FIXED GUIDEWAY TRANSIT AND PASSENGER RAIL SYSTEMS: FIRE SAFETY REQUIREMENTS
|
|
|
- Eustace Baldwin
- 9 years ago
- Views:
Transcription
1 ISRAEL STANDARD SI 5435 January 2006 ICS CODE: FIXED GUIDEWAY TRANSIT AND PASSENGER RAIL SYSTEMS: FIRE SAFETY REQUIREMENTS Translation of Israel National Deviations only The Standards Institution of Israel 42 Chaim Levanon Street, Tel-Aviv, Tel , Fax ,
2
3 SI 5435 (translation of Israel Natinal Deviations only) Notice of measure of compliance of Israeli Standards with foreign Standards or documents This Standard, excluding the Israel national deviations, is identical to the American Standard, ANSI/NFPA 130: 2000 Descriptors: fire safety, passenger transport, railway vehicles, railway equipment, fire resistance. Updating the Standard Israel Standards are reviewed periodically at least every five years, in order to adapt them to scientific and technological developments. Users of Standards should ascertain that they are in possession of the latest editions of the Standard including its Amendments. A document appearing in the Reshumot (The Israeli Official Journal) as an Amendment may be a separate Amendment, or an Amendment incorporated into the Standard. Official Standard Whether the document or parts of it are Official should be checked. An Official Standard or Amendment (in whole or in part) takes effect 60 days following publication of the notice in the Reshumot, unless the notice states otherwise for the effective date. Standards Mark A manufacturer of a product complying with the requirements of the applicable Israel Standards is entitled, after being licensed by the Standards Institution of Israel, to mark it with the Standards Mark: Copyright This Standard or any part of it may not be photocopied, copied or published by any means whatsoever, without prior permission in writing of the Standards Institution of Israel.
4
5 Introduction to the Israel Standard This Israel Standard is the American Standard ANSI/NFPA 130 from the year 2000, approved as an Israel Standard with Israel national deviations. The following are brought in the Hebrew language: - The Scope clause with Israel national deviations - Details of the Israel national deviations to the clauses of the American Standard Israel national deviations were added only in places where it was necessary to modify the requirements of the American Standard to the legal requirements, regulations, Israel Standards and the organizational system in Israel. After the Hebrew part, the American Standard is brought in the English language only. Scope (Clause 1-1 of the American Standard with Israel national deviations) This Standard covers fire safety requirements for fixed guideway transit and passenger rail systems. These are underground, surface, and elevated systems of light transit, "metro trains" and heavy passenger vehicles. The Standard is applicable to the rail guideways, the vehicles themselves vehicles and cars, stations, maintenance and storage areas and their facilities, smoke control systems, emergency communication and emergency procedures. The Standard relates to the fire safety of passengers and the employees in the stations, on the rail guideways and on the vehicles themselves. This Standard establishes minimum requirements for each of the identified subsystems. In the case of difficulty in maintaining a specific requirement given in this Standard, due to topographic or other reasons related to the physical design of the rail system, the Firefighting and Rescue Commissioner has the authority to lighten the requirement according to the specific reason and the principles of the Standard. In addition to this Standard, other Israel Standards are applicable to the safety of the rail system, such as SI 1227 Part 2, SI 5350, SI and SI Parts 1 and This Standard shall not cover requirements for the following: 1. Conventional freight systems; 2. Buses and trolley coaches; 3. Circus trains; 4. Tourist, scenic or historic operations; 5. Any other system of transportation not included in the definition of To the extent where a system, including those listed above in subclauses 1 to 5 introduces hazards of a similar nature to those addressed herein, this Standard, shall be permitted to be used as a guide. 1
6 1-1.3 Nothing in this Standard is intended to prevent the use of new methods, materials or devices, provided that sufficient technical data are submitted to the authority having jurisdiction to demonstrate that the new methods, materials and devices are equivalent to or superior to the requirements of this Standard with respect to fire resistance and safety. This use of new methods, materials or devices is conditional on meeting the requirements of Israeli laws or Israel Standards, and lacking an Israel Standard, the requirements of an International Standard, regional Standard or national standard, and approval of the authority having jurisdiction. Details of Israel national deviations to the clauses of the American Standard CHAPTER 1 - GENERAL 1-2 Purpose The clause is applicable with the following addition: Design, construction and maintenance Light transit systems, "metro" train systems and heavy passenger train systems shall be designed, constructed and maintained in such a manner that during a fire or a firerelated emergency incident, it will provide protection of the persons that are not aware of the initial development of the fire, for a period required for their egress, to transfer them to another location or to protect them on location Constructive completeness The constructive completeness of stations, structures and tunnels shall be maintained for the time period required for the egress of persons, to transfer them to another location or to protect them on location trapped in the structure, and to protect the fire-fighting and rescue services Effectiveness of the emergency systems The emergency systems shall be effective in reducing the danger or easing the situation during use. Also the systems shall be reliable and maintained at a level in which they were designed to operate and remain available for operation according to plan. 1-3 Characteristics of Fire Safety The clause is applicable with the following addition: The protection methods described in this Standard are based on the assumption that there is one fire source. 1.5 Definitions The clause is applicable with Israel national deviations noted below: 2
7 1-5.3 Authority The definition is not applicable and shall be replaced by the following: Authority - In systems established on a concession agreement where the state is a party: applicable authority, as defined in the concession agreement. - In systems not established on the said concession agreement: Ministry of Transportation or a body appointed on its behalf Authority Having Jurisdiction The following shall be added to the definition: The person authorized for this matter is the Chief Firefighting Inspector Combustible Load of a Vehicle The following shall be added to the definition: This value shall also be expressed in SI units Command Post The definition is not applicable and shall be replaced by the following: Forward Command Post The location at the emergency occurrence site where the person in command is present and contains the command, coordination, control and communication operations Effective Fire Load The following shall be added to the definition: This value shall also be expressed in SI units Fixed Guideway Transit System The following shall be added to the definition: This definition refers to light trains and "metro" trains Flame Spread Index The definition is not applicable and shall be replaced by the following: Flame Spread Index Flame spread index as defined by Israel Standard SI 755 clause (Fire spread test). Note: This test is applicable also to other materials, in addition to construction materials Guideway After the words "underground tunnels", add the words, "and stations". 3
8 Listed The definition is not applicable and shall be replaced by the following: Listed A. Equipment, components and services included in the list approved by an approved laboratory (A) and complying with the applicable Israel Standards; or B. Equipment, components and services included in the list approved by an approved laboratory and approved by UL (B) or FM (C) laboratories as complying for use according to NFPA Standards, or approved by other national laboratories; or C. Equipment, components and services included in the list approved by an approved laboratory and equivalent to those approved as given in subclause B, and also approved by the authority having jurisdiction Noncombustible The definition is not applicable and shall be replaced by the following: Noncombustible Construction material classified as VI.4.4 in accordance with Israel Standard SI Passenger Rail System The following shall be added to the definition: This definition refers to a heavy passenger train Point of Safety The definition is applicable with the following modifications: - The words, "An enclosed" to "outside the structure" are not applicable and shall be replaced by the following: A safe outlet path as defined in the clause of definitions of the Design and Construction Regulations (request for license, conditions and fees) Add the following after the word, "passengers": such as the second tunnel in a system consisting of two tunnels, separated from the point of fire and smoke Specific Optical Density The definition is not applicable and shall be replaced by the following: Smoke density The smoke density for construction materials determined in accordance with Israel Standard SI 755, clause 2.4 (Smoke density). For all other materials, the optical density (A) (B) (C) The Standards Institution of Israel or anyone approved by the Director of Standardization in accordance with Clause 12(a) of the Standards Law 1953, to test equipment, components and services for compliance with the requirements of the Standard and to issue a test certificate accordingly. Underwriters Laboratories. Factory Mutual. 4
