Medium Voltage Switchgear
|
|
|
- Vanessa Whitehead
- 9 years ago
- Views:
Transcription
1 s Medium Voltage Switchgear Type SIMOSEC up to 27.6 kv, Extendable, Metal-Enclosed up to 1200 A Medium Voltage Switchgear OPERATING INSTRUCTIONS Description Installation Operation Maintenance Order no.: Revision: 02
2 Important The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of responsibility to use sound practices in application, installation, operation, and maintenance of the equipment purchased. Siemens reserves the right to make changes in the specifications shown herein or to make improvements at any time without notice or obligations. Should a conflict arise between the general information contained in this publication and the contents of drawings or supplementary material or both, the latter shall take precedence. Qualified Person For the purpose of this manual and product labels a qualified person is one who is familiar with the installation, construction, or operation of the equipment and the hazards involved. In addition, this person has the following qualifications: (a) is trained and authorized to de-energize, clear, ground, and tag circuits and equipment in accordance with established safety practices. (b) is trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices. (C) is trained in rendering first aid. Note These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes, the matters should be referred to the local sales office. The contents of this instruction manual shall not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens Energy, Inc. The warranty contained in the contract between the parties is the sole warranty of Siemens Energy, Inc. Any statements contained herein do not create new warranties or modify the existing warranty. 2 REVISION 02 * OPERATING INSTRUCTIONS SIMOSEC *
3 Safety instructions Introduction Qualified Person Signal Words Dangerous Procedures Field Service Operation...6 Description Features Panel versions Components Three-position switch-disconnector Operating mechanisms for the three-position switches Current and voltage transformers Protection and control equipment HV HRC (current limiting) fuse assembly Interlocks Bus bars Cable connection Rating plates Ready-for-service indicator for SF 6 gas Voltage detection systems Accessories Technical data Electrical data, pressure values, temperature Tightening torques Protection against solid foreign bodies, electric shock and ingress of water Standards and guidelines Type of service location Service conditions Insulating capacity and site altitude Three-position switch-disconnector Make-proof grounding switch (feeder grounding switch) Selection of HV HRC (current limiting) fuses Cable terminations...34 Installation Receiving, Handling & Storage Unloading the switchgear and transporting to the place of installation Installing the panels Installing the end wall Aligning the panel and fastening to the foundation Aligning and joining another panel Installing the bus bar Installing the ground bus bar Installing the end wall Connecting the station ground grid to the switchgear frame Connecting high voltage cables Preparing connection of high voltage cables Cable connection types Installing cold shrink insulation at cable connections Connecting cable panel to high voltage Connecting fuse switch panel to high voltage Connecting metering panel to high voltage Installing and connecting low voltage equipment Installing secondary cables Connecting low voltage wiring Connecting the space heater Switchgear extension Placing SIMOSEC switchgear into service Safety instructions Instructing the operating personnel Checking the assembly work and the accessories Final work Testing the switchgear electrically Operating the switchgear for test Testing Connecting operating voltage (high voltage)...69 Operation Indicators and control elements To be observed for operation Verification of readiness for service Verification of safe isolation from supply of a feeder Operating the three-position switch Indicators and control elements of the three-position switch Preconditions for operation Switching the three-position switch to CLOSED position Switching the three-position switch to OPEN position Switching the three-position switch to GROUNDED position Switching the three-position switch from GROUNDED to OPEN position * OPERATING INSTRUCTIONS SIMOSEC * REVISION 02 3
4 19.7 Switching the three-position switch with FII-Protection-System (option) Operating the make-proof grounding switch Indicators and control elements of the make-proof grounding switch Preconditions for operation Switching the make-proof grounding switch to GROUNDED position Switching the make-proof grounding switch to OPEN position Grounding of panels that do not have switching devices Maintenance Switchgear maintenance Recommended Hand Tools Recommended Maintenance and Lubrication Cleaning the switchgear Checking corrosion protection Returning SIMOSEC switchgear to service Access to the switchgear Identifying the panel Removing the cable compartment cover Removing the cover of the compartment for customer low voltage equipment Removing the cover of the bus bar compartment Testing Verification of grounding Verification of correct terminal-phase connections Cable testing Cable sheath testing Replacing HV HRC (current limiting) fuses Preparing fuse replacement Removing HV HRC (current limiting) fuse link Checking the fuse tripping mechanism Installing the HV HRC (current limiting) fuses Completing fuse replacement Switchgear recycling Help Index REVISION 02 * OPERATING INSTRUCTIONS SIMOSEC *
5 Safety instructions Safety instructions 1 Introduction The SIMOSEC medium voltage metal-enclosed switchgear is designed to meet all the applicable ANSI, NEMA and IEEE standards, or the applicable IEC standards, as appropriate for the specific contract. Successful application and operation of this equipment depends as much upon proper installation and maintenance by the user as it does upon the careful design and manufacture by Siemens. The purpose of this instruction manual is to assist the user in developing safe and efficient procedures for the installation, maintenance and use of the equipment. Contact the nearest Siemens representative if any additional information is desired. 2 Qualified Person For the purpose of this manual and product labels a Qualified Person is one who is familiar with the installation, construction or operation of the equipment and the hazards involved. In addition, this person has the following qualifications: Training and authorization to energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety practices. Training in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses, face shields, flash clothing, etc., in accordance with established safety procedures. Training in rendering first aid. 3 Signal Words The signal words "Danger", "Warning" and "Caution" used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as: Danger Warning Caution Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury * SAFETY INSTRUCTIONS * REVISION 02 5
6 Safety instructions 4 Dangerous Procedures In addition to other procedures described in this manual as dangerous, user personnel must adhere to the following: 1. Always work only on de-energized equipment. Always de-energize and ground the equipment before performing any tests, maintenance, or repair. 2. Always perform maintenance on the switching device after the spring-charged mechanisms are discharged. 3. Always let an interlock device or safety mechanism perform its function without forcing or defeating the device. 5 Field Service Operation Siemens can provide competent, well-trained Field Service Representatives to provide technical guidance and advisory assistance for the installation, overhaul, repair and maintenance of Siemens equipment, processes and systems. Contact regional service centers, sales offices or the factory for details, or telephone Siemens Field Service at ( outside the U.S.). 6 REVISION 02 * SAFETY INSTRUCTIONS *
7 Description Description 6 Features SIMOSEC is an extendable, three-phase, metal-enclosed indoor switchgear. Make-proof grounding switch Three-position switch-disconnector Current transformer Capacitive voltage detection system HV HRC (current limiting) fuse Voltage transformer Fig. 1: Single line diagram of typical SIMOSEC switchgear Discharge Switch 1.6 ka/1 sec Two-position switch Cable connection CS MT FS Cable switch panel Metering panel Fuse switch panel SIMOSEC switchgear is used for power distribution in systems up to 27.6 kv: for customer substations, distribution substations and switching substations of utilities in public buildings such as high-rise buildings, airports, hospitals, sports arenas in industrial plants. The ratings of your SIMOSEC panels are provided on the rating plates. The following systems are used: Individual panels, for free combination and extension Three-pole primary enclosure Phases arranged one behind the other Bus bar system at top or bottom, as needed for the application Air-insulated bus bar and cable connection system for conventional cable terminations Three-position switch-disconnector, metal-enclosed, with air-insulated primary terminals and gas-insulated switching functions (maintenance-free quenching system) Switching devices in stainless-steel SF 6 -filled vessel, without seals, with welded-in bushings (sealed for life) Metal-enclosed panel design Panel heating for severe climatic / ambient conditions to prevent condensation Three-phase current transformer (option), factory-assembled on the feeder bushings Integrated low voltage compartment for installation of: - terminals - MCBs - pushbuttons - protection devices - low voltage cables * DESCRIPTION SIMOSEC * REVISION 02 7
8 Description Security of operation and reliability due to: Low life-cycle-costs and high availability throughout the entire product service life cycle as a result of: Type (design) and routine (production) tested panels Standardized and manufactured using numerically controlled machines Quality management system according to DIN EN ISO 9001 More than 350,000 switchgear components in operation worldwide for many years No cross insulation between phases (all insulation phase-ground) Operating mechanisms outside switchgear vessel (gas compartment) Maintenance-free operating mechanism parts Mechanical switch position indication integrated in mimic diagram Switchgear interlocking system with logical mechanical interlocks Cable testing without the need to isolate the bus bar (see Cable testing on page 98) Low-maintenance technology concept Climatic independence Minimum space requirement Provisions for extension and replacement (modular switchgear concept) Installation and extension without SF 6 gas work Long service life of switching devices Standardized protection and control equipment Ecological manufacture and utilization/recycling 8 REVISION 02 * DESCRIPTION SIMOSEC *
9 Description 7 Panel versions Fig. 2: Cable switch panel CS (shown with main bus in the middle) Fig. 3: Fuse switch panel FS (shown with main bus on top) 1 Sockets for capacitive voltage detection system 15 Gas-insulated vessel for switching device 2 Manual operation for the mechanism of the load-break / 16 Bushing-type insulator for feeder disconnecting function 3 Indicator Fuse intact / Fuse blown 17 Cable connection 4 Switch position indicator for load-break and for grounding function 18 Cable termination (not in scope of supply) "CLOSED-OPEN-GROUNDED" 5 Manual operation for the mechanism of the grounding function 19 Cable connection compartment 6 Sockets for capacitive voltage detection system 20 Three-position switch 7 Insulating cap on bus bar (for > 15 kv) 21 Grounding bus bar 8 Bus bar 22 Spring-operated mechanism for three-position switch 9 Bushing-type insulator for bus bar 23 Grounding connection (for location see dimension drawings) 10 Ready-for-service indicator for switching device 24 Option: Local-remote switch for the motor operating mechanism of the three-position switch 11 Interlocking lever of cable compartment cover (with three-position switch) 25 Option: Momentary-contact rotary control switch "CLOSED - OPEN" for motor operating mechanism for three-position switch 12 Pressure relief device for switching device 26 Option: HV HRC (current limiting) fuse 13 Locking device for three-position switch 27 Post insulator 14 Cable compartment cover/ door 28 Low voltage compartment * DESCRIPTION SIMOSEC * REVISION 02 9
10 Description 8 Components For further information about modules or components of your SIMOSEC switchgear, please refer to the medium voltage switchgear catalog. 8.1 Three-position switch-disconnector The three-position switch-disconnector is designed to break normal currents of up to 600 A and to ground the feeder cables of the panel. a s d f g h Bushing-type insulator for bus bar Spring-operated mechanism with detachable lever Mounting location for three-phase current transformer (option) Bushing-type insulator for feeder Three-position switch-disconnector Switchgear vessel made of stainless steel Fig. 4: Three-position switch-disconnector 600 A Mode of operation The three-position switch-disconnector combines the functions of a switch-disconnector and a make-proof grounding switch. Make-proof grounding switches are grounding switches with short-circuit making capacity. The switch shaft with the moving contact pieces rotates inside the chamber containing the fixed contact pieces. Compression vanes, which rotate in conjunction with the switch shaft, divide the arcing chamber into two subchambers, each of which changes in conjunction with the rotation. During the switching movement, the compression vanes generate a pressure difference between the subchambers. The SF 6 gas flows through a nozzle, causes a directional blow-out of the breaking arc and quenches it rapidly. Interlocking is not necessary as the "CLOSED" and "GROUNDED" functions cannot be implemented simultaneously. Features Switch-disconnector Metal-enclosed, with gas-insulated, maintenance-free quenching principle No external cross insulation between phases Designed as a multi-chamber switch with the functions: - switch-disconnector and - make-proof grounding switch Three-position switch-disconnector with air-insulated primary connections for bus bar and feeder Operation via pivoting-arm welded gas-tight in the front of the switchgear vessel Hermetically welded, gas-tight stainless-steel vessel Up to 600 A 10 REVISION 02 * DESCRIPTION SIMOSEC *
11 Description Equipment Shunt (trip) release (F-release) (option) Spring-operated/stored-energy mechanisms can be equipped with a shunt release. Remote electrical switching off / tripping of the three-position switch-disconnector is possible via the shunt release, e.g., transformer overtemperature tripping. The shunt release is deactivated by means of an auxiliary switch which is coupled mechanically with three-position switch-disconnector, or, in versions without auxiliary switch, by means of a signalling switch. Auxiliary switch (option) Each operating mechanism of the three-position switch-disconnector can be optionally equipped with an auxiliary switch for the switch position indication. - 2NO + 2NC 8.2 Operating mechanisms for the three-position switches The operating mechanism box of the panel accommodates all electrical and mechanical control elements required for closing and opening the three-position switch. Types of operating mechanisms for the three-position switch: Manual spring-operated mechanism The spring-operated mechanism is used for the three-position switches. Switching movements are executed independently of the speed at which the operating lever is moved. Manual spring-operated/stored-energy mechanism The spring-operated/stored-energy mechanism is used for three-position switch-disconnectors in transformer feeders (as transformer switch). Switching movements are executed independently of the speed at which the operating lever is moved. Stored energy is available to trip the switch by means of a striker pin of an HV HRC (current limiting) fuse or a shunt release (F-release). The energy to trip the switch is stored when the switch is operated from the OPEN position to the CLOSED position. After tripping (e. g. by means of the striker pin of the HV HRC (current limiting) fuse or the shunt release) the switch position indicator of the switch-disconnector shows TRIPPED. Since tripping occurs only as a result of a protective device operation (e.g., operation of fuse), re-closing of the switch is not allowed. Before the switch can be reclosed, the switch must be operated to the GROUNDED position to allow for correction of the problem that led to the tripping action * DESCRIPTION SIMOSEC * REVISION 02 11
