CISPI DESIGNATION

Size: px
Start display at page:

Download "CISPI DESIGNATION 310-11 12"

Transcription

1 CISPI DESIGNATION SPECIFICATION FOR COUPLING FOR USE IN CONNECTION WITH HUBLESS CAST IRON SOIL PIPE AND FITTINGS FOR SANITARY AND STORM DRAIN, WASTE, AND VENT PIPING APPLICATIONS. This specification is issued under fixed designation 310; number immediately following designation indicates year original adoption or, in case revision, year last revision. A number in parenses indicates year last reapproval without change. Specifications for se couplings were originally a part standard T. With publication standard for pipe and fittings only, Institute deleted all specifications for se couplings re from and issued specification refore. Current revision approved March 16, 28, Last previous edition The new revision has been edited to reflect manufacturer testing requirements for couplings. GENERAL INFORMATION Several different types hubless couplings are available for use in hubless cast iron sanitary and storm drain, waste and vent piping applications to connect hubless cast iron soil pipe and fittings by using a sleeve-type, or some or type coupling device. It is purpose this Designation CISPI , 12, to furnish information as to characteristics one such sleeve-type couplings and also to furnish suggestions as to installation such couplings when applied to cast iron soil pipe and fittings manufactured in accordance with CISPI Designation 301, latest revision. It must be noted that installation procedures are not a mandatory portion this Designation and illustrative installation instructions included herein are not to be applicable for couplings or than those manufactured in accordance with this designation. The hubless couplings described herein are composed a stainless steel shield, clamp assembly and an elastomeric sealing sleeve conforming to requirements ASTM C564. This elastomeric material was selected for sealing sleeve because balanced combination outstanding properties makes it resistant to abrasion, oil, grease, chemicals, sun, wear, ozone, heat and cold. This elastomeric sealing sleeve also provides a cushioning element in coupling to avoid shock and vibration and to assure a noiseless plumbing system. The 300 series stainless steel was selected for clamp and shield assemblies because it possesses high corrosion resistant characteristics, which have been demonstrated to exist in underground corrosion tests conducted by U.S. Department Commerce through National Bureau Standards. CAST IRON SOIL PIPE INSTITUTE 1064 Delaware Avenue SE Atlanta, Georgia Phone:

2 1. PURPOSE AND SCOPE 1.1 Purpose. The purpose this specification is to establish criteria for material dimensions and dimensional tolerances for one type coupling used in hubless cast iron soil pipe and fittings for sanitary and storm drain, waste and vent piping applications in accordance with general needs producers, distributors, and users. 1.1 Scope. This specification covers coupling assembly identified in following tables. COUPLING ASSEMBLY TABLE Rubber Sealing Sleeve 1, 2, 2A, 3 Shield and Clamp 4, 5, 5A Manufacturer s Item Coupling Assembly TABLES 1-6 Group 022 Code Item# /2 2 x 1-1/ x 2 4 x Size Note: When ordering by se EDP numbers, be sure to include check (3) digit following item number ( ). This check digit is verification group and item number you select. 1.2 Several different types hubless couplings are available for use in hubless cast iron sanitary and storm drain, waste and vent piping applications to connect hubless cast iron soil pipe and fittings by using a sleeve-type, or some or type coupling device. It is purpose this specification to furnish information as to characteristics one such sleeve-type coupling when applied to cast iron manufactured in accordance with Specification A888, latest revision, and CISPI-301, latest revision. 2 REQUIREMENTS FOR THE HUBLESS COUPLINGS REFERENCED IN THIS SPECIFICATION 2.1 DESCRIPTION. The couplings are a sleeve-type. Each coupling shall consist a sealing sleeve and a shield and clamp assembly which joins two spigot ends pipe and/or fittings Each coupling is designed to permit normal expansion, contraction and deflection sanitary and storm drain, waste, and vent piping applications. 2.2 Sealing Sleeve. The sealing sleeve shall be tested in accordance with ASTM D3677 and be manufactured from a properly vulcanized virgin compound where primary elastomer is polychloroprene (neoprene). 2

3 2.2.1 The sealing sleeve shall be made a compound containing a high quality elastomer that complies with dimensions, material specifications, chemical and physical properties as shown in Tables 1, 2, 2A and 3. All surfaces sealing sleeve shall be smooth except for specified marking. The sealing sleeves shall be free from imperfections and porosity The sealing sleeve shall consist one piece conforming to physical requirements Specification ASTM C564. The sealing sleeve shall be tested by sealing sleeve manufacturer for compliance to ASTM C564 during each day production not to exceed 24 hours for each size sealing sleeve being produced. These tests shall be performed at manufacturer location during time production. These tests shall include hardness, elongation and tensile strength, tear strength and compression set. Heat aging, water absorption, ozone resistance, and oil immersion tests shall be performed annually or when formulation or source supply changes, whichever occurs first When testing pipe sealing gaskets, sleeves, prepared specimens shall shall be be 1 1-in. disks disks cut cut from prepared samples in. to ( mm) inches to.090-in. thick and (2.286 not mm) to exceed thick and seven not (7) to exceed plies. seven The thickness (7) plies. For hubless disk coupling shall be gasket measured inserts per a ASTM test specimen D395 measuring Since.43 in. all ( specimens mm) from X.75 sealing in. (19.05 sleeves mm) may are be curved, cut directly not flat, from it is part important provided to measure sample is thickness consistent in thickness. center The thickness disk with sample specimen shall be measured laying in accordance a concave with manner. Test Methods Measure D395, thickness section each Since ply all and specimens add from measured hubless thickness pipe gaskets each are curved, ply (not not to flat, exceed it is important seven plies) to measure to determine thickness original in plied center up thickness sample (to). with The specimen plied up laying target in thickness a concave shall manner. be approximately Measure thickness 0.50 inches. each Take ply and original add measured plied up thickness (to) each and multiply (not to it exceed by 0.75 seven to determine plies) to determine thickness original spacer plied up bar thickness to be used (to) (tn). and Assemble multiply it by.75 plied to up determine specimens thickness in test fixture spacer (ASTM bar D395 to be used figure (tn). 3) Assemble with proper plied thickness up specimens spacer in bars text and fixture place (Test in oven Methods for 22 D395, hrs. at Fig ) +/- with 2 (70 proper +/- 1 thickness C). At spacer bars end and place test in period oven for take 22 h at 158 device +/- 2 F from (70 +/- oven 1 C). and At remove end test period specimens take immediately device from and allow oven and to cool remove per ASTM test specimens D immediately After and allow cooling to cool period in accordance measure with final Test thickness Methods D395, at section center After plied up cooling test specimen period measure placed in a final concave thickness position at on center dial micrometer plied up test to determine specimen placed final a thickness concave position (ti). Calculate on dial micrometer compression to determine set expressed final as a thickness percentage (ti). Calculate original deflection compression as set follows: expressed as a percentage original deflection as follows: CB = [(to-ti)/(to-tn)]x100 x CB = compression set value test method B to = original plied up thickness ti = final plied up thickness tn = thickness spacer bar used manufacturer sealing sleeve, n entity that molds sealing sleeve covered by this standard specification. 2.3 Shield and Clamp Assembly. The shield and clamp assembly shall consist (1) a 300 Series stainless steel corrugated shield, (2) two stainless steel bands for sizes 1 ½, 2, 3, and 4, (see Fig. 1.); four stainless steel bands for sizes 5, 6, 8 and 10, (see Fig. 2.); six stainless steel bands for sizes 12 and 15 (see Fig. 3.) and (3) a stainless steel tightening device for each band. Each tightening device housing shall interlock with a band at unslotted end. The bands are to be fastened to shield by riveting or such or method that shall insure that bands shall not become separated from shield. The shield and clamp assembly shall comply with dimension and material specifications, as are given in Tables 4, 5, and 5A Clamp assemblies shall be tested to withstand no less than 125% manufacturers stated installation torque or a minimum 60 lbf-in. applied torque, whichever is greater, without visible signs failure. The clamp assembly shall be tested over a steel mandrel appropriate diameter and torqued as required. These tests shall be performed randomly on selected samples during course production as needed but not less than one clamp per shift per size during band production manufacturer clamp assembly and shield, n entity that attaches clamp assembly to shield for couplings covered by this standard specification. 3