9 is the density determined according to the American Society for Testing and Materials document ASTM E Station, Open The definition is not applicable and shall be replaced by the following: Station, Open A station that at least 50% of the ceiling or wall is open, or that the open area in the ceiling or wall is less but it has been shown by an engineering analysis, as defined in clause that the dispersion of smoke is effective and that the bottom smoke layer does not sink below a height of 2.2 m from the highest floor level where people are found, for ten minutes Tenable Environment The definition is not applicable and shall be replaced by the following: Tenable Environment An environment that permits self rescue of persons during a specific time period. - The following new definitions shall be added after definition : The English term, "shall" A term in the American Standard that indicates a mandatory requirement The English term, "should" A term in the American Standard that indicates a recommendation or proposal but not a requirement Mean release rate of heat Mean release of heat per unit area for a time period beginning from ignition and ending 180 seconds afterwards, as measured (in kw/m²) in accordance with NFPA 271 or ASTM E Entering persons load Number of passengers boarding the train from the platform Exiting persons load Number of passengers alighting from the train to the platform Rate of smoke release The rate of smoke release in a fire occurrence, as a function of time (m²/s) Time interval between trains Time interval between the arrival of successive trains to the platform at the station Connecting persons load Number of passengers traveling on the train between two stations Non-mechanical emergency ventilation system System of smoke collectors, smoke openings or/and smoke shelves, designed to respond to the environmental criteria without the use of bellows. 5
10 Train car A unit of vehicle compartments (three at most) constituting one unit. Chapter 2 Stations 2-1 General The clause is applicable with the following addition: Application The following shall be added to the clause: This chapter is also applicable to stations for heavy passenger trains. 2-2 Construction The clause is applicable with the following Israel national deviations: Construction Materials The clause is not applicable and shall be replaced by the following: Construction Materials Construction materials of bearing elements of the station shall be noncombustible (type VI.4.4), as defined in Israel Standard SI 755. Other building materials shall meet the appropriate requirements specified in Israel Standard SI 921, Part 6. Fire resistance according to the criteria of stability, as defined in Israel Standard SI 931, Part 1.1, of bearing elements of an enclosed station (D) adjacent to the train guideways up to a distance of 5 m from the edge of the adjacent guideway, shall be at least 90 minutes. Fire resistance according to the criteria of stability of all the bearing elements in the ancillary spaces shall be as required below in clause Fire resistance according to the criteria of stability of all the other bearing elements of an enclosed station shall be at least 60 minutes, for enclosed stations (D), unless they support a construction element above, having a higher requirement. In this case, their fire resistance shall be at least as the upper elements Safeguards During Construction The reference to NFPA 241 is not applicable and shall be replaced by: Work Safety Order. Where relevant requirements by law are lacking, the requirements of the American document NFPA 241 shall be applicable. (D) Enclosed station see definition
11 Ancillary Spaces The clause is not applicable and shall be replaced by the following: Ancillary Spaces Fire resistance of separation elements and the envelope of service spaces according to the criteria of completeness and insulation capacity, as defined in Israel Standard SI 931, Part 1.1 shall be as follows (E) : A. Transformer and switching stations: a fire separation of 180 minutes from any space whatsoever; B. Electrical control rooms, electrical rooms, battery rooms, trash rooms, train control rooms and accompanying battery rooms: a fire separation of 120 minutes from any space whatsoever; C. Public spaces: a fire separation of 120 minutes from non-public spaces Doors and Openings The words, "shall be protected" to the end of the clause are not applicable and shall be replaced by the following: shall be protected by fire doors classified as 1.5/1.5/0.5 as defined in Israel Standard SI 1212, excluding the transformer and switching stations that shall be protected by fire doors classified as 3/3/0.5 as defined in Israel Standard SI Fire Separation The last sentence, beginning with, "The fire separation for" is not applicable Openings The reference to NFPA 80 is not applicable and shall be replaced by: SI 1212 Fire doors: Fire resistance - After clause , the following clause shall be added: Platform end doors Separation of the platform at stations from the guideways by horizontal sliding doors (PED) are permitted if the following conditions are met: A. The doors permit emergency egress from the train to the platform without any connection to the stopping location of the train. B. The doors permit egress when the force applied to them from the train does not exceed 222 N. C. The doors are designed to withstand positive and negative pressures caused by passing trains. (E) The designer shall calculate the required fire resistance in order to check if a higher fire resistance than that required by the clause, is needed. 7
12 2-4 Wiring Requirements The clause is applicable with the following modifications: The reference to NFPA 70 is not applicable and shall be replaced by: Israel Electricity Law with its regulations and relevant Israel Standards. If relevant Israel Standards are lacking, the requirements of relevant European Standards shall apply The reference to NFPA 70 is not applicable and shall be replaced by: Israel Electricity Law with its regulations and relevant Israel Standards. If relevant Israel Standards are lacking, the requirements of relevant European Standards shall apply The reference to NFPA 70 is not applicable and shall be replaced by: Israel Electricity Law with its regulations and relevant Israel Standards. If relevant Israel Standards are lacking, the requirements of relevant European Standards shall apply The reference to IEEE 383 is not applicable and shall be replaced by: Israel Standard SI 1739, Part Means of Egress The clause is applicable with the following Israel national deviations: General The reference to NFPA 101 is not applicable and shall be replaced by: Design and Construction Regulations (request for license, conditions and fees) Occupant Load The words, "exit lanes" in the line before the last is not applicable and shall be replaced by the words: egress lanes The reference to NFPA 101 is not applicable and shall be replaced by: Design and Construction Regulations (request for license, conditions and fees) Number and Capacity of Exits Exit Lanes, Doors and Gates Stairs, Stopped Escalators, and Ramps of Over 4 Percent Slope The following shall be added to the clause: Measurement of the width of escalators shall be between the center of the handrails on both sides. The width of the surface and the angle of the escalators shall comply with the requirements of the Design and Construction Regulations (request for license, conditions and fees) for escalators Doors and Gates The following shall be added to the clause: The width of the minimum light opening of the door shall be 900 mm. 8
13 2-6 Emergency Lighting The clause is applicable with the following Israel national deviations: A. The reference to NFPA 101 is not applicable and shall be replaced by: Design and Construction Regulations (request for license, conditions and fees), the second addition, for lighting orientation, and Israel Standard SI 20, Part B. The following shall be added to the clause: The signs and symbols shall be in accordance with the Design and Construction Regulations (request for license, conditions and fees), the second addition. Where relevant requirements are lacking, the signs and symbols shall be in accordance with NFPA Fire Protection The clause is applicable with the following Israel national deviations: Protective Signaling Systems The reference to NFPA 72 is not applicable and shall be replaced by: SI 1220, all parts. Where relevant definitions or requirements are lacking in the Israel Standard, the definitions and requirements in the American document, NFPA 72, shall apply The clause is not applicable and shall be replaced by the following: In service areas, including spaces between ceilings, automatic fire and smoke detectors shall be installed that meet the requirements of Israel Standard SI 1220, all parts. Where relevant definitions or requirements are lacking in the Israel Standard, the definitions and requirements in the American document, NFPA 72, shall apply Emergency Communication The clause is not applicable and shall be replaced by the following: A public address system and emergency voice alarm devices, such as emergency telephones complying with the American document, NFPA 72, and local (interior) fire alarm push buttons are required to be installed in stations Automatic Sprinkler Systems The following shall be added to the clause: An automatic sprinkler system shall also be installed in walkways for the public in enclosed stations The clause is not applicable and shall be replaced by the following: Installation of the sprinkler systems shall be in accordance with Israel Standard SI The following shall be added to the clause: The alternative systems in places such as electrical rooms, communication rooms and control rooms may be gas extinguishing systems ("clean systems"). 9
14 2-7.4 Standpipe and Hose Systems The clause is not applicable and shall be replaced by the following: Near every entrance to an underground station, a hydrant shall be installed with a 4" standpipe with a 3" diameter double extinguishing tap (having a split head) that complies with the requirements of Israel Standard SI 448. Within the station firefighting stands shall be installed with a maximum spacing of 50 m between them. The stands shall include a 2" diameter firefighting tap in accordance with Israel Standard SI 448, a reel for firefighting in accordance with Israel Specification, SII 308, two 15 m long hoses complying with Israel Standard SI 365 and a branch. Installation of the hydrants shall be in accordance with Israel Standard SI The water pressure in the line shall not be less than 2 bars and not greater than 7 bars. The minimum water flow to the 3" extinguishing tap shall be 400 l/min, and 250 l/min. to the 2" extinguishing tap. The fire extinguishing piping shall be designed to supply an overall water flow of 1300 l/min. at a dynamic pressure of not less than 2 bars The clause is not applicable The dimension, "100 ft (30.5 m)" is not applicable and shall be replaced by 50 ft (15 m) Portable Fire Extinguishers The clause is not applicable and shall be replaced by the following: Portable Fire Extinguishers The number, size, type and location of portable fire extinguishers shall be as required by Israel Standard SI 129, Part 2. - After clause 2-7.5, a new clause shall be added as follows: 2.8 Rescue Means A lift shall be installed in accordance with the requirements of the Equal Rights Law for Persons with Disabilities, 1999 and the Equal Rights Regulations for Persons with Disabilities (arranging accessibility for public transportation services), The lift shall meet the requirements given in Israel Standard SI 5350, clause 5.19 (Lifts Basic requirements). Chapter 3 Trainways 3-1 General The clause is applicable with the following Israel national deviations: 10