12 Description a s d f g h CLOSED indication TRIPPED indication OPEN indication GROUNDED indication Indication FUSE INTACT Indication FUSE BLOWN Fig. 5: Switch position indication Motor operating mechanism (option) - Remote operation applied to terminals (standard) - Local operation by means of momentary-contact rotary control switch, spring return (option) - Local-remote switch as maintained-contact rotary control switch, non-spring-return (option) Fig. 6: Spring-operated mechanism Fig. 7: Spring-operated/stored-energy mechanism a Operating mechanism for three-position switchdisconnector with optional motor operating mechanism s Manual operation of detachable lever mechanism for the grounding function d f Switch position indicator (mechanical) Spring 12 REVISION 02 * DESCRIPTION SIMOSEC *
13 Description Switch positions of the three-position switch Three-position switch-disconnector up to 600 A Switch position CLOSED OPEN GROUNDED Fig. 8: Switch positions of the three-position switch a s Bus bar connection Feeder, e.g., for cable connection * DESCRIPTION SIMOSEC * REVISION 02 13
14 Description Switch-positions of the make-proof grounding switch Make-proof grounding switch Switch positions OPEN GROUNDED Fig. 9: Switch-positions of the make-proof grounding switch a s Bus bar connection Feeder, e.g., for cable connection (option) or for metering (option) 14 REVISION 02 * DESCRIPTION SIMOSEC *
15 Description 8.3 Current and voltage transformers Fig. 10: Toroidal-type current transformers installed around the cables Fig. 11: Block-type current transformers and voltage transformers in the billing metering panel Block-type current transformer 4MA7 a Three-phase current transformer 4MC63 53 d (not shown) s Cable-type current transformer 4MC70 33 f Voltage transformer 4MR 4MC70 33, 4MC70 31 toroidal-type current transformers and 4MC70 32 bus-type current transformer Single-pole toroidal-core current transformer Free of dielectrically stressed cast-resin parts (due to design) Inductive type Climate-independent Secondary connection by means of a terminal strip inside the panel 1A or 5A CT secondary rating, to suit order requirements 4MA7 block-type current transformer / 4MR voltage transformers Dimensions according to DIN Part 8 Single-pole indoor block-type current transformer Single-pole indoor voltage transformer Cast-resin insulated Secondary connection by means of screw-type terminals 1A or 5A CT secondary rating, to suit order requirement * DESCRIPTION SIMOSEC * REVISION 02 15
16 Description 8.4 Protection and control equipment Protection and control equipment is supplied according to the customer s specifications. The devices are installed in the standard low voltage compartment (item 28, see Fig. 3, page 9). For details please refer to the schematic diagrams for the switchgear. Mimic diagram Local-remote switch (option) The mimic diagram on the control panel corresponds with the switching functions of the panel. The local-remote switch determines the location from which the three-position switch can be motor-operated. a s Local-remote switch, maintainedcontact (non-spring-return) Momentary-contact rotary control switch (spring-return) Fig. 12: Control panel section The local-remote switch latches (non-spring-return) in the corresponding switch position. LOCAL position: Local operation REMOTE position: Remote operation from the control room/monitoring station 16 REVISION 02 * DESCRIPTION SIMOSEC *
17 Description Momentary-contact rotary control switch (option) The three-position switch is CLOSED-OPENED locally with its motor operating mechanism. This function is only active when the local-remote switch (option) is in the LOCAL position. The momentary-contact rotary control switch is spring-return type and returns to the center position (M position) automatically. OPEN CENTER POSITION (M) CLOSE Bay controller (option) For information on the bay controller (e.g., SIPROTEC 4), please refer to the instruction manual for the protective device. 8.5 HV HRC (current limiting) fuse assembly a s d f Dimension e Striker pin HV HRC (current limiting) fuse Extension tube Fig. 13: HV HRC (current limiting) fuse in transformer panel The HV HRC (current limiting) fuse assembly protects downstream cable runs and/or devices. The fuses used in SIMOSEC switchgear are manufactured by Bussman. The fuses comply with IEC and ANSI/IEEE C They are a general purpose current limiting fuse. The time-current characteristics of the fuses comply with the parameters for E-rated fuses as defined by ANSI C The three-position switch-disconnector in the transformer feeder in combination with Bussmann HV HRC (current limiting) fuses was tested according to ANSI/IEEE C * DESCRIPTION SIMOSEC * REVISION 02 17
18 Description Features HV HRC (current limiting) fuses according to DIN (main dimensions) with striker pin in medium version Thermal striker pin tripping when the corresponding Bussmann HV HRC (current limiting) fuse is used. Dimension e=21.14 in (537 mm) up to 27.6 kv preset at the factory Option: Dimension e=17.4 in (442 mm) possible with extension tube (95 mm) Open the cover for fuse replacement is only possible when: - the feeder is grounded, so you can open the door - the compartment cover is unscrewed Option: When the cable compartment door is opened, the switch cannot be operated from the "GROUNDED" position to the "OPEN" position Option: Shunt release on the operating mechanism of the three-position switch-disconnector Option: "TRIPPED indication" of the fuse in the fuse switch panel switch at a remote electrical indication with a normally-open contact (1NO) Option: "FUSE BLOWN" indication with a microswitch Principle of fuse tripping In the event that a HV HRC (current limiting) fuse has tripped (striker pin tripped), the three-position switch-disconnector of the transformer feeder is tripped via a time relay or via a linkage provided at the fuse contact. Fig. 14: Principle of fuse tripping a Striker pin not tripped (fuse intact) s Striker pin tripped (fuse blown) 18 REVISION 02 * DESCRIPTION SIMOSEC *
19 Description 8.6 Interlocks Control gate of the three-position switch The control gate of the three-position switch prevents switching directly from "CLOSED" to "GROUNDED" or from "GROUNDED" to "CLOSED", as the operating lever must be reinserted in the "OPEN" position. Cable compartment cover, screwed on De-grounding lock-out at the three-position switch If the cable compartment cover is removed, the three-position switch-disconnector of the transformer panel cannot be "DE-GROUNDED". Note The cable compartment cover can only be removed when the three-position switch is in "GROUNDED" position. Closing lock-out (option) If the cable compartment door is opened, the three-position switch cannot be switched to the "CLOSED" position. Locking device The control gate of the three-position switch-disconnector and the three-position disconnector can be locked in all three switch positions. ONLY GROUNDING/DE-GROUNDING POSSIBLE SWITCHING NOT POSSIBLE ONLY OPENING/CLOSING POSSIBLE * DESCRIPTION SIMOSEC * REVISION 02 19
20 Description FII-Protection-System (option) The Fuse-Installed-Intact-Protection-Sytsem (FII-Protection-Sytsem) prevents moving the three-position switch to CLOSED position if any fuse is blown or not installed. Fig. 15: Shuttter of FII-Protection-Sytsem 20 REVISION 02 * DESCRIPTION SIMOSEC *
21 Description 8.7 Bus bars Fig. 16: Bus bar compartment (bus with heat shrink insulation and insulating caps for >15 kv) Features Metal-enclosed bus bar compartment Bus bars bolted from panel to panel Versions: A - heat shrink insulation (option) - insulating caps (standard for over 15 kv) 8.8 Cable connection Features Cable termination points are arranged one behind the other Uniform cable connection height per panel (see dimension drawings) With cable bracket or cable clamps and grounding points for cable shields Access to the cable connection compartment only when feeder has been grounded Features for cable terminal For thermoplastic-insulated cables For paper-insulated mass-impregnated cables For connection cross-sections (cable size)* up to 300 mm 2 (600 kcmil) Cable bottom entry (from below) - standard Cable top entry (from above) - optional Applicable cable types are described in Section "Cable terminations" (see Description, Page 34). Installation of high voltage cables is described specifically for each panel in the operating Instructions (see Connecting high voltage cables on page 53). * Larger connection cross-sections on request * DESCRIPTION SIMOSEC * REVISION 02 21
22 Description 8.9 Rating plates The rating plate identifies the components and the technical data. Rating plate are provided as follows: bottom-right on the control panel in the operating mechanism box (inside cover) a s d f g h j Switchgear type Year of manufacturing Panel number Order number Technical data Test mark for performed acceptance test (pressure test) of the vessel Order number of operating instructions Fig. 17: Rating plate on the control panel Fig. 18: Rating plate in the operating mechanism box 22 REVISION 02 * DESCRIPTION SIMOSEC *
23 Description 8.10 Ready-for-service indicator for SF 6 gas The ready-for-service indicator for SF 6 gas shows the gas density in the three-position switch required to operate the panel. a s d Indication of operating state Green area: Panel ready for operation Red area: Panel not ready for operation DO NOT SWITCH! Isolate this feeder immediately! Fig. 19: Ready-for-service indicator for SF 6 gas If a three-position switch filled with SF 6 gas is not ready for operation (see Checking the ready for service indicator on page 42), then: Do not energize the switchgear Do not operate the switchgear Contact the Siemens Field Service (see Field Service Operation on page 6). Features Easy to read Self-monitoring Independent of temperature and pressure variations Option: Alarm switch 1NO + 1NC for remote electrical indication Fig. 20: Principle of gas density monitoring with ready-for-service indicator a s d f Measurement box in gas-filled stainless-steel vessel Magnetic coupling Indication in red area: PANEL NOT READY FOR OPERATION DO NOT SWITCH! Indication in GREEN area: PANEL READY FOR OPERATION * DESCRIPTION SIMOSEC * REVISION 02 23
24 Description For the ready-for-service indicator, a gas-tight measurement box is installed on the inside of the switchgear vessel. A coupling magnet, which is fitted to the bottom end of the measurement box, transmits its position to an outside armature through the non-magnetic switchgear vessel. This armature moves the ready-for-service indicator of the switchgear. While changes in the gas density during the loss of gas, which determines the dielectric capability, are displayed, changes in the gas pressure due to temperature and external pressure variations are not. The gas in the measurement box has the same temperature as that in the switchgear. The temperature effect is compensated via the same pressure change in both gas volumes Voltage detection systems Voltage detection systems are provided for verification of safe isolation from supply. Regular tests of the voltage detection systems must be performed by the user and documented. Voltage detection systems according to IEC and EN (VDE ) with: HR system (standard) LRM system (option) Integrated voltage detection system CAPDIS-S1/-S2 (option) Fig. 21: Voltage detection system via capacitive voltage divider (phase L3 shown) a HR indicator, plug-in type -C1: capacitance integrated into bushing or post insulator -C2: capacitance of the connection leads and of the voltage indicator to ground 24 REVISION 02 * DESCRIPTION SIMOSEC *
25 Description HR system The control panel section of the three-position switch contains: a s d f Plug-in voltage indicator (such as Horstmann HR-ST) Ground test socket Capacitive test socket for L2 Socket cover Fig. 22: Control board section: Sockets for capacitive voltage detection system Features of HR system Verification of safe isolation from supply phase by phase by insertion in each socket pair Voltage indicator flashes if high voltage is present Measuring system and voltage indicator can be tested Does not require auxiliary power 8.12 Accessories Standard accessories: SIMOSEC documentation (operating and installation instructions) Operating lever for three-position switch/ grounding switch (black grip) Further accessories according to order documentation/purchase order (selection): Operating lever for three-position switch (black grip) Operating lever for grounding switch (red grip) Double-bit key HV HRC (current limiting) fuses Surge arresters Test fuses for mechanical simulation of the striker pin of HV HRC (current limiting) fuses in transformer feeders Fig. 23: Test fuse for striker pin function tests HR/LRM voltage indicators Test units to check the capacitive interface and the voltage indicators * DESCRIPTION SIMOSEC * REVISION 02 25
26 Description Fig. 24: Functional tester (Horstmann type HO-ST) Phase comparison test units (e.g., make Pfisterer, type EPV) Fig. 25: Electronic phase comparer 26 REVISION 02 * DESCRIPTION SIMOSEC *
27 Description 9 Technical data 9.1 Electrical data, pressure values, temperature The technical data of your switchgear/panels are shown on the rating plate. Complete switchgear Rated insulation level Rated voltage U r [kv] Rated short-duration (one minute) powerfrequency withstand voltage U d, rms Rated lightning impulse withstand voltage U p peak Rated frequency f r [Hz] 50/60 Rated continuous current I 1) r Standard [A] 600 of bus bar Option 1200 Rated short-time withstand for switchgear with t k = 2 s rated duration up to current I k Rated peak withstand current I p up to [ka] peak Rated filling pressure p 2) [PSI (kpa)] 21.8 (150) re at 20 C Min. operating pressure p 2) me (absolute) 18.9 (130) Ambient temperature T for panels without secondary equipment [ C] -30 to +40 Cable-switch panel type CS; cable connection panel type CC Rated voltage U r [kv] Rated continuous current I 1) r for panel type CS [A] 600 for panel type CC Rated fault closing current, I ma ka(asym) Transformer panel type FS, FU Rated voltage U r [kv] Rated continuous current I 1) r for feeder [A] 200, 600 Rated peak withstand current I p up to [ka] peak Rated fault closing current, I ma ka(asym) up to [ka] peak Reference dimension "e" 3) for HV HRC (current limiting) fuses [mm] 537 / 21.1 Bus bar grounding panel type BG Rated voltage U r [kv] Rated fault closing current, I ma ka(asym) up to [ka]peak * DESCRIPTION SIMOSEC * REVISION 02 27
28 Description Bus bar voltage metering switch panel types MS2, MS3 Rated voltage U r [kv] Rated peak withstand current I p up to [ka] peakl Rated fault closing current, I ma ka(asym) up to [ka] peak Metering panel type S, MT3, MC3, bus riser panel BR Rated voltage U r [kv] Rated continuous current I 1) r [A] 600, ) The rated continuous currents apply to ambient temperatures of 40 C. 2) Pressure values for SF 6 -insulated vessels. 3) The fuse assembly is designed for a reference dimension "e" = 537 mm. With reference dimension "e" = 442 mm, an extension tube (95 mm long) is required. 9.2 Tightening torques If not stated otherwise, the following tightening torques apply to SIMOSEC switchgear: Joint: material/material Metal joints: steel/-steel e. g.: front plates, top plates, etc. Grounding bus bar: steel/copper copper/copper steel/copper Current conductor joint: copper/copper copper/copper Thread M6 (self-cutting) M8 M8 M8 M10 M8 M10 Tightening torque 9 lbf ft (12 Nm) 16 lbf ft (21 Nm) 16 lbf ft (21 Nm) 16 lbf ft (21 Nm) 23 lbf ft (30 Nm) 16 lbf ft (21 Nm) 23 lbf ft (30 Nm) Switchgear grounding: steel/cable lug M12 37 lbf ft (50 Nm)* Cable shield grounding M10 23 lbf ft (30 Nm)* M12 (all other cable panels) * The tightening torque at the cable lug joint depends on : - material of cable lug - instructions of termination manufacturer - instructions of cable manufacturer max. 37 lbf ft (50 Nm)* (all other cable panels) 28 REVISION 02 * DESCRIPTION SIMOSEC *
