/u9l1a.html http://www.physicsclassroom.com/class/circuits/u9l1b.html
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS Paul A Zoubek, CSP, CIH Occupational Services, Inc. San Diego, CA 619-861 861-0612 [email protected] OCCUPATIONAL SERVICES, INC. BACKGROUND Update Update
Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION
PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION CODING: Words underlined are additions to the 1999 NEC Words stricken are deletions to the 1999 NEC Adopted by Ordinance 99-73
ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers
ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers This handout is intended to be a general overview of residential electrical requirements as noted in the 2014 National Electrical
Three-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
Tips for connecting 24-volt power
Digital Designer s Guide Application NoteAN0604D Revision B Tips for connecting 24-volt power This application note covers choosing a transformer and connecting 24 volt AC power to a KMC Controls DDC controller.
Residential Electrical System Aging Research Project. Dave Dini Sr. Research Engineer Underwriters Laboratories
Residential Electrical System Aging Research Project Dave Dini Sr. Research Engineer Underwriters Laboratories Aging Residential Electrical Systems Research Project Sponsors Fire Protection Research Foundation
3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer
How Much Voltage Drop Is Acceptable?
How Much Voltage Drop Is Acceptable? Article supplied by Ideal The National Electrical Code (NEC) recommends that the combined voltage drop of the electrical system (branch circuit and feeders) not exceed