15 3-1.1 The following shall be added to the clause: This chapter is also applicable to heavy passenger trainways. 11
16 3-1.3 Warning Signs The last sentence, beginning with the words, "The warning signs" is not applicable and shall be replaced by the following: The warning signs shall clearly state the hazard (e.g. "Danger, high voltage 1500 volts") and shall be in accordance with Israel Standard SI 659 and Israel Standard SI 3864, Part 1 (F) Emergency Telephone The words, from "and at other locations" are not applicable and shall be replaced by the following: An emergency telephone (firemen's telephone) shall be installed also next to each passage between tunnels, next to each egress exit and next to every other fire stand. The telephone shall meet the requirements in the American document, NFPA Underground (Subways) The clause is applicable with the following Israel national deviations: Construction Materials and The text in these clause is not applicable and shall be replaced by the following: According to the performance technology and its components, the construction materials of bearing elements, perimeter walls and lining components shall be of the "noncombustible" type (VI.4.4) as defined in Israel Standard SI 755. The fire resistance of bearing elements shall not be less than 90 minutes Underwater tubes The clause is not applicable and shall be replaced by the following: Underwater tube Underwater tubes shall be of the "noncombustible" type (VI.4.4). The fire resistance of the tubes shall not be less than 90 minutes The following shall be added to the clause: Connections of combustible materials shall be at least of type V.0 in accordance with the American Standard, UL 94. When using continuous material for anchoring or rail insulating, it shall be of type IV.3.2 or better in accordance with Israel Standard SI The clause is not applicable and shall be replaced by the following: (F) SI 3864 Part 1 is in preparation. Until its publication, the requirements shall be as specified in The Standards Institution of Israel Specification, SII
17 Fire resistance according to the stability criteria, as defined in Israel Standard SI 931, Part 1.1 of bearing elements of egress shafts and ventilation system shafts shall be at least 180 minutes Wiring Requirements The reference to NFPA 70 is not applicable and shall be replaced by: Israel Electricity Law with its regulations and relevant Israel Standards. If relevant Israel Standards are lacking, the requirements of relevant European Standards shall apply The reference to NFPA 70 is not applicable and shall be replaced by: Israel Electricity Law with its regulations The reference to Article 310 of NFPA 70 is not applicable and shall be replaced by: Israel Electricity Law with its regulations and relevant Israel Standards. If relevant Israel Standards are lacking, the requirements of relevant European Standards shall apply The reference to IEEE 383 is not applicable and shall be replaced by: Israel Standard SI 1739, Part The following shall be added to the clause: Alternatively, the wiring for emergency lighting and emergency signs shall be fireproof and shall be placed within piping, resistant to a temperature of 500 C without embedment of the piping in concrete Emergency Exit Details The clause is not applicable and shall be replaced by the following: In a unified (G) tunnel (two rails in the tunnel) the egress openings to a safe outlet path shall be one of the following alternatives: A. Openings on each side of the tunnel where the distance between any two openings on the same side does not exceed 380 m. When there is a proven limitation, presented and approved by the Firefighting Authority, such as lack of room due to structures, topographic problems and road rights, openings shall be installed on one side only provided that flat walking surfaces, at the rail height (so that the rails are embedded in the surface) without obstacles and protrusions. The walking surfaces shall be at intervals of up to 95 m and 5 m wide between egress lanes. B. Openings on each side of the tunnel where the distance (measured along the tunnel) between any two openings on any side does not exceed 380 m and provided that between the egress lanes there is a flat uniform surface at the rail height (so that the (G) or unitised or integrated. 13
18 rails are embedded in the surface), without obstacles and protrusions through the whole width between the egress lanes and through the whole tunnel length. Stairways shall be designed in accordance with the Design and Construction Regulations for the sheltered stairways. The stairway shall lead directly outdoors. A stretcher lift shall be installed, backed-up with an emergency generator, if at least one of the following conditions exist: A. The difference in levels between the lowest step to the highest step in the sheltered stairway exceeds 20 m; B. The difference in levels between the lowest step to the highest step in the sheltered stairway exceeds 15 m and the tunnel length is greater than 760 m Subclause (1): A. The following shall be added to the clause: In cross sheltered cross passageways, air shall be supplied by over-pressure to prevent the entrance of smoke. The design shall be based on Israel Standard SI 1001 Part 2.2. The minimum velocity of air flow from the sheltered cross passageway to the tunnel where an emergency incident has occurred, where the doors between them are open, shall be one m/s. B. The value "800 ft (244 m)" is not applicable and shall be replaced by 250 m Doors The following shall be added to the clause: The hardware installed shall be identical to the hardware tested together with the door in the required fire resistance test and complied with the requirement. The doors in cross sheltered passageways may be sliding doors, provided that they are also smoke and fire doors complying with the requirements of Israel Standard SI Exit hatches The clause is not applicable and shall be replaced by the following: Exit hatches Exit openings may exist in the egress paths only if the following conditions are met: A. The hatches are equipped with a manual handle that can be easily opened from the side of egress. B. The hatches can be opened by not more than one opening operation. C. The force required to open the hatch, applied to the opening unit shall not exceed 133 N. D. The hatch shall be equipped with a handle that automatically holds the latch open to preclude accidental closure Hatches shall be capable of being opened from the outside in a manner that allows access by authorized personnel only. 14
19 Emergency exits with hatches shall be identified from outside by a marking and sign warning against their obstruction. All the openings shall be protected in a manner that prevents vehicle parking or other means above it, and shall allow free opening of the latches and free exit from these openings. 15
20 Emergency Lighting The following shall be added to the clause: All the signs for cases of emergency shall be written in accordance with the instructions in clause After clause , the following new clause shall be added: Directional signs Tunnels longer than 60 m shall be equipped with directional signs directing to the exit Signs shall be installed at maximum spacing of 25 m from each other on both sides of the underground or closed rails that direct to the station or exit Every directional sign, including that lit by emergency lighting, shall be written in Hebrew, with the addition of a symbol (pictogram). The sign, text and symbol shall be in accordance with the Design and Construction Regulations, second addition, and lacking relevant requirements, the sign, text and symbol shall be in accordance with NFPA 101. See Annex A for an example of a marking for the exit opening Exit openings from tunnels shall be marked by illuminated lit signs Special Directional Signs In tunnels requiring a smoke control system, directional means shall be installed showing the direction of egress required during an emergency event. The control of the egress direction by directional means shall be from the Control Center. The default shall be in the direction opposite to the smoke release flow. The directional means shall include visual devices installed in the tunnels Traction Power Traction Power Contact Rail Protection The reference to NFPA 255 is not applicable and shall be replaced by: Israel Standard SI 755. The flame spread rating shall be at least V The reference to IEEE 383 is not applicable and shall be replaced by: Israel Standard SI 1739, Part 3, clause 2.5 (Flame Tests) Traction Power Overhead Contact System Protection The clause is applicable with the following modification: The reference to IEEE 383 is not applicable and shall be replaced by: Israel Standard SI 1739, Part 3, clause 2.5 (Flame Tests) Egress for Passengers The following shall be added to the beginning of the clause: If the width of the egress lane at the walking surface height is less than 90 cm, the 16
21 evacuation of persons with mobility disabilities shall be, if necessary, with rescue chairs as specified in Israel Standard SI After clause , the following clause shall be added: Width of Egress Lane in Tunnels Double Tunnels - In double tunnels (one track in the tunnel), there shall be an egress pathway whose net width is at least 1.10 m, on the side nearest the parallel tunnel measured from the egress walkway surface, up to a height of 2.10 m above the egress walkway surface, without obstacles and protrusions. - Alternatively, there shall be egress pathways on both sided of the tunnel. Each pathway shall have at least 70 cm net width, measured from the egress walkway surface, up to a height of 2.10 m above the egress walkway surface, and at least a net width of 80 cm measured at a height of 1.42 m above the egress walkway. Also, there shall be access pathways for firemen on both sides of the tunnel, between the rail lines and the egress walking surface. The access pathways shall be flat, at the track pavement level, without obstacles along the whole tunnel, and a net width of at least 70 cm, measured on the track bed between the rail base and the walking surface. In addition to that, there shall be crosspassages between the two egress walkways, opposite the exits to corridors connecting parallel tunnels, as defined in clause Between the crosspassages and the egress walkways, there shall be a connection by sloped surfaces, whose incline does not exceed 8 %, as required in Chapter H of the Design and Construction Regulations (request for license, conditions and fees). The threshold of the egress walkway near the track bed shall be marked with an emitting light along its whole length. - Alternatively, another solution can be given provided that it is approved by the Firefighting Authority Unified (G) Tunnels In unified tunnels (two tracks in a tunnel), there shall be an egress pathway on both sides of the tunnel. The pathway net width shall be at least 1.10 m, measured from the egress walkway surface, up to a height of 2.10 m above the egress walkway surface, without obstacles and protrusions Protection Automatic Fire Protection The following shall be added to the clause: Along the whole tunnel trainway where a smoke removable system is required, detectors shall be installed of the heat detector type or camera detectors in a closed 17