4 2.4 Marking. The sealing sleeves shall be marked with raised letters at location shown in Table This Marking. marking The shall sealing consist sleeves pipe size, shall country be marked origin, with raised manufacturer s letters at identifying location mark, shown mold in Table number, 1. cavity This marking number, shall and ASTM consist C564, pipe latest size, revision. country Such origin, marking manufacturer s shall not exceed identifying.02 in mark, relief. mold number, cavity 2.4.1number, The shield and ASTM and clamp C564, assembly latest revision. shall be Such marked marking with shall indented not exceed letters.02 at in relief. location shown in Tables The and shield 5. All and marking clamp shall assembly be placed shall on be marked band with assemblies indented letters screw at housing location as shown in Tables 4 and and Marking All marking on shall band be shall placed consist band pipe size. assemblies Marking on screw screw housing housing as shown shall consist in Tables clamp 4 and manufacturer s 5. Marking on name band or registered shall consist U.S. Trademark, pipe size. Marking words on ALL screw STAINLESS, housing and shall country consist origin. clamp manufacturer s name or registered U.S. Trademark, words ALL STAINLESS, and country origin. Size 1-1½" thru 4" TWO BANDS Size 5", 6", 8", and 10" FOUR BANDS Figure 1 Figure COUPLINGS REQUIREMENTS AND TEST METHODS COUPLINGS 3.1 Assemble REQUIREMENTS each coupling tested AND according TEST METHODS to manufacturer's instructions between two sections 3.1 Assemble randomly each selected coupling hubless tested cast according iron soil pipe to meeting manufacturer's requirements instructions CISPI-301 between two or Specification sections randomly A888 and selected conduct hubless following cast iron test: soil deflection pipe meeting and shear. requirements In addition, an CISPI-301 unrestrained or hydrostatic Specification test A888 shall and be conduct performed between following two test: sections deflection machined and shear. steel In addition, pipe. The an unrestrained hydrostatic tests shall shall be be performed on between randomly two selected sections couplings machined each steel size pipe. during The unrestrained course production hydrostatic using tests shall first be article performed selection on not randomly to exceed selected 30 days. couplings The deflection each size and during shear tests course shall be performed production on using randomly first article selected selection couplings not to each exceed size 30 during days. production The deflection whenever and shear a change tests shall design be occurs performed not on to randomly exceed 120 selected days, couplings whichever is each shorter size during period. production PROPER whenever SAFETY a PRECAUTIONS change design SHALL occurs or BE not STRICTLY to exceed 120 OBSERVED days, whichever AT ALL is TIMES. shorter period. PROPER SAFETY PRECAUTIONS SHALL BE STRICTLY Deflection OBSERVED Test: AT ALL TIMES Deflection A Test: test apparatus such as one shown in Fig. 4 is suggested. Or testing apparati that provide restraint A to test apparatus assembly such shall as also be one permitted. shown in Close Fig. 4 is outboard suggested. ends Or testing pipe with apparati test that plugs. provide restraint to assembly shall also be permitted. Close outboard ends pipe with test plugs Fill assembly with water, expel all air, and hydrostatically pressurize to 4.3 psi (29.6 kpa) for duration Fill assembly test. One with pipe water, shall expel be rigidly all air, supported and hydrostatically and while pressurize assembly to is 4.3 under psi (29.6 pressure, kpa) for raise duration opposite end test. One or pipe shall pipe be 1/2 rigidly in. (12.7 supported mm) per and linear while foot assembly pipe. Maintain is under pressure, pressure raise for 5 minutes. opposite Any end leakage shall or mean pipe failure. 1/2 in. (12.7 mm) per linear foot pipe. Maintain pressure Shear for Test: 5 minutes. Any leakage shall mean failure Shear Test: Support two joined lengths randomly selected hubless cast iron soil pipe on blocks, a minimum /2 Support in. (38.1 two mm) joined high, lengths at three locations. randomly One selected length hubless shall be cast a minimum iron soil pipe 24 in. on blocks, (609.6 mm) a minimum length, 11/2 supported in. (38.1 on mm) blocks, high, one at three near locations. uncoupled One length end, and shall be or a minimum immediately 24 adjacent in. (609.6 to mm) couplings. length, supported Firmly restrain on blocks, this length one near in position uncoupled as shown end, in and Fig. 5. The or or immediately coupled length adjacent shall to be a couplings. minimum Firmly 5 ft restrain (1.52 m) this in length in and position supported as shown by a single Fig. block 5. The 6 in. or (152.4 coupled mm) from length shall end be a minimum pipe. 5 ft (1.52 m) in length and supported by a single block 6 in. (152.4 mm) from end pipe. 4 4 Size 12" and 15" SIX BANDS Figure 3

5 Fill assembly with water and expel all air. Apply a load 50 lb/in. nominal diameter at a point 6 in. (152.4 mm) from edge coupling upon a 12 in. (304.8 mm) length (3 by 3) angle iron or load distribution pad located on top pipe immediately adjacent to coupling pipe having one support only. Under this loading re shall be no visible leakage or displacement more than 3/8 in. (9.53 mm) from true alignment adjacent to coupling, when an internal pressure equivalent to a 10 ft (3.05 m) head water 4.3 psi (29.6 kpa) is applied. Maintain load and internal pressure for 15 minutes Unrestrained Hydrostatic Test: Assemble each coupling tested according to manufacturer's instruction between two sections machined steel pipe and conduct thrust test The assembly shall consist a maximum outside diameter pipe connected to a minimum outside diameter pipe with diameters as referenced in Table 6 and lengths as shown in Fig. 6. Machine plain ends pipe to be used for thrust test to correct diameters. Plain ends shall have in. (0.38 mm) deep grooves machined circumferentially around m at 1/8in. (3.18 mm) intervals down pipe section for a distance equal to that covered by elastomeric sealing sleeve coupling being tested. The tool used to machine grooves shall have a 60 inclined angle and cut into pipe from a perpendicular position. The surface between grooves shall be a la turned surface 125 RMS The plain ends pipe for thrust test shall be uncoated and cleaned with acetone and thoroughly dried before each assembly Test Method: Support pipe assemblies in a manner that does not restrain joint movement as shown in Fig Fill pipe assembly (as required in 3.1.3) with water, expelling all air. Increase hydrostatic pressure at a rate 1 psi (6.9 kpa) every 30 s until specified test pressure is reached. The specified test pressure shall be 20 psi (137.9 kpa) for 1 1/2 in. (38.1 mm) through 5 in. (127 mm), 18 psi (124.1 kpa) for 6 in. (152.4 mm), 10 psi (68.9 kpa) for 8 in. (203.2 mm), and 6 psi (41.4 kpa) for 10 in. (254 mm) pipe, 12 in. (305 mm), and 15 in. (380 mm). When specified test pressure is reached, hold it for 5 minutes. Any leakage or axial joint movement more than in. (3.81 mm) shall mean failure. 4 CERTIFICATION 4.1 Upon request purchaser, design pressional, or administrative authority having jurisdiction where products are being installed, shall be furnished certification documents by manufacturer, stating samples representing each lot have been tested and inspected by manufacturer for quality as indicated in this specification and requirements have been met. If requested by purchaser, design pressional, or administrative authority having jurisdiction where products are being installed, self-certification shall be accompanied by manufacturer quality control test reports as prepared in accordance with Sections 2 & 3 this specification. Self-certification shall include legal name and address each manufacturer. 4.2 Third Party certifiers or inspectors shall utilize procedures detailed in Annex A when conducting inspections at manufacturing locations. 5

6 TABLE 1. RUBBER SEALING SLEEVE (Dimensions in inches) 6

7 Note Dimensions found in se drawings are for informational purposes only. The dimensions found Note in table Dimensions are mandatory. found in Tolerances se drawings are found are for in informational Table 2a. The purposes center stop only. measurement dimensions shall A be and B 3/32 found (0.094 ) in table minimum, are mandatory. measured Dimensions at top D1 and center D2 stop. found This in measurement table are reference shall be for considered mold a design. non critical Tolerances dimension. are found The 5 in draft Fig. 2. on The center stop width is for manufacturing is (3/32).094 plus purposes 5 and draft it angle. shall be Sealing permissible ring to shape have and different dimensions or no draft are to angle manufacturer s on center design. stop. Sealing ring shape and dimensions are to manufacturer design. DIMENSIONS IN INCHES 1 1½ B Dimensional Tolerances to be RMA Class 3 (See Table 2A) 7

8 TABLE 2: REDUCING RUBBER SEALING SLEEVE (Dimensions in inches) *Note C dimension is a reference dimension only DIMENSIONS FOR REDUCING SEALING SLEEVES DIMENSIONS IN INCHES 2 x 1-1/2 3 x 2 4 x 3 A B C D D D Dimensional Tolerances to be RMA Class 3 (See Table 2A) 8

9 TABLE 2A. DIMENSIONAL TOLERANCES FOR RUBBER Standard Dimensional Tolerances RMA CLASS 3 Size (Inches) Closure (Plus or Minus) and over multiplied by These are commercial tolerances. All diametral dimensions shall have a tolerance +/- 1 percent. TABLE 3. RUBBER SEALING SLEEVE PHYSICAL REQUIREMENTS Material: Physical Tests: The sealing sleeve shall be made from an elastomeric compound that meets requirements ASTM C564. The sealing sleeve shall be tested in accordance with ASTM D3677 and be manufactured from a properly vulcanized virgin compound where primary elastomer is polychloroprene (neoprene). The test specimens shall be obtained from finished sealing sleeves and tested pursuant to methods described in following table. TESTS Test Physical Tests ASTM Min or Max Requirements Method Tensile Strength 1500 psi min. D412 Elongation 250 min. D412 Durometer (Shore A) 70 ± 76 F ± 5 F D2240 Accelerated Aging 15% max. tensile and 20% max. elongation D573 deterioration, 10 points max. increase in hardness, all determinations after oven aging for 96 hours at 158 F. Compression Set 25% max after 22 hours at 158 F. D395 Method B Oil Immersion 80% max. volume change after immersion in D471 ASTM oil IMR903 for 70 hours at 212 F. Ozone Cracking No visible cracking at 2 times magnification D1149 sealing sleeve after 100 hours exposure in 1.0 ppm ozone concentration at 100 F. Testing and inspection to be on sealing sleeve which is loop mounted to give approximately 20% elongation outer surface. Tear Resistance Die C; 150 lbs. Min. per inch thickness D624 Water Absorption 20% max. by weight after 7 days at 158 F. D471 9