29 Description 9.3 Protection against solid foreign bodies, electric shock and ingress of water The medium voltage switchgear SIMOSEC complies with the following degrees of protection: Degree of protection IP2X IP3X IP3XD (on request) IP65 Type of protection Protection against solid foreign bodies: Protected against the penetration of solid foreign bodies; diameter 0.5 in (12.5 mm). Protection against electric shock: Protected against access to dangerous parts by means of a finger (the distance between a test finger with a diameter of 0.5 in (12.5 mm) to dangerous parts must be sufficient). Protection against the ingress of water: No definition. Protection against solid foreign bodies: Protected against the penetration of solid foreign bodies; diameter 0.1 in (2.5 mm). Protection against the ingress of water: No definition. Protection against electric shock: Protected against access to dangerous parts by means of a wire (the distance between a test rod with a diameter of 0.1 in (2.5 mm) and a length of 3.94 in (100 mm) to dangerous parts must be sufficient) Protection against solid foreign bodies: Protected against the penetration of solid foreign bodies; diameter 0.1 in (2.5 mm). Protection against the ingress of water: No definition. Protection against electric shock: Protected against access to dangerous parts by means of a wire (the distance between a test rod with a diameter of 1 mm and a length of 3.94 in (100 mm) to dangerous parts must be sufficient) Protection against solid foreign bodies: Dust-proof; no penetration of dust. Protection against the ingress of water: Protected against water jets; water which is directed towards the enclosure from any direction may not have a damaging effect. Protection against electric shock: Protected against access to dangerous parts by means of a wire (test probe with a diameter of 0.04 in (1 mm) may not penetrate) Application Enclosure of live parts under high voltage Enclosure of live parts under high voltage in switchgear with locking device Enclosure of live parts under high voltage in switchgear with locking device Metal enclosure of gas-filled switchgear vessels * DESCRIPTION SIMOSEC * REVISION 02 29
30 Description 9.4 Standards and guidelines SIMOSEC switchgear complies with the following relevant standards and specifications: IEC-, ANSI-, IEEE-Standards IEC ANSI/IEEE Std C ANSI/IEEE Std C ANSI/IEEE Std C ANSI/IEEE Std C ANSI/IEEE Std ANSI/IEEE Std C CSA C22.2 No M 1983 CSA C22.2 No EEMAC G11-1 (Measurement of Corona) Transport regulations According to Annex A of the European agreement about international transport of hazardous materials (Anlage A des Europäischen Übereinkommens über die internationale Beförderung gefährlicher Güter auf der Straße (ADR), SF 6 gas insulated medium voltage switchgear manufactured by Siemens is not categorized as hazardous materials with respect to transport procedures, and are exempt from special transport regulations according to ADR, Section b. 9.5 Type of service location SIMOSEC switchgear can be used in an indoor installation in accordance with IEC (Power installations exceeding AC 1kV) and VDE 0101 and the NEC: Outside lockable electrical service locations at places which are not accessible to the public. The equipment enclosure in which the indoor SIMOSEC switchgear is installed must have doors that are lockable. Inside lockable electrical service locations. A lockable electrical service location is a room or place which is reserved exclusively for the operation of electrical equipment and is kept under lock and key. Access is restricted to authorised personnel and persons who have been properly instructed in electrical engineering. Untrained or unskilled persons may only enter under the supervision of authorised personnel or properly instructed persons. In any event, access to the equipment must be restricted to authorized personnel. 30 REVISION 02 * DESCRIPTION SIMOSEC *
31 Description 9.6 Service conditions SIMOSEC switchgear is intended for application under the usual service conditions defined in ANSI/IEEE C , clauses 4 and 8.1. Generally, usual service conditions are defined as an environment in which the equipment is not exposed to excessive dust, acid fumes, damaging chemicals, salt air, rapid or frequent changes in temperature, vibration, high humidity, and extremes of temperature. For application is other than usual service conditions defined by ANSI/IEEE C , Consult Siemens. SIMOSEC switchgear is largely insensitive to climate and ambient conditions by virtue of the following features: No cross insulation between phases Metal enclosure of switching devices (e.g. three-position switch) in gas-filled stainlesssteel switchgear vessel Dry-type bearings in operating mechanism Essential parts of the operating mechanism made of corrosion-resistant materials Use of climate-independent current transformers * DESCRIPTION SIMOSEC * REVISION 02 31
32 Description 9.7 Insulating capacity and site altitude Insulating capacity The insulating capacity is verified by testing the switchgear with rated values of shortduration power-frequency withstand voltage and lightning impulse withstand voltage according to IEC / VDE 0670 Part 1000, and ANSI/IEEE C The rated values are referred to sea level and to normal atmospheric conditions (14.7 PSI, 68 F, lb/ft 3 humidity in accordance with IEC and VDE 0111) and ANSI/IEEE Std 4. The insulating capacity decreases with increasing altitude. For site altitudes above 1000 m, the correction factor a is recommended, depending on the actual site altitude above sea level. Rated voltage (r.m.s. value) [kv] Rated short-duration (one minute) power-frequency withstand voltage (rms value) - Across isolating distance [kv] Between phases and to ground Rated lightning impulse withstand voltage (peak value) - Across isolating distance [kv] Between phases and to ground Fig. 26: Correction factor a as a function of the site altitude in meters above sea level Rated short-duration power-frequency withstand voltage to be selected Rated short-duration power-freq. withstand voltage W * a Example: 3000 m site altitude above sea level 15 kv switchgear rated voltage 95.0 kv rated lightning impulse withstand voltage Rated lightning impulse withstand voltage to be selected Rated lightning impulse withstand voltage W * a Rated lightning impulse withstand voltage to be selected 95 kv = 118 kv 1.1 * 0.73 Result: According to the above table, switchgear for a rated voltage of 27.6 kv should be selected. 32 REVISION 02 * DESCRIPTION SIMOSEC *
33 Description 9.8 Three-position switch-disconnector The three-position switch is tested in accordance with: IEC ANSI/IEEE C CAN/CSA C22.2 No Make-proof grounding switch (feeder grounding switch) Rated voltage U r kv Make-proof grounding function of the three-position switch-disconnector Rated fault closing current I ma up to ka (asym) Rated short-time withstand current I k up to ka Selection of HV HRC (current limiting) fuses Allocation of HV HRC fuses and transformers The fuses used in SIMOSEC switchgear are manufactured by Bussmann. The fuses comply with IEC and ANSI/IEEE C They are a general purpose current limiting fuse. The time-current characteristics of the fuses comply with the parameters for E-rated fuses as defined by ANSI C The fuse dimensions comply with the requirements of DIN The three-position switch-disconnector in the transformer feeder of SIMOSEC switchgear in combination with Bussmann HV HRC (current limiting) fuses was tested in accordance with IEC and ANSI/IEEE C Please contact us for applications or HV HRC (current limiting) fuses from other manufacturers * DESCRIPTION SIMOSEC * REVISION 02 33
34 Description 9.11 Cable terminations Connection height Panel family CS1+2 FS1+2+3 FU1+2+3 CC1+2 CG1+2 MC3 Top cable entry Main switch or vertical copper bar in upper position (fuse assembly in lower position) Main switch or vertical copper bar in lower position (fuse assembly in upper position) 490 mm / 19.3" 2550 mm / 100.4" Middle cable connection to top 940 mm / 37" 2250 mm / 88.6" to bottom 1240 mm / 49" 2250 mm / 88.6" Bottom cable enty Main switch or vertical copper bar in upper position (fuse assembly in lower position) Main switch or vertical copper bar in lower position (fuse assembly in upper position) 490 mm / 19.3" 2550 mm / 100.4" 490 mm / 19.3" 2550 mm / 100.4" not available not available 490mm / 19.3" 2550mm / 100.4" not available 940 mm / 37" 2250 mm / 88.6" not available 1240 mm / 49" 2250 mm / 88.6" not available not available 490mm / 19.3" 2250mm / 88.6" 490 mm / 19.3" 2250 mm / 88.6" 490 mm / 19.3" 2250 mm / 88.6" For actual dimensions, please remark the dimension drawings. 490 mm / 19.3" 2550 mm / 100.4" 490 mm / 19.3" 2550 mm / 100.4" 530 mm / 20.8" 2250 mm / 88.6" not available not available not available 940 mm / 37" 2250 mm / 88.6" 1240 mm / 49" 2250 mm / 88.6" not available 490 mm / 19.3" 2250 mm / 88.6" 940 mm / 37" 2250 mm / 88.6" 1240 mm / 49" 2250 mm / 88.6" not available not available not available not available not available 490 mm / 19.3" 2250 mm / 88.6" 580 mm / 22.8" 2250 mm / 88.6" Principle of cable connection Fig. 27: Drawing of the principle of cable connections 34 REVISION 02 * DESCRIPTION SIMOSEC *
35 Installation Installation 10 Receiving, Handling & Storage The installation of the switchgear should be carefully planned before the equipment arrives at the site. This can avoid delays or equipment damage resulting from inadequate facilities or handling. Receiving Each transport unit of type SIMOSEC metal-enclosed switchgear is securely blocked and braced for shipment. It is crated, boxed, or covered as required by shipping conditions. Whatever method of shipment, every precaution is taken to insure its safe arrival. lf special handling is required, it is so indicated. Handle the switchgear assembly carefully when unloading because relatively delicate instruments are included. Identification When the shipment includes more than one shipping group or equipment for more than one substation, marking tags are attached to each crate or package for identification. The drawing number on the tag is also on the shipping list. The shipping list identifies the contents with the section numbers included in the shipping group. Refer to the general arrangement drawing for the location of each section within the group lineup. Use this information to simplify the assembly operation and save unnecessary handling. Inspection & Unpacking Inspect the equipment as soon as possible after receiving for any damage that may have occurred in transit. Examine before unpacking the package itself, as a damaged package may indicate an area of damage within. Be careful when unpacking equipment. Do not damage the plastic film protection during unloading. Check the ready-for-service indicator for SF 6 gas Do not climb onto the roof of the sections. Do not use sledge hammers and crowbars. They may damage the finish, if not the equipment itself. Use nail pullers. Examine the equipment after unpacking for any possible damage. Check the shipping manifest to be certain that all items have been received. Make certain that any shortage is noted on the freight bill and contact the carrier immediately. Notify the Siemens sales office of any shortage or damage * INSTALLATION SIMOSEC * REVISION 02 35
36 Installation Shipping Damage Claims Important: The way visible shipping damage is treated by consignee prior to signing the delivery receipt can determine the outcome of the damage claim to be filed. Notification to carrier within the 15 day limit on concealed damage is essential if loss resulting from unsettled claims is to be eliminated or minimized. Arrival of Shipment Note whether equipment is properly protected from the elements. Note trailer number on which the equipment arrived. Note blocking of equipment. Ensure count agrees with delivery receipt during unloading. Prior to unloading when possible: Make immediate inspection for visible damage upon arrival, and prior to disturbing or removing packaging or protective wrapping. Document transportation damage photographically. When total inspection cannot be made on vehicles prior to unloading: Perform close inspection during unloading. Note visible damage on the delivery receipt. Document transportation damage photographically. Damage Note any visible damage on the delivery receipt and have damage acknowledged with the driver's signature. Detail the damage as much as possible. Document transportation damage photographically. Include a notation "Possible internal damage, subject to inspection" on delivery receipt. Do not let the shipment be signed for by the consignee or his agent, if the driver will not sign the delivery receipt with damage noted. Notify the Siemens sales office immediately of any damage. Arrange for a carrier inspection of damage immediately. Be sure equipment is properly protected from any further damage by covering it properly after unloading. Important: The following steps should be performed to eliminate loss due to claims by carrier that equipment was damaged or further damaged on site after unloading: Do not move equipment from the place it was set when unloading. Do not remove or disturb packaging or protective wrapping prior to carrier damage inspection. Have the equipment inspected by carrier prior to handling after receipt. 36 REVISION 02 * INSTALLATION SIMOSEC *
37 Installation Inspection Documentation & Repair Make further inspection, if practical, for possible concealed damage while the carrier's inspector is on site. Do the inspection for concealed damage within 15 days of receipt of equipment if it is not practical at the time the carrier's inspector is present. Notify the carrier again and make inspection if concealed damage is found, prior to taking any corrective action to repair. Notify Siemens sales office immediately. The carrier inspection report and/or driver's signature on the delivery receipt does not constitute approval to repair. Obtain the original of the carrier inspection report and forward it along with a copy of the noted delivery receipt to the Siemens sales office. Siemens must have approval from the carrier before any repair work can be performed. The documents must be provided to Siemens before approval can be obtained, Note: Any determination as to whether the equipment was properly loaded or properly prepared by shipper for over-the-road travel cannot be made at the destination. Shipments are not released from the factory without a clear bill of lading. Approved methods are employed for preparation, loading, blocking and tarping of the equipment before it leaves the Siemens factory. Therefore, if the equipment is received in a damaged condition, this damage to the equipment had to occur while enroute due to conditions beyond Siemens control. lf the procedure outlined above is not followed by the consignee, purchaser, or his agent, Siemens cannot be held liable for repairs. Siemens will not be held liable for repairs in any case where the work was performed prior to authorization from Siemens * INSTALLATION SIMOSEC * REVISION 02 37
38 Installation Switchgear room Please observe the following points when selecting and preparing the switchgear room: Space to move switchgear into the room Room size Door dimensions Construction and load-bearing capacity of the floor Illumination, heating and power supply Installation of foundation rails Installation of high voltage cables Grounding system Tools / Auxiliary means Before starting to work on the switchgear, provide the tools / auxiliary means required: Angular hex key 10 mm (Allen screwdriver) Torx screwdriver T30 M6 Torque wrench lbf ft (20-36 Nm) Ratchet, 1/4 drive Extension 1/4 drive, length 6 (150 mm) Sockets, metric, 1/4 drive (10 mm, 13 mm, 16 mm, 18 mm) Laser level Shim plates for adapting for floor unevenness in ( mm) or as needed Household cleaner Suitable movable lifting device Roller crowbars Transport rollers 38 REVISION 02 * INSTALLATION SIMOSEC *