22 circuit that meet the requirements of NFPA 72. All the detectors shall transmit notices to the central supervising station of the train and to the Firefighting authority in whose jurisdiction the event occurred. Calibration of the detection systems shall meet the requirements of all parts of Israel Standard SI Lacking any specific requirements in all parts of Israel Standard SI 1220, the requirements in the American document, NFPA 72 shall apply Standpipe and Hose Systems The clause is not applicable and shall be replaced by the following: Hydrant Systems Hydrant systems shall be installed in all the underground or original trainways, as follows: A hydrant on a 4" diameter standpipe with a double 3" diameter fire tap, complying with the requirements of all parts of Israel Standard SI 448 shall be installed every 90 m, at most, with threaded couplings that comply with the requirements of Israel Standard SI 449, and next to them a cabinet, each containing 15 m long hoses complying with the requirements of Israel Standard SI 365, one multi-use branch and a 12 kg powder extinguisher complying with the requirements of Israel Standard SI 570 Part 1. The number of hoses shall be determined according to the distance between hydrants, divided by 30 and rounded upwards. Alternatively, in place of an extinguisher, fire extinguishing reels shall be installed whose length matches the distance between hydrants, that are permanently connected to the water system. The water feed line shall be at least 4" in diameter. The water pressure in the line shall not be less than 2 bars and not more than 7 bars. Installation of the hydrants shall be in accordance with Israel Standard SI The minimum water flow to the 3" extinguisher tap shall be 400 l/min and 250 l/min to a 2" extinguisher tap. The fire extinguishing piping shall be designed to supply a total water flow rate of 2000 l/min at a dynamic pressure that is not less than 2 bars The clause is not applicable and shall be replaced by the following: For tunnels longer than 120 m, hydrant systems shall be installed The following shall be added to the clause: For 4" diameter piping, the water pressure shall not be less than 2 bars and not more than 7 bars and the minimum water rate shall be as follows: For a 3" extinguisher tap 400 l/min; For a 2" extinguisher tap 250 l/min The last sentence, beginning "Exposed tunnel" to the end of the clause is not applicable and shall be replaced by the following: 18
23 The piping along the tunnels shall be painted red. The fire taps shall be marked with red-white light reflecting paint Standpipe Installations in Tunnels under Construction The clause is not applicable and shall be replaced by the following: A permanent hydrant system containing a hydrant on a 4" diameter standpipe with a double 3" diameter fire tap, complying with the requirements of all parts of Israel Standard SI 448 shall be installed every 60 m, with threaded couplings that comply with the requirements of Israel Standard SI 449, and next to them a cabinet, each containing 15 m long hoses complying with the requirements of Israel Standard SI 365, one multi-use branch and a 12 kg dry powder extinguisher complying with the requirements of Israel Standard SI 570 Part 1. The number of hoses shall be determined according to the distance between hydrants, divided by 30 and rounded upwards.. The water feed line shall be at least 4" in diameter. The water pressure in the line shall not be less than 2 bars and not more than 7 bars. Installation of the hydrants shall be in accordance with Israel Standard SI The minimum water flow to a 3" extinguisher tap shall be 400 l/min and 250 l/min to a 2" extinguisher tap. The fire extinguishing piping shall be designed to supply a total water rate of 2000 l/min at a dynamic pressure that is not less than 2 bars The requirement for a hydrant with a 2½" diameter extinguisher tap is not applicable and shall be replaced by the following: A hydrant with a 3" diameter extinguisher tap in compliance with all parts of Israel Standard SI The following shall be added to the clause: The discharge line shall be equipped with threaded couplings for fire extinguishing equipment in accordance with Israel Standard SI 449 and a closing cover Portable Fire Extinguishers The clause is not applicable and shall be replaced by the following: Portable Fire Extinguishers Portable fire extinguishers shall be provided in such numbers, sizes and types and at such locations in tunnels as determined in accordance with Israel Standard SI 129 Part 2. - After clause , the following new clause shall be added: Protection of Metal Piping The protection of metal piping shall be in accordance with that required in Israel Standard SI 5350, clause 5.14 (Protection of metal piping). 19
24 3-2.8 Flammable and Combustible Liquids Intrusion Median and Sidewalk Terminations The dimension "6 in. (152.4 mm)" is not applicable and shall be replaced by: 150 mm Aboveground Atmospheric Storage Tanks The words, "Class I flammable liquid or Class II or Class III combustible liquids" are not applicable and shall be replaced by: all containers containing ignitable or flammable materials Underground Storage Tanks The words, "Class I flammable liquid or Class II or Class III combustible liquids" are not applicable and shall be replaced by: all containers containing ignitable or flammable materials The following shall be added to the clause: The containers buried in the ground and their piping shall comply with the requirements of Israel Standard SI 4571 Part Service Stations A. The dimension "6 in. (152.4 mm)" is not applicable and shall be replaced by: 150 mm. B. The words, "from adjacent subway property" are not applicable and shall be replaced by: from tunnel ventilation gratings or from tunnel entrances or exits Existing Storage Tanks in or under Buildings The following shall be added to the clause: The text in this clause is also applicable to Class C fuel defined in the Business License Regulations (petroleum storage), 1976, for the storage of 2,200 or more liters The following shall be added to the clause: The text in this clause is only applicable to Class C fuel defined in the Business License Regulations (petroleum storage), 1976, for the storage of less than 2,200 liters The words, "tanks shall be UL-listed double wall" are not applicable and shall be replaced by: the tanks shall comply with the requirements of Israel Standard SI 4571 Part Surface The clause is applicable with the following Israel national deviations: Construction Materials The clause is not applicable and shall be replaced by the following: Construction Materials 20
25 All construction materials and construction products, including acoustic walls up to a distance of 10 m from the edge of the track, shall be "noncombustible" (VI.4.4). Acoustic walls or continuous fences greater than 10 m distance shall be at least type V.3.3 as defined in Israel Standard SI Electrical Wiring and Cable Requirements The reference to NFPA 70 is not applicable and shall be replaced by the following: The Israel Electricity Law with its regulations and the relevant Israel Standards. Lacking relevant Israel Standards, the requirements of relevant European Standards shall apply Emergency Access The clause is not applicable and shall be replaced by the following: A lane shall be provided between every two stations to allow the travel of a fire and rescue vehicle through the whole length of the track route. It shall be at least 4 m wide. The height without obstacles shall be at least 4.70 m for the complete length and width of travel path. The height can be lowered to 4.20 m under structures (such as bridges) and near the entrance and exit from them. Access points shall be provided for a fire and rescue vehicle from the regional road system to this lane, at distances not greater than 3 km. for the length of the route. Where the distance between two stations does not exceed 3 km, one access point is sufficient and it shall be widened to allow maneuvering and return of the fire vehicle at each end of the access lane. Where the rail strip is fenced in and the access lane along the route is between the fenced region, the access to the lane shall be through a gate or a free opening in the fence, at least 4.5 m wide and at least 4.2 m free height. Alternatively, or in sections along the route, where there is no such lane, access shall be provided for firemen to the rail route, such that the maximum walking distance from the access opening for the entrance of firemen to the farthest point in the rail route, accessible through this opening, does not exceed 190 m. The net width of the opening, including the gate, if installed, shall not be less than 1.6 m. Such an access gate shall be located so that the fire and rescue vehicle can approach it from the regular road system. Alternatively, the accessibility of fire and rescue forces shall be possible by specific equipment in accordance with the requirements of the Fire authority, that can travel on the rail. This equipment shall be supplied by the rail operator. Alternatively, the accessibility of fire and rescue forces shall be possible in a manner that an emergency vehicle can travel on the track bed, and enables it to maneuver at each end of the access lane. 21
