RISKS OF ACCUMULATED SULFUR IN SULFUR RECOVERY UNITS
|
|
|
- Brett Miller
- 9 years ago
- Views:
Transcription
1 RISKS OF ACCUMULATED SULFUR IN SULFUR RECOVERY UNITS By: Ellen Ticheler-Tienstra, Anne van Warners, Rien van Grinsven and Sander Kobussen of Jacobs Comprimo Sulfur Solutions Abstract While recovering sulfur in an SRU depends on condensation of sulfur, its unintended condensation and accumulation can present problems. The paper analyses areas where this may be expected and presents case histories of sulfur build-up in SRU equipment, such as waste heat boilers, reheaters, sulfur condensers and coalescers. The risks involved in accumulation of sulfur are discussed, both for the operation of Claus plants and for the operation of SUPERCLAUS plants, for which liquid sulfur may pose extra risks. Ways are discussed to prevent accumulation and minimize the risks. This paper focuses on the most common type of SRU configurations, not on sub-dewpoint type SRUs. Introduction From time to time operational issues in an SRU are related to accumulation of liquid sulfur. These issues can be experienced in any SRU but operating experience over the past 25 years has shown that SUPERCLAUS and EUROCLAUS installations are sensitive to liquid sulfur accumulation, as will be discussed below. In the modified Claus process, sulfur is produced both in the thermal and in the catalytic s. Since the Claus reaction is a chemical equilibrium, the production of sulfur is inhibited if sulfur vapor is already present in the process gas. Therefore a sulfur condenser is generally used to condense and remove the produced sulfur and ensure continued conversion to sulfur in subsequent (s). As a general rule the sulfur production is progressing as shown in table 1. This also shows the relative contribution of each to the total sulfur production. Sulfur Production (%) Thermal First catalytic Second catalytic Third catalytic SUPERCLAUS Coalescer 3 Claus 2 Claus
2 This table is based on a typical refinery feed of 75 vol.% H 2 S, 5 vol.% NH 3, 10 vol.% CO 2, 10% H 2 O, 0.3 vol.% C 2 H 6 and almost complete removal of sulfur vapor from the process stream. The condensers are not removing all of the sulfur, it is sufficient to stay above the sulfur dew point in the following catalytic. In the sub-dewpoint processes (CBA, Sulfreen, MCRC) there is some deliberate condensation of sulfur to below the dewpoint to force the Claus equilibrium closer to completion. Fire risk of accumulated liquid sulfur Principles of a sulfur fire The best known risk of accumulated liquid sulfur is that of a sulfur fire. For this to happen, air (or better: oxygen) has to be present in sufficiently high concentrations (>10%). At lower concentrations of free oxygen in the process gas the sulfur will be oxidized to SO 2 thereby generating extra heat of oxidation. A sulfur fire can also lead to corrosion that is higher than normally experienced. Besides sulfur vapor (from liquid sulfur) and oxygen in sufficiently high concentrations (>10 vol.%) there has to be an ignition source. The following sources have been identified: No additional source, when the temperature in the process at that point is above the autoignition temperature of sulfur. The auto ignition temperature most often mentioned is 230 C but values ranging from 190 C to 261 C have been reported, possibly linked to the sulfur particle size. Pyrophoric iron sulfide (FeS), when exposed to air (oxygen) will ignite a sulfur/air mixture Static electricity generated by liquid sulfur agitation. Sulfur, being one of the best electric insulating liquids known, and having a high dielectric constant can easily generate enough static electricity to cause a spark ignition Oxygen concentration during normal SRU operation During normal operation of a Claus unit with a good quality main burner hardly any oxygen will slip from the main combustion chamber to the catalytic s, therefore the process gas does not contain free oxygen and there is no risk of a sulfur fire. During normal operation (the risk of) oxygen ingress arises from air instead of nitrogen purges on the main burner, fuel gas fired direct reheaters (inline burners) and in the SUPERCLAUS process, where air is introduced to selectively oxidize H 2 S to elemental sulfur. The oxygen concentrations in these cases are limited and will not lead to sulfur fires.
3 In case of a SUPERCLAUS or EUROCLAUS installation, oxygen concentration is designed to be just enough to convert H 2 S and keep the catalyst in an oxidized state. In the reactor outlet there should be just 0.5% to 1.0% oxygen present. Oxygen concentration during abnormal SRU operation The risk of a sulfur fire increases as soon as higher concentrations of oxygen enter the system. This happens most often when the main burner is in the start-up phase and/or operated with fuel gas, e.g. during heating up, hot standby or during taking the unit out of operation, when the burner is operated not substoichiometrically, but with excess air. In the first two modes of operation (heating up with sulfur in the unit and hot standby) this is due to wrong setting of the air to fuel gas ratio. This can occur easily, when the main burner is not operated with a fuel gas of constant composition (preferably natural gas), but with a fuel gas of varying composition (and Mol. Weight, which leads to wrong fuel gas flow metering). A fuel gas analyzer (e.g. Wobbe index meter) could be installed to compensate for fluctuations in fuel gas composition and air demand. In the last mode of operation (taking the unit out of operation for maintenance), it is the intention to gradually convert FeS to Fe 2 O 3 in a controlled way by increasing the oxygen slip from the main burner.