39 11 Unloading the switchgear and transporting to the place of installation Installation Transport unit Packing Transport unit and packing Transport units consist either of: individual switchpanels one panel per pallet (for interconnection at site) several panels per pallet (for interconnection at site) or pre-assembled panel groups up to a maximum of 3 panels, with interconnection bus bars installed (optional) and accessories. The transport units can be packed as follows: on pallets, covered with plastic film in a seaworthy crate (switchgear is sealed with desiccant bags in plastic film) other packings in special cases (e.g., cardboard box for air-freight). Unloading and transport at site Please observe: The handling equipment must be suitable for the weight marked on the transport unit. For planning purposes, a weight of 900 lbs (400 kg) per panel should be assumed. Leave the transport units packed as long as possible. Open the plastic film only as far as required for transport. Lifting cables so that the angle between cables is less than 90. Move the transport unit as far as possible before removing the wooden pallet. Transport with lifting device A panel group consisting of more than two panels is transported with a spreader bar (not furnished) to prevent the panels from being damaged during lifting. Transport units with switchgear end walls are equipped with the special lifting device. For transport with a fork-lift truck the transport unit is lifted by means of two carrying rods (not furnished) which are fitted through the lifting device holes * INSTALLATION SIMOSEC * REVISION 02 39
40 Installation a s f g Transport unit Lifting device with holes Crane Spreader bar Remove packing. Attach the lifting cables or other lifting means to the transport unit as shown in the illustration. Remove or open the cable compartment cover from the panel subframe. Remove the transport unit from the wooden pallet. The transport unit is bolted to the wooden pallet at the switchgear subframe. Remove plastic film. Take out the accessories, if applicable. Remove the bolts that secure the switchgear frame to the wooden pallet. Dispose of the packing material in an appropriate manner. Lift the transport unit. Slowly move the transport unit to the desired location. Slowly lower the transport unit. Remove the lifting cables, spreader bar or other lifting means. Remove the lifting device. Undo the bolts. Remove the lifting device. Reinstall the bolts (protection against electric shock and foreign bodies). Transport at site without wooden pallet If the transport unit cannot be lowered directly onto its mounting position, please proceed as follows: 40 REVISION 02 * INSTALLATION SIMOSEC *
41 Installation a s Transport unit Transport roller (reinforced roller) Fig. 28: Transport with transport roller Transport the transport unit as far as possible using the lifting device. Slowly lower the transport unit onto the transport roller (reinforced rollers). Push the transport unit to the mounting position. Lift the transport unit at the side edges with roller crowbars and lower it slowly onto the mounting position. Storage When switchgear is not to be installed immediately, it should be unpacked, inspected within 15 days of receipt and stored in a clean dry location. Indoor switchgear is neither weather resistant nor drip resistant. Store SIMOSEC equipment indoors. Provide an adequate covering and place a heat source of approximately 100 watts output within each panel to prevent condensation if it is to be kept in a humid or unheated area * INSTALLATION SIMOSEC * REVISION 02 41
42 Installation Checking the auxiliary switch of the ready-for-service indicator Checking the ready for service indicator The auxiliary switch of the ready-for-service indicator can latch tight in the red area due to extreme shocks during transport. To put the ready-for-service indicator into operation again, the plastic part fixed at the auxiliary switch must be brought to the initial position again by hand. The following check can be carried out safely with the panel in operation. Undo the four screws a of the front cover and remove this front cover. a s Screws Ready-for-service indicator s a a a a Fig. 29: SIMOSEC front Insert the top of a screwdriver through the cutout of the red/green plastic disc. Fig. 30: Screwdriver in cutout of the red/green plastic disc Push the small lever of the microswitch and keep it in this position, then turn the red/ green plastic disc carefully downwards until the pointer is in the green; keep this position. 42 REVISION 02 * INSTALLATION SIMOSEC *
43 Installation Take the screwdriver out of the red/green plastic disc. Now check whether the indicator shows the green area and the disc remains in this position. If the ready-forservice indicator remains in this position (showing the green area), please check whether the magnet is positioned at the mark. Fig. 31: Position of the ready-for-service indicator magnet If the magnet is positioned exactly on the lower mark, the gas pressure is correct. Fig. 32: Magnet positioned on the lower mark Fasten the front cover to close the front side of the panel * INSTALLATION SIMOSEC * REVISION 02 43
44 Installation 12 Installing the panels If required, the actions described in this section must be repeated until all panels are bolted together. In the operations described in the following sections, it is assumed that the transport units are installed starting either from the left or right. a new switchgear unit or group is being installed which has not been connected to a source of power yet, and that it is therefore not energized Installing the end wall There must not be any partition wall between the end wall and the frame of the end panel. Partition walls are only used to separate individual panels, respectively the cable compartments (see Fig. 37: Bolted joint of panels, page 47). The end panels are shipped from the factory without partition wall, except for group orders without a specified panel configuration. In this case, remove the partition wall before starting installation. a s d f g Left end panel Frame of end panel Left end wall Fixing points Screw with contact washer Fig. 33: Fixing points of left end wall Installing left end wall Align the end wall with the panel frame. Secure the end wall to the frame of the panel with the bolts provided. Installing right end wall The right end wall is mounted in a similar manner. 44 REVISION 02 * INSTALLATION SIMOSEC *
45 Installation 12.2 Aligning the panel and fastening to the foundation Aligning the panel Observe the minimum distances to the side and rear wall of the switchgear room in accordance with the switchgear arrangement drawing. For the dimensions and minimum distances of the panels, please refer to the dimension drawing and arrangement diagram for the switchgear. The switchgear may have a level difference of 0.04 in/yd (1 mm/m) as a maximum. Align the panel in horizontal position. Align the panel in vertical position. Check to assure that the panel is aligned (levelled to a maximum level difference of 0.04 in/yd (1 mm/m). Fastening the panel to the foundation Fasten the panel to the foundation at 4 points at least. There are two possibilities for fastening the panel to the foundation : bolting to sill channels (not furnished) bolting to foundation inserts (not furnished) a s d f g h Base frame of the panel Sill channel Insert Foundation Washer (inner diameter 10.5 mm, outer diameter W 31.5 mm) Screw with contact washer Fig. 34: Bolting to sill channel Fig. 35: Bolting to foundation inserts * INSTALLATION SIMOSEC * REVISION 02 45
46 Installation Bolting the panel to the sill channels Bolting the panel to the foundation inserts Align the panel in horizontal and vertical position. Bolt the panel to the sill channels, without distorting the panel. Drill holes for inserts according to the hole pattern (see dimension drawing). Install the insert anchors. Clean drilling dust and debris from the panel. Align the panel in horizontal and vertical position. Bolt the panel to the foundation inserts, without distorting the panel Aligning and joining another panel For trouble-free operation, all panels must be in vertical position and may only have a horizontal level difference (mis-alignment) of 0.04 in/yd (1 mm/m). Establish the same level (0.04 in/yd (1 mm/m)) using shims f. Align the panel d in horizontal and vertical position. a s d f Foundation Aligned panel Next panel shims in ( mm) Fig. 36: Alignment and levelling of panels 46 REVISION 02 * INSTALLATION SIMOSEC *
47 Installation Joining panels Materials to join the panels are furnished with the switchgear. a s d f Bolted joints at the panel frame Partition wall Bolt with contact washer Pressnut Fig. 37: Bolted joint of panels Bolt panels together, without distorting panels. Verify horizontal and vertical alignment of panels. Joining rear walls In case of free-standing (i.e., installed with an aisle behind the switchgear) arrangement, the rear walls of the panels must be joined with connecting links. a s d Rear wall Connecting link Bolting point Fig. 38: Joining rear walls (for free-standing arrangement only) Bolt the connecting link onto the rear walls * INSTALLATION SIMOSEC * REVISION 02 47
48 Installation 12.4 Installing the bus bar Access to bus bar compartment Access to bus bar compartment: from the side (during installation) from the front side a s Bus bar compartment Front cover of bus bar compartment Fig. 39: Access to bus bar compartment Cleaning insulators / bus bars Clean insulators / bus bars with cleaning agent (household cleaner) and a lint-free cloth. Dry insulators / bus bars with a lint-free cloth. Do not use any abrasive cleaner or wire brush on plated contact surfaces. 48 REVISION 02 * INSTALLATION SIMOSEC *
49 Installation Fastening bus bars a Insulator s Spacer d Bus bar f Conical spring washer g Holding clip h Shrink-on sleeve (optional) j Bolt M10 for bus bars Fig. 40: Fastening bus bars Assemble the bus bars and the fixing material on the points of contact of the panel. Screw the bus bar tight (tightening torque 37 lbf ft (50 Nm)) * INSTALLATION SIMOSEC * REVISION 02 49
50 Installation Installing insulating caps (> 15 kv only) Position insulating cap and align with holding clip. Snap insulating cap onto holding clip. Check that insulating cap is properly seated in the holding clip. a s d f g Bus bar joint Bus bar with heat shrink Holding clip Insulating cap of bus bar end piece Insulating cap of bus bar joint Fig. 41: Installing insulating cap (for over 15 kv ) 50 REVISION 02 * INSTALLATION SIMOSEC *
51 Installation 12.5 Installing the ground bus bar All panels of the switchgear are conductively connected together by means of the ground bus bar. The ground bus bar is pre-mounted. The ground bus bars of the panels must be connected by jumpers. Interconnect the ground bus bars by the jumpers. Ground bus bar standard Fig. 42: Bolted joint of ground bus bar (standard) a Panel frame d Ground bus bar g Nut s Pressnut f Conical spring washer h Carriage-head bolt j Connection bar (delivery position) Ground bus bar 25 ka/ 1s Fig. 43: Bolted joint of ground bus bar (25 ka/ 1s) * INSTALLATION SIMOSEC * REVISION 02 51
52 Installation 12.6 Installing the end wall The installation of the switchpanels is completed by installing the second end wall (see Installing the panels on page 44) Connecting the station ground grid to the switchgear frame The switchgear must be connected to the station ground grid at the grounding points. The position of the grounding points is shown in the dimension drawing. Recommended points of connection for the station ground: the two end panels every third panel of the switchgear each metering panel. The station ground can be optionally connected to the panel internally or externally. Select mounting direction of station ground (internal or external). Bolt the station ground to the switchgear frame (apply 52 lbs ft or 70 Nm). Check that the switchgear frame is properly grounded. a s d f g h j k l Right end panel Station ground connection Nut M12 Cable lug Panel frame Conical spring washer 3 washers (inner diameter 17mm, outer diameter W 51 mm ) Carriage-head bolt Grounding point ; Left end panel Fig. 44: Switchgear frame with grounding point (bolted joint M12) 52 REVISION 02 * INSTALLATION SIMOSEC *
53 Installation 13 Connecting high voltage cables 13.1 Preparing connection of high voltage cables Preconditions Preconditions for connecting high voltage cables to the panels: The switchgear frame is connected to the station ground. The window-type current transformers are mounted on the high voltage cables. The cables have been terminated according to the manufacturer's instructions. Cleaning cable/ cable lug Aligning high voltage cable Clean cable/ cable lug with a lint-free cloth. Align cable with connection location. Align the hole pattern of the cable lug of the cable connection. Securing high voltage cable to cable bracket If the C-rail (see Fig. 49, Page 61) is located in the area of the cable termination, shift the cable bracket so that the cable clamps are located at the required distance from the termination. When securing the cables, ensure that the cable clamps are around the outer sheath of the cable.the cable clamps should fit snugly, but should not compress the cable. Secure the cable in the cable clamp. Mounting Window-type current transformers If there is not enough space available for the window-type current transformer between the cable clamps and the floor cover (protection against small animals), the transformer can also be mounted underneath the optional floor cover * INSTALLATION SIMOSEC * REVISION 02 53
54 Installation Break the recess for the retaining device out of the optional floor cover at the point provided for this purpose. Bolt the retaining device for the window-type current transformer to the cable bracket. Mount the window-type current transformer on the retaining device. Install the secondary leads of the window-type current transformer through the metal duct to the associated terminal strip in the terminal connection compartment. Connecting cable shields The cable shields of all three phases (L1, L2 and L3) are connected to one common grounding point. The cable shields have to be routed through the windows of the current transformers. Route the cable shields directly to the C-rail, or alternatively, to the ground bus bar. Ensure a minimum clearance of 210 mm (8.27 in) to live parts. Bolt the cable shields to the C-rail, or alternatively, to the ground bus bar Cable connection types a s d f Cold shrink insulation (for over 15 kv) Cable lug Cable termination Heat shrink insulation (>15 kv, factory installed) Fig. 45: Cable connection type CC 1 Fig. 46: Cable connection type CS 1 54 REVISION 02 * INSTALLATION SIMOSEC *
55 Installation Fig. 47: Cable connection type CS 2 Fig. 48: Cable connection type FS * The first skirt of the bushing must be wrapped by the cold shrink. ** Field-installed cold shrink insulation (item a) must overlap factory-installed heat shrink (item f) * INSTALLATION SIMOSEC * REVISION 02 55
56 Installation 13.3 Installing cold shrink insulation at cable connections NOTE! Before installing, read the supplier s documentation of the cold shrink insulation. NOTE! Before installing, the cold shrink insulation should be at room temperature. If the cold shrink insulation is installed while cold, the material may not contract (shrink) fully. Before installing, bring the cold shrink insulation up to room temperature. Determine the length of the cold shrink Measure the distance between the second skirt of the bushing type insulator and a reference-point, e. g., the middle of the lower hole in the cable connection terminal, and note the distance. Measure the distance between the upper edge of the cable termination and a reference-point, e. g., the middle of the lower hole in the cable lug and note the distance. 56 REVISION 02 * INSTALLATION SIMOSEC *