26 The following shall be added to the clause: All the signs shall be in Hebrew. 3-4 Elevated The clause is applicable with the following Israel national deviations: Construction Materials The clause is not applicable and shall be replaced by the following: Construction Materials The construction materials of all elements supporting the system and sustaining its operation shall be of the "noncombustible" type (VI.4.4) in accordance with Israel Standard SI Traction Power The following shall be added to the clause: For protection of the subject structure against corrosion resulting from electric current on the conductor strip of the train, the requirements of Israel Standards SI 1227 (H) Part 2 and SI Part 2 shall be fulfilled Electric Wire and Cable Requirements The reference to NFPA 70 is not applicable and shall be replaced by the following: The Israel Electricity Law with its regulations Emergency Access A. The value "2500 ft (762 m)" is not applicable and shall be replaced by the following: 1250 ft (380 m). B. The following shall be added to the clause: If there are bridges or embankments higher than 30 m above the access roadway: 1. Access shall be possible in a manner that an emergency vehicle can travel on the track bed. 2. Along the track, a 3" diameter fire tap in accordance with all parts of Israel Standard SI 448 shall be installed every 90 m. The water feed line shall be at least 4" in diameter. The line water pressure shall not be less than 2 bars and not greater than 7 bars. The minimum water flow to a single 3" fire tap shall be 400 l/min. 3. Where there are two separate bridges, there shall be escape bridges permitting foot access for the firemen, at intervals not exceeding 760 m from each other Egress for Passengers The last sentence is not applicable and shall be replaced by the following: (H) This Standard is being revised. The subject of protection against corrosion resulting from electric current on the conductor strip will be dealt with in the new standard. 22
27 Egress points shall be lit by emergency lighting. If the egress pathway at the height of the walk surface is less than 90 cm, rescue of persons with mobility disabilities shall be performed, as necessary, by means of rescue chairs as specified in Israel Standard SI Chapter 4 Emergency Ventilation System 4-1 General The clause is applicable with the following Israel national deviations: The following shall be added after items (1) and (2): and a heavy passenger train The following shall be added after items (1) and (2): and a heavy passenger train The clause is not applicable and shall be replaced by the following: Where required by clause 4-1.2, the engineering analysis of the ventilation system shall use analytical simulation software appropriate for the quantitative analysis of the dynamic flow of air created in tunnels during fires, and that is equivalent to the results obtained from the use of computational fluid dynamics (CFD) techniques. The results of the analysis shall also contain air velocities not during a fire ("cold") that can be measured during certification (receiving inspection) in order to verify that the air system installed meets the requirements defined by the engineering analysis. The system shall be designed to maintain the required airflow rates for at least the anticipated evacuation time. 4-2 Design The clause is applicable with the following addition: The following subclause (4) shall be added: (4) Take into consideration the maximum number of trains that may be present between the air shafts during an emergency. 4-3 Emergency Ventilation Fans The clause is applicable with the following addition: Testing of the bellows may also be tested in accordance with all parts of the British Standard, BS Devices The clause is applicable with the following Israel national deviations: 23
28 4-4.1 The following shall be added to the clause: The requirements are applicable to the permanent components in the station The clause is not applicable and shall be replaced by the following: The materials of which the devices are made, excluding finishes (such as paint) shall be of the noncombustible type (VI.4.4). The materials shall be designed to withstand an ambient temperature of 250 C for at least one hour The following shall be added to the clause: The design shall take into consideration that any failure of a single device due to the outbreak of a fire shall allow full smoke control by the other devices. This subject shall be specifically checked in the design for each and every device. 4-7 Power and Wiring The clause is applicable with the following modifications: The clause is not applicable and shall be replaced by the following: The supply of electricity to the smoke control system shall be from two independent electrical sources, where each of them is an emergency generator (specific only for emergency equipment) that meets the requirements of the Israel Electricity Law and Electricity Regulations (installation of generators for low voltage), 1987 and the requirements of the Design and Construction Regulations) request for license, conditions and fees), second addition, electric generator. The feeders from these electrical sources to the individual components shall be isolated from one another up to the division board. Requirements of the clause in the American Standard that do not exist in the above referenced documents shall be in accordance with NFPA The reference to NFPA 70 is not applicable and shall be replaced by the following: The Israel Electricity Law with its regulations and the relevant Israel Standards. Lacking relevant Israel Standards, the requirements of the relevant European Standards shall apply The reference to NFPA 70 is not applicable and shall be replaced by the following: The Israel Electricity Law with its regulations and the relevant Israel Standards. Lacking relevant Israel Standards, the requirements of the relevant European Standards shall apply The reference to NFPA 70, Article 310 is not applicable and shall be replaced by the following: The Israel Electricity Law with its regulations and the relevant Israel Standards. Lacking relevant Israel Standards, the requirements of the relevant European Standards shall apply The reference to IEEE 383 is not applicable and shall be replaced by the following: Israel Standard SI 1739 Part 3. 24
29 Chapter 5 Vehicles 5-2 Construction The clause is applicable with the following Israel national deviations: Structural Fire Resistivity Component Test Criteria The reference to NFPA 251 is not applicable and shall be replaced by the following: All parts of Israel Standard SI Interior Fire Propagation Resistance The following shall be added to the clause: The following paragraph shall be added before the note, Exception: Alternatively, all the components of the assembly specified in Table in the German Standard, DIN 5510, parts 1 and 2 with the additional requirement in the original note (6) to Table 5-2.4A, shall be tested. If the tests are performed in Israel, they shall be performed by an approved laboratory that shall test all the components of the assembly specified in the new Table 5-2.4A, as follows: 25
30 Table 5-2.4A Test procedures and minimum performance requirements for testing the flammability and smoke emission characteristics of rail transit vehicle construction materials (with reference to Table 5-2.4) Category Function of material Test procedure Requirement (cushions, mattresses to be [ASTM E 162 to [to be cancelled] cancelled) seats (1,2,5) (bed frame to be cancelled) be cancelled] SI 5419 Intermediate hazard Ds(1.5) 100; Ds(4) 175 Vehicle seating (sleeping and food preparation to be cancelled) Curtains (1,2,3,5) Panels and coatings ASTM E 662 SI 5093 (tablecloths and upholstery ASTM E 662 to be cancelled) Walls (1,5,10) SI 755 ASTM E 662 Ceilings (1,5,10) SI 755 ASTM E 662 Partitions, tables and SI 755 shelves (1,5) ASTM E 662 Windscreen (1,5) SI 755 ASTM E 662 Air conditioning ducting (1,5) SI 755 ASTM E 662 Windows (4,5) SI 755 ASTM E 662 Light diffusers (5) UL 94 ASTM E 662 Flooring Structural (6) SI Covering (7) ASTM E 648 ASTM E 662 Insulation Elastomers Equipment boxes and covers Thermal insulation (1,2,5) SI 755 ASTM E 662 Acoustic insulation (1,2,5) SI 755 ASTM E 662 Window gaskets, door SI 1984 nosing, roof mats (1,10) Exterior shells, diaphragms and articulation bellows (1,5) Equipment boxes and covers ASTM E 662 SI 755 ASTM E 662 Pass Ds(4) 200 IV Ds(1.5) 100; Ds(4) 200 IV (1.5) 100; Ds(4) 200 IV (1.5) 100; Ds(4) 200 IV (1.5) 100; Ds(4) 200 V Ds(1.5) 100 IV Ds(1.5) 100; Ds(4) 200 V.0 Ds(1.5) 100; Ds(4) 200 Pass CR 0.5 w/w² Ds(1.5) 100; Ds(4) 200 V Ds(4 100 V Ds(4) 100 Fire spread 10 mm/min or the flame extinguishes before the line marked at 125 mm Ds(1.5) 100; Ds(4) 200 IV Ds(1.5) 100; Ds(4) 200 Notes: (1) Original note (1) in Table is applicable with the requirement of dripping grade 2 per SI 755. (2) Original note (2) in Table is applicable. (3) Original note (3) in Table is applicable. (4) Original note (4) in Table is applicable. (5) Original note (5) in Table is applicable. (6) Original note (6) in Table is applicable. (7) Original note (7) in Table is applicable. (8) Note (8) is not applicable (arms shall be tested as part of the chair). (9) Note (9) is not applicable. (10) Original note (10) in Table is applicable. Key to table: Text between round parentheses ( ) subjects cancelled with their tests. Text between square brackets [ ] tests cancelled for subjects mentioned. 26
31 5-2.5 Electrical Insulation In subclause (a), the reference to ICEA S-19/NEMA WC3, UL 44 and UL 83 are not applicable and shall be replaced by the following: Israel Electricity Law with its regulations and the relevant Israel Standards and International Standard IEC Electrical Fire Safety Requirements The clause is applicable with the following modifications: Propulsion Motors The reference to IEEE 11 is not applicable and shall be replaced by the following: IEC Motor Control A. The reference to IEEE 16 is not applicable and shall be replaced by the following: European Standards EN and EN B. In the third paragraph, the words, "approved by the authority having jurisdiction" are not applicable and shall be replaced by the following: approved by an approved laboratory Wiring Minimum Wire Size A. In subclause (1), the conductor "No. 14 AWG" is not applicable and shall be replaced by the following: conductor with minimum cross-section of 2.5 mm². B. In subclause (2), the conductor "No. 22 AWG" is not applicable and shall be replaced by the following: conductor with minimum cross-section of 0.4 mm². C. In subclause (3), the conductor "No. 18 AWG" is not applicable and shall be replaced by the following: conductor with minimum cross-section of one mm². 5-5 Emergency Egress Facilities The clause is applicable with the following Israel national deviations: The last sentence, beginning with the words, "Alternate emergency exit" is not applicable and shall be replaced by the following: so that in any case, at least two exits separated from each other shall be installed in each train car. - After clause 5-5.3, the following new clauses shall be added: 27