10 TABLE 4. SHEILD AND CLAMP ASSEMBLY (Dimensions in inches) 10

11 Note: A single corrugation pattern is shown in drawing or corrugations unique to individual manufacturers are acceptable. The P dimension is allowed on eir end corrugated section. A P dimension is required on shield designs that have a single corrugated pattern. It shall be permitted for P dimension to not apply to all coupling designs. Measure corrugated material thickness and formed thickness with calipers or disc micrometer. Three random measurements shield thickness and corrugated height shall be taken and median used as value. Pipe Dimensions in Inches Size P *C L min W Min. X 7 Max. 1 ½ ± / ± / ± / ± / ± / ± / ± / ± / ± / ± / *Note C Dimension is a reference dimension only. MATERIAL SPECIFICATIONS Band Type 301 AISI Stainless Steel Minimum Tensile 140,000 PSI for 1 ½ to 15 ; Type 304 AISI Stainless Steel shall be permitted; Type 304 AISI Stainless Steel Minimum Tensile 140,000 PSI. Screw Housing Type 301 AISI Stainless Steel for 1 ½ to 15 ; Type 304 AISI Stainless Steel shall be permitted. Screw - Type 305 AISI and or Type 304L AISI Annealed Stainless Steel 5/16 Hex Head/Shoulder for 1 ½ 10 ; 3/8 Hex Head/Shoulder for 12 and 15 is required for couplings which require installed torque greater than 60 inch pounds. When or than 3/8 hex head screw is used on 12 and 15 couplings, coupling shall be labeled with required installation torque. Shield - Type 301 AISI and or Type 304 AISI Stainless Steel Bright Annealed Only (Annealed & Pickled Not Acceptable) Hardness Rockwell B-100 (Vickers 240) per ASTM A240/A240M Max. (Max. Burr Height Not to Exceed 25% Thickness) Eyelets/Rivets - Type 300 Series AISI Stainless Steel 11

12 Notes 1 Construction for sizes 1 ½ thru 10 shields have corrugations tapering in height from to at dimension Y. Y equals maximum 1 inch. (Type A Only) 2 Position clamps on shield as shown from inside end clamp. Shield overlap to be as shown or reversed on 5, 6, 8, 10, 12 and 15 only. 3 Location Specified marking Manufacturer s name, all stainless, country origin, trade name or mark. See Table 5 for details. 4 Location specified marking Size See Table 5 for details. 5 Securely fasten each clamp to shield, two places for sized 1 ½ to 4, three places for sizes 5, 6, 8, 10, 12, and Details detent on 5, 6, 8, and 10 bands are shown in Table 5A (optional for 12 and 15 ). 7 Max X is that dimension to which clamp must open and still maintain positive engagement screw in slots clamping band. Min. X is that dimension to which clamping band must close and still maintain positive engagement screw in slots clamping band. 12

13 FIG. 4 Deflection Test 13

14 FIG. 5 Shear Test TABLE 6 Dimensions and Tolerances for Hubless Pipe and Fittings Size, in. (mm) Outside Diameter, in. (mm) 11/2 (38) 1.90 ± 0.06 (48.26 ± 1.52) 2 (51) 2.35 ± 0.09 (59.69 ± 2.29) 3 (76.2) 3.35 ± 0.09 (85.09 ± 2.29) 4 (102) / 0.05 ( / 1.27) 5 (127) / 0.05 ( / 1.27) 6 (152) / 0.05 ( / 1.27) 8 (203) 8.38 ± 0.09 ( ± 2.29) 10 (254) ± 0.09 ( ± 2.29) 12 (305) ± 0.13 (317.5 ± 3.30) 15 (380) ± 0.13 (402.8 ± 3.30) 14

15 WATER INLET " [15.3] OR LESS 6 1. Pressure Regulator 2. Pressure Gauge (1 PSI Increments, 0-30 PSI) 3. Dial Indicator 4. Air Bleed Off Vent 5. PIPE 6. Coupling 7. Alignment Brackets 8. Clamp 9. Test Stand /8" Quick Disconnect Coupling 11. 3/8" Rubber Hose FIG. FIG. 6 Unrestrained Unrestrained Hydrostatic Hydrostatic Test Test Annex Annex A (Mandatory (Mandatory Information) Information) The The following following supplementary supplementary requirements requirements shall shall be be applied applied when when manufacturer manufacturer or or seller seller products products covered covered by by this this specification specification utilizes utilizes third third party party certification certification agencies agencies as as part part ir ir certifications certifications as as detailed detailed in in Section Section 4, 4, Certification Certification this this specification. specification. A1. A1. Third Third Party Party certification certification audit audit or or inspection inspection A1.1 A1.1 Third Third Party Party certifiers certifiers or or inspectors inspectors conducting conducting regular regular inspections inspections at at manufacturer s manufacturer s production production facility facility shall shall include include but but not not be be limited limited to to following following procedures procedures during during each each audit audit or or inspection inspection A1.1.1 A1.1.1 A review review manufacturer s manufacturer s records records to to verify verify compliance compliance with with Sections Sections 2 and and 3 this this standard. standard. Copies Copies manufacturer s manufacturer s quality quality control control test test reports reports shall shall be be added added to to third third party party certifier s certifier s audit audit or or inspection inspection reports. reports. A1.1.2 A1.1.2 Random Random inspection inspection manufacturer s manufacturer s finished finished goods goods inventory inventory shall shall be be conducted conducted during during each each audit audit or or inspection. inspection. These These audits audits or or inspections inspections shall shall include include a dimensional dimensional and marking inspection not less than 10 randomly 15 selected couplings different sizes and types. Each sealing sleeve used as part a coupling shall 15be subject to requirements appropriate coupling standard. 15

16 APPENDIX The following non-mandatory appendix includes installation suggestions for proper installation hubless cast iron soil pipe and fittings joined by couplings included in this CISPI 310 designation. These suggested instructions shall not be considered a mandatory part this designation. NON-MANDATORY APPENDIX 16 17

17 INSTALLATION PROCEDURES FOR HUBLESS CAST IRON SOIL PIPE AND FITTINGS FOR SANITARY AND STORM DRAIN, WASTE AND VENT PIPING APPLICATIONS 1. Introduction 1.1 Several different types hubless couplings are available for use in hubless cast iron sanitary and storm drain, waste, and vent piping applications to connect hubless cast iron soil pipe and fittings by using a sleeve-type, or some or type coupling device. It is purpose this portion designation CISPI to furnish procedures as to installation couplings, which are manufactured in accordance with CISPI Designation when applied to cast iron soil pipe and fittings manufactured in accordance with CISPI Standard 301, latest revisions. It must be noted that se installation procedures are not intended to be applicable for couplings not made in accordance with CISPI THE INSTALLATION PROCEDURES STATED BELOW ARE ILLUSTRATIVE ONLY AND ARE NOT A MANDATORY PORTION OF CISPI DESIGNATION Purposes 2.1 These installation procedures provide guidelines for installation, use and inspection hubless cast iron soil pipe and fittings for sanitary and storm drain, waste, and vent piping applications when coupling device described in Designation is used. 2.2 All construction projects involve many variables, hence it is not possible to state in advance every installation consideration which may apply in field. In end, final and controlling judgment decisions concerning installation questions that arise must be made in design and on job taking into account prevailing circumstances or conditions. The Institute cannot assume such responsibilities. These procedures are not a substitute for such informed judgments and for manufacturerprovided installation instructions but it is hoped y will be helpful. 2.3 Complete stability all components hubless cast iron soil pipe and fittings for sanitary and storm drain, waste, and vent piping applications should be given prime consideration. 3. Methods Cutting Cast Iron Soil Pipe There are several methods successfully cutting cast iron soil pipe. These methods may be placed into two basic categories; those that require external power for ir operation and those methods that require only hand operation. Methods that require external power are usually used for prefabrication work or high volume cutting operations. Examples this type equipment would be: (1) abrasive saw (chop SAW), (2) power hack saw, and (3) an electrically actuated hydraulic snap cutter. Before using electrical equipment this nature, manufacturer s operating instructions should be carefully reviewed for safe use equipment. There are two hand operated cutting tools that are used in industry today: (1) standard steel pipe cutter using cutting wheels specifically designed to cut cast iron soil pipe, and (2) snap cutter. The snap cutter accounts for majority all cuts made on cast iron soil pipe in field. 17