57 Installation Add the two distances together and add 1 inch to the sum of the distances. r The result of this addition is the necessary length of the cold shrink. This length is approximately equal to the length a (see Fig. 45: Cable connection type CC 1, page 54). Cut the cold shrink insulation to its necessary length Measure from the upper edge, i. e., the side opposite the loose pull tab, of the cold shrink and mark the determined length at the cold shrink. a Loose pull tab NOTE! While cutting the cold shrink insulation, use care that you do not cut the loose pull tab in the middle of the cold shrink insulation. Do not cut the pull tab in the middle of the cold shrink insulation. Cut the cold shrink insulation carefully using a handsaw at the marked distance while turning the cold shrink insulation around its axis * INSTALLATION SIMOSEC * REVISION 02 57
58 Installation Mounting of the cold shrink Pull the cold shrink insulation over the cable termination. The loose pull tab of the cold shrink insulation must point away from the switchgear cable connection terminal. Bolt the the high voltage cable together with the cable connection terminal (tightening torque 37 lbf ft or 50 Nm). 58 REVISION 02 * INSTALLATION SIMOSEC *
59 Installation Push the cold shrink insulation over the bushing so that the end of the cold shrink insulation is located between the first and the second skirt of the bushing. You can use the neighboring bushing as reference. Pull down the loose pull tab gently while unwinding in a counter-clockwise direction * INSTALLATION SIMOSEC * REVISION 02 59
60 Installation Finish the mounting of the cold shrink insulation by pulling down gently the loose pull tab completely. The cold shrink insulation material must fully cover all bare conductors. r The cold shrink insulation is correctly installed. 60 REVISION 02 * INSTALLATION SIMOSEC *
61 Installation 13.4 Connecting cable panel to high voltage a s d f g h Cold shrink insulation (for over 15 kv) Cable connection terminal Cable termination Cable clamp C-rail Grounding point of cable shields (alternatively, connect to the ground bus bar) Fig. 49: Cable connection in cable panel All cable panels have a similar cable connection. Cable panels: CS cable switch Cable panel with make-proof grounding switch Cable panels without switching devices For the exact panel dimensions, such as the cable connection height, please refer to the dimension drawing and arrangement diagram for the specific panel. Connecting high voltage cables Check the tightening torque (37 lbf ft or 50 Nm) of the bolted joint between the cable connection terminal and the bushing-type insulator. Put the cold shrink (for over 15 kv) over the cable connection (see Installing cold shrink insulation at cable connections on page 56). Bolt terminated cable to the cable connection terminal and avoid undue strain on bushing type insulator. For the tightening torques of the cable lugs / cable terminations, please observe the manufacturer's instructions, however do not exceed 37 lbf ft (50 Nm) * INSTALLATION SIMOSEC * REVISION 02 61
62 Installation 13.5 Connecting fuse switch panel to high voltage a s d f g h j k Upper fuse contact Discharge switch HV HRC (current limiting) fuse Second fuse contact Post insulator Grounding point of cable shields (alternatively, connect to the ground bus bar) Cable termination Bolted joint at point of cable connection Fig. 50: Cable connection in fuse switch panel For the exact panel dimensions, such as the cable connection height, please refer to the dimension drawing and arrangement diagram for the switchgear. Connecting high voltage cables Bolt terminated cable to the cable connection terminal and avoid undue strain on bushing. For the tightening torques of the cable lugs / cable terminations, please observe the manufacturer's instructions, however do not exceed 37 lbf ft (50 Nm). 62 REVISION 02 * INSTALLATION SIMOSEC *
63 Installation 13.6 Connecting metering panel to high voltage a s d f g h j k l Bus bar 4MA7 block-type current transformer Cable connection terminal Bolted joint of cable connection terminal and cable lug Cable termination Grounding point of cable shields (alternatively, connect to ground bus bar) Cold shrink insulation (for over 15 kv ) Connection of voltage transformer Voltage transformer Fig. 51: Cable connection in metering panel For the exact panel dimensions, such as the cable connection height, please refer to the dimension drawing and arrangement diagram of the switchgear. Installing block-type current transformers or voltage transformers Connecting high voltage cables Connect the voltage transformer s primary to the cable termination at the desired point. Check the tightening torque (37 lbf ft or 50 Nm) of the bolted joint between the cable and the block-type current and/or voltage transformers. Bolt terminated cable to the cable connection terminal and avoid undue strain on bushing. For the tightening torques of the cable lugs / cable terminations, please observe the manufacturer's instructions, however do not exceed 37 lbf ft (50 Nm) * INSTALLATION SIMOSEC * REVISION 02 63
64 Installation 14 Installing and connecting low voltage equipment 14.1 Installing secondary cables a s d f g h j Panel Cover, screwed on Entry area for secondary cables Metal duct for secondary cables (option) Terminal connection compartment for customer low voltage wiring Low voltage compartment Control compartment Fig. 52: Cable routing for customer low voltage wiring The secondary cables are routed above the control compartment behind the screwed-on cover. The secondary cables can be installed directly into the terminal connection compartment either from above through an entrance bushing or conduit fitting or from below through a flexible metal conduit (not furnished) arranged along the switchgear frame. Please observe the correct polarity of the secondary leads of the window-type current transformers to be connected Connecting low voltage wiring Connect all customer low voltage wiring according to the terminal plug and cable designations of the circuit diagrams of the switchgear Connecting the space heater The individual panels of SIMOSEC switchgear are equipped with a space heater to prevent condensation. Rating 100 W Connect the space heater terminal according to the circuit diagrams for the switchgear. 64 REVISION 02 * INSTALLATION SIMOSEC *
65 Installation 15 Switchgear extension If required, installed switchgear can be extended with additional panels, or the existing panel configuration can be modified. After disconnecting and grounding the electric circuits, and after discharging any stored-energy in operating mechanisms, additional panels can be installed and connected. The procedure to be followed for switchgear extension is the same as for first installation 16 Placing SIMOSEC switchgear into service 16.1 Safety instructions The correct and safe operation of this switchgear is conditional on: Proper transportation Correct storage Correct assembly and installation Careful operation in accordance with established procedures which comply with applicable codes and regulations Use of proper Personal Protective Equipment (PPE) (see NFPA 70E) 16.2 Instructing the operating personnel The operating personnel should have these instructions available. Instruct operating personnel in theory and practice of switchgear operation. Ensure that the operating personnel are familiar with all operational details when placing equipment into service Checking the assembly work and the accessories Accessories supplied with the equipment: Operating instructions Operating levers for three-position switch Double-bit keys (if necessary) Circuit diagrams Voltage detector or voltage detection system Ensure that the above listed accessories are easily accessible. Ensure that the assembly work has been performed correctly (see sections 12-14). Ensure that all covers have been installed and enclosure hardware torqued to the correct values. Ensure that all electrical connections have been torqued to the correct values * INSTALLATION SIMOSEC * REVISION 02 65
66 Installation 16.4 Final work Visual inspection of switchgear Check data on the rating plates according to the circuit diagrams. Clean the switchgear thoroughly. Remove all foreign matter. Clean all insulation with a lint-free cloth Close all covers/doors Check safety/warning labels provided at the switchgear. Checking the accessories 16.5 Testing the switchgear electrically Checking the grounding Check the following at the panels: All grounding connections are properly made Proper operation of all discharge switches Fuse switch panel: Movable grounding contacts (option) touching on all three phases in GROUNDED position a s Discharge switch in OPEN position Discharge switch in GROUNDED position Fig. 53: Movable grounding contact in fuse switch panel (option) Checking high voltage connections Check that cables have been properly terminated and connections are insulated. Check correct phase sequence of cables. Check correct installation and grounding of cable ground shields. Check covers of capacitive test sockets Check grounding connections including bus connections in switchgear and connections to system ground. Check that insulating caps are properly installed and undamaged. Check insulation for damage. Check tightening torque of bolted joints. Check that cable clamps are properly installed for all high voltage cables. Checking low voltage connections Check low voltage wiring for correct installation. Check tightness of terminal screws. Check secondary wiring of transformers. Check that any current transformer that is not connected to a permanent load device has the secondary terminals connected with a short-circuiting jumper. 66 REVISION 02 * INSTALLATION SIMOSEC *
67 Installation 16.6 Operating the switchgear for test SIMOSEC switchgear is operated mechanically and electrically for test at the factory. Before commissioning, operate the switchgear again mechanically and electrically for test. Mechanical operation The panels are delivered from the factory with all switching devices in "GROUNDED" position, and the closing and opening springs of the stored-energy mechanisms partially charged. Operate the different switching options of each panel several times. Switch the three-position switches several times to each position (CLOSED, OPEN, and GROUNDED), verifying the correct indication of the associated switch position indicators at the same time. Test interlocking conditions of each switching option (without using excessive force). The switch positions of the SIMOSEC switchgear are described in the operating instructions Testing low voltage system Check the auxiliary circuits according to the circuit diagram and manual. Switch on control voltage using an external source. Check the indicators according to the circuit diagram and the mimic diagram of the switchgear. Check the control elements according to the circuit diagram and the mimic diagram of the switchgear. Fig. 54: Warning label Electrical operation The switch positions of SIMOSEC switchgear are described in the operating instructions. Operate the different switching options of each panel several times. Verify correspondence between the switch position indication on the control panel and the actual switch position using the view port. Test interlocking conditions of each switching option (without using excessive force) * INSTALLATION SIMOSEC * REVISION 02 67
68 Installation 16.7 Testing SIMOSEC switchgear is well prepared to fulfill the following tests: Rated Maximum Voltage kv (rms) Power Frequency Withstand kv (rms) Field Test Voltage kv (rms) kv (dc) Following tests should be made on the equipment (observe manufacturers and local prescriptions): An insulation resistance test is made on the high voltage circuit to be sure that all connections made in the field are properly insulated. An insulation resistance test is also advisable on the control circuit. A dielectric test, if possible, should be made on the high voltage circuit for one minute at one of the above shown voltages (see table) corresponding to the rated voltage of the equipment. (Note: Voltage transformers, control power transformers, surge arresters, and surge capacitors must be disconnected during this test. The test sockets of capacitive voltage indication system must be grounded). Note: The DC test voltage is given as a reference only for those using DC Tests to verify the integrity of connected cable installations without disconnecting the cables from the switchgear. It represents values believed to be appropriate and approximately equivalent to the corresponding power frequency withstand test values specified for each voltage rating of switchgear. The presence of this column in no way implies any requirement for a DC withstand test on AC equipment or that a DC withstand test represents an acceptable alternative to AC withstand tests. When making DC Tests, the voltage should be raised to the test value in discrete steps and held for a period of one minute. In accordance with ANSI C Clause 6.5, Field Dielectric Tests are also recommended when new units are added to an existing installation, or after major field modifications. The equipment should be put in good condition prior to the field test. It is not expected that equipment shall be subjected to these tests after it has been stored for long periods of time or has accumulated a large amount of dust, moisture, or other contaminants without being first restored to good condition. A dielectric test on secondary and control circuits should be made for one minute at 1125 volts AC or 1590 volts DC. The above voltages are in accordance with NEMA Standards. (Note: Certain control devices, such as motors and motor circuits, should be tested at 675 volts AC. Electronic devices should be tested at the voltages specified in the instruction manual for the electronic device). 68 REVISION 02 * INSTALLATION SIMOSEC *
69 Installation 16.8 Connecting operating voltage (high voltage) The connection is conditional on complete and trouble-free commissioning Switch all switching devices to "OPEN" position. Ground cable feeders without connected high voltage cables at the feeder, and secure the grounding switch against de-grounding (opening). Verify correct terminal-phase connections with respect to next incoming feeder: Apply operational high voltage to opposite substation. Connect phase comparison test unit (e.g., make Pfisterer, type EPV) to the capacitive test sockets of one phase at the panel and at the adjacent panel. Test all three phases using phase comparitor. Connect tested incoming feeder (bus bars / feeders) according to the specifications / the instructions of the switchgear owner * INSTALLATION SIMOSEC * REVISION 02 69
70 Operation Operation 17 Indicators and control elements a s d f g h j k l Rating plate Low voltage compartment "Ready-for-service" indicator for SF 6 gas Interlocking lever for cable compartment cover (with three-position switch) Control gate for three-position switch Cable connection compartment View port for three-position/ two position/ grounding switch Indicator "Fuse intact / Fuse blown" Three-position switch drive ; Momentary-contact rotary control switch "ON - OFF" and local-remote switch for the motor operating mechanism of the three-postion switch (option) A Sockets for capacitive voltage detection system S View port for the discharge switch Fig. 55: Indicators and control elements For detailed information about the modules and components of your SIMOSEC switchgear, please refer to the individual sections of these instructions and the corresponding catalog. 70 REVISION 02 * OPERATION SIMOSEC*