32 5-5.4 When required by clause 3-2.6, the vehicles shall be equipped with chairs for rescuing persons with mobility disabilities as specified in Israel Standard SI The vehicles shall be equipped with warning systems that comply with the requirements in the clause dealing with warning system (2.6) in Israel Standard SI 1918 Part Marking and Instructions for Operating Emergency Egress Openings Emergency egress openings shall be marked with signs The operating instructions of the emergency egress openings from the vehicle shall be marked inside the vehicle on the emergency egress openings or near them, with light emitting material and shall be readable. 5-6 Protection The clause is applicable with the following Israel national deviations: Portable Fire Extinguishers The clause is not applicable and shall be replaced by the following: Portable Fire Extinguishers Each vehicle shall be equipped with one extinguisher with extinguishing capability for class A, B and C fires, where the minimum extinguishing rating shall be A-13 for solids and B-70 for liquids. In vehicles with a cab, one extinguisher shall be placed next to the driver and an additional extinguisher near one of the entrance (exit) openings. In vehicles without a cab, the extinguisher shall be near one of the entrance (exit) openings. The extinguishers shall comply with Israel Standard SI 987. Alternatively, an equivalent extinguisher or other extinguishing device approved by the Fire Authority may be used, Maintenance of the extinguishers shall be as given in Israel Standard SI 129 Part 1. Installation of the extinguishers shall be as given in Israel Standard SI 129 Part Lightning Protection The conductor "No. 6 AWG" is not applicable and shall be replaced by the following: conductor with minimum cross-section of 16 mm² Testing and Maintenance Testing A. The reference to IEEE 11 and IEEE 16 are not applicable and shall be replaced by the following: EN B. In the line before the last, the words, "and any additional" to the end of the clause are not applicable Maintenance The following shall be added to the clause: 28
33 The implication of the word, "Authority" is the Authority legally in-charge of the operator. Chapter 6 Vehicle Storage and Maintenance Areas 6-1 General The clause is applicable with the following modifications: The last sentence, beginning with the words, "Implementation of these " is not applicable. 6-2 Open areas The clause is applicable with the following Israel national deviations: Water Supply The reference to NFPA 24 is not applicable and shall be replaced by the following: A permanent hydrant shall be installed, as follows: A. A hydrant with a 3" diameter double fire tap, in accordance with Israel Standard SI 448 shall be installed at the entrance to the site, not farther than 10 m from it, with threaded couplings complying with Israel Standard SI 449. B. At the site itself, extinguishing stations shall be installed that include an extinguishing cabinet containing a 3/4" diameter reel, 25 m long with a multi-purpose branch, 2" extinguishing tap with two 2" hoses and a multipurpose branch and a 6 kg powder or equivalent extinguisher. The distance between the two extinguishing stations shall not exceed 50 m. Between two extinguishing stations, a 3" fire tap shall be installed without a cabinet, without hoses and without a branch. The water supply shall be through a feeder line, at least 4" in diameter. The water pressure in the line shall not be less than 2 bars and not greater than 7 bars. The minimum water flow to the 3" extinguishing tap shall be 400 l/min and 250 l/min to a 2" extinguishing tap. The fire extinguishing piping shall be designed in a manner that provides a total water flow of 800 l/min at a dynamic pressure that is not less than 2 bars Emergency Access The clause is not applicable and shall be replaced by the following: Emergency Access At least two entrance opening shall be provided for a fire and rescue vehicle. The width of the access lanes and the gates shall be at least 4.5 m. Within the installation itself, square preparations for a fire and rescue vehicle in the open area shall be established. 29
34 The square preparations shall permit full "coverage" for fire extinguishing. The "coverage" radius of the square shall not exceed 45 m Fire Extinguishers The reference to NFPA 10 is not applicable and shall be replaced by the following: Fire extinguishers in accordance with the relevant Israel Standards (SI 570 Part 1, SI 987 and SI 318) shall be installed. Maintenance of the extinguishers shall be in accordance with Israel Standard SI 129 Part 1. The type of extinguishers, their number, location and installation shall be in accordance with Israel Standard SI 129 Part Structures The clause is applicable with the following Israel national deviations: Structural Requirements The clause is not applicable and shall be replaced by the following: Structural Requirements The materials of the bearing elements shall be of the "noncombustible" type (VI.4.4) Roofs The clause is not applicable and shall be replaced by the following: Roof Coverings Every roof covering shall be at least of type V.3.3 in accordance with Israel Standard SI Application The reference to NFPA 70 and the American document, ANSI C2, is not applicable and shall be replaced by the following: Israel Electricity Law with its Regulations Traction Power Overhead Conductors A. The dimension, "10 ft (3.05 m)" is not applicable and shall be replaced by the following: 4.90 m. B. The reference to NFPA 70 and the American document, ANSI C2, is not applicable and shall be replaced by the following: Israel Electricity Law with its Regulations Power Rail Conductors The reference to NFPA 70 and the American document, ANSI C2, is not applicable and shall be replaced by the following: Israel Electricity Law with its Regulations Maintenance Pit Areas 30
35 A. The words, "The authority having jurisdiction shall determine whether" are not applicable and shall be replaced by the following: In those cases where the maintenance pit is intended for servicing a mobile train car with systems operating on fuels, the safety measures in the pit shall be as follows: B. At the end of the clause, the following shall be added: Permanent lighting set-ups, explosion proof, Class 1 Division 2, shall be installed along the wall on both sides. Drainage openings in the floor shall be sealed against leakage to the ground. Wastes, oils, etc. shall flow through an oil separator to the sewerage or ventilated external receiving pit Overhead Cranes The reference to NFPA 70 is not applicable and shall be replaced by the following: Israel Electricity Law with its Regulations and FEM (Standards published by the German Society of lifting equipment manufacturers, accepted in all of Europe) Standards and the German Standard, DIN 15018, Parts 1 and Ventilation Abovefloor Ventilation The reference to NFPA 90A is not applicable and shall be replaced by the following: Israel Standard SI 1001 Part Draft Stops The last sentence in the clause is not applicable and shall be replaced by the following: The location of the draft stops shall be established such that every single enclosed area shall not exceed 700 m². The height of the draft stops shall be at least 1/8 of the space height. 6-4 Fire Protection Suppression Systems The clause is applicable with the following Israel national deviations: Automatic Suppression Systems A. The reference to NFPA 13 is not applicable and shall be replaced by the following: Israel Standard SI B. The reference to NFPA 72 is not applicable and shall be replaced by the following: All parts of Israel Standard SI Requirements that are not covered in all the parts of Israel Standard SI 1220 shall be as specified in NFPA 72. C. The sprinkler system installed shall be of the "preaction double interlock" type activated by smoke detectors. On detecting fire, the detection system shall stop the electric feeder panel as a precondition to activating the sprinkler system Protective Signaling Systems A. The first word, "Nonsprinklered" is not applicable. 31
36 B. The reference to NFPA 72 is not applicable and shall be replaced by the following: All parts of Israel Standard SI Requirements that are not covered in all the parts of Israel Standard SI 1220 shall be as specified in NFPA 72. C. This requirement is not applicable to structures used for maintenance of the diesel car Standpipe and Hose Systems The clause is not applicable and shall be replaced by the following: Hydrant Systems If required, a permanent hydrant system shall be installed, including a hydrant on a 4" diameter standpipe with a 3" diameter double fire tap, complying with the requirements of all parts of Israel Standard SI 448, with threaded couplings complying with Israel Standard SI 449, installed every 60 m, at most, with a cabinet next to it containing two 15 m hoses each, complying with Israel Standard SI 365, a multipurpose branch and a 12 kg dry powder extinguisher complying with Israel Standard SI 570 Part 1. Installation of the hydrants shall be in accordance with Israel Standard SI The water feed line shall be at least 4" in diameter. The water pressure in the line shall not be less than 2 bars and not greater than 7 bars. The minimum water flow to the 3" extinguishing tap shall be 400 l/min and 250 l/min to a 2" extinguishing tap. The fire extinguishing piping shall be designed in a manner that provides a total water flow of 2000 l/min at a dynamic pressure that is not less than 2 bars Portable Fire Extinguishers General The reference to NFPA 10 is not applicable and shall be replaced by the following: Israel Standard SI 129 Part Offices and showrooms The last sentence, beginning with the words, "The number and " is not applicable and shall be replaced by the following: The type, number, location and installation shall be in accordance with Israel Standard SI 129 Part 2. The extinguishers themselves shall comply with the relevant Israel Standards (SI 570 Part 1, SI 987 and SI 318) Hazardous Areas The extinguishers installed shall comply with class A, class B and class C fires. The type, number, location and installation shall be in accordance with Israel Standard SI 129 Part 2. The extinguishers themselves shall comply with the relevant Israel Standards (SI 570 Part 1, SI 987 and SI 318) Additional Locations The extinguishers installed shall comply with class B and class C fires. The type, 32
37 number, location and installation shall be in accordance with Israel Standard SI 129 Part 2. 33