18 There are several types snap cutters available, following procedure has been found to produce consistently good cuts: 1) After marking pipe length to be cut, position chain cutter squarely around pipe to ensure a straight cut. The maximum number wheels possible should be in contact with pipe. 2) Score pipe by applying pressure on handles to make cutter wheels indent pipe. 3) Rotate pipe a few degrees and n apply quick final pressure to complete cut. If a piece pipe is unusually tough, score pipe several times before making your final cut. Scoring pipe before actual cut is key to a clean straight cut. Cast iron soil pipe may also be cut with a hammer and a cold chisel. This method cutting is very time consuming and should only be used if snap cutters are not available. Again, protective equipment, such as safety goggles, should be used. The procedure for cutting soil pipe with a hammer and chisel are as follows: 1) Measure length to be cut and mark cut line completely around circumference pipe. 2) Place mark to be cut on a 2 by 4 so edge 2 by 4 is directly under mark. 3) By striking chisel with hammer, cut a groove following your mark all way around circumference pipe. 4) Continue cutting as outlined above in (3) until pipe is cut. This procedure may take several revolutions pipe before it is cut. Installers should be aware safety considerations, including need to use protective equipment, such as safety goggles, when cutting cast iron soil pipe. 4 Definitions 4.1 Joint A place where two ends pipe or fittings are connected. 4.2 Coupling A mechanical device by which ends pipe or fittings are connected. 4.3 Hanger A device by which or to which something is hung or hangs. 4.4 Support To hold up or to serve as a foundation or prop. 4.5 Restrain To limit, restrict or keep under control. 4.6 Restraint A device that restricts movement. 4.7 Seismic Shock, earthquake, to shake. 4.8 Torque A force that produces or tends to produce rotation or torsion: A turning or twisting force. 4.9 Alternately A change from one to anor repeatedly. 5 Clamp and Sealing Sleeve Installation Hubless cast iron soil pipe is joined by using hubless coupling. Several different types hubless couplings are available. The following will outline installation procedures hubless couplings that meet requirements CISPI It must be noted that se installation procedures 18

19 are not intended to be applicable for couplings or than those manufactured in accordance with CISPI Installation procedures from manufacturer shall be followed for best performance. These couplings are manufactured using a stainless steel shield and clamp assembly and an elastomeric sealing sleeve conforming to requirements Specification C564. The following steps should be taken to ensure a proper joint. 1) Place sealing sleeve on end one pipe or fitting and stainless steel clamp and shield assembly on end or pipe or fitting. 2) Firmly seat pipe or fitting ends against integrally molded center stop inside elastomeric sealing sleeve. 3) Slide stainless steel shield and clamp assembly into position centered over sealing sleeve and tighten bands. The bands should always be tightened using a properly calibrated torque wrench set at 60 lbf-in. or specific torque required by manufacturer couplings, which require a higher torque. For larger diameter couplings that have four bands, inner bands should be tightened first and n outer bands tightened. In all cases, when tightening bands y should be tightened alternately to ensure that coupling shield is drawn up uniformly. (A) TYPICAL HUBLESS COUPLING HUBLESS PIPE SEALING SLEEVE STAINLESS STEEL SHIELD STAINLESS STEEL RETAINING CLAMP HUBLESS PIPE 6. SUGGESTED INSTALLATION INSTRUCTIONS UNDERGROUND INSTALLATION PROCEDURES The physical properties cast iron soil pipe make it a good choice for DWV (Drain, Waste and Vent) material for underground installation. The two keys for proper underground installation are trench preparation and backfilling. 19

20 The trench should be wide enough to assemble joints. Total load on pipe includes both earth load and truck load. For additional information refer to CISPI s Trenching Recommendations for Cast Iron Soil Pipe brochure or CISPI handbook. Safety procedures in trenching should be observed, including provisions to avoid collapse trench wall. The trench bottom should be stable enough to support complete barrel pipe. If possible barrel should rest on even and undisturbed soil. In certain conditions, that is, rocky, it becomes necessary to excavate deeper than needed, place and tamp back fill material to provide an appropriate bed. Holes should be provided at each joint for hub or couplings to allow for continuous support barrel along trench bottom. If ditch must be excavated deeper than depth drainage pipe, place and tamp backfill material to provide uniform support for pipe barrel. Many times in installation underground soil pipe it is necessary to change direction line. Cast iron soil pipe will allow this through deflection in joints. Installation should initially be completed in a straight line and n deflected to appropriate amount. Maximum deflections should not exceed 1/ 2 in. per foot pipe. This would allow 5 in. deflection for a 10-ft piece soil pipe. For changes in direction greater than se deflections an appropriate fitting should be used. 1 The use adhesive lubricants is permissible as recommended by manufacturer. When adhesive lubricants are used wait 24 hours before testing. The use adhesive lubricant does not take place proper joint restraint. Once installation (for joining methods refer to Part 5) is completed, underground section is ready for test. Because this portion system is usually largest diameter pipe it may be necessary to restrain system or joints from movement prior to testing. This may be done by partially backfilling and leaving joints exposed for inspection, or rodding or bracing, or both. After testing is completed, trench can be properly backfilled. When backfilling, care should be taken to protect pipe from large rocks, stones, or frozen fill material etc., that could damage pipe. Cast iron soil pipe laid on a solid trench bottom requires no tedious placement selected backfill materials. Installers should always consider local conditions, codes, manufacturer instructions, and architect/engineer instructions in any installation. 20

21 ABOVEGROUND INSTALLATION PROCEDURES With attention to a few basic rules installation cast iron soil pipe and fittings is easily accomplished. 1) Cast iron soil pipe installed in horizontal position shall be supported at every coupling. The hanger shall be placed within 18 in. coupling. Joints used for connecting cast iron soil pipe possess sufficient shear strength to require one hanger per joint. For 12 in. and 15 in. hubless pipe, hangers shall be placed on both sides coupling when installing full 10-ft lengths. 2) Installations requiring multiple joints within a four foot developed length shall be supported at every or or alternating couplings. Vertical components shall be secured at each stack base and at sufficiently close intervals to keep system in alignment and to adequately support pipe and its contents. Riser clamps, sometimes called floor or friction clamps are required for vertical piping in multi-story structures in order for each floor not to exceed 15 ft. 21

22 r strapping a closet bend under a sub-floor and how a clevis type hanger has been used. hubless blind plug is used for a required cleanout, complete coupling and plug accessible for removal and replacement. ection closet rings, floor and shower drains and similar slip-over fittings, and Large Diameter Fittings n hubless pipe and fittings to soil pipe hubs may be accomplished by use ead and oakum or compression joints. Horizontal pipe and fittings five (5) (5) in. in. and and larger shall shall be be suitably restrained braced to prevent horizontal 54 INSTALLATION movement. This shall be done at every branch opening or change direction by use braces, blocks, rodding or or suitable method, to prevent movement. Closet bends, traps, trap-arms and similar branches must be secured against movement in any direction. Closet bends installed above ground shall be stabilized by firmly strapping and blocking. Where vertical closet stubs are used y must be stabilized against horizontal or vertical movements. Figure 10 Bracing Large-Diameter Pipe (continued). INSTALLATION Figure 11 Cross-Section View Closet Bend Showing Flange Properly Secured. Figure 10 Bracing Large-Diameter Pipe (continued on facing re 10 Bracing Large-Diameter Pipe (continued). Figure 12 Method Using Hanger for Closet Bend. 22 Figure 10 Bracing Large-Diameter Pipe (continued on facing page).

23 INSTALLATION 55 INSTALLATION 55 Vertical Piping INSTALLATION 55 Vertical Piping Vertical components should be secured at each stack base and at sufficiently close intervals to keep GENERAL Vertical Piping INSTALLATION INSTRUCTIONS Vertical system in components alignment should and to be adequately secured at support each stack weight base and at sufficiently pipe and its close contents. intervals Floor to keep clamps, A. system sometimes Vertical in alignment Piping: called friction and to clamps, adequately are required support for vertical weight piping pipe in multistory and its contents. structures Floor so that clamps, each Vertical components should be secured at each stack base and at sufficiently close intervals to keep sometimes floor carries called its share friction clamps, load. are Figures required 13 and for 14 vertical show piping some typical in multistory brackets structures or braces so for that vertical system in alignment and to adequately support weight pipe and its contents. Floor clamps, each floor piping. 1) sometimes carries Secure Figure called its vertical 15 share shows friction piping a method clamps, load. at sufficiently Figures clamping are required 13 close and for 14 intervals pipe vertical show at each some to keep floor piping typical using in multistory brackets pipe a friction in alignment structures or braces or floor so for and clamp. that vertical to support each piping. If floor carries Figure vertical weight its 15 piping share shows is a to pipe method stand and free load. its Figures clamping contents. any support, 13 and Support 14 pipe show at if each no stacks structural some floor at typical using ir element brackets a bases friction is available and or or braces floor at sufficient for for clamp. support floor vertical and stability piping. If intervals vertical during Figure 15 piping to meet construction, shows is to a method stand requirements free secure clamping any support, piping local codes. in pipe or its if at no proper Approved each structural position metal floor using element by clamps means a friction is available or adequate hangers or floor for clamp. support should metal be and stakes stability used or braces for If vertical during this fastened purpose. piping construction, to pipe. is to stand free secure any piping support, in or its if proper no structural position element by means is available adequate for support metal stakes 2) If and stability or vertical braces during fastened piping is construction, to to stand pipe. free any support or if no structural element is available for support and stability during construction, secure secure piping in piping its proper in its position proper by position means by means adequate metal adequate stakes stakes or braces or braces fastened fastened to to pipe. pipe. Figure 13 Bracket for Vertical Pipe. Figure 13 Bracket for Vertical Pipe. Figure 13 Bracket for Vertical Pipe. Figure 14 One Hole Strap for Vertical Pipe. Figure 14 One Hole Strap for Vertical Pipe. Figure 14 One Hole Strap for Vertical Pipe. Figure 15 Method Clamping Pipe at Each Floor, Figure 15 Method Using a Friction Clamping Clampor Floor Pipe Clamp. at Each Floor, Figure 15 Method Using a Friction Clamping Clampor Floor Pipe Clamp. at Each Floor, Using a Friction Clampor Floor Clamp. 23