4 Oxygen concentration during abnormal SUPERCLAUS operation In the selective oxidation of a SUPERCLAUS plant, higher concentrations of oxygen can be present during heating up or shutting down or during a bypass of the selective oxidation. A bypass of the selective oxidation occurs on high temperature in the catalyst bed or on high inlet H 2 S concentration and protects the selective oxidation during upsets, preventing too high temperatures in the reactor. In such a case the reactor temperature is maintained by purging the reactor with air. This also keeps the catalyst under oxidizing conditions and prevents ingress from sulfur containing tail gas via the back-end of the selective oxidation. So, during a bypass the atmosphere in the selective oxidation contains 20% oxygen. When this atmosphere comes in contact with any accumulated sulfur in the piping or equipment (reheater, condenser, coalescer) then there is an increased risk of fire. As to liquid sulfur, it is important to note that the selective oxidation catalyst does not retain liquid sulfur in its pores, unlike Claus catalyst. So sulfur in the selective oxidation catalyst does not contribute to the risk of a sulfur fire. An obvious result of a sulfur fire is damage to equipment. Condenser tubes and mist pads are especially vulnerable. Sometimes the fire is limited, either by available sulfur or oxygen, and will give a noticeably higher temperature but no damage. Note however, that in every sulfur fire not only SO 2 but also SO 3 /sulfuric acid will be produced. Sulfuric acid can eventually lead to extensive corrosion damage in lines and equipment. Other effects of accumulated liquid sulfur Besides the risk of a sulfur fire there are other effects of accumulation of sulfur. When the level of stagnant sulfur has risen high enough, it will impede the flow of process gas and cause pressure drops forcing lower gas feed rates. A sudden limitation to the capacity or an increased main burner inlet pressure may be a sign of sulfur accumulation. Yet a normal inlet pressure is no guarantee that there is no sulfur accumulation. If there is a pool of liquid sulfur, the flow of process gas can entrain liquid sulfur, carrying it downstream in the form of mist or even slugs of liquid sulfur. An illustration of this effect is the upward flow of raindrops on the windscreen of a car above a certain speed. In downstream equipment, the sulfur can be knocked out and will accumulate at low points in the unit. This results in a pool of liquid sulfur, when the sulfur cannot be drained properly. In this respect it is relevant to mention that agitation of liquid sulfur by the process gas flow can generate static electricity and act as an ignition source, as described before.
5 Another effect of entrained sulfur is obstruction of lines or demister pads. Entrained sulfur has been found to plug instrument lines and even tail gas analyzers. Also the efficiency of demister pads can be compromised by accumulation of sulfur in the pad. Furthermore, a nowadays not unimportant side-effect of entrained sulfur reaching the incinerator is a higher stack SO 2 emission. Finally, when an installation containing liquid sulfur is allowed to cool, the sulfur will solidify and mechanically removing the solid sulfur in lines and equipment can be very difficult and time consuming. Case histories It is believed that sulfur accumulation as described in this paper occurs widely, but is often not identified or recognized in a Claus unit. In the case histories below, several incidents in the Claus s and in the selective oxidation of SUPERCLAUS installations are described. It will however be clear that this type of incidents is in no way unique for SUPERCLAUS.
6 Case 1: Refinery application, 3 Claus unit Description: The unit was operating fine but because of a small instrument problem the acid gas was shut down and the unit was operated in hot standby mode. After approx. 30 minutes a sulfur fire was seen in the first reheater. This is a general SRU case. Cause: Sulfur had accumulated in the first reheater and could not drain because of a wrong slope of the reheater. Also the sliding strips in the reheater shell prevented proper draining of sulfur. In hot standby mode, the air/fuel gas ratio was too high and consequently air contacted the accumulated sulfur. The ignition source is not known, it could be either pyrophoric iron sulfide or hot reheater tubes. Initial oxidation of sulfur by air may have increased the temperature in the reheater to above the auto ignition temperature. On the first signs of a fire, the operator reacted by admitting more air to the unit, thereby increasing the fire.
7 Case 2: Natural gas application, 2 Claus unit with SUPERCLAUS tail gas treating Description: The unit had been in operation for a year without problems. During a maintenance shutdown the coalescer was found full of solid sulfur reaching up to halfway the inlet nozzle. Also the sulfur outlet of the last condenser was found to be full of solid sulfur. No sulfur fire was experienced, but the solid sulfur had to be removed mechanically. This is a general SRU case. Cause: The rundowns of the last condenser and the coalescer were combined without a seal in between. During operation there was a suspicion of a full coalescer because vibrations were noticed in the coalescer vessel. Also there was more SO 2 in the stack than in the coalescer outlet, indicating sulfur entrainment from the coalescer to the incinerator. Staff checked the coalescer and observed gas flow from an opening in the coalescer sulfur rundown line. From this they wrongly concluded that the coalescer vessel was empty. Later it was found that the combined rundown was partially blocked and the condenser outlet was completely blocked.
8 Case 3: Natural gas application, 2 Claus unit with SUPERCLAUS tail gas treating Description: During normal operation the tail gas analyzer signal was seen to fall away periodically. Also the sulfur flowing out of the last Claus condenser was coming in surges and vibrations were noticed. The plant appeared to operate at nominal acid gas flow. This is a general SRU case. Cause: It was found that, although the acid gas input flow rate was as per design, the H 2 S content of the acid gas was higher, by 40%. This caused overloading of the Claus condensers resulting in entrainment of sulfur and plugging of the downstream tail gas analyzer. Because of this the analyzer read-out became unreliable.
9 Case 4: Refinery application, two Claus units, each with 2 Claus s and SUPERCLAUS tail gas treating, with common incinerator and stack Description: One of the two SRUs had been in operation, while the other unit was cold. Also the SUPERCLAUS of the standby unit was cold and was not being purged. Since the outlet lines of the two units were connected, tail gases from the hot unit could diffuse back into the cold unit. After one year, the cold Claus unit was started up and was operating in Claus mode for 3 weeks while the SUPERCLAUS unit was still cold. When after this period attempts were made to heat up the SUPERCLAUS reactor with hot start up air, it was found that the SUPERCLAUS was blocked. After heating up the SUPERCLAUS condenser with steam the air started to flow and a sulfur fire occurred in the condenser and outlet line. Cause: Two separate but linked causes were identified. The first one was that corrosive gases and sulfur vapor diffused back from the hot unit (SRU 1) to the cold unit (SRU 2), causing corrosion and forming pyrophoric iron sulfide in the outlet line and outlet channel of the cold condenser; also the cold demister pad was plugged with sulfur. The second cause was accumulation of sulfur in SRU 2 during the 3 weeks of operation in Claus mode, due to plugging of the run down line from the coalescer of SRU 2. At some point in time the liquid sulfur was flowing back to the cold part of SRU 2 via the connected run down lines and filling part of the condenser up to the inlet channel. When the condenser of SRU 2 was heated up, the hot start up air contacted the liquid sulfur. In itself that could not start a fire because the air was not hot enough, the fire did not start in the inlet channel. But when the air contacted pyrophoric iron sulfide in the outlet channel, ignition occurred. The sulfur fire damaged the demister pad and part of the outlet line. Sulfuric acid produced by the fire caused secondary corrosion damage.