38 6.5 Operations and Maintenance The clause is applicable with the following Israel national deviations: Vehicle Maintenance Batteries The last sentence, beginning with the words, "The entire electrical " is not applicable and shall be replaced by the following: All the electrical systems shall comply with the requirements of the Israel Electricity Law and its Regulations and the relevant Israel Standards Painting/Cleaning/Paint Removal The following shall be added to the clause: All the cleaning operations mentioned in the clause shall be in accordance with the Safety at Work Order. Cleaning requirements that do not appear in the Safety at Work Order shall be in accordance with NFPA Welding The reference to NFPA 51B is not applicable and shall be replaced by the following: Israel Standard SI Industrial Trucks Fuel Handling The reference to NFPA 58 is not applicable and shall be replaced by the following: All parts of Israel Standard SI 158. Requirements that are not "covered" by SI 158 shall be in accordance with NFPA The reference to NFPA 30 is not applicable and shall be replaced by the following: Business License Regulations (Petroleum storage), Chapter 7 Emergency Procedures 7-4 Emergency Procedures The clause is applicable with the following Israel national deviations: A. In subclause (f), the words, "Command post" are not applicable and shall be replaced by the following: Forward command post B. In subclause (f), the words, "auxiliary command post" are not applicable and shall be replaced by the following: Auxiliary forward command post C. In subclause (g), the words, "including communication instruments", shall be added. 34
39 D. In subclause (h)(8), the words: regional firefighting information desk, the police, Magen David Adom, Homefront Command, the electric company, the municipal information desk and the local water plant shall be added. 7-5 Participating Agencies The clause is applicable with the following Israel national deviations: A. The text in items (1), (4) and (11) is not applicable and shall be replaced by the following: Magen David Adom B. The text in items (2), (7) and (9) is not applicable and shall be replaced by the following: Municipal Information Desk C. A new item (12) shall be added, as follows: (12) Homefront Command D. A new item (13) shall be added, as follows: (13) Ministry of the Environment 7-6 Central Supervising Station (CSS) The clause is applicable with the following addition: The following shall be added to the clause: The CSS or the Security Center shall be staffed for 24 hours a day throughout the year. 7-7 Liaison The clause is applicable with the following addition: The following shall be added to the clause: The test shall be conducted by the operating authority. 7-8 Command Post The clause is applicable with the following modifications: The clause title is not applicable and shall be replaced by the following: Forward command post The words, "Command Post" are not applicable and shall be replaced by the following: Forward command post The words, "Command Post" are not applicable and shall be replaced by the following: Forward command post The words, "Command Post" are not applicable and shall be replaced by the following: Forward command post. 35
40 7-9 Auxiliary Command Post The clause is applicable with the following modifications: The clause title is not applicable and shall be replaced by the following: Auxiliary forward command post The words, "Auxiliary Command Post " are not applicable and shall be replaced by the following: Auxiliary forward command post The words, "Auxiliary Command Post" are not applicable and shall be replaced by the following: Auxiliary forward command post Removal and Restoring Traction Power The clause is applicable with the following addition: The following shall be added to the clause: by the operating authority or who that has been certified on its behalf. Chapter 8 Communications 8-1 General The clause is applicable with the following addition: There shall be communications accessibility to all the bodies providing emergency services (police, Fire Co., Magen David Adom and Homefront Command). A map with the sectorial limits and details of the extent of responsibility of all the emergency services shall be placed in the CSS. 8-2 Central Supervising Station (CSS) and Command Post Relationship The clause is applicable with the following addition: The following shall be added to the clause: In the CSS, in the room assigned to the head of the forward command post, there shall be stations ready for rapid connection both by radio communication and direct telephone line communication to the emergency services desk. 8-3 Radio Communication The clause is applicable with the following addition: After the words, "ancillary equipment", the following shall be added: such as pagers. 36
41 8-4 Telephone The clause is applicable with the following Israel national deviations: At the end of the first sentence, the words, "authority having jurisdiction" are not applicable and shall be replaced by the following: the regional emergency services dispersed along the trainway. - The following shall be added at the end of the clause: Next to every other fire extinguishing station, an emergency telephone (firemen's telephone) to the control room shall be installed, as specified in the American document NFPA After clause 8-4.2, the following new clause shall be added: At the CSS, a telephone system direct to the call desks of the bodies providing emergency services (police, Fire Co., Magen David Adom and Homefront Command) shall be installed. 8-7 Public Address (PA) system The clause is applicable with the following Israel national deviations: The following shall be added to the clause: The public address system required by this clause shall meet the requirements of the Israel Standard series SI In place of PA systems, there shall be an emergency PA system as required by clause Chapter 9 Referenced Publications This chapter is applicable with the addition of the following Standards and documents; Israel Standards SI 20 Part Luminaires: Luminaires for emergency lighting SI 129 Part 1 - Portable fire extinguishers: Maintenance SI 129 Part 2 - Portable fire extinguishers: Selection, installation and marking SI 158, all parts - Installations for liquefied petroleum gases (LPG) SI Carbon dioxide portable fire extinguishers SI Non-percolating layflat delivery hoses and hose assemblies for fire fighting purposes SI 448, all pars - Fire hydrant SI Threaded couplings for firefighting equipment SI 570 Part 1 - Portable fire extinguishers, powder stored pressure type: Extinguisher 37
42 SI Identification marks and warning signs for equipment containing fluids, gases or electrical cables SI Behaviour during fire of building materials Test methods and classification SI 921 Part 6 - Behaviour during fire of building materials: Requirements for entertainment buildings and public gathering buildings SI 931, all parts - Fire resistance of building elements SI Rechargeable portable extinguishers of the halogenated hydrocarbon type SI 1001 Part 1 - Fire safety in buildings: Air conditioning and ventilating systems SI 1001 Part Fire safety in buildings: Smoke control systems Buildings, except residential buildings up to 12 meter height SI Fire doors: Fire resistance SI 1220, all parts - Fire detection systems SI 1227 Part 2 - Loads and geometrical requirements for bridges: Railway bridges SI Sprinkler systems: Installation SI 1739 Part 3 - Tests on electric cables under fire conditions: Test on a grouped vertical cables SI 1918, all parts - Accessibility of the built environment SI 1984 Part 1 - Elastomeric profile for sealing of metalwork items and internal safety windows in shelters and protected areas SI 3864 Part 1 (I) - Graphical symbols Safety colours and safety signs: Design principles for safety signs in workplaces and public areas SI Above ground fire hydrant: Installation SI Fire prevention during welding, cutting and other hot work SI 4571 Part 1 - Double-wall underground fuel tanks: Production and cathodic protection SI Flammability of curtains for public or institutional use SI Construction and operation of light rail transit systems SI Resistance to ignition of upholstered furniture for non-domestic seating by testing composites SI Light rail applications Fixed installations Electric traction overhead contact lines SI Part 1 - Light rail applications Fixed installations Protective provisions relating to electric safety and earthing SI Part 2 - Light rail applications Fixed installations Protective provisions against the effects of stray currents caused by d.c. traction systems The Standards Institution of Israel Specifications (I) In preparation. 38
43 SII Safety signs and colours SII Reel for fire fighting Israel documents Israel Electricity Law, 1954, with revisions and regulations Electricity Regulations (Installation of generators for low voltage), 1987, with revisions Business Licensing Regulations (Petroleum storage), 1976, with revisions Safety at Work Order (new version), 1970, with revisions Design and Construction Regulations, 1956, with revisions Design and Construction Regulations (Request for license, conditions and fees), 1970, with revisions International Standards IEC Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V Part 7: Flexible cables screened and unscreened with two or more conductors IEC Electric traction Rotating electrical machines for rail and roadvehicle - Part 2: Electronic convertor-fed alternating current motors European Standards EN Railway applications Environmental conditions for equipment EN Railway applications Electronic equipment used on rolling stock EN Railway applications Electronic power converters for rolling stock National Standards BS 5588, all parts - Fire precautions in the design, construction and use of buildings DIN 5510 part Preventive fire protection in railway vehicles; levels of protection, fire preventive measures and certification DIN 5510 part Preventive fire protection in railway vehicles Part 2: Fire behaviour and fire side effects of materials and parts; Classification, requirements and test methods DIN part Cranes; steel structures; verification and analyses DIN part Cranes; steel structures; principles of design and construction Foreign documents Underwriters Laboratories Inc.: UL 94 Test for flammability of plastic materials for parts in devices and appliances American Society for Testing and Materials document: ASTM E Standard test method for heat and visible smoke release rates for materials and products using an oxygen consumption calorimeter National Fire Protection Association Standard: NFPA Standard method of test for heat and visible release rates for materials and products using an oxygen consumption calorimeter 39
44 After Chapter 9 and before appendix A, the following Annex A shall be added: 40
45 Annex A Example of marking for exit opening (normative) This Annex shows an example for marking the exit opening. The marking shall contain text in Hebrew with the addition of a symbol (pictogram). Fig. 1 (dimensions in centimeters) 41
MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS
CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
Errata has been identified as follows:
2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
Area of Rescue Assistance Communication System ADA Code Applicable excerpts:
Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment
5-8.1.4* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness.
NFPA 101 Life Safety Code Section 5-8 Illumination of Means of Egress 5-8.1 General. 5-8.1* Illumination of means of egress shall be provided in accordance with this section for every building and structure
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
OREGON FIRE CODE Interpretations and Technical Advisories
OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application
Building Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company
RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau g GUIDELINE FOR SAFETY REQUIREMENTS FOR HAUNTED HOUSES PURPOSE This guide is intended to provide safety standards and regulations for the construction
Walking and Working Surface Checklist:
Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:
Errata NFPA 1. Fire Code. 2015 Edition
Errata NFPA 1 Fire Code 2015 Edition Reference: 2.2, Table 6.1.14.4.1(a) and (b), 13.3.1.6, 13.7.2.13.2.1, 14.11.3.3, 18.5.2, 18.5.3, 20.1.2, 20.1.5.12, 25.1.1, 25.3, 25.4, A.3.3.164.2, and A.13.3.2.9.1
Certification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager
FIRE RATED WIRING What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager INTRODUCTION OBC requirements for emergency power OBC requirements for emergency power for fire alarm systems and other building
Fire Safety Requirements for Child Care Centre
Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
- 5 - Table1. Maximum Compartment Volumes
- 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,
Fire Safety In High Rise Building
Fire Safety In High Rise Building CLASSIFICATION OF BUILDINGS AS PER NATIONAL BUILDING CODE 1. GROUPING. Group A - Residential : Lodgings, Dwellings, Dormitories, Flats, Hotels. Group B Group C - Educational
Important Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
FIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
INTERNATIONAL FIRE CODE SECTION 3103 TEMPORARY TENTS AND MEMBRANE STRUCTURES
INTERNATIONAL FIRE CODE SECTION 3103 TEMPORARY TENTS AND MEMBRANE STRUCTURES 3103.1 General. All temporary tents and membrane structures shall comply with this section. 3103.2 Approval required. Tents
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES
CHAPTER 24 TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES > SECTION 2401 GENERAL 2401.1 Scope. Tents, canopies and membrane structures shall comply with this chapter. SECTION 2402 DEFINITIONS 2402.1 Definitions.
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.
1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310
Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS
Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44
We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.
September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
Planning Information. Passenger and Freight Elevators.
A company of ThyssenKrupp Elevator Thyssen Aufzüge tk This planning information will give you an overview of the most important planning criteria of passenger and freight elevators. However you should
Fire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
St. John s University
St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica
Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
Interfacing Elevators with Fire Alarm and Sprinklers
Interfacing Elevators with Fire Alarm and Sprinklers IEEE Atlanta Chapter May 15, 2006 Brian K Fabel, PE Agenda Today s Codes NFPA, ASME, IBC/IFC Conflicts/Issues Tomorrow s Codes? Applicable Codes NFPA
The following definitions apply with regard to requirements specified in this document:
GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
CHAPTER 9 FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes
Requirements for Hydrogen Storage and Use
Requirements for Hydrogen Storage and Use I. INTRODUCTION Fire and Life-Safety Group (FLS) The following is a summary of the fire and building code requirements for the storage and use of hydrogen. These
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection OSHA Office of Training and Education 1 Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers
A Code Review for Emergency Generators and Indoor Use of Portable Generators
A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a
Minnesota State Department of Public Safety
Minnesota State Department of Public Safety 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us Inspection
Australian/New Zealand Standard
Australian/New Zealand Standard The use of ventilation and air conditioning in buildings - Part 1: Fire and smoke control in buildings UPDATED AS/NZS 1668.1:2015 What is the scope of this Standard? The
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:
MOTOR FUEL DISPENSING SAFETY
STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
EAST LINDSEY DISTRICT COUNCIL ~ RESIDENTIAL CARAVAN SITES CONDITIONS OF SITE LICENCE
Residential Site Licence Conditions of Licence February 2014 EAST LINDSEY DISTRICT COUNCIL ~ RESIDENTIAL CARAVAN SITES Index of conditions CONDITIONS OF SITE LICENCE 1. Period of use 2. Bases 3. Siting
Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
Law No. (9) of 2012 Amending some provisions of Law No. (13) of 1997 Concerning the Civil Defense
Law No. (9) of 2012 Amending some provisions of Law No. (13) of 1997 Concerning the Civil Defense We, Hamad Bin Khalifa Al-Thani, Emir of the State of Qatar Having pursued the Constitution, And the Law
Current as of 11/10/08 1 of 1
BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that
Overview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
Decree of the Ministry of the Environment. on fire safety of garages
E4 THE NATIONAL BUILDING CODE OF FINLAND Fire safety of garages Guidelines 2005 Decree of the Ministry of the Environment on fire safety of garages Adopted in Helsinki, 22 March 2005 Pursuant to the Decision
STANDARD SITE LICENCE CONDITIONS FOR RESIDENTIAL PARK HOME SITES IN GUILDFORD CARAVAN SITES AND CONTROL OF DEVELOPMENT ACT 1960 (AS AMENDED)
STANDARD SITE LICENCE CONDITIONS FOR RESIDENTIAL PARK HOME SITES IN GUILDFORD CARAVAN SITES AND CONTROL OF DEVELOPMENT ACT 1960 (AS AMENDED) CONDITIONS ATTACHED TO SITE LICENCE NO: (insert ref) (insert
AUSTRALIAN HUMAN RIGHTS COMMISSION NOTICE OF DECISION ON APPLICATION FOR TEMPORARY EXEMPTIONS: AUSTRALASIAN RAILWAY ASSOCIATION
AUSTRALIAN HUMAN RIGHTS COMMISSION DISABILITY DISCRIMINATION ACT 1992 (Cth), Section 55 DISABILITY STANDARDS FOR ACCESSIBLE PUBLIC TRANSPORT 2002 (Cth), Section 33A.1 DISABILITY (ACCESS TO PREMISES BUILDINGS)
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services
MITT ROMNEY GOVERNOR KERRY HEALEY LT. GOVERNOR EDWARD A. FLYNN SECRETARY The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services P.O. Box 1025 State Road Stow, Massachusetts
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
Commercial Fire Inspections
Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10
Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10 This document was developed by the Orange County Fire Chiefs Association, Orange County Fire Marshal Committee.
BS5839 Part 1:2002 Overview
BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire
Safety Inspection Checklist
Inspector(s): Building: Room Number (s): Department/Unit: Date Inspected: Supervisor: To customize your local inspection checklist, delete or add as required. Inspection Headings: 1. Administrative 8.
UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS
Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and guards.
Section 9.8. Stairs, Ramps, Handrails and Guards 9.8.1. Application 9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and
Healthcare Engineering. Code Summary Report
American Society for Healthcare Engineering Code Summary Report CODE SUMMARY HEALTH CARE NEW BUILDINGS This code summary is based on the following codes: 2000 Edition NFPA 101, The Life Safety Code (LSC),
IFE Level 4 Certificate in Fire Science and Fire Safety (HL)
IFE Level 4 Certificate in Fire Science and Fire Safety (HL) Unit 2: Fire Safety Unit Reference Number: D/505/5932 Introduction This unit focuses on the prevention and detection of fire in premises and
The replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
RESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK CASTLEMEAD CAMBERWELL ROAD LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
OPTIONAL INFORMATION GUARDING FLOORS, STAIRS, AND OTHER OPENINGS SELF INSPECTION CHECKLIST
OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: GUARDING FLOORS, STAIRS, AND OTHER OPENINGS Guidelines: This checklist covers some of the
Heavy Metro Systems Light Rail Systems Automated Metros APMs Airport Link/City Shopping New & Retrofit Installations. w w w. platformscreendoors.
R a i l V e h i c l e S y s t e m s P l a t f o r m S y s t e m s A p p l i c a t i o n s Heavy Metro Systems Light Rail Systems Automated Metros APMs Airport Link/City Shopping New & Retrofit Installations
FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes
FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,
MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST
OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations
RESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK MARIE CURIE SCEAUX GARDENS ESTATE LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
FLAMMABLE AND COMBUSTIBLE LIQUIDS
GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
http://www.iccsafe.org/
Sections R311 and R312 from the 2006 International Residential Code These sections of Chapter 3 of the 2006 International Residential Code for One and Two Family Dwellings (R311 and R312) including the
FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH
FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH Safety signs are the primary way to communicate important warnings and messages to your employees, on-site contractors and other
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
NFPA 101 2012 SELECT SIGNIFICANT CHANGES
NFPA 101 2012 SELECT SIGNIFICANT CHANGES William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com [email protected] Expertly Engineering Safety From Fire INTRODUCTION NFPA 101 is
Safe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
Caravan Sites and Control of Development Act 1960. Permanent Residential Mobile Home Sites Licence Conditions
Caravan Sites and Control of Development Act 1960 Permanent Residential Mobile Home Sites Licence Conditions 1 Permanent Residential Mobile Home Site Licence Conditions Caravan Sites and Control of Development
SECTION.3400 - MECHANICAL: ELECTRICAL: PLUMBING
SECTION.3400 - MECHANICAL: ELECTRICAL: PLUMBING 10A NCAC 13D.3401 HEATING AND AIR CONDITIONING Heating and cooling systems shall meet the American Society of Heating, Refrigerating, and Air Conditioning
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
LIQUEFIED PETROLEUM GASES
CHAPTER 38 LIQUEFIED PETROLEUM GASES SECTION 3801 GENERAL 3801.1 Scope. Storage, handling and transportation of liquefied petroleum gas (LP-gas) and the installation of LP-gas equipment pertinent to systems