24 B. Horizontal Piping, Suspended : 1) Support horizontal piping and fittings at sufficiently close intervals to maintain alignment and prevent sagging or grade reversal. Support each length pipe by an approved hanger located not more than 18 in. from joint. For 12 in. and 15 in. hubless pipe, hangers shall be placed on both sides coupling when installing full 10-ft lengths. 2) Support terminal ends all horizontal runs or branches and each change direction or alignment with an approved hanger. 3) Closet bends installed above ground should be firmly secured. C. Horizontal Piping, Underground : 1) To maintain proper alignment during backfilling, stabilize pipe in proper position by partial backfilling and cradling. 2) Piping laid on grade should be adequately secured to prevent misalignment when slab is poured. 3) Closet bends installed under slabs should be adequately secured. D. Installation Inside Building: 1) Installation Suggestions According to most authorities and plumbing codes, it is sufficient to support horizontal pipe at each joint, that is, 5-ft pipe should be supported at 5-ft intervals, 10-ft in length may be supported at 10-ft intervals. Supports should be adequate to maintain alignment and prevent sagging and should be placed within 18 in. joint. NOTE: For 12 in. and 15 in. hubless pipe, hangers shall be placed on both sides coupling when installing full 10-ft lengths. When system is filled with water, sufficient beam strength is provided by cast iron soil pipe to carry load with hangers every ten feet. Any horizontal supports or clamps illustrated in Figures 1 and 2 may be used, depending on conditions or what is regarded as essential by contractor, architect or engineer. Whatever method support or clamp is used for horizontal line, care should be exercised to make certain that line has a proper grade (1/4 in. or more per foot). 24

25 Hangers may be fastened to wood members or beams with wood screws, lag screws or large nails. For fastening to I beams, bar joists, junior beams or or structural members, beam clamps or C clamps may be used. Fasteners for masonry walls may be expansion bolts or screws, or where a void is present, toggle bolt may be used. Studs shot into masonry by explosion method may also be used. Along a wall, a bracket made structural members or a cast bracket may be used. Adequate provision should be made to prevent shear. Where components are suspended in excess eighteen (18) in. by means non-rigid hangers y should be suitably braced against movement horizontally, ten called sway bracing. Examples sway bracing are illustrated in Figures 3 and 4. Horizontal Installation Large Diameter Pipe: Horizontal pipe and fittings five (5) (5) in. in. and and larger must must be be suitably restrained braced to prevent horizontal movement. This must be done at every branch opening or change direction by use braces, blocks, rodding or or suitable method, to prevent movement or joint separation. Figure 5 illustrates several methods bracing. restraint. 25

26 Suggested Installation Horizontal Fittings: Suggested Installation Horizontal Fittings: a) Hangers a) Hangers should be should provided be as provided necessary to as provide necessary alignment to provide and grade. alignment Hangers should and grade. be Hang provided provided at each horizontal at each branch horizontal connection. branch Hangers connection. should be Hangers adequate should to maintain be alignment adequate to main and prevent sagging and should be placed adjacent to coupling. By placing hangers properly, and prevent proper grade sagging will be and maintained. should Adequate be placed provision adjacent should to be made coupling. to prevent By placin shear. Where properly, pipe and fittings proper are grade suspended will in be excess maintained. eighteen Adequate inches by means provision non-rigid should be ma hangers shear. y should Where be suitably pipe and braced fittings against are movement suspended horizontally, in excess ten called eighteen sway bracing. inches by mean Refer to hangers Figures 3 y and 4 should for illustrations. be suitably braced against movement horizontally, ten called b) Closet bends, Refer traps, to Figures trap-arms 3 and similar 4 for illustrations. branches must be firmly secured against movement in any direction. Closet bends installed above ground should be stabilized. Where vertical closet studs b) are Closet used y bends, must be traps, stabilized trap-arms against and horizontal similar or vertical branches movement. must be In Figures firmly 6 secured and 7, against see illustration any direction. for strapping Closet a closet bends under installed a sub-floor above and ground how a clevis should type hanger be stabilized. has been Where used to an studs advantage. are used y must be stabilized against horizontal or vertical movement. In Fi c) When a hubless see illustration blind plug for is used strapping for a required a closet cleanout, bend under complete a sub-floor coupling and plug how must a clevis be type ha accessible used for removal to an advantage. and replacement. d) The connection closet rings, floor and shower drains and similar slip-over fittings and connection c) When hubless a hubless pipe blind and fittings plug is to used soil pipe for a hubs required may be cleanout, accomplished complete by use coupling and caulked lead accessible and oakum for or removal compression and joints. replacement. d) The connection closet rings, 26 floor and shower drains and similar slip-over fi connection hubless pipe and fittings to soil pipe hubs may be accomplished

27 27

28 Seismic Restraints: The following recommendations are some factors to consider when installing cast iron pipe in seismically active areas. All installations must comply with local codes and instructions architects or engineers who are responsible for piping design. A. Brace all pipe 2 in. and larger. Exceptions: Seismic braces may be omitted when top pipe is suspended 12 in. or less from supporting structure member and pipe is suspended by an individual hanger. 28

29 B. Vertical Piping Attachment Vertical piping shall be secured at sufficiently close intervals to keep pipe in alignment and carry weight pipe and contents. Stacks shall be supported at ir bases and if over two stories in height at each floor by approved floor clamps. At vertical pipe risers, whenever possible, support weight riser at a point or points above center gravity riser. Provide lateral guides at top and bottom riser, and at intermediate points not to exceed 30 ft-0 in. on center. C. Horizontal Piping Supports Horizontal piping shall be supported at sufficiently close intervals to prevent sagging. Trapeze hangers may be used. Pipe, where top pipe is 12 in. or more from supporting structure shall be braced on each side a change direction 90 or more. D. Traverse Bracing 40 ft-0 in. o.c. maximum spacing unless orwise noted. One pipe section may act as longitudinal bracing for pipe section connected perpendicular to it, if bracing is installed with 24 in. elbow or tee similar size. E. Longitudinal Bracing 80 ft-0 in. o.c. maximum spacing unless orwise noted. F. Miscellaneous Provide large enough pipe sleeves through walls or floors to allow for anticipated differential movements. WHERE MULTIPLE SHIELD AND CLAMP JOINTS OCCUR IN A CLOSELY SPACED ASSEMBLY (THAT IS, FITTING FITTING-FITTING, ETC.) A 16 GAUGE HALF SLEEVE MAY BE INSTALLED UNDER THE ASSEMBLY WITH A PIPE HANGER AT EACH END OF THE SLEEVE. 29

30 Vertical Piping: Vertical components should be secured at each stack base and at sufficiently close intervals to keep system in alignment and to adequately support weight pipe and its contents. Floor clamps, sometimes called friction clamps, are required for vertical piping in multi-story structures in order for each floor to carry its share load. Figures 9 and 10 show some typical brackets or braces for vertical piping. Figure 11 shows a method clamping pipe at each floor, using a friction or floor clamp. If vertical piping is to stand free any support or if no structural element is available for support and stability during construction, secure piping in its proper position by means adequate metal stakes or braces fastened to pipe. 30

31 31 31

32 Testing and Inspection Once roughing-in is completed on a cast iron piping project, it is important to test and inspect all piping for leaks. The installer usually is required to notify plumbing inspector administrative authority having jurisdiction over plumbing work before tests are made. Concealed work should remain uncovered until required tests are made and approved. When testing, system should be properly restrained at all bends, changes direction, and ends runs. There are various types tests used for installed cast iron soil pipe and fittings. These are water or hydrostatic, air, smoke and peppermint. Proper safety procedures and protective equipment should be employed during all testing procedures. Installers should always consider local conditions, codes, manufacturer installation instructions, and architect/engineer instructions in any installation. A water test, also called a hydrostatic test, is made all parts drainage system before pipe is concealed or fixtures are in place. This test is most representative operating conditions system. Tests this type may be made in sections on large projects. After all air is expelled, all parts system are subjected to 10-ft hydrostatic pressure (4.3 psi) and checked for leaks. Test Procedures: Water Test - A water or hydrostatic test is most common all tests used to inspect a completed cast iron soil pipe installation. The purpose test is to locate any leaks at joints and correct se prior to putting system in service. Since it is important to be able to visually inspect joints, water tests should be conducted prior to closing in piping or back fill underground piping. As water fills a vertical cylinder or vertical pipe it creates hydrostatic pressure. The pressure increases as height water in vertical pipe increases. The Cast Iron Soil Pipe Institute recommends 10-ft hydrostatic pressure (4.3 psi). This is recommended test by most plumbing codes. To isolate each floor or section being tested, test plugs are inserted through test tees installed in stacks. All or openings should be plugged or capped with test plugs or test caps (see Figure 12). Prior to beginning test, all bends, changes direction and ends runs should be properly restrained. During test, thrust forces are exerted at se locations. Thrust is equal to hydrostatic pressure multiplied by area. Thrust pressures, if not restrained, will result in joint movement or separation causing failure test. All air entrapped in system should be expelled prior to beginning tests. Once stack is filled to ten feet, an inspector makes a visual inspection section being tested to check for joint leaks. In most cases, where se leaks are found, hubless couplings have not been torqued to recommended 60 lbf-in. or for couplings requiring higher torque improper torquing occurred. Proper torquing will correct problem. Fifteen minutes is a suitable time for water test. Once system has been successfully tested it should be drained and next section should be prepared for test. Thrust Forces: Thrust or displacement forces are encountered as pipe or cylinder is filled with water. The higher fill greater force acting to separate a joint. The Thrust Table shows pounds force tending to cause joint separation when using pipe from 1 ½ to 15 and a head water from 10 to