10 Case 5: Natural gas application, 3 Claus unit with SUPERCLAUS tail gas treating Description: Within a period of two weeks, two sulfur fires were experienced in the SUPERCLAUS condenser. The SRU had been in operation for eight years without incidents. The fires occurred when the Selective Oxidation was bypassed and (oxidation) air was allowed through the SUPERCLAUS bed. The fire resulted in some severe damage/corrosion to the internal of condenser. Cause: It was found that the sulfur lock was blocked by debris and that sulfur had accumulated in the last condenser (SUPERCLAUS condenser), even flowing through the condenser tubes to the inlet channel. Upon bypassing the SUPERCLAUS reactor, hot undiluted air at a temperature of 252 C contacted the liquid sulfur in the inlet channel. Since the auto-ignition temperature of liquid sulfur in pure air (20% O 2 ) is 230 C a sulfur fire resulted. As is commonly seen, the fire spread from the inlet channel through the condenser into the outlet channel and caused severe damage of the condenser.
11 Case 6: Refinery application, three Claus s and a EUROCLAUS tail gas treating Description: During normal operation the tail gas analyzer signal was seen to fall away periodically for 5 to 10 minutes. To investigate this, the SUPERCLAUS was bypassed for a longer period. After 30 minutes a sulfur fire started, but it was at that moment not noticed by the DCS operator. To maintain the temperature in the SUPERCLAUS extra air was added upstream of the reheater, thereby intensifying the fire. Cause: Because of a failure of the catalyst grid, catalyst particles were carried through the final Claus condenser and accumulated in the sulfur lock, causing a blockage. Sulfur accumulated and entrained sulfur was carried over to the SUPERCLAUS reheater by the process gas flow. There the sulfur mist was knocked out and accumulated in the reheater inlet line. The sulfur could not flow back to the condenser because the SUPERCLAUS inlet valve had been closed. Oxidation air, used to purge the SUPERCLAUS reactor during the period of bypass, slowly diffused upstream until the O 2 concentration was high enough to cause a fire. The exact ignition source is not known, it could be either pyrophoric iron sulfide or hot SUPERCLAUS reheater tubes. Interestingly, the steam temperature in the reheater was probably not high enough to cause ignition, but the initial oxidation of sulfur by air may have increased the temperature in the reheater to above the auto ignition temperature. The sulfur fire damaged the reheater tube bundle and the reheater inlet line.
12 Case 7: Natural gas application, 2 Claus unit with SUPERCLAUS tail gas treating Description: The unit had been running normally but the SUPERCLAUS condenser outlet temperature was higher than normal. During SUPERCLAUS bypass operation, air was introduced to keep the unit warm and ready for normal SUPERCLAUS operation. The condenser outlet temperature was seen to rise from 207 to 232ºC in 20 minutes. Analysis of the coalescer outlet gas showed an SO 2 content of 3.5 vol.%, indicating a sulfur fire. When the sample (Strahman) valve in the condenser gas outlet line was opened white smoke was escaping. It was concluded that accumulated sulfur in the SUPERCLAUS condenser outlet channel was burning. Upon closing the air supply block valve, the fire extinguished and normal operation could be resumed. Cause: Partial plugging of the SUPERCLAUS condenser rundown line had caused liquid sulfur to accumulate in the condenser outlet channel. Because of malfunctioning of the pressure control the condenser temperature had risen to above 170ºC, thereby making the sulfur more viscous and making it harder to drain properly. Also the control valve in the oxidation air line was leaking and causing some oxidation of sulfur. Upon admitting more air, a moderate sulfur fire started, that could be easily extinguished. No damage to the equipment was observed.
13 Case 8: Refinery application, three Claus s and a EUROCLAUS tail gas treating Description: A few hours after the SUPERCLAUS was taken into operation, the rundown valve of the coalescer was opened and, unexpectedly, a large flow of sulfur appeared in the funnel that lasted for more than a quarter of an hour. The SUPERCLAUS condenser rundown had been opened just before and had shown only one minute of large sulfur flow. Apparently sulfur had accumulated in the coalescer. No damage was seen. Cause: The bypass line ties in on top of the gas outlet line of the coalescer, close to the coalescer. From the tie in point the gas outlet line slopes back to the coalescer, so part of the condensed sulfur in the bypass line will end up in the coalescer on gravity flow. The SRU had been in Claus mode for approx. 4 months. Apart from condensed sulfur flowing back, also heavy entrainment from the last Claus condenser may have contributed to the large amount of sulfur in the coalescer. Apparently the last Claus condenser had been operating with a plugged sulfur rundown for some time. A lesson learned is to always take the coalescer rundown in operation and to expect some sulfur flow from it. Accumulation could have caused a sulfur fire if pyrophoric material had come in contact with the sulfur.