71 Operation 18 To be observed for operation Before operation, always verify readiness for service of the panels to be operated Verification of readiness for service The "ready-for-service" indicator for SF 6 gas shows the gas density in the three-position switch required to operate the panel. a s d Indication of operating state Green area: Panel ready for operation Red area: Panel not ready for operation DO NOT SWITCH! Isolate this feeder immediately! Fig. 56: Ready-for-service indicator for SF 6 gas If a three-position switch filled with SF 6 gas is not ready for operation: Do not put the switchgear into operation Do not operate the switchgear Contact the Siemens Service Operation Verification of safe isolation from supply of a feeder Verify safe isolation from supply of the switchgear or the panel: with the voltage indicator of the capacitive voltage detection system * OPERATION SIMOSEC * REVISION 02 71
72 Operation Verification of safe isolation from supply with the capacitive voltage detection system a s d f Plug-in voltage indicator (such as Horstmann type HR-ST) Ground test socket Capacitive test socket for L2 Socket cover Fig. 57: Control board section: Sockets for capacitive voltage detection system Proceed as follows: Determine type of measuring system HR (= High Resistive System). Select suitable indicator HR-ST. Verify perfect operation of indicator. Remove cover from test socket. Plug in the voltage indicator. Read indicator: If the indicator flashes or lights up, the phase is energized. If the indicator does not flash or light up, the phase is not energized. Remove indicator. Replace cover in test socket. Check the other phases in the same way. 72 REVISION 02 * OPERATION SIMOSEC*
73 Operation 19 Operating the three-position switch Cable panels, bus sectionaliser panels and fuse switch panels are equipped with a threeposition switch disconnector Indicators and control elements of the three-position switch a Opening for the operating lever of the three-position switch s Ready-for-service indicator for SF 6 gas d f g h j k Interlocking lever for cable compartment cover (option) Control gate for three-position switch Socket for capacitive voltage indicators (blue label) Socket for capacitive voltage indicators (yellow label) Switch position indicator Indicator: Fuse intact/ Fuse blown Fig. 58: Control panel of cable switch panel with three-position switch-disconnector Fig. 59: Control panel of fuse switch panel with three-position switch-disconnector a s Coded operating lever for the switchdisconnector (red grip) Operating lever (black grip) for grounding switch Fig. 60: Operating levers for three-position switch * OPERATION SIMOSEC * REVISION 02 73
74 Operation Possible switch positions of the three-position switch-disconnector The operating lever is mechanically coupled to the switching operation through the operating shaft. a s d CLOSED position OPEN position GROUNDED position Fig. 61: Switch positions of the threeposition switch-disconnector with detachable lever mechanism GROUNDED - Switch-disconnector open - Grounding switch closed - Cable compartment cover unlocked (option) Option: In the fuse switch panel, the feeder can be grounded via a mechanical, positively coupled discharge switch located in the panel subframe OPEN - Switch-disconnector open - Grounding switch open - Cable compartment cover locked (option) CLOSED - Switch-disconnector closed - Grounding switch open - Cable compartment cover locked (option) 74 REVISION 02 * OPERATION SIMOSEC*
75 Operation TRIPPED (optional) (fuse switch panel only) - Switch-disconnector tripped by a HV HRC (current limiting) fuse or a shunt trip release - Grounding switch open - Cable compartment cover locked (option) - Three-position switch tripped 19.2 Preconditions for operation Preconditions for operating the three-position switch: Cable compartment cover installed Switchgear ready for service Operating lever available Control gate unlocked 19.3 Switching the three-position switch to CLOSED position Push control gate of three-position switch to the right and hold. Insert operating lever (with black grip) onto operating shaft of operating mechanism. Move operating lever up to the "CLOSED" position * OPERATION SIMOSEC * REVISION 02 75
76 Operation The three-position-switch of the cable / bus sectionalizer and fuse switch panel is now closed. Remove operating lever. Install padlock at center position of control gate of three-position switch (if desired). Stow away operating lever. The three-position switch is protected against unauthorized use, if the control gate is padlocked Switching the three-position switch to OPEN position Push control gate of three-position switch to the right and hold. Insert operating lever (with black grip) onto operating shaft of operating mechanism. Move operating lever down to the "OPEN" position. 76 REVISION 02 * OPERATION SIMOSEC*
77 Operation The three-position switch of the cable / bus sectionaliser and fuse switch panel is open. Remove operating lever. Install padlock at center position of control gate of three-position switch (if desired). Stow away operating lever. The three-position switch is protected against unauthorized use, if the control gate is padlocked Switching the three-position switch to GROUNDED position Establish safe isolation from supply voltage. Verify that the panel feeder of the three-position switch is isolated from supply. Use the capacitive voltage detection system (see Verification of safe isolation from supply with the capacitive voltage detection system on page 72). Remove padlock (if present) from control gate of three-position switch (option). Push control gate of three-position switch to the left and hold * OPERATION SIMOSEC * REVISION 02 77
78 Operation Insert operating lever (with red grip) onto operating shaft of operating mechanism. Move operating lever down to the "GROUNDED" position. Verify the position of the switch through the viewport. GROUNDED position in fuse panel: Verify that the discharge switch is closed - i.e., the movable grounding contact (option) is touching the second fuse contact - through the inspection window of the cable compartment cover. Position of discharging contacts with discharge switch in GROUNDED position. Remove operating lever. Install padlock at center position of control gate of three-position switch (if desired). Stow away operating lever. The three-position switch is protected against unauthorized use, if the control gate is padlocked. 78 REVISION 02 * OPERATION SIMOSEC*
79 Operation 19.6 Switching the three-position switch from GROUNDED to OPEN position Obtain clearance for removal of ground in accordance with established procedures for lockout-tagout complying with OSHA regulations and NFPA 70E. Verify that all work requiring grounding has been completed. Verify that all personnel are clear of conductors. Verify that any temporary grounds or short-circuits have been removed. Verify that all covers and doors have been closed. Remove padlock (if present) from control gate of three-position switch. Push control gate of three-position switch to the left and hold. Insert operating lever (with red grip) onto operating shaft of operating mechanism. Move operating lever up to the "OPEN" position. OPEN position in fuse switch panel Verify that the discharge switch is in OPEN position - i.e., the movable grounding contact (option) is not touching the second fuse contact - through the inspection window of the cable compartment cover. Position of grounding contacts with grounding switch in OPEN position. Remove operating lever. Install padlock at center position of control gate of three-position switch (if desired). Stow away operating lever. The three-position switch is protected against unauthorized use, if the control gate is padlocked * OPERATION SIMOSEC * REVISION 02 79
80 Operation 19.7 Switching the three-position switch with FII-Protection-System (option) The Fuse-Installed-Intact-Protection-System (FII-Protection-System) could be installed in fuse switch panels. It prevents to switch the three-position switch to CLOSED position if only one fuse is blown or not installed. To switch the three-position switch to OPEN position is possible if the FII-Protection-System is active. Switch to CLOSED position The shutter of the FII-Protection-System is visible in the slot for closing/opening of the three-position switch. Fig. 62: Shuttter of FII-Protection-System To switch the three-position to CLOSED position is blocked by the shutter. Fig. 63: Switching to CLOSED position blocked by shutter Check if fuses are blown or not installed. Replace or install fuses. Check if the shutter of the FII-Protection-System is still visible in the slot for closing/ opening of the three-position switch. Switch the three-position switch to CLOSED position. 80 REVISION 02 * OPERATION SIMOSEC*
81 Operation Switch to OPEN position Switching the three-position switch to OPEN position is always possible even if the FII- Protection-System is active or not. Fig. 64: Switching to OPEN position is always possible Switch the three-position switch to OPEN position. Check if fuses are blown or not installed. Replace or install fuses. Check if the shutter of the FII-Protection-System is still visible in the slot for closing/ opening of the three-position switch * OPERATION SIMOSEC * REVISION 02 81
82 Operation 20 Operating the make-proof grounding switch Panels with make-proof grounding switch: Cable grounding panel CG Bus bar grounding panel BG, CG 20.1 Indicators and control elements of the make-proof grounding switch a s d f g Opening for the operating lever mechanism of the make-proof grounding switch Ready-for-service indicator for SF 6 gas Control gate for fault make grounding switch Socket for capacitive voltage indicators Switch position indicator Fig. 65: Control panel of cable grounding panel with make-proof grounding switch Fig. 66: Control panel of bus bar grounding panel with make-proof grounding switch 82 REVISION 02 * OPERATION SIMOSEC*
83 Operation Possible switch positions of the make-proof grounding switch a s GROUNDED position OPEN position Fig. 67: Switch positions of the make-proof grounding switch with detachable lever mechanism GROUNDED - Make-proof grounding switch closed - Cable connection compartment unlocked OPEN - Make-proof grounding switch open - Cable connection compartment locked 20.2 Preconditions for operation Preconditions for operating the make-proof grounding switch: Switchgear ready for service Operating lever available Absence of voltage, feeder isolated * OPERATION SIMOSEC * REVISION 02 83
84 Operation 20.3 Switching the make-proof grounding switch to GROUNDED position Verify safe isolation from voltage supply of bus bar. Verify the position of the switch through the viewport. Establish safe isolation from supply if required. Verify that the bus bars and the panel feeder of the make-proof grounding switch are isolated from supply. Remove padlock (if present) from control gate of make-proof grounding switch. Push control gate of make-proof grounding switch to the left and hold. Insert operating lever (with red grip) onto operating shaft of operating mechanism. Move operating lever down to the "GROUNDED" position. The bus bar grounding switch is in the "GROUNDED" position. Remove operating lever. Install padlock at center position of control gate of make-proof grounding switch (if desired). Stow away operating lever. The make-proof grounding switch is protected against unauthorized use, if the control gate is padlocked. 84 REVISION 02 * OPERATION SIMOSEC*
85 Operation 20.4 Switching the make-proof grounding switch to OPEN position Obtain clearance for removal of ground in accordance with established procedures for lockout-tagout complying with OSHA regulations and NFPA 70E. Verify that all work requiring grounding has been completed Verify that all personnel are clear of conductors Verify that any temporary grounds or short-circuits have been removed Verify that all covers have been reinstalled Remove padlock (if present) from control gate of make-proof grounding switch. Push control gate of make-proof grounding switch to the left and hold. Insert operating lever (with red grip) onto operating shaft of operating mechanism. Move operating lever up to the "OPEN" position. r The bus bar grounding switch is in the de-grounded position. Remove operating lever. Install padlock at center position of control gate of make-proof grounding switch (if desired). Stow away operating lever. The make-proof grounding switch is protected against unauthorized use, if the control gate is padlocked * OPERATION SIMOSEC * REVISION 02 85
86 Operation 21 Grounding of panels that do not have switching devices Panels that have no switching devices: Cable panel CC Bus riser panel BR Metering panels MC, MT Fuse panel Cable panels, bus riser panels or metering panels must be grounded via the grounding devices of the panels allocated for this purpose or by means of grounding cables. Grounding cables are not furnished as part of SIMOSEC switchgear. Grounding cables are available from a number of suppliers, including W.H.Salisbury & Co. and A.B. Chance (Hubbell Power Systems). Grounding cables should be used in accordance with the instructions of the grounding clamp manufacturer and in accordance with applicable regulatory requirements, including those of OSHA. Fig. 68: Grounding of a metering panel using grounding cables (example) 86 REVISION 02 * OPERATION SIMOSEC*
87 Maintenance Maintenance 22 Switchgear maintenance Periodic inspections and maintenance are essential to obtain safe and reliable operation of the switchgear. When SIMOSEC switchgear is operated under "Usual Service Conditions", maintenance and lubrication is recommended at ten year intervals. The maintenance intervals of devices (e.g., relays, PLC s, etc.) installed in the switchgear may differ. "Usual" and "Unusual" service conditions for Medium Voltage Metal-Enclosed Interrupter Switchgear are defined in ANSI/IEEE C , clauses 4 and 8.1. Generally, "usual service conditions" are defined as an environment in which the equipment is not exposed to excessive dust, acid fumes, damaging chemicals, salt air, rapid or frequent changes in temperature, vibration, high humidity, and extremes of temperature. The definition of "usual service conditions" is subject to a variety of interpretations. Because of this, you are best served by adjusting maintenance and lubrication intervals based on your experience with the equipment in the actual service environment. Under indoor operating conditions, SIMOSEC requires low maintenance. The climatic and local ambient conditions determine the extent of cleaning work to be performed. We recommend an annual visual inspection. If required, the intervals have to be adjusted to the climatic and local ambient conditions. Independently of the regular maintenance, immediately determine the cause of faults and short circuits as well as partial discharges, and replace damaged parts by original parts if required. If you have any questions, please contact Siemens Service (see Field Service Operation on page 6). Introduction and Maintenance Intervals Regardless of the length of the maintenance and lubrication interval, Siemens recommends that switching devices should be inspected and exercised annually. For the safety of maintenance personnel as well as others who might be exposed to hazards associated with maintenance activities, the safety related work practices of NFPA 70E should always be followed when working on electrical equipment. Maintenance personnel should be trained in the safety practices, procedures and requirements that pertain to their respective job assignments. This manual should be reviewed and retained in a location readily accessible for reference during maintenance of this equipment. The user must establish a periodic maintenance program to ensure trouble-free and safe operation. The frequency of inspection, periodic cleaning, and preventive maintenance schedule will depend upon the operation conditions. NFPA Publication 70B, "Electrical Equipment Maintenance" may be used as a guide to establish such a program * MAINTENANCE SIMOSEC * REVISION 02 87