33 THURST TABLE Thrust or Displacement Forces Encountered in Hydrostatic Testing Hubless Cast Iron Soil Pipe Pipe 11/ Size, in. HEAD, feet Press ure, Thrust, lb Thrust, lb Thrust, lb Thrust, lb Thrust, lb Thrust, lb Thrust, lb Thrust, lb Thrust, lb Thrust, lb water psi Area, OD in A Thrust = Pressure Area. 33

34 34 34

35 Typical power operated torque tools used for coupling assembly

36 NOTES

SUBMITTAL 10 FEET. Cast Iron Soil Pipe Products Hubless Pipe & Fittings HUBLESS PIPE 10 FEET*

SUBMITTAL 10 FEET. Cast Iron Soil Pipe Products Hubless Pipe & Fittings HUBLESS PIPE 10 FEET* QUALITY SYSTEM SUBMITTAL Hubless Pipe & Fittings R E G I S T R AT I O N Manufacturer s T J B 10 FEET HUBLESS PIPE 10 FEET* NOM. SIZE B INSIDE DIAMETER J OUTSIDE DIAMETER 1 1/2 1.50 1.90 0.16 0.13 28.4

More information

SECTION 221413 FACILITY STORM DRAINAGE PIPING

SECTION 221413 FACILITY STORM DRAINAGE PIPING SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

SECTION 33 11 00.11 POLYVINYL CHLORIDE (PVC) PIPE

SECTION 33 11 00.11 POLYVINYL CHLORIDE (PVC) PIPE SECTION 33 11 00.11 POLYVINYL CHLORIDE (PVC) PIPE PART 1: GENERAL 1.01 SECTION INCLUDES PVC pressure pipe and fabricated fittings in nominal sizes 4-inches through 12-inches with cast iron pipe equivalent

More information

Wastewater Capital Projects Management Standard Construction Specification

Wastewater Capital Projects Management Standard Construction Specification CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,

More information

SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS

SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. The requirements for pipe material and installation in sewer and drainage collection systems. All materials

More information

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL 1.01 DESCRIPTION A. Furnish and install all storm drains, including manholes, inlets, service lines and other appurtenant

More information

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC) APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines

More information

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel

More information

The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.

The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified. Section 33 0200- Page 1 of 4 PART 1 - GENERAL 1.1 DESCRIPTION OF WORK The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.

More information

DIVISION 4300 STORM DRAINAGE

DIVISION 4300 STORM DRAINAGE DIVISION 4300 STORM DRAINAGE SECTION 4305 STORM SEWER PART 1 - GENERAL 1.01 SCOPE This section covers the construction of storm sewers for the collection and transport of stormwater runoff. 1.02 REFERENCES

More information

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701) SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701) 55-1 GENERAL The Contractor shall perform all work required by the plans for construction of pipe for storm drains, precast polymer trench drains

More information

SECTION 02630 STORM DRAINAGE SYSTEM

SECTION 02630 STORM DRAINAGE SYSTEM SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE

More information

Guidelines for Earthquake Bracing Residential Water Heaters

Guidelines for Earthquake Bracing Residential Water Heaters Guidelines for Earthquake Bracing Residential Water Heaters Department of General Services Division of the State Architect In accordance with the Health and Safety Code Section 19215, the Division of the

More information

Guidelines for Earthquake Bracing of Residential Water Heaters

Guidelines for Earthquake Bracing of Residential Water Heaters Guidelines for Earthquake Bracing of Residential Water Heaters Department of General Services Division of the State Architect 1102 Q Street, Suite 5100 Sacramento, CA 95814 Phone: (916) 324-7099 Fax: (916)

More information

SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS

SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS PART 1: GENERAL 1.01 COORDINATION OF WORK Connection to existing pipelines may require shutdown of AW facilities. Closely coordinate construction work

More information

Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer

Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer The user may choose to adopt part or all of this Model Specification; however, the user should ensure that all parts

More information

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13)

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13) Page 1 of 7 STONE STRONG SYSTEMS SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised ) PART 1: GENERAL 1.01 Description A. Work includes furnishing and installing precast modular blocks

More information

AMERICAN Mechanical Joint Pipe For Water, Sewage or Other Liquids

AMERICAN Mechanical Joint Pipe For Water, Sewage or Other Liquids AMERICAN Mechanical Joint Pipe For Water, Sewage or Other Liquids The AMERICAN Mechanical Joint was developed by the American Cast Iron Pipe Company and first marketed in 1929. Since that time, millions

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

SECTION 02400 - STORM DRAIN SYSTEM

SECTION 02400 - STORM DRAIN SYSTEM SECTION 02400 - STORM DRAIN SYSTEM CONTENTS: Part 1 - General... 1 1.01 Work Included... 1 1.02 Related Requirements... 1 1.03 Reference Standards... 1 1.04 Quality Assurance... 1 1.05 Measurement And

More information

SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS

SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS 1001 SOUTH LEECHBURG HILL LEECHBURG, PA 15656 Phone: 724-845-9355 Fax: 724-845-1186 SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS 1. General

More information

SECTION 9.02 BUILDING SUBSURFACE DRAINS (PERIMETER, ETC.)

SECTION 9.02 BUILDING SUBSURFACE DRAINS (PERIMETER, ETC.) CHAPTER 9 SEWER / STORM DRAIN / IRRIGATION LINES SECTION 9.01 GENERAL This section covers the requirements for piping materials and installation of Lehi City sewer, storm drainage and irrigation collection

More information

Top 10+ Mistakes of DWV plumbing design

Top 10+ Mistakes of DWV plumbing design Top 10+ Mistakes of DWV plumbing design Listed below are the some of the most frequently missed items, noticed by our inspectors, at plumbing rough-in when non-plumbers attempt plumbing design. Most of

More information

San Antonio Water System Standard Specifications for Construction ITEM NO. 1100 SLIP-LINING SANITARY SEWERS

San Antonio Water System Standard Specifications for Construction ITEM NO. 1100 SLIP-LINING SANITARY SEWERS ITEM NO. 1100 SLIP-LINING SANITARY SEWERS 1100.1 DESCRIPTION: This item shall consist of slip-lining sanitary sewer pipe, which is accomplished by pulling or pushing liner pipe into existing sewers by

More information

4 Installation Requirements

4 Installation Requirements 4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming

More information

SECTION 15105 DUCTILE IRON PIPE AND FITTINGS

SECTION 15105 DUCTILE IRON PIPE AND FITTINGS SECTION 15105 DUCTILE IRON PIPE AND FITTINGS PART 1 GENERAL.01 COORDINATION OF WORK Connection to existing pipelines may require shutdown of Owner facilities. Closely coordinate construction work and connections

More information

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS While its use is not required, this checklist has been prepared to provide the field inspector a summary

More information

A. This Section includes the following for soil, waste, and vent piping inside the building:

A. This Section includes the following for soil, waste, and vent piping inside the building: June 2014, Draft 01 22 1316 Sanitary and Waste Vent Piping PART 1. GENERAL 1.01 Summary A. This Section includes the following for soil, waste, and vent piping inside the building: 1. Pipe, tube, and fittings.