14 Classification by causes The most obvious cases of liquid sulfur accumulation are seen when the rundown of sulfur from the unit is restricted. A common cause is blockage by catalyst dust or debris. Therefore catalyst loading should be done in such a way that little dust is produced and dust must always be removed during loading. After loading dust should be blown out and the reactor below the grid should be inspected and cleaned. In one example it was found that catalyst had been discharged through the lock, the sulfur rundown line and all the way down into the sulfur collection vessel. It should be noted that dust or debris can also combine with sulfur and turn into a form of sulfur concrete. In this state the sulfur will be immobilized and can lead to a fire when favored by the other conditions (air, ignition). Another problem is malfunction of tracing or jacketing. In such cases often the stream trap is found to be not working properly, either by poor design, fouling or mechanical defect. Blockage can also be caused by wrongly designed outlet lines, e.g. not taking into account the high viscosity that can be expected at temperatures over 158 C. This effect is aggravated further downstream the SRU, where the lower H 2 S concentration in liquid sulfur causes a higher viscosity. An obvious cause, but still seen sometimes is wrong sloping or routing of lines. If not done properly, sulfur may accumulate in the bottom of equipment or in pockets. As an example, we sometimes observe condensed sulfur in the WHB outlet, where it is not supposed to be according to the designs. Other cases are those where sulfur accumulates after having been supplied by some means of transport, such as: Diffusion of sulfur vapor from a hot place to a cold place Knock out of entrained sulfur (mist, slugs) Overflow of liquid sulfur from one unit to another connected unit via connected rundowns or connected tail gas lines. Classification by equipment Another classification of the cases can be made according to the equipment involved. Condensers Plugging of the rundown will lead to flooding of the condenser with liquid sulfur, starting in the outlet channels and the lower tubes. But also in the inlet channel liquid sulfur will accumulate. It is good engineering practice to prevent accumulation of liquid sulfur by making the bottom of the inlet channel flush with the lower condenser tubes. Most practical is to make a concrete floor in the inlet channel.
15 One might consider that accumulation of sulfur in a condenser can be detected via the pressure drop over the condenser or via the total pressure drop over the SRU. This method is not straightforward because there may be several other causes for an increase in pressure drop, besides flooding of tubes (such as fouled demister, increased throughput etc.). Furthermore it has been found that sometimes hardly any increase in pressure drop is noticed. Even if the sulfur rundown is completely blocked and the condenser is filling up, this will not become noticeable because a considerable percentage of tubes has to be blocked for this. Also liquid sulfur appears to be easily entrained with the gas to the next. One could consider to install a thermocouple with alarm in the inlet channel of the condenser, measuring the temperature just above the concrete layer at the bottom of the inlet channel. In case liquid sulfur is present a lower temperature will be measured, so checking the temperature behavior might help making sure there is no accumulation. Demister pads Demisters are often applied in condensers and coalescers. Demisters consist of a large area of thin stainless steel wires Over time, pads may collect sulfur that combines with dust and turns into a form of sulfur concrete. In this state it will stay in the pad and can lead to a fire when favored by the other conditions (air, ignition). Such a fire is enhanced by the large surface area in the pad. This is one of the explanations for mysteriously disappearing demister pads. Reheaters Several cases of fire in reheater inlet lines have been seen. In all these cases, entrained sulfur from an upstream condenser was carried with the process gas over to the reheater, where the mist was knocked out and collected in the inlet line. In some cases sulfur could not drain because of a wrong slope. Also the sliding strips or baffles in the reheater shell may prevent proper draining of sulfur, so proper draining holes should be designed. Coalescers Although coalescers are designed to collect sulfur, the outlets can easily become plugged since the nominal sulfur flow coming from a coalescer is so small. Despite enlarged jacketing at the bottom of the coalescer, we have seen quite some cases of unexpectedly filled coalescers.
16 Recommended operational procedure Flush test To detect partial plugging of rundown lines, locks and funnels the flush test is an excellent tool. It is recommend to do this test preferably every shift but at least every day. If this procedure is carried out consistently a partial sulfur blockage will be detected in an early, so that no liquid sulfur build-up can take place. Also by this procedure partial plugging may be flushed out before it completely blocks the line. The test is done by closing the run down line and let a head of sulfur build up. On reopening, the operator observes the flow of sulfur in the look box (or sight glass) and a large flow of sulfur should be seen. If the sulfur is only flowing as normal then there is a partial plugging. In such a case the flush test is repeated with the waiting time doubled, before reopening. This may help clean the condenser run-down line by flushing with a large flow. When this is not successful, the partial blockage is removed by rodding or by steam pressure. Nowadays looking glasses have become in use more widely instead of the open look boxes. The gush of flowing sulfur can also be seen with properly dimensioned looking glasses, since during normal operation the flow only partly fills the glass. It may take some experience to judge the relative increase in flow based on the time that the glass stays filled. Test details The flush test has to be carried out for each separate sulfur run-down line, one after the other. The test is done from back to front, so it starts with the coalescer. The hand valve in the coalescer rundown is closed for two hours, as the sulfur production of this lock is marginal. In case the coalescer and the last condenser have a common lock, the condenser run down valve should be closed after 1.5 hours, and waited for 30 minutes to proceed. Then the coalescer rundown is opened and it is checked whether sulfur is flowing. If there is no flow or a small flow, the procedure is repeated with an interval of 4 hours. In the mean time all steam traps of this rundown line should be checked to confirm that the heating is functioning. When no sulfur is running the run down line should be unplugged. Next the last condenser is checked. After 10 minutes the line is opened and a gush of sulfur should be seen. The procedure is repeated for the other locks. For the third sulfur condenser a time of 10 minutes is advised, for the second condenser 5 minutes and the same for the first condenser, for units with a capacity of 100 t/d and more. For smaller units the times can be increased in ratio to the sulfur production capacity.
17 The time to close the valve depends on the expected sulfur production in the vessel (condenser/coalescer) and is summarized in the following table. To prevent cold sections of steam jacketing, check at regular intervals with a lump of solid sulfur whether the steam traps are so hot that the solid sulfur is melting. Thermal First catalytic Second catalytic Third catalytic SUPERCLAUS Coalescer 3 Claus 2 Claus 5 minutes 5 minutes 10 minutes 10 minutes 10 minutes 2 hours 5 minutes 5 minutes 10 minutes - 10 minutes 2 hours Cleaning sulfur boots One of the reasons for a (partial) plugging could be the accumulation of solids (sulfur concrete, catalyst particles, scaling) in the sulfur boot at the outlet of the sulfur condenser. The sulfur boots should be checked to see if they are clean, this should be done more frequently after initial start-up and on a regular basis later on. These boots protect the locks from plugging with solids. When the boot is full with solids the dirt will end up in the bottom of the sulfur lock and the lock has to be cleaned also, which is a far more extensive operation. When there are indications that a sulfur rundown line is blocked, the blockage may be cleared by rodding. To enable rodding the sulfur run-down line is provided with crosses. Alternatively LP steam can be connected to the top of the sulfur seal, first with the upstream rundown valve open. The steam should flow back to the vessel and small vibrations should be noticeable from the steam bubbling through the sulfur filled line. When the upstream line has been cleared the upstream valve can be closed to do a new flush test to check the line is free of restrictions. Lessons learned Reviewing the cases that have been presented we can draw up some guidelines to prevent accumulation of sulfur. Expect sulfur to accumulate in every vessel, including reheaters. This should be taken into account when designing and sloping the lines. Design equipment such that sulfur cannot accumulate and is always freely draining away from the equipment. Keep every part of an installation hot, even when that part is not actually in operation, to prevent condensation and solidification at cold spots. Identify overloading by looking at the total sulfur quantity being produced, so consider not only the acid gas feed rate but also the H 2 S content.