88 Maintenance A preventive maintenance program is not intended to cover reconditioning or major repair, but should be designed to reveal, if possible, the need for such actions in time to prevent malfunctions during operation. Switchgear assemblies are enclosed on all sides and top with sheet metal. Access into the enclosure is provided by doors or removable covers. Although the bus and connections may be covered with insulating materials in metal-enclosed switchgear assemblies, it is a coordinated insulation system; insulation plus air or creep distance equals a given insulation level Recommended Hand Tools SIMOSEC switchgear uses metric fasteners. For additional information call Siemens. 88 REVISION 02 * MAINTENANCE SIMOSEC *
89 Maintenance 22.2 Recommended Maintenance and Lubrication Periodic maintenance and lubrication should include all the tasks shown in table below. 1. Before any maintenance work is performed within primary compartments, make certain that the equipment is completely de-energized, tested, grounded, tagged or properly identified and released for work in an authorized manner. 2. Before starting work on the switchgear, the following should be completed on any equipment that will affect the area of the work: A. Disable remote control and automatic transfer schemes. B. De-energize all direct and back feed power and control sources, test and ground. C. Disconnect all voltage and control power transformers. D. Open all disconnects. E. Ground outgoing circuits. 3. Include the following items in your inspection procedure: A. Check general condition of switchgear installation. B. Inspect switchgear interior for accumulation of dust, dirt or any foreign matter. C. Examine indicating lamps and replace as required. D. Check terminal block contacts for loose connections. E. Check instrument and control switches and inspect their contacts. F. Check for proper condition of instrument transformers. Replace burned out fuses, if any. Check primary and secondary connections. G. Remove dust and other contaminants from all insulators and insulation. H. Inspect bus bars and connections for proper condition. If bus bars are overheating check for poor or loose connections or for overload. I. Examine all safety interlocks. J. Check space heaters and thermostat (if equipped) for proper operation. K. Maintain other equipment per their respective instruction book requirements. L. Replace, reassemble, re-insulate, return all items to proper operating conditions and remove grounds prior to energization. The list of tasks in the table does not represent an exhaustive survey of maintenance steps necessary to ensure safe operation of the equipment. Particular applications may require further procedures. Should further information be desired or should particular problems arise which are not covered sufficiently for the Purchaser's purposes, the matter should be referred to the local Siemens sales office * MAINTENANCE SIMOSEC * REVISION 02 89
90 Maintenance 22.3 Cleaning the switchgear Most of the plastics and synthetics used in insulation systems are attacked by solvents containing aromatics or halogenated hydrocarbons. The use of these may cause crazing and deformation of the material reducing the dielectric strength. Use only water and household cleaner to clean insulation. To clean the switchgear or single components please use the recommended cleaning agents and aids. Cleaning agents and cleaning aids Cleaning agents and cleaning aids Contents Use WD40 Water-resistant spray-oil Corrosion protection for sliding parts Household cleaner and water Cast-resin parts, control panels, covers, transformers Brush Dust Lint-free cleaning rag Humid cleaning, drying Vacuum cleaner Drilling chips, rubble, dust 90 REVISION 02 * MAINTENANCE SIMOSEC *
91 Maintenance 22.4 Checking corrosion protection Scratches, impacts or bare spots in the surface painting of the switchgear enclosure can produce corrosion. Touch-up set Contents Use 8DX2 011 Paint pen in color Light Basic SN700 Scratches, impacts, bare spots 8DX2 012 Paint tin in color Light Basic SN700 Scratches, impacts, bare spots on request Paint pen in color "light gray No. 61 per ASTM D (Munsell notation 8.3 G6.10/0.54) Scratches, impacts, bare spots on request Paint tin in color "light gray No. 61 per ASTM D (Munsell notation 8.3 G6.10/0.54)" Scratches, impacts, bare spots 22.5 Returning SIMOSEC switchgear to service Follow the proceduces given in Placing SIMOSEC switchgear into service (see Installation, Page 65). 23 Access to the switchgear 23.1 Identifying the panel The accessibility, safety measures and work operations are dependent on the panel type. Identify the panel type and proceed accordingly * MAINTENANCE SIMOSEC * REVISION 02 91
92 Maintenance 23.2 Removing the cable compartment cover There are two kinds of locking systems available for the cable compartment cover: Interlocked cable compartment cover (panels with grounding switch) Screwed-on cable compartment cover (panels without switching devices, e.g. ME1) Open interlocked cable compartment door Check panel grounding (see Switching the three-position switch to GROUNDED position on page 77). Fig 69: Position of grounding contacts with discharging switch in CLOSED position Fig 70: Position of grounding contacts with discharging switch in OPEN position Fig 71: Switch-disconnector positions using view port 92 REVISION 02 * MAINTENANCE SIMOSEC *
93 Maintenance Verify that the grounding switch is closed, i.e., that the movable discharge switch contacts are touching the lower fuse contacts - through the inspection window of the cable compartment cover, or that the moving contacts of the switchdisconnector are in the GRD ( grounded ) position. Push interlocking lever upwards and hold in this position. Fig 72: Push interlocking lever upwards Open the cable compartment door. Fig 73: Open cable compartment door Release the interlocking lever * MAINTENANCE SIMOSEC * REVISION 02 93
94 Maintenance Open screwed-on cable compartment door Check panel grounding (see Switching the three-position switch to GROUNDED position on page 77). Remove the two screws securing the cable compartment door. Fig 74: Screwed-on cable compartment door Open the screwed-on cable compartment door. Close the cable compartment door To close the cable compartment door, proceed in reverse order. Remove the screwed-on cable compartment cover Check panel grounding (see Switching the three-position switch to GROUNDED position on page 77). Remove the 4 screws in the corners of the cable compartment cover. Fig 75: Screwed-on cable compartment cover Remove the screwed-on cable compartment cover. Replace the screwed-on cable compartment cover To replace the screwed-on cable compartment cover, proceed in reverse order. 94 REVISION 02 * MAINTENANCE SIMOSEC *
95 Maintenance 23.3 Removing the cover of the compartment for customer low voltage equipment a s d f g Compartment cover Screwed on cover Compartment for customer low voltage equipment Control panel cover for a panel without switching devices Control panel cover for a panel with switching devices Fig 76: Access to the compartment for customer low voltage equipment Removing the compartment cover Remove the screws that secure the compartment cover. Remove the compartment cover * MAINTENANCE SIMOSEC * REVISION 02 95
96 Maintenance 23.4 Removing the cover of the bus bar compartment a s Bus bar compartment cover Bus bar compartment Fig 77: Access to bus bar compartment Remove the screws on the bus bar compartment cover. Remove the bus bar compartment cover. 24 Testing 24.1 Verification of grounding The integrity of ground connections should be verified before performing any tests. Check the following at each panel: All grounding connections properly made. Proper operation of grounding switches. Check that all three movable grounding contacts of the discharging switch touch the cable termination point as shown in Fig. 69, page 92, and that the moving contact of switch-disconnectors are in the GRD ( grounded ) position as shown in Fig. 70, page REVISION 02 * MAINTENANCE SIMOSEC *
97 Maintenance 24.2 Verification of correct terminal-phase connections The three-position switch-disconnector of the feeder to be tested must be in OPEN position. The switchgear main bus bar must be energized. The outgoing circuit must also be energized from the remote source (not by closing the three-position switchdisconnector). Verify correct terminal-phase connections at the capacitive test sockets of the panel to be tested as compared to the test sockets of an adjacent panel conntacted to the same main bus bar, and whose three-position switch-disconnector is closed. The phase connections are verified using a phase comparison test unit. Plug the test leads of the phase comparison test unit into the L1 test sockets of the two panels. Fig 78: Use of electronic phase comparer Read the indication. Proceed in the same way with the test sockets of the other phases ( L2 and L3 ). If the test unit shows coincidence in each case, the phase sequence of the tested feeder is correct * MAINTENANCE SIMOSEC * REVISION 02 97
98 Maintenance 24.3 Cable testing For cable testing, the operating and installation instructions of SIMOSEC switchgear must be observed as well as the specifications and recommendations of the cable and cable termination manufacturers. Voltage transformers or surge arresters connected to the circuit to be tested must be removed or disconnected. SIMOSEC switchgear is designed for rated voltages up to 27.6 kv and the connected cable can be tested with a DC test voltage of up to 72 kv for cable tests. During this test, the main bus bar voltage can be energized at normal system AC voltage up to 27.6 kv. Do not exceed test voltage recommended by the cable manufacturer. Rated voltage of switchgear DC test voltage, maximum value VLF* test voltage cosine-rectangular waveform rms (peak) voltage VLF* test voltage sinusoidal waveform rms (peak) voltage 15 kv 55 kv 22 (22) kv 16 (22) kv 27.6 kv 72 kv 33 (33) kv 23 (33) kv * Very Low Frequency. Refer to IEEE Std , IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF). For cosine-rectangular waveform, the rms value is taken as equal to the peak value. For sinusoidal waveform, the rms value is times the peak value if distortion is less than 5%. Preconditions for testing: Procedure to be followed for cable testing: Three-position switch in "OPEN" position Isolate the panel feeder to be tested. Isolate all sources of voltage from the cable circuit to be tested, and lockout switching devices to prevent re-energization. Verify safe isolation from sources of voltage. Ground the cable to be tested. OPEN compartment cover (see Removing the cable compartment cover on page 92). Connect source of test voltage to the cable connection point of cable to be tested. Switch switching devices of panel to be tested to test position (OPEN position). Test cable in accordance with instructions of the test equipment manufacturer. Do not exceed test voltage recommended by the cable manufacturer. After test is complete, ground the cable that was tested. Remove test connections from the cable connection point. Reinstall the cable compartment cover. The cable has been tested. Other panels can be tested, or the panel can be put into operation again. 98 REVISION 02 * MAINTENANCE SIMOSEC *
99 Maintenance 24.4 Cable sheath testing Isolate the panel feeder to be tested. Isolate all sources of voltage from the cable circuit to be tested, and lockout switching devices to prevent re-energization. Verify safe isolation from sources of voltage. Ground the cable to be tested. Remove the cable compartment cover (see Removing the cable compartment cover on page 92). Isolate the cable shield from the ground connection. Perform cable shield test in accordance with cable manufacturer s recommendations. Reconnect the cable shield to ground. Reinstall the cable compartment cover. The cable shield has been tested. Other cable shields can be tested, or the panel can be put into operation again. 25 Replacing HV HRC (current limiting) fuses Always replace the HV HRC (current limiting) fuses in all three phases. The actions described in this section are in logical order. In practice it may be necessary to deviate from the sequence recommended here Preparing fuse replacement Ground transformer panel (see Operation, Page 77). Remove cable compartment cover (see Removing the cable compartment cover on page 92). The cable connection compartment with the HV HRC (current limiting) fuse links is accessible * MAINTENANCE SIMOSEC * REVISION 02 99
100 Maintenance 25.2 Removing HV HRC (current limiting) fuse link a s d Post insulator Upper fuse contact HV HRC (current limiting) fuse link Fig 79: Removing HV HRC (current limiting) fuse link Grasp the HV HRC (current limiting) fuse in the lower portion of the fuse body. Pull the HV HRC (current limiting) fuse towards the front of the panel to release the fuse from the fuse clips. The HV HRC (current limiting) fuse has been removed Checking the fuse tripping mechanism When first placing the SIMOSEC switchgear into service and before installing replacement HV HRC (current limiting) fuse, check the tripping behavior of the switchdisconnector in all three phases, preferably by means of test fuses. To check the fuse tripping mechanism on switchgear connected to the power system, the panel to be tested must be isolated and grounded, including the bus bars. 100 REVISION 02 * MAINTENANCE SIMOSEC *
101 Maintenance a s d f g Test fuse (option) Striker pin Upper fuse contact Lower fuse contact HV HRC (current limiting) fuse Fig 80: HV HRC (current limiting) fuse assembly with fuse installed Install test fuse instead of the HV HRC (current limiting) fuse. Close switch-disconnector. Trip striker pin of test fuse. Verify that the striker pin of the test fuse trips the switch-disconnector and that the switch-disconnector is in the "TRIPPED" position. Open switch-disconnector. Verify by control the movement of the switch position indication (see Fig. 5: Switch position indication, page 12) that the tripping mechanism is charged. While switching the three-position switch from CLOSED to OPEN position the switch position indicator changes from TRIPPED to OPEN. This means that the stored-energized mechanism is pre-charged * MAINTENANCE SIMOSEC * REVISION
102 Maintenance 25.4 Installing the HV HRC (current limiting) fuses Select correct HV HRC fuse as shown on switchgear drawings. Grasp HV HRC (current limiting) fuse in the middle of the fuse body, with the fuse striker pin installed closest to the switch. With the fuse tilted as needed, insert the upper end of the fuse in the upper clip, and then move the fuse to vertical and install the lower end of the fuse in the lower fuse clip. Check that the fuse is installed uniformly into both the upper and lower fuse clips. a s d Grounding switch Upper fuse contact HV HRC (current limiting) fuse Fig 81: Installing HV HRC (current limiting) fuse 25.5 Completing fuse replacement Install cable compartment cover see Close the cable compartment door on page 94. Put fuse switch panel into operation (see Placing SIMOSEC switchgear into service on page 65). 102 REVISION 02 * MAINTENANCE SIMOSEC *
103 Maintenance 26 Switchgear recycling The switchgear is an environmentally compatible product. The switchgear can be disposed of in environmentally compatible manner in compliance with existing legislation. Always observe the local laws, regulations, guidelines and standards for work, health and environmental protection. The components of the switchgear should be recycled in an environmentally compatible way by dismantling into sorted scrap and residual mixed scrap. For this purpose, evacuate the SF 6 gas professionally and have it recycled. The switchgear mainly consists of the following materials: Galvanized steel (enclosure and operating mechanisms) Stainless steel (vessel) Copper (conductor bars) Silver (contacts) Cast-resin epoxy (bushings and post insulators) Plastic material (arcing chamber and fuse tripping mechanism) Sulphur hexafluoride (SF 6 ) Silicone rubber The switchgear does not contain hazardous materials. Auxiliary devices such as short-circuit indicators, relays, instruments, etc., should be disposed of as electronic scrap. Batteries have to be disposed of professionally. As for disposal of SF 6 gas and further information, please contact Siemens Service (see Field Service Operation on page 6). 27 Help Should these operating instructions not answer all your questions about installation, operation and servicing of your SIMOSEC switchgear, please contact your Siemens sales partner. Reporting faults Should an operational fault have occurred on your SIMOSEC switchgear, which you cannot clear by yourself according to the information given in these operating instructions, please contact Siemens Service immediately (see Field Service Operation on page 6). Please provide to following data to help us in answering the issue. Type, serial and panel number of the switchgear (see rating plate) Precise description of the fault (e.g. with a copy of the associated page of these instructions, photos, drawings, sketches or circuit diagrams) * MAINTENANCE SIMOSEC * REVISION
104 28 Index A Accessories... 25, 65 Accessories - checking Aligning and joining another panel Aligning the panel Assembly work, checking before commissioning Auxiliary means - installation B Bay controller - SIPROTEC Bus bar - installing Bus bar compartment - access Bus riser panel - grounding Busbars Bus-type current transformer C Cable compartment cover - removing Cable connection Cable panel - connecting to high voltage Cable panel - grounding Cable sheath testing Cable shields - connecting Cable terminations Cable testing Cable-type current transformer Checking gas density SF 6 gas Cleaning the switchgear Closing lock-out Components Connecting - high voltage Control elements Control elements - make-proof grounding switch Control elements - three-position switch Control equipment Control gate - three-position switch Correct terminal-phase connections - verification Corrosion protection - ensuring Cover of busbar compartment - removing Cover of compartment for customer low voltage equipment - removing Current transformer D De-grounding lock-out Description... 7 Disposal E Electrical data Electrical operation - test End wall - installing Environmental protection F FII-Protection-System... 20, 80 Fuse - fitting Fuse - removing Fuse replacement - completing Fuse replacement - preparing Fuse switch panel - connecting to high voltage Fuse tripping mechanism - checking Fuse-Installed-Instact-Protection-System Fuse-Installed-Intact-Protection-System Fuses - replacing G Gas density SF 6 gas - checking Ground bus bar - installing Ground grid - connecting Grounding - checking H Heater - connecting Help High voltage - connecting High voltage cables - connecting HR system HV HRC (current limiting) fuse - installing HV HRC (current limiting) fuse - removing HV HRC (current limiting) fuse - replacing HV HRC (current limiting) fuse assembly I Indicators Installation Installation - auxiliary means Installation - final work Installation - tools Installing cold shrink insulation at cable connections Installing panels Instructing the operating personnel Instrument transformer Insulating capacity Insulating caps - installing Interlocked cable compartment door Interlocks L Local-remote switch Locking device Low voltage equipment - installing Low voltage system - test Low voltage wiring - connecting LRM system M Maintenance Maintenance - switchgear Make-proof grounding switch - control elements Make-proof grounding switch - de-grounding Make-proof grounding switch - grounding REVISION 02 * INDEX SIMOSEC *
105 Make-proof grounding switch - switch position indicator...82 Mechanical operation - test...67 Metering panel - connecting to high voltage...63 Metering panel - grounding...86 Mimic diagram...16 O Operating levers - three-position switch...73 Operating mechanisms - three-position switches...11 Operating personnel, instructing...65 Operating switchgear for test...67 Operating voltage - connecting...69 Operation...70 P Packing...39 Panel - identification...91 Panel - installing...44 Panel versions...9 Placing switchgear into service...65 Power-frequency voltage test at site...68 Protection against electric shock...29 Protection against ingress of water...29 Protection against solid foreign bodies...29 Protection equipment...16 R Rating plate...22 Ready-for-service indicator... 23, 71 Ready-for-service indicator, checking...42 Recycling - switchgear S Safety instructions... 5, 65 Secondary cables - installing...64 Service conditions...31 Service location...30 SF 6 gas... 23, 71 Shipping damage claims...36 SIPROTEC Site altitude...32 Standards...30 Station ground to switchgear frame - connecting...52 Storage...41 Switch position indicator - make-proof grounding switch...82 Switch position indicator - three-position switch...73 Switchgear - cleaning...90 Switchgear - electrical test...66 Switchgear access...91 Switchgear extension...65 Switchgear features...7 T Technical data...27 Test operation...67 Testing...96 Three-phase current transformer...15 Three-position switch - closing...75 Three-position switch - control elements...73 Three-position switch - de-grounding...79 Three-position switch - grounding...77 Three-position switch - opening...76 Three-position switch - operating...73 Three-position switch - operating levers...73 Three-position switch - switch position indicator...73 Three-position switch-disconnector...10 Three-position switches - operating mechanisms...11 Tightening torques...28 Tools - installation...38 Torques...28 Transformer protection...33 Transport at site...39 Transport regulations...30 Transporting...39 U Unloading...39 V Voltage detection systems...24 Voltage transformer...15 W Window type current transformers - mounting * INDEX SIMOSEC * REVISION
106 Imprint Siemens AG Energy Sector Division Power Distribution Schaltanlagenwerk Frankfurt Carl-Benz-Str. 22 D Frankfurt Siemens AG 2010
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated
www.siemens.com/medium-voltage-switchgear Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated Medium-Voltage Switchgear Catalog HA 40.2 2014 Answers for infrastructure and
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy.
Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00 Answers for energy. Unit substation solution with type SIMOSEC primary switches, dry-type transformer
SF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact
AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125
Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
Switchgear Type 8DH10 up to 24 kv, Gas-Insulated, Extendable
CatalogHA. 00 Switchgear Type DH0 up to kv, Gas-Insulated, Extendable Medium-Voltage Switchgear Power Transmission and Distribution Switchgear Type DH0, up to kv, Gas-Insulated, Extendable Contents Application,
8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy
Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility
ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA
MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,
Vario-Series Accessories
Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT User Manual SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 - e-mail: [email protected]
www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.
s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage
MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
3AH5 Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG 11.05 2010
Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.05 2010 Answers for energy. R-HG11-172.tif 2 Siemens HG 11.05 2010 Contents Contents Page 3AH5 Vacuum Circuit-Breakers Medium-Voltage
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast
Masterclad Medium Voltage Passive Arc-Resistant Switchgear
Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand
Technical catalogue TK 503/01 E. ZX0.2 Gas-insulated medium voltage switchgear
Technical catalogue TK 503/01 E ZX0.2 Gas-insulated medium voltage switchgear Contents Page 1 Applications 4 2 Characteristics 5 3 Your benefit 6 4 Technical data 7 4.1 Technical data of the panel 7 4.2
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor
INSTALLATION, OPERATION AND MAINTENANCE MANUAL For SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor Yeomans Chicago Corporation 3905 Enterprise Court P.O. Box 6620 Aurora, IL 60598-0620 Phone:
Installation. Smart-UPS VT and MGE Galaxy 3500. Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V
Installation Smart-UPS VT and MGE Galaxy 3500 Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V Contents Safety... 1 SAVE THESE INSTRUCTIONS...............................
Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet
Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
Step 1. Item 6. Item 1
Voltage Regulators QD3/T350 Motor Replacement Kit Kit Number 57A63675100B Service Information S225-50-35 Contents General..................................... 1 Parts Supplied...............................
Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer [email protected]. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer [email protected] Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
Components for System Solutions E9/5. Ex d Enclosure System Made of Light Metal or Stainless Steel, "Flameproof Enclosure" Series 8264. www.stahl.
> Installation chamber can be fully used > Up to three mounting levels can be used > Saving of weight > Compact > Easy to combine > 26 enclosure versions > 15 window versions www.stahl.de 10303E00 The
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12
Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: [email protected] Cleaveland/Price Type TP-C2 Motor Operator
MEDIUM VOLTAGE SWITCHGEAR CATALOGUE. Code: P2490_xx
MEDIUM VOLTAGE SWITCHGEAR for secondary distribution CATALOGUE Code: P2490_xx CONTENTS 1 About us 2 Medium Voltage Business Unit Portfolio 3 Overview 8 Medium Voltage Switchgear Types. Equipment used.
ADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
Series 8146/5-V37 and Series 8150/5-V37
www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection
Remote Monitoring and REC 501 Control Unit Product Guide
Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the
Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
R.C.C.B. s two-pole LEXIC
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX
Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX Class 6065 Instruction Bulletin 6065-13 11/2011 Retain for future use. Hazard Categories and Special Symbols Read these instructions carefully and look
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number
DLP-PU/E Instruction Manual
Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv
High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage
Instructions For SF 6 Refill Kit
S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles Instructions For SF 6 Refill Kit TABLE OF CONTENTS Section Page Section Page INTRODUCTION..................................
Welcome IEEE Members and Guests Jan 20, 2014
Welcome IEEE Members and Guests Jan 20, 2014 Copyright Siemens AG 2010. All rights reserved. MEDIUM VOLTAGE GAS INSULATED SWITCHGEAR By Sharif Ahmed of Siemens Canada Copyright Siemens AG 2010. All rights
Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V
Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................
The following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
Type GM-SG-AR 5 kv and 15 kv arc-resistant metal-clad switchgear instruction manual. Answers for energy.
Type GM-SG-AR 5 kv and 15 kv arc-resistant metal-clad switchgear instruction manual Installation operation maintenance E50001-F710-A254-X-4A00 Answers for energy. Hazardous voltages and high speed moving
High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution
High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
Reliance DuraStar ORDINARY LOCATION INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS
STORAGE and HANDLING The LED Illuminator meets or exceeds all applicable specifications when shipped from the factory. All units should be inspected upon receipt to ensure that no damage has been incurred
Elektromotoren und Gerätebau Barleben GmbH
Elektromotoren und Gerätebau Barleben GmbH OPERATING INSTRUCTIONS Transformer Protection Relay NM Series (Buchholz principle) Elektromotoren und Gerätebau Barleben GmbH Table of contents Page 1. Safety
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
Medium voltage VCP-W MR2 (integral racking)
Supersedes March 2013 Contents Description Page Notices and warnings...................... 2 Introduction.............................. 3 Breaker pan configurations.................. 3 Inspection/maintenance.....................
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
Packaged Terminal Air Conditioner Wall Sleeve Installation
Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation
CAS 36 Ring Main Unit
Power distribution networks Ring Main Unit Catalogue 2008 A new path for achieving your electrical installations A comprehensive offer The range is part of a comprehensive offer of products that are perfectly
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
Explosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits
Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide
Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management
OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd
OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132
SURGE PROTECTIVE DEVICES
SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood
Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04
Circuit Breaker LTB D with Motor Drive Motor Drive ABB PP/H/HV - Page 1 Ed 2006-04 Technology Traditional technology Traditional spring operating mechanism: Closing mechanism ABB PP/H/HV - Page 2 Tripping
HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
Arc Flash Avoidance and its Application to Overhead Traveling Cranes
Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR
COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR Copyright Material IEEE Paper No. PCIC 2003-13 Eddie Wilkie Eaton Cutler-Hammer 3990 Old Tasso Road NE Cleveland, TN 37312 USA Abstract
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
Low Voltage Switchboards The Best Technical Solution for Your Ship
The Best Technical Solution for Your Ship Wärtsilä SAM Electronics Optimal Power Distribution The uninterrupted supply of power to systems and consumers onboard modern ships is an extremly important matter.
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
Electronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
Molded Case Circuit Breaker Specifications Bulletin Number 140U-D
Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents
REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)
SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY
RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions
Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED
Safe and secure distribution of medium voltage with AX1
Safe and secure distribution of medium voltage with AX1 The intelligent switchgear AX1 is a modern, air-insulated switchgear that lies at the very front line of safety and security safety for operating
Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon
Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
Operating Instructions
Important information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect
Voltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
How To Build A Low Voltage Capacitor Lvcp
Low Voltage Capacitor LVCP The new choice for Power Factor Correction LVCP : the new choice for Power Factor Correction The LVCP is a compact and powerful capacitor. It offers high modularity, unmatched
Application Technique. Safety Function: Magnetic Door Switch Monitoring
Application Technique Safety Function: Magnetic Door Switch Monitoring Products: MC1 Magnetically-coded Door Switch, Guardmaster Dual-input Safety Relay Safety Rating: CAT. 3, PLd to EN ISO 13849-1: 2008
Infrarot-Bewegungsmelder IP44
Infrarot-Bewegungsmelder IP44 infrared motion sensors IP44 ODA (weiß) slim ODA (schwarz) slim 95174 96000 ODA (weiß) ODA (schwarz) 95175 96001 Betriebsanleitung User s Manual User s Manual infrared motion
Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1
MainswitchSurfacemounting Partno. P3-63/I4/SVB Articleno. 207343 CatalogNo. SP3-063-I4CRQ IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