More information

TECHNICAL NOTE Lining of Casings with SaniTite HP Pipe

TECHNICAL NOTE Lining of Casings with SaniTite HP Pipe TECHNICAL NOTE Lining of Casings with SaniTite HP Pipe TN 5.18 October 2015 In sanitary sewer, it is often necessary to use trenchless technology methods to install a casing pipe under high volume roads,

More information

IHSS-N1 WELDED HONEYCOMB CORE SPECIFICATION. Generated: Sergiy Papyshev Engineering. Approved: Don Prysi Manufacturing. Approved: Merzuk Ramic Quality

IHSS-N1 WELDED HONEYCOMB CORE SPECIFICATION. Generated: Sergiy Papyshev Engineering. Approved: Don Prysi Manufacturing. Approved: Merzuk Ramic Quality IHSS-N1 WELDED HONEYCOMB CORE SPECIFICATION Generated: Sergiy Papyshev Engineering Approved: Don Prysi Manufacturing Approved: Merzuk Ramic Quality Approved: Steven Barnett Administrative DATE DATE DATE

More information

SECTION 33 05 16.13 PRECAST CONCRETE UTILITY STRUCTURES

SECTION 33 05 16.13 PRECAST CONCRETE UTILITY STRUCTURES SECTION 33 05 16.13 PRECAST CONCRETE PART 1 - GENERAL 1.01 SECTION INCLUDES A. This item shall consist of the construction of both sanitary and storm sewer precast concrete manholes in accordance with

More information

PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta

PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification Number: 3503-11.2.610 Rev. 2 Rubber Lined Steel Pipe and Fittings Mechanically Coupled Plain End Type System Issued Revised Approved

More information

CONTRACT SPECIFICATIONS - SEISMIC ISOLATION BEARINGS

CONTRACT SPECIFICATIONS - SEISMIC ISOLATION BEARINGS CONTRACT SPECIFICATIONS - SEISMIC ISOLATION BEARINGS 1.0 DESIGN 1.1 Scope of Work 1.1.1 This work shall consist of furnishing Isolation Bearings and installing Isolation Bearing Assemblies at the locations

More information

BIBBY-STE-CROIX Cast Iron Soil Pipe and Fittings

BIBBY-STE-CROIX Cast Iron Soil Pipe and Fittings Cast Iron Soil Pipe and Fittings Bibby-Ste-Croix is a Canadian manufacturer of cast iron soil pipe and fittings. Bibby s strength through the years has been its commitment to meeting the changing requirements

More information

V47 Series Temperature Actuated Modulating Water Valves

V47 Series Temperature Actuated Modulating Water Valves V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information

Beacon Hill Sewer District Standard Specifications

Beacon Hill Sewer District Standard Specifications Beacon Hill Sewer District Standard Specifications Residential Gravity Side Sewer Including Design Criteria and Standard Construction Drawings Residential Gravity Side Sewer Design Criteria 1. Provisions

More information

TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE

TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE TECHNICAL SPECIFICATION PART 8000 - PRECAST CONCRETE TABLE OF CONTENTS Item Number Page 8100 PRECAST CONCRETE CONSTRUCTION - GENERAL 8-3 8101 General

More information

LS 2540 SEWER LATERALS AND INSPECTION TEES

LS 2540 SEWER LATERALS AND INSPECTION TEES LS 2540 SEWER LATERALS AND INSPECTION TEES A. Summary B. Submittals C. Site Information D. Sewer Pipe and Fittings E. Lateral Locations F. Lateral Installation G. Inspection Tee Installation H. Removal

More information

INDEX. Sec. No. Items Page Nos.

INDEX. Sec. No. Items Page Nos. INDEX Sec. No. Items Page Nos. 1. Types of Pipe............... MSSP- 2 2. Concrete Pipe............... MSSP- 2 thru MSSP-3 3. ABS and PVC Truss Pipe............... MSSP- 3 4. ABS and PVC Solid Wall Pipe...............

More information

STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY

STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY Approved and adopted as Official Document Number 800576 this 10th day of December, 1980 Donald R. Boyd, P.E., Director Water

More information

How to Install Hardwood Flooring Over a Sub Floor

How to Install Hardwood Flooring Over a Sub Floor How to Install Hardwood Flooring Over a Sub Floor Installation Preparation Instructions Read the entire instructions before starting your project. 1) INSPECT EACH PLANK (see fig. a) Wood is a natural product

More information

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona for Earthen Material and Straw Bale Structures SECTION 70 - GENERAL "APPENDIX CHAPTER 7 - EARTHEN MATERIAL STRUCTURES 70. Purpose. The purpose of this chapter is to establish minimum standards of safety

More information

TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe

TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe TN 5.14 February 2010 Introduction It may be at times necessary, in an aging infrastructure, to rehabilitate drainage and sanitary lines

More information

SECTION 15140 - PIPE HANGERS AND SUPPORTS

SECTION 15140 - PIPE HANGERS AND SUPPORTS Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the

More information

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions. SECTION LS 2530 SANITARY SEWERS PART 1 GENERAL 1.1 SUBMITTALS A. General: Submit the following in accordance with The General Conditions. 1. Product data for drainage piping specialties. 2. Shop drawings

More information

SECTION 08000 STORM DRAINAGE TABLE OF CONTENTS

SECTION 08000 STORM DRAINAGE TABLE OF CONTENTS SECTION 08000 STORM DRAINAGE 08010 DESIGN A. Location B. Sizing TABLE OF CONTENTS 08020 MATERIALS A. Pipe Materials B. Structure Materials C. Installation D. Inlets and Outlets 08030 INSPECTIONS AND TESTING

More information

CONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION

CONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION CONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION General 7 www.meadowburke.com 877-518-7665 MB1109 CONCRETE FLOOR SLAB AND CASTING BED CONSTRUCTION Quality Construction Begins at Ground Level Everything

More information

Section 02702 SEWER PIPE INSTALLATION AND TESTING

Section 02702 SEWER PIPE INSTALLATION AND TESTING PART 1 - GENERAL Section 02702 SEWER PIPE INSTALLATION AND TESTING 1-1. SCOPE. This section covers the installation and testing of all sewer pipe furnished under the following specification sections: Concrete

More information

SFI SPECIFICATION 28.1 EFFECTIVE: SEPTEMBER 23, 2011 *

SFI SPECIFICATION 28.1 EFFECTIVE: SEPTEMBER 23, 2011 * SFI SPECIFICATION 28.1 EFFECTIVE: SEPTEMBER 23, 2011 * PRODUCT: Polymer (Foam-Filled) Fuel Cells 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards

More information

Drive shaft, servicing

Drive shaft, servicing Volkswagen Passat B6 - Drive shaft, servicing Стр. 1 из 41 40-7 Drive shaft, servicing Drive shafts, overview I - Assembly overview: Drive axle with CV joint VL100 40-7, Drive axle with CV joint VL100,

More information

53.03 MATERIALS FOR SEWER LINER PIPE AND FITTINGS: The following materials are approved for installation in sanitary sewer lines:

53.03 MATERIALS FOR SEWER LINER PIPE AND FITTINGS: The following materials are approved for installation in sanitary sewer lines: Division 53: Slip-Lining of Existing Sewer Line 53.01 GENERAL: This section includes all labor, materials, transportation, equipment necessary to rehabilitate by means of Instituform deteriorated sections

More information

CHAPTER 9 VENTS. copper drainage tube Type DWV, Schedule 40 plastic piping, or borosilicate glass.

CHAPTER 9 VENTS. copper drainage tube Type DWV, Schedule 40 plastic piping, or borosilicate glass. CHAPTER 9 VENTS 901 GENERAL 901.1 Scope The provisions of this chapter shall govern the materials, design, construction, and installation of vents. 901.2 Protection of Trap Seals The protection of trap

More information

SECTION 03400 PRECAST CONCRETE STRUCTURES

SECTION 03400 PRECAST CONCRETE STRUCTURES PART 1 GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, and equipment required to install precast concrete manholes, sanitary leaching rings, pump station, valve chamber, structures, frames,

More information

DeZURIK 3-20" BAW AWWA BUTTERFLY VALVES WITH TRANSFER MOLDED SEAT

DeZURIK 3-20 BAW AWWA BUTTERFLY VALVES WITH TRANSFER MOLDED SEAT 3-20" BAW AWWA BUTTERFLY VALVES WITH TRANSFER MOLDED SEAT Instruction D10386 August 2013 Instructions These instructions provide installation, operation and maintenance information for BAW Butterfly Valves.

More information

Section 2100-Trenching and Tunneling

Section 2100-Trenching and Tunneling SECTION 5200 - STORM SEWER PART 1 - GENERAL 1.01 SCOPE: This Section covers installation of storm sewer mains and culverts. Topics include permits and fees, trench widths, pipe laying, bedding, initial

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller

AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller January 2013 AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller Milliken Valve Company 190 Brodhead Avenue, Suite 100 Bethlehem, PA 18017 Phone: (610) 861-8803 Fax:

More information

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing

More information

Green Thread Product Data

Green Thread Product Data Green Thread Product Data Applications Dilute Acids Caustics Produced Water Industrial Waste Hot Water Condensate Return Materials and Construction All pipe manufactured by filament winding process using

More information

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector Plumbing Helpful Hints Residential Construction Bert Polk Plumbing Inspector Lincoln County 2015 Waste and vent fittings Vent 90 medium 90 long 90 1/16 bend,1/8 bend,1/6 bend, medium 90 san tee combination

More information

EFFECTIVE FEBRUARY 2014. note: drainage permit required to call for a dampproof inspection

EFFECTIVE FEBRUARY 2014. note: drainage permit required to call for a dampproof inspection EFFECTIVE FEBRUARY 2014 note: drainage permit required to call for a dampproof inspection 1. ROOF DRAINS/DECK DRAINS (INTERIOR ) All roof and deck drains within the perimeter of the building shall be APPROVED

More information

SECTION 1 GENERAL REQUIREMENTS

SECTION 1 GENERAL REQUIREMENTS Page 1 of 6 SECTION 1 GENERAL REQUIREMENTS 1. SCOPE OF WORK: The work to be performed under the provisions of these documents and the contract based thereon includes furnishing all labor, equipment, materials,

More information

Check for deteriorated, shifting or missing tie-down pads. Replace if needed.