18 Use the flush test to detect sulfur accumulation in condensers and coalescer. Always maintain a positive purge flow over the SUPERCLAUS in bypass to prevent diffusion. Carefully check during such operation for any deviation in temperature in the SUPERCLAUS. Conclusion Unintentional accumulation of sulfur occurs frequently and in hindsight can almost always be explained. As with other conditions that may arise in an SRU, accumulation in itself is only harmful when other conditions are met simultaneously.
Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard
Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Introduction SRU s (Sulfur Recovery Units) are critical pieces of equipment in refineries and gas plants. SRUs remove sulfur compounds from certain
STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE
Page 1 of 9 PURPOSE Steam is the most commonly used heating medium for maintaining process temperatures. Compared to other heating media, steam contains a significant amount of heat energy, and this heat
The Single Absorption Scrubbing Sulfuric Acid Process
The Single Absorption Scrubbing Sulfuric Acid Process Leonard J. Friedman, Samantha J. Friedman Acid Engineering & Consulting, Inc. 17770 Deauville Lane, 33496, USA [email protected] Keywords: Sulfuric
Energy Efficient Operations and Maintenance Strategies for Boilers
Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must
Routine and Emergency Boiler Operation
Routine and Emergency Boiler Operation Learning Outcome When you complete this module you will be able to: Describe the routine safe and efficient operation of a packaged boiler. Learning Objectives Here
Factory owners must ensure the boiler is:
Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised
Boiler Preparation, Start-Up and Shutdown
Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.
The soot and scale problems
Dr. Albrecht Kaupp Page 1 The soot and scale problems Issue Soot and scale do not only increase energy consumption but are as well a major cause of tube failure. Learning Objectives Understanding the implications
Description of Thermal Oxidizers
Description of Thermal Oxidizers NESTEC, Inc. is a full service equipment supplier specializing in solutions for plant emission problems. The benefit in working with NESTEC, Inc. is we bring 25+ years
Control Device Requirements Charts For Oil and Gas Handling and Production Facilities
Device Charts For Oil and Gas Handling and Production Facilities Purpose/Scope: The purpose of this document is to provide standardized guidance for use by the regulated community and air permit reviewers,
Gas-Fired, Residential Storage Type Water Heaters
Consulting, Resource, Education, Training, and Support Services for Home Inspectors A candle loses no light when it lights another candle. Gas-Fired, Residential Storage Type Water Heaters Most inspectors
TRIAL CHEMICAL CLEANING OF FOULED APH BASKETS
TRIAL CHEMICAL CLEANING OF FOULED APH BASKETS Dr. Abhay Kumar Sahay, AGM(CC OS) Bijay Manjul, AGM( Operation) Kahalgaon Boiler has three inputs Steam generator 1. WATER 2. COAL 3. AIR Burner Air preheater
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.
Steam Tables What They Are How to Use Them The heat quantities and temperature/ pressure relationships referred to in this Handbook are taken from the Properties of Saturated Steam table. Definitions of
C. starting positive displacement pumps with the discharge valve closed.
KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the
SULFUR RECOVERY UNIT. Thermal Oxidizer
SULFUR RECOVERY UNIT Thermal Oxidizer BURNERS FLARES INCINERATORS PARTS & SERVICE SULFUR RECOVERY UNIT Thermal Oxidizer Tail Gas Thermal Oxidizer designed and built to GOST-R requirements. Zeeco can meet
5.2. Vaporizers - Types and Usage
5.2. Vaporizers - Types and Usage 5.2.1. General Vaporizers are constructed in numerous designs and operated in many modes. Depending upon the service application the design, construction, inspection,
Heating Water by Direct Steam Injection
Heating Water by Direct Steam Injection Producing hot water by direct steam injection provides a solution where large volumes of hot water at precise temperatures are required, and where energy and space
PROCEDURES PREVENTION OF ACCIDENTAL IGNITION
Page No: 1 of 7 6.0 PURPOSE (192.751) All possible precautions shall be exercised to prevent the accidental escape and ignition of gas. Whenever possible, potential sources of ignition should be eliminated
Air Eliminators and Combination Air Eliminators Strainers
Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.
Pulverized Coal Pipe Testing and Balancing
Pulverized Coal Pipe Testing and Balancing By Richard F. (Dick) Storm, PE The first step in optimizing combustion system performance is balancing the air and fuel flowing through each of the plant's coal
Module 5: Combustion Technology. Lecture 34: Calculation of calorific value of fuels
1 P age Module 5: Combustion Technology Lecture 34: Calculation of calorific value of fuels 2 P age Keywords : Gross calorific value, Net calorific value, enthalpy change, bomb calorimeter 5.3 Calculation
CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2
WASTE HEAT BOILERS CONTENTS 1 INTRODUCTION... 3 2 CONCEPTION OF WASTE HEAT BOILERS... 4 2.1 Complex Solution...4 2.2 Kind of Heat Exchange...5 2.3 Heat Recovery Units and Their Usage...5 2.4 Materials
A Guide to Trouble-Free Cooling Towers
A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 38 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia CAUSTIC AND CHEMICAL TABLE OF CONTENT
Compressed Gas Cylinder Program
Department of Environmental Health & Safety Procedures Compressed Gas Cylinder Program March 2010 Compressed Gas Cylinder Program Page 1 of 8 Table of Contents I. Introduction II. III. IV. Policy Scope
Select the Right Relief Valve - Part 1 Saeid Rahimi
Select the Right Relief Valve - Part 1 Saeid Rahimi 8-Apr-01 Introduction Selecting a proper type of relief valve is an essential part of an overpressure protection system design. The selection process
SIBIR MANUAL V110 KE. English page 5 RKE - 1D 822 70 66-02
SIBIR MANUAL RKE - 1D V110 KE English page 5 822 70 66-02 2 1 A. Flue tube E. Adapter I. Thermostat B. Flue baffle F. Burner base J. Lever arm C. Control knob G. Lamp glass D. Fuel gauge H. Lamp glass
Steam System Efficiency. Bill Lumsden Leidos Engineering
Steam System Efficiency Bill Lumsden Leidos Engineering Steam System Efficiency Steam System Efficiency Key Take-aways: Review of the properties of ice, water, and steam Learn the basics of steam trap
Presentation Outline. Background
Introduction ENVIRONMENTAL SYSTEMS, INC. Innovative Air Pollution Control Solutions Air Pollution Abatement Technologies for the Oil and Natural Gas Processing Industries. Jeff Kudronowicz / Application
WATER WALL BOILER FOR AIR AND OXYGEN FIRED CLAUS SULPHUR RECOVERY UNITS
WATER WALL BOILER FOR AIR AND OXYGEN FIRED CLAUS SULPHUR RECOVERY UNITS Abstract Mahin RAMESHNI, P.E. Technical Director, Sulphur Technology [email protected] WorleyParsons 125 West Huntington
Optimization Design for Sulfur Dioxide Flow Monitoring Apparatus in Thermal Power Plants Hao-wei Hu 1, a, Xue Yang 1, b and Xiao-wei Song 1, c
International Conference on Information Sciences, Machinery, Materials and Energy (ICISMME 2015) Optimization Design for Sulfur Dioxide Flow Monitoring Apparatus in Thermal Power Plants Hao-wei Hu 1, a,
How To Clean Up A Reactor Water Cleanup
General Electric Systems Technology Manual Chapter 2.8 Reactor Water Cleanup System TABLE OF CONTENTS 2.8 REACTOR CLEANUP SYSTEM... 1 2.8.1 Introduction... 2 2.8.2 System Description... 2 2.8.3 Component
Torino Nord. Cogeneration Plant. The gas turbine. The steam generator. The Torino Nord cogeneration plant produces electricity and heat for district
PLANT TORINO NORD Iren Energia is the company in the Iren Group whose core businesses are the production and distribution of electricity, the production and distribution of thermal energy for district
1 DESCRIPTION OF THE APPLIANCE
1 DESCRIPTION OF THE APPLIANCE 1.1 INTRODUCTION The cast iron SF boilers are a valid solution for the present energetic problems, since they can run with solid fuels: wood and coal. These series of boilers
Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service
BP Lower 48 Onshore Operations Safety Manual Page 4.19 1 Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service I. General Requirements A. After motor vehicle accidents and underground excavation
Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves
Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves CRANE Energy Flow Solutions TM Donald H. Johnson Crane Energy Flow Solutions 1 Crane Co. Resolution Made By Richard Teller
BRAZED PLATE INSTALLATION MANUAL
www.brazedplate.com BRAZED PLATE INSTALLATION MANUAL S.E.C. Heat Exchangers P.E.I. CANADA C0A 1A0 tel; 902-659-2424 fax; 902-659-2800 Table of Contents Description...2 Mounting position...3 Piping connections......3
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
Waste Incineration Plants
Waste Incineration Plants Modern Technology for a better Environmental Welcome at Hafner! We Manufacture Systems for Energy Recovery from Wastes and Biomass as well as for Treatment of Hazardous Wastes.
Evaluating Thermal & Catalytic Oxidation Technology for VOC, HAP & Odor Abatement. John Strey
Evaluating Thermal & Catalytic Oxidation Technology for VOC, HAP & Odor Abatement John Strey Experience Installing Quality Equipment Since 1987 Over 3,000 Air Abatement Systems Installed Worldwide Unbiased
DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING
By Philip Sutter Pick Heaters, Inc. DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING INTRODUCTION Many process plants currently use steam or hot water to heat jacketed devices such as tanks,
COMBUSTION. In order to operate a heat engine we need a hot source together with a cold sink
COMBUSTION In order to operate a heat engine we need a hot source together with a cold sink Occasionally these occur together in nature eg:- geothermal sites or solar powered engines, but usually the heat
Mechanical Seal Piping Plans
Mechanical Seal Piping Plans Single Seals plans 01, 02, 03, 11, 13, 14, 21, 23, 31, 32, 41 Dual Seals plans 52, 53A, 53B, 53C, 54, 55 Quench Seals plans 62, 65A, 65B, 66A, 66B Gas Seals plans 72, 74, 75,
Operation & Maintenance Manual
Manual # OMAV2-SUMP1 High Performance Air & Dirt Separators Manual # 9636-1230 Rev. A Operation & Maintenance Manual 340 West 8 th Street Peru, IN 46970 PH: 765 472 3351 FX: 765 472 3968 www.thrushco.com
HAZARD RISK ASSESSMENT
HAZARD RISK ASSESSMENT Mt Grace Batchelor Magnesium Project A hazard risk assessment was undertaken to identify and assess the consequences of unplanned incidents that may pose safety, environmental risks,
Nitrogen Blanketing for Methanol Storage and Transportation
Nitrogen Blanketing for Methanol Storage and Transportation Overview Air is the enemy of many materials. Not only can oxygen cause safety concerns and product degradation, but moisture, dirt, hydrocarbons
Combustion Pulsation and Noise by Dan Banks, P.E., Banks Engineering Inc.