Check for deteriorated, shifting or missing tie-down pads. Replace if needed. C C 0 5 C H A S S I S F R A M E Chassis Frame Overview The Blue Bird Vision s chassis frame consists of two main C-channel rails which run the entire length of the bus, and several different kinds of cross

More information

DiscPlus DX195 and DX225 Air Disc Brakes

DiscPlus DX195 and DX225 Air Disc Brakes Revised 11-04 Technical Bulletin Revised 1 Technical 11-04 Bulletin DiscPlus DX195 and DX225 Air Disc Brakes Inspection, Installation and Diagnostics Air Disc Brake Inspection Intervals and Procedures

More information

FORM DESIGN. easy to work with, and generally available.

FORM DESIGN. easy to work with, and generally available. Forms play a major role in concrete construction. They give the plastic concrete its shape and hold it until it hardens. Forms protect the concrete, assist in curing it, and support any reinforcing rods

More information

LAYING BLOCK AND BRICK

LAYING BLOCK AND BRICK LAYING BLOCK AND BRICK Products highlighted in this section: SAKRETE Type N Mortar Mix SAKRETE Type S Mortar Mix Brick And Block Laying Basics The first step in building a brick or block wall is to construct

More information

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE 6.01 SCOPE The work covered by this section of the specifications consists of the furnishing of all plant, labor, materials, equipment and supervision and performing all operations involved in the construction

More information

60.12. Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING

60.12. Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING 60.1 D-O-L FxE expansion couplings are a bolted, split-sleeve design that provides for expansion and contraction at the coupled joint. These couplings are furnished with restraint rings that, when affixed

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION

SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION 1. SCOPE Pipe subsoil drains shall be constructed in accordance with this specification and in conformity with the lines, grades and cross-sections shown

More information

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing 1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize

More information

Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996

Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996 CITY OF SAN JOSE BUILDING DIVISION POLICY Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996 All new and replacement water heaters installed

More information

These features have made Lo Torc valves the choice of high pressure plug value users, worldwide:

These features have made Lo Torc valves the choice of high pressure plug value users, worldwide: LO TORC Plug Valve The high value, dependable performance, and low maintenance requirements of Halliburton Lo Torc valves can help reduce overall operating costs and help cut downtime. These features have

More information

SANITARY SEWER SPECIFICATIONS

SANITARY SEWER SPECIFICATIONS SANITARY SEWER SPECIFICATIONS OCTOBER 2003 HARVEST-MONROVIA WATER, SEWER, AND FIRE PROTECTION AUTHORITY SECTION 1.00 1.10 Purpose The purpose of this document is to assemble the sewer specifications, policies,

More information

1993 SUSPENSION Volkswagen Front. EuroVan

1993 SUSPENSION Volkswagen Front. EuroVan Article Text ARTICLE BEGINNING 1993 SUSPENSION Volkswagen Front EuroVan DESCRIPTION FWD independent suspension is an double-wishbone type with torsion bars mounted on upper control arm. Wheel is supported

More information

Installation Manual. Solar Pool Heating System. Read the complete manual before beginning the installation

Installation Manual. Solar Pool Heating System. Read the complete manual before beginning the installation Solar Pool Heating System Installation Manual Read the complete manual before beginning the installation 1. Sizing the System Visit www.techno-solis.com to size the system using the sizing calculator.

More information

Royal Seal Gasketed Sewer Pipe

Royal Seal Gasketed Sewer Pipe Royal Seal Gasketed Sewer Pipe Royal Seal Gasketed Sewer Pipe Royal Seal gasketed sewer pipe with our specially designed Double Seal Locked-In (DSLI ) gasket is an extremely durable pipe with a leak proof

More information

PANELIZED HOME INSTALLATION GUIDELINE

PANELIZED HOME INSTALLATION GUIDELINE PANELIZED HOME INSTALLATION GUIDELINE A typical home package will be constructed of Snap-N-Lock Insulated Panels clad with steel skins. 4" panels will be used for the walls, and 6" panels for the roof.

More information

Installation Instructions For Slider Casement Air Conditioners

Installation Instructions For Slider Casement Air Conditioners Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT

More information

SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes seismic restraints and other earthquake-damage-reduction measures for electrical

More information

I BEAM TRACK INSTALLATION

I BEAM TRACK INSTALLATION PDQ 0/700 FESTOON SYSTEM INSTALLATION AND MAINTENANCE INSTRUCTIONS INTRODUCTION The PDQ Festoon System was designed to run on one of three sizes of I-beams: S x., S8 x 8. and S x.. System trolleys must

More information

A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.

A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials. PART 1 GENERAL 1.1 SCOPE A. This item shall include the work necessary for the installation of storm sewer line construction. B. Reference Section 3800 Trenching and Backfill and the General Conditions,

More information

Round Housing with Side Ports

Round Housing with Side Ports Power Steering Steering Control Unit (SCU) Parts and Repair Information 5 Series Steering Control Units 001 Square Housing with Side Ports Round Housing with Side Ports T E L RP Round Housing with End

More information

SECTION 02401 - SANITARY SEWER PIPE

SECTION 02401 - SANITARY SEWER PIPE PART 1 - GENERAL 1.1 DESCRIPTION A. The WORK under this Section includes providing all labor, materials, tools and equipment necessary for furnishing and installing sanitary sewer pipe, in accordance with

More information

CEEN 162 - Geotechnical Engineering Laboratory Session 7 - Direct Shear and Unconfined Compression Tests

CEEN 162 - Geotechnical Engineering Laboratory Session 7 - Direct Shear and Unconfined Compression Tests PURPOSE: The parameters of the shear strength relationship provide a means of evaluating the load carrying capacity of soils, stability of slopes, and pile capacity. The direct shear test is one of the

More information

SWIMMING POOL, SPA, & HOT TUB GUIDELINES

SWIMMING POOL, SPA, & HOT TUB GUIDELINES SWIMMING POOL, SPA, & HOT TUB GUIDELINES Pool permit cost is based on the total value of the project. See Permit Fee Schedule Table 1A. A. Adopted construction codes and installation requirements 1. 2015

More information

Char-Lynn Spool Valve Hydraulic Motors. Repair Information. W Series Geroler Motors

Char-Lynn Spool Valve Hydraulic Motors. Repair Information. W Series Geroler Motors Char-Lynn Spool Valve Hydraulic Motors Repair Information W Series Geroler Motors with Parking Brake 004 Nut Key Ring, Retaining Bearing Ring, Retaining Ring, Retaining Washer (Thick), Pressure Washer,

More information

Installation Instructions 4508 4508S

Installation Instructions 4508 4508S SYMPHONY Spread Lavatory Faucet with Speed Connect Drain Congratulations on purchasing your American Standard faucet with Speed Connect drain, a feature found only on American Standard faucets. Speed Connect

More information

Featuring TJ Rim Board and TimberStrand LSL

Featuring TJ Rim Board and TimberStrand LSL #TJ-8000 SPECIFIER S GUIDE TRUS JOIST RIM BOARD Featuring TJ Rim Board and TimberStrand LSL Multiple thicknesses, grades, and products to cover all your rim board needs 1¼" Thickness matches lateral load

More information

Wisconsin Building Products Evaluation

Wisconsin Building Products Evaluation Safety & Buildings Division 201 West Washington Avenue P.O. Box 2658 Madison, WI 53701-2658 Evaluation # 200813-O Wisconsin Building Products Evaluation Material Best Management Standards for Foundation

More information

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors. SUBDRAINS AND FOOTING DRAIN COLLECTORS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Subdrains B. Subdrain Cleanouts and Outlets C. Footing Drain Collectors D. Storm Sewer Service and Connections 1.02 DESCRIPTION

More information

General Guidelines for Repairing Buried PE Potable Water Pressure Pipes

General Guidelines for Repairing Buried PE Potable Water Pressure Pipes 515 General Guidelines for Repairing Buried PE Potable Water Pressure Pipes Introduction Traditional piping systems have gasket-sealed bell and spigot joints every 20 feet, which can be a potential maintenance

More information

Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL

Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL 155 E. Front Street (rear) Lititz, PA 17543 Phone (717) 625-1930 Fax (717) 625-1931 Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL CONSTRUCTION SPECIFICATIONS AND DETAILS

More information

SECTION 724 PIPE CULVERTS

SECTION 724 PIPE CULVERTS SECTION 724 PIPE CULVERTS 724.1 Description. This work shall consist of providing pipe or pipe arch of the diameter or shape designated, laid upon a firm bed and backfilled as specified. Where appropriate

More information

necessary for years of satisfactory service. SmartBlock insulating form concrete walls share the

necessary for years of satisfactory service. SmartBlock insulating form concrete walls share the Chapter 7 PLUMBING AND ELECTRICAL 7.1 Introduction to Plumbing and Electrical Consideration of support services such as plumbing and electrical systems from the preliminary schematics phase through final

More information

SECTION 02732 BUILDING SEWERS. B. Connection of building sanitary drainage system to municipal sewers.

SECTION 02732 BUILDING SEWERS. B. Connection of building sanitary drainage system to municipal sewers. SECTION 02732 BUILDING SEWERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Lateral piping, fittings, and accessories. B. Connection of building sanitary drainage system to municipal sewers. 1.02 REGULATORY

More information

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS Section Page 36-1 GENERAL... 36.1 36-2 PIPEMAKING EQUIPMENT... 36.1 36-3 TRENCH EXCAVATION... 36.1 36-4 SPECIAL FOUNDATION TREATMENT...

More information