Combustion Pulsation and Noise by Dan Banks, P.E., Banks Engineering Inc. Posted: August 1, 2007 The natural flame instability in any flare or furnace produces noise. In rare cases, the noise can be loud
Austin Peay State University Department of Chemistry CHEM 1111. Empirical Formula of a Compound
Cautions Magnesium ribbon is flammable. Nitric acid (HNO 3 ) is toxic, corrosive and contact with eyes or skin may cause severe burns. Ammonia gas (NH 3 ) is toxic and harmful. Hot ceramic crucibles and
Enhancing SRUs with oxygen-enriched air
M ost refiners have now moved toward a higher standard of s u l p h u r - r e c o v e ry efficiency to comply with clean fuels regulations that impose a reduction of sulphur in refined products. While
Why use Tigerloop in fuel heating systems?
The Original Oil De-aerator Why use Tigerloop in fuel heating systems? Reliability New products are continually being developed in the modern oil heating industry in order to satisfy new laws and regulations
DURR Thermal Oxidizer Research. 4/27/2004 Intel Corporation Community Meeting
DURR Thermal Oxidizer Research History of Research A small group consisting of community members Steve Martinez and Edward Pineda along with Intel employees Peter Clugston, Heath Foott and Bill Westmoreland
HOW TO SELECT A LOW VOLUME (L.V ) BOILER
HOW TO SELECT A LOW VOLUME (L.V ) BOILER FREQUENTLY ASKED QUESTIONS OR COMMENTS ON BOILERS Dear Potential Customer: Low Volume Operator Exempt boilers have been marketed in Ontario to eliminate the requirement
No. Name Description Main input Data Main Output Data. cooling duty, process in/out temperature, inlet air temperature
1 AIRCOOLER Air cooler preliminary sizing cooling duty, process in/out temperature, inlet air temperature No of fans, Air cooler Dimension, bare area, no of rows, Fan Diameter, fan power 2 BLOW DOWN FACILITATOR
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
www.garrisonwaterheaters.com Electric & Gas Water Heaters
www.garrisonwaterheaters.com Electric & Gas Water Heaters Hot Water: Take it for Granted with Garrison According to the U.S. Department of Energy, the average American home uses 64 gallons of hot water
Filtering Samples to On-Line Process Analyzers. Guidelines for Proper Filtration and Delivery of Samples to On-Line Process Analyzers
Filtering Samples to On-Line Process Analyzers Guidelines for Proper Filtration and Delivery of Samples to On-Line Process Analyzers Filtering samples to on-line analyzers Use these guidelines to ensure
National- Spencer Inc.
9-27-2010 National- Spencer Inc. 19.2V HEAVY DUTY GREASE GUN PRODUCT SPECIFICATION Charger Input Power 110 VAC Battery Output Power 19.2V Battery Capacity 1500 MAH Battery Pack Charge Time 1 Hour Maximum
GAS HEATING IN COMMERCIAL PREMISES
ENERGY EFFICIENCY OFFICES GAS HEATING IN COMMERCIAL PREMISES www.energia.ie www.energia.ie Typically, energy reductions of 10% or more can be made easily through maintenance and low cost improvements.
Development of Coal Gasification System for Producing Chemical Synthesis Source Gas
27 Development of Coal Gasification System for Producing Chemical Synthesis Source Gas TAKAO HASHIMOTO *1 KOICHI SAKAMOTO *1 KATSUHIRO OTA *2 TAKASHI IWAHASHI *3 YUUICHIROU KITAGAWA *4 KATSUHIKO YOKOHAMA
2A.1 Features of Chiller Control Components... 104. 2A.3 Chilled-Water Supply Temperature Control... 107. 2A.4 Cooling-Water Supply Control...
Appendix 2A: Chiller Control Principles... 104 2A.1 Features of Chiller Control Components... 104 2A.2 Start-up and Shutdown... 105 2A.2.1 Start-up...105 2A.2.2 Shutdown...106 2A.3 Chilled-Water Supply
QUADRANT SR- Thermal Oxidizer Process Design & Environmental Control Benefits for the Sand Coating Industries
> 99% VOC, HAP & CO Destruction Efficiency Time, temperature and turbulence are the basic design principles required for organic pollutant control. In the QUADRANT-SR SERIES Recuperative Thermal Oxidizers,
Chemical Fume Hoods. Environmental Health and Safety 974-5084
Chemical Fume Hoods Environmental Health and Safety 974-5084 Regulatory References Prudent Practices in the Laboratory 2011 (National Research Council of The National Academies): Laboratory chemical hoods
I. STEAM GENERATION, BOILER TYPES
I. STEAM GENERATION, BOILER TYPES and BOILER PLANT SYSTEMS 1 Steam Generation Water s Unique Properties: High Thermal Capacity (Specific Heat) High Critical Temperature Ideal Medium for Heat Delivery High
Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE
Hot Water Boilers and Controls Why Condensing Boilers are Different Presented Oct. 14, 2008 Long Island Chapter, ASHRAE H.W. Boilers and Controls Major types of boilers Advantages and disadvantages Resistance
CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!
CPX/HT Series REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM High-performance products. Designed for you! COMPRESSED AIR WATER CONTAMINATION Atmospheric air contains water in vapor form in different
Section 20 TABLE OF CONTENTS Pressurized Equipment and Systems. 20.A General... 20-1. 20.B Compressed Air and Gas Systems... 20-4
Section 20 TABLE OF CONTENTS Pressurized Equipment and Systems Section: Page 20.A General... 20-1 20.B Compressed Air and Gas Systems... 20-4 20.C Boilers and Systems... 20-7 20.D Compressed Gas Cylinders...
Originators of the Flexible Water Tube design
BRYAN FLEXIBLE WATER TUBE AB SERIES STEAM AND WATER BOILER 900,000 TO 3,000,000 BTUH FORCED DRAFT GAS, OIL OR DUAL FUEL FIRED Water Boiler AB120-W-FDGO Steam Boiler AB250-S-150-FDG Originators of the Flexible
TEMA DESIGNATIONS OF HEAT EXCHANGERS REMOVABLE BUNDLE EXCHANGERS NON REMOVABLE BUNDLE EXCHANGERS SOURCE: WWW.WERMAC.ORG/
TEMA DESIGNATIONS OF HEAT EXCHANGERS Because of the number of variations in mechanical designs for front and rear heads and shells, and for commercial reasons, TEMA has designated a system of notations
AMMONIA AND UREA PRODUCTION
AMMONIA AND UREA PRODUCTION Urea (NH 2 CONH 2 ) is of great importance to the agriculture industry as a nitrogen-rich fertiliser. In Kapuni, Petrochem manufacture ammonia and then convert the majority
Haldor Topsøe Catalysing Your Business
Haldor Topsøe Catalysing Your Business Haldor Topsøe A/S Established: 1940 Ownership: Haldor Topsøe Holding A/S (100%) Annual turnover: ~ 700 MM EUR Number of employees: ~ 2,050 Offices worldwide Copenhagen
COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.
Page 1 of 5 COMPRESSED GASES A compressed gas is defined as any mixture of gases in a container with a pressure exceeding 40 psi. at 70 o F, or 104 psi. at 130 o F; or any flammable liquid with an absolute
Design Considerations for Heated Gas Fuel
g GER-4189B GE Power Systems Design Considerations for Heated Gas Fuel D.M. Erickson S.A. Day R. Doyle GE Power Systems Greenville, SC Contents Introduction..................................................................1
ENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
Heat-Pipe Heat Exchanger
Heat-Pipe Heat Exchanger Heat Pipe Heat Exchanger For air-air 1 Heat Pipe Heat Exchanger Heat exchanger, which transfers the heat from one medium to another, is the most common thermal equipment in various
If you accidentally get battery acid on your skin, flush it with lots of water
RV Battery Savvy To properly maintain and extend the life of your RV batteries you need to have a basic understanding of what a battery is and how it works. Batteries used in RVs are lead acid batteries.
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
FIRE SAFETY FOR OFFICE WORKERS
FIRE SAFETY FOR OFFICE WORKERS This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program and the subject
Energy Saving Fact Sheet Boilers
Energy Saving Fact Sheet Boilers Turn a burning issue into real energy savings You need a boiler to heat your premises and provide hot water or to generate steam for use in industrial processes. Unfortunately,
1. The Kinetic Theory of Matter states that all matter is composed of atoms and molecules that are in a constant state of constant random motion
Physical Science Period: Name: ANSWER KEY Date: Practice Test for Unit 3: Ch. 3, and some of 15 and 16: Kinetic Theory of Matter, States of matter, and and thermodynamics, and gas laws. 1. The Kinetic
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas
Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas Mark Schiffhauer, ATSI Engineering Services Cameron Veitch, Combustion and Energy Systems Scott Larsen, New York State Energy
Float and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
Coker Furnace On-Line Spalling
Coker Furnace On-Line Spalling - Safe, Clean, Proven, & Profitable By: Jack Adams, Adams Project Managers, Inc. ([email protected]) Gary C. Hughes, Bechtel Hydrocarbon Technology Solutions, Inc. ([email protected])
SIX REASONS TO DRY BIOGAS To A LOW DEWPOINT BEFORE COMBUSTION IN A CHP ENGINE STEVEN SCOTT MARKET DEVELOPMENT MANAGER ALTERNATIVE ENERGIES
SIX REASONS TO DRY BIOGAS To A LOW DEWPOINT BEFORE COMBUSTION IN A CHP ENGINE STEVEN SCOTT MARKET DEVELOPMENT MANAGER ALTERNATIVE ENERGIES Filippo Turra Product Manager Cooling Technology INTRODUCTION
Steam System Best Practices Condensate System Piping
Steam System Best Practices Condensate System Piping Summary The best method for improving steam system energy efficiency, reducing chemical costs, and reducing make-up water costs is to return the maximum
Lecture 35: Atmosphere in Furnaces
Lecture 35: Atmosphere in Furnaces Contents: Selection of atmosphere: Gases and their behavior: Prepared atmospheres Protective atmospheres applications Atmosphere volume requirements Atmosphere sensors
Flushing and Cleaning the A/C System
Flushing and Cleaning the A/C System Once an AC system has been contaminated or has suffered a failure, the most important part of the AC service to restore the cooling performance to the system = FLUSHING
Boiler & Pressure Vessel Inspection discrepancies and failures
Boiler & Pressure Vessel Inspection discrepancies and failures Water Heaters / Pressure Vessels Pressure Vessels are inspected once every three years. This requires a test of A: safety relief devices B:
In-Line Air Separators
Air Elimination & Control In-Line Air Separators The AC models of air separators deliver all the quality and performance you expect from Taco products. They are built to last with shell, heads and ANSI
Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services
Preventive Maintenance State Energy Assessment Workshop By: DTE Energy Partnership & Services Do you know? World wide research has shown that one of the reasons causing 80% of the accidents is deficient
CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
Steam Sterilization Cycles for Lab Applications
Steam Sterilization Cycles for Lab Applications Presented by Gary Butler STERIS Life Sciences August 2009 Early Steam Sterilizers Koch Upright Sterilizer First Pressurized Sterilizer First built by Pasteur-Chamberlain
FLASH TANK ECONOMIZER PRODUCT GUIDE
FLASH TANK ECONOMIZER PRODUCT GUIDE Overview A flash tank is used to recover blowdown energy in the form of flash steam and blowdown. This can only be used with a deaerator or some other pressurized device.
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem
Mechanical Seal Piping Plans
Mechanical Seal Piping Plans Companion Booklet Single Seals Dual Seals Quench Seals Second. Cont. Dual Gas Introduction A primary factor in achieving highly reliable, effective sealing performance is to
Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009
Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 By Carsten Palle, VID Fire-Fill, www.vid.eu Presented at ISTSS
On-Line Fire Extinguisher Training
On-Line Fire Extinguisher Training The USC Fire Safety Office is delighted you have chosen to take the on-line version of our fire extinguisher training. This power-point presentation will give you some
CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS
CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS BULLETIN 240-10-3 June 2004 Supersedes June 1983 Many centrifugal systems get little maintenance. As a result they operate with the refrigerant highly contaminated
EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT
EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES