Fire Risk Assessment Block of 12 Flats, 1-12 Thirlestane, St Albans

Size: px
Start display at page:

Download "Fire Risk Assessment Block of 12 Flats, 1-12 Thirlestane, St Albans"

Transcription

1 This report in issued in accordance with our terms and conditions, a copy of which is available on request. LABC Consult Ltd 66 South Lambeth Road London SW8 1RL t: f: e: consult@labc.uk.com w: Block of 12 Flats, 1-12 Thirlestane, St Albans A Report to: St Albans City & District Council Date: 29/08/2013 Project No: St Albans, 1-12 Thirlestane Issue No: 1 Document Reference: 1-12 Thirlestane, St Albans Page: 1 LABC Consult Limited is a wholly owned subsidiary of District Surveyors Association trading as LABC. Registered in England and Wales No Registered Office 66 South Lambeth Road, London SW8 1RL

2 Revision History Issue No : 01 Issue Date : 29/08/2013 Reason for Revision: Amended following peer review Issue No : Issue Date : Reason for Revision: Prepared by: Christopher Bell (For and on behalf of LABC Consult) Reviewed by: John Allen (For and on behalf of LABC Consult) Validity This report is formulated on the basis of the information and experience available at the time of preparation. It is applicable to the above-mentioned project only in accordance with the client s instructions. It is only valid provided no other modifications are made other than those for which a formal opinion has been sought and given by LABC Consult. Surveyor Christopher Bell Page No.: 2 of 46

3 IMPORTANT NOTES AND DEFINITIONS This is a legal document as required by The Regulatory Reform (Fire Safety) Order It should be read and fully understood by the Responsible Person(s) and kept in a safe place such as your Emergency Plan file. The fire risk assessment process is a dynamic one and staff should be constantly vigilant to see that fire safety is not compromised by damage to safety equipment or changes to the way the premises are used. This assessment should be reviewed in-house at least twice annually (by the responsible person ) and when any physical or procedural changes are made to or in the use of the premises. Following implementation of any recommendations made the risk the premises should be maintained at, or reduced to, at least a tolerable level. Consideration should be given to having the assessment reviewed by a competent consultant, or other competent person periodically. This is especially relevant after a significant change to the structure / layout of the premises or the way in which they are used or managed. Responsibility Good management dictates that Responsible Persons ensure that employees and other relevant persons who may be within, or in the immediate vicinity of the workplace are protected from the potentially life threatening effects of fire. In law, the Responsible Person is likely to be the employer or some other person having a degree of control over the premises. Although they may have nominated a designated employee or appointed a competent assessor to carry out the risk assessment on their behalf, delegation does not absolve the responsible persons from the duty imposed upon them. Competent person(s) nominated under Article 15(1)(b) to assist with procedures for serious and imminent danger and for danger areas: and competent person(s) nominated under Article 13(3)(b) to assist with fire fighting measures must receive adequate training and be given sufficient time to carry out those duties. General Fire Precautions Article 8 Imposes a duty on the responsible person to take such general fire precautions as may be necessary to safeguard the safety of his/her employees and other relevant persons while they are in, on or within close proximity to his premises. General fire precautions include measures to reduce the risk of a fire starting and spreading, the provision of adequate means of escape and ensuring they can be safely used at all material times, the provision for detecting and giving warning of fire and for fighting fires on the premises. He/she must also take measures in relation to arrangements for action to be taken in the event of fire including the training of staff and measures to mitigate the effects of fire. Article 9 requires the responsible person to make a suitable and sufficient assessment of the fire risks to which relevant persons are exposed in order to identify the general fire precautions necessary to protect them. This will involve identifying combustible substances and sources of ignition, looking at their proximity to one another and assessing the likelihood of a fire occurring and spreading. It also involves the identification of any unsafe acts or conditions that could compromise safety. Surveyor Christopher Bell Page No.: 3 of 46

4 Article 18 requires that one or more competent persons be appointed to assist in undertaking the preventative and protective measures. Arrangements must be in place to ensure adequate co-operation between them, and they must be provided with any information relative to their duties. Risk Assessment is an on-going dynamic part of any business. Care should be taken when making alterations to your premises, to ensure that any changes are recorded in your Risk Assessment document. People Especially at Risk Articles 9 and 19 require that people especially at risk are identified and that the information is recorded. That may include children or young people below the age of 16 & 18 years respectively who are employed, people who work in isolated locations, or who have restricted mobility or other difficulty. People who are sedated, taking medication or likely to be under the influence of drink or drugs to such an extent that it will impair their awareness or ability to respond to an emergency alarm would also be included. The outcome of any access audit carried out under the Disability Discrimination Act 1995 [as amended and extended 2005] should be taken into account. Preventative and Protective Measures Article 10 requires the responsible person to implement any preventive or protective measures on the basis of avoiding risks where possible, combating risks that cannot be avoided, replacing the dangerous with less dangerous, adapting to technical progress, developing a coherent overall prevention policy, giving priority to collective protective measures over protection of the individual and giving appropriate instructions to staff. Article 11 requires that effective arrangements for the planning, organisation, control and review of the preventative and protective measures are in place. Those arrangements must be recorded in writing where there are 5 or more employees, or a licence or alterations notice is in force requiring it. Dangerous Substances Article 12 deals with the elimination or reduction of risks from dangerous substances. If the risk from a dangerous substance cannot be eliminated it must be reduced and controlled. The detrimental effects of fire must be mitigated. Article 16 requires that, information on emergency arrangements must be available to relevant persons, except where the risk assessment shows that because of the quantity of dangerous substances in or on the premises and the control measures introduced, there is only a slight risk to them. Fire-fighting and Detection Article 13 requires that the premises are, to the extent that is appropriate, equipped with a means of detecting and giving warning of fire and that appropriate fire fighting equipment is provided where it is necessary to safeguard the safety of relevant persons. What fire fighting equipment is appropriate is determined having regard to the dimensions and use of the premises, the equipment and materials contained on the premises, chemical substances present and the maximum number of persons present. Means of Escape Article 14 requires the provision of an adequate number of exits of a suitable size and distribution. Exits must lead directly to a place of safety and be kept clear and available for use. Emergency routes and exits Surveyor Christopher Bell Page No.: 4 of 46

5 must be indicated by signs and those that require illumination must also be provided with emergency lighting. Procedures for Serious and Imminent Danger Article 15 requires that safety procedures, including fire drills, must be established to be followed in the event of serious and imminent danger and that a sufficient number of people are nominated to assist in the evacuation of the workplace. Maintenance and Testing Article 17 requires that wherever necessary to safeguard the safety of relevant persons the premises and any facilities, equipment and devices provided in connection with them must be subject to a suitable system of maintenance and be maintained in efficient working order and in good repair. The minimum periods for checking and testing of equipment should be in accordance with the relevant British Standard and training should be carried out at least twice per year or when a change of circumstance requires it. The table below gives guidance and recommendations on this. In comparatively small premises of tolerable risk evacuation drills may take the form of walking the escape routes and familiarising staff with the position of fire exits and the fire alarm operating points. In larger and/or more complex buildings such as department stores, large office blocks, multi-occupied premises or shopping centres, a full evacuation drill will probably be necessary and any laid down policy should be followed in such cases. Fire fighting equipment MAINTENANCE AND TESTING DRILLS Item Check / Test Period Service Period Fire alarm and fire detection equipment Emergency lighting Training in fire safety Weekly visual inspection by staff Weekly on site by staff carrying out tests of call points on a rotational basis Monthly illumination test by site staff On induction Annually by a competent person Twice yearly by a competent engineer Annually system inspection and full rated discharge test Refresher training at least once per year and preferably more often Safety Assistance Article 18 requires the responsible person to appoint a sufficient number of competent people to assist him/her in undertaking and monitoring the preventive and protective measures in the premises and to make arrangements for adequate co-operation between them. They must also be given sufficient time to fulfil their function in this respect. Provision of Information to Employees Article 19 requires that employees are provided with comprehensive and relevant information on risks, preventative and protective measures and the names of persons nominated to assist with the evacuation of the premises. Surveyor Christopher Bell Page No.: 5 of 46

6 Provision of Information to External Employers and the Self-employed Article 20 imposes a requirement to provide comprehensible and relevant information to employers of employees from outside undertakings and self employed persons on the risks to those employees and what preventive and protective measures have been taken to safeguard them. Training Article 21 requires that employees are provided with adequate safety training at the time they are first employed, when there is a change in work equipment, technology or system of work and that such training is repeated periodically. Co-operation and co-ordination Article 22 requires that where two or more responsible persons have duties for premises they must cooperate with each other, co-ordinate their measures and inform each other of risks arising out of the conduct of the undertaking. Validity This risk assessment is only effective once all the actions have been carried out and provided that no alterations have taken place since the assessment. It should be formally reviewed in-house at least twice per year by the responsible person and periodically by a competent fire risk assessor whenever significant change has taken place. The above notes are intended to give a broad view of the requirements of the order and the detail should not be relied upon in specific instances of doubt or challenge against enforcement by the fire, licensing, or building control authorities etc. Surveyor Christopher Bell Page No.: 6 of 46

7 Regulatory Reform (Fire Safety) Order 2005 FIRE RISK ASSESSMENT 1. CLIENT DETAILS Address of premises 1-12 Thirlestane St Albans Herts AL1 3PD Contact details Andrew llott Estates Services Officer Name of Area Manager Name of Site Manager Person seen on site Responsible person (e.g. employer) or person having control of the premises Person(s) and/or organisations having an obligation under Article 5(4) by virtue of a contract of tenancy Competent person(s) nominated under Article 18(1) to assist the responsible person in undertaking the preventive and protective measures: Competent person(s) nominated under Article 13(3)(b) to assist with fire fighting measures: Assessor Name As Above Andrew llott Andrew llott Tenants and leaseholders of individual Flats may be considered as having control of the premises in respect of the maintenance of the Flat entrance doors. To be confirmed. (TBC) None None Christopher Bell Date of 02/07/13 Date of Previous Suggested Date for Review Not Known Three months Surveyor Christopher Bell Page No.: 7 of 46

8 The purpose of this report is to provide an assessment of the risk to life from fire in these buildings, and, where appropriate, to make recommendations to ensure compliance with the Regulatory Reform (Fire Safety) Order The report does not specifically address the risk to property or business continuity from fire. Surveyor Christopher Bell Page No.: 8 of 46

9 GENERAL INFORMATION 2. THE BUILDING 2.1 Number of Floors: Four Floors 2.2 Approximate Floor Area: 219m2 each floor Total 875m2 2.3 Walls construction: 2.4 Floor construction: Concrete External facing brickwork/upvc Cladding. Internal masonry walls/partitions 2.5 Roof construction: Concrete Flat roof (assumed) 2.6 Stair and stair core construction: Concrete 2.7 Compartmentation (including period of fire resistance where known): Building appears compartmented to 60 minute fire resisting standard 2.8 Rating of fire doors: Existing Notional FD30 Doors 2.9 Places of higher fire hazard: Refuse chute/bin store 2.10 Occupancy type: Residential (General Needs Occupancy) 2.11 Fire & Rescue Service (State location & whether fire station retained / manned full time): Herts Fire & Rescue St Albans Community Fire Station 153 London Road St Albans AL1 9AY 2.12 Accessibility for fire-fighting: Good. Access to full footprint of building 2.13 Water Supply: Fire Hydrant in footpath adjacent to block 2.14 Risk assessment undertaken to common parts, and access gained to typical internal flat in block. (Non-destructive) Surveyor Christopher Bell Page No.: 9 of 46

10 3. THE OCCUPANTS 3.1 Maximum no. of occupants No. of employees 3.3 No. of members of the public 3.4 No. of sleeping occupants No. of young persons (under 18 years of age) 3.6 No. of occupants with a disability (Where persons with disabilities are present, record details of the type of disability, e.g. PRM, deafness, vision etc.) Not Known. General Occupancy assumed, with no high risk groups of people. N.B. If this is not the case then the risk will require re-assessment OCCUPANTS ESPECIALLY AT RISK 3.7 Are the fire safety arrangements for sleeping occupants in terms of fire detection and warning and emergency lighting satisfactory? 3.8 Are the fire safety arrangements and procedures for any relevant persons present with physical, mental, visual or hearing difficulties satisfactory? 3.9 Have Personal Emergency Evacuation Plans (PEEPS) been prepared where appropriate? 3.10 Are Personal Emergency Evacuation Plans (PEEPS) kept as part of the Emergency Plan? 3.11 Are the fire safety arrangements and procedures for any lone workers or other occupants working in remote areas satisfactory? 3.12 Are the fire safety arrangements and procedures for any workers engaged as part of a work experience scheme satisfactory? 3.13 Are the fire safety arrangements for any employees under the age of 18 yrs satisfactory? 3.14 Do the fire safety arrangements for the employment of young persons take account of their inexperience, lack of awareness of risks and immaturity? Is a procedure is in place to ensure that the parents of any child employed are 3.15 provided with information regarding any risks to that child and the measures taken to protect against them? See comments 3.16 It is assumed that suitable procedures are in place for any lone maintenance team/contract workers. See item 18.5 Surveyor Christopher Bell Page No.: 10 of 46

11 4. RELEVANT FIRE SAFETY LEGISLATION AND ENFORCEMENT ACTION 4.1 The following fire safety legislation applies at these premises: Regulatory Reform (Fire Safety) Order 2005 Housing Act The legislation is enforced by: Herts Fire & Rescue Service Other legislation that may have significant implications for fire precautions in the premises: Details of any outstanding matters in connection with enforcement such as Enforcement or Alterations Notices: Building Regulations TBC 5. FIRE LOSS EXPERIENCE 5.1 Previous fire losses TBC 5.2 Any loss prevention action taken to minimise the fire risk as a result TBC Surveyor Christopher Bell Page No.: 11 of 46

12 FIRE HAZARDS AND THEIR ELIMINATION OR CONTROL SOURCES OF IGNITION 6. ELECTRICAL SOURCES OF IGNITION 6.1 Fixed wiring installation periodically inspected and tested? TBC (Specify date of last test) 6.2 PAT testing carried out? (Specify date of last test) 6.3 Is there an absence of personal electrical appliances? Yes 6.4 Is there a suitable limitation on the use of trailing leads and adapters? Yes 6.5 Are all incandescent lights kept clear of flammable materials? Yes 6.6 Confirmation required that the fixed wiring installation of individual flats, and common areas has been inspected and tested. (Intervals of 10 years for long term tenancy, 5 years for shorter, & 5 years for common areas) The electrical intake/meter cupboard door on the ground floor within the common stairway is not to a FD30 standard. (Fig 1) 7. SMOKING POLICY AND SMOKING ARRANGEMENTS 7.1 Smoking prohibited in the building? Yes 7.2 No Smoking signs clearly displayed throughout the building? Yes 7.3 Suitable arrangements for those who wish to smoke? No 7.4 Absence of any evidence of breaches of policy? Yes 7.5 No no smoking signs, and no external receptacle for smoking Surveyor Christopher Bell Page No.: 12 of 46

13 8. PORTABLE HEATERS AND OPEN FLAME EQUIPMENT 8.1 Is the use of the more hazardous types of portable heater, such as radiant bar fires or LPG appliances avoided? 8.2 Are open-flame and radiant fires and/or similar equipment are adequately guarded where necessary? 8.3 Is the use of any open flame equipment such as bunsen burners, blowlamps and blowtorches etc. restricted to safe areas? 8.4 Are portable heaters properly guarded and secured in position? 8.5 Are suitable measures taken to minimize the possibility of combustible materials being ignited by portable heaters? 8.6 Given the above, is adequate control exercised over the use of portable heaters? 8.7 None 9. FIXED HEATING INSTALLATIONS 9.1 Is the main heating for the premises provided by a low pressure hot water system, under-floor heating, night storage heaters, high-level fixed radiant heaters, a warm air system, or some other safe form? 9.2 Are fixed heating installations such as night storage heaters, under-floor heating, high-level fixed radiant heaters and warm air systems clear of combustible materials? 9.3 Are fixed heating installations such as night storage heaters, under-floor heating, high-level fixed radiant heaters and warm air systems regularly tested? 9.4 Given the above, is the main source of heating for the premises provided in a safe form for the particular environment? Yes Yes 9.5 No heating to common areas Generally gas boilers installed to flats. Residents to ensure regular servicing. 10. CATERING ARRANGEMENTS 10.1 Are extractor filters changed or cleaned regularly, i.e. in accordance with the guidance published by the Heating and Ventilation Contractors Association? Surveyor Christopher Bell Page No.: 13 of 46

14 10.2 Is the extraction ductwork cleaned regularly, i.e. in accordance with the guidance published by the Heating and Ventilation Contractors Association? 10.3 Are deep fat fryers properly cleaned on a regular basis? 10.4 Are deep fat fryers protected by a fixed fire suppression system? 10.5 Are suitable portable extinguishing appliances available? 10.6 Are cooking fats and oils stored appropriately? 10.7 Given the above, are reasonable measures taken to prevent fires as a result of cooking? 10.8 None 11. LIGHTNING 11.1 Does the building have a lightning protection system fitted? 11.2 Is any lightning protection system provided tested annually? Retrospective installation of lightning protection is rarely likely to be considered essential for compliance with legislation in existing blocks of flats. However, any existing lightning protection systems should be subject to regular inspection and testing. Guidance on this is available in BS EN Not evident It was noted that the TV aerial distribution board is located on an external wall, and open to the elements. It is recommended that this be provided with a suitable enclosure. (Fig 2) 12. ARSON 12.1 Does basic security against unauthorised entry by outsiders appear to be sufficient? No 12.2 Are external storage / yard areas enclosed by fences, walls & gates No 12.3 Are bins / skips stored outside the building locked overnight? No Are external fire loads kept well away from the premises and perimeter fence where they will be unavailable for ignition by outsiders? Are corridors, rooms, or areas accessible to outsiders kept clear of combustible refuse and other easily ignited items? Surveyor Christopher Bell Page No.: 14 of 46 No No

15 12.6 Is there a policy for controlling and disposing of combustible refuse? Yes 12.7 Given the above, are reasonable measures taken to prevent fires as a result of arson? No Common access lobby/stairwell not secure from unauthorised entry. (Fig 3) 12.8 Refuse Chute within stairwell, and bin store below not enclosed in fire resisting construction, and not secure/locked, and is located immediately adjacent to fire exit. (Fig 4, 5, & 6) See also item OTHER SOURCES OF IGNITION 13.1 Are processes using oxidising chemicals properly controlled? 13.2 Are manufacturing processes producing significant heat properly controlled? 13.3 Are any pyrotechnics and/or explosives used in or on the premises properly controlled? Battery Charging Facilities 13.4 Are the battery charging facilities provided with the correct safeguards against arcing and sparking? 13.5 Are batteries of the valve regulated ( maintenance free ) type which are much less likely to release hydrogen than vented batteries? 13.6 Are the battery-charging facilities provided with dedicated extraction to prevent the build up of hydrogen to minimise the risk of explosion? 13.7 Given the above, are reasonable measures taken to prevent fires as a result of other sources of ignition? 13.8 None SOURCES OF FUEL 14. GAS 14.1 Are annual tests carried out on pipework and appliances by a Gas Safe registered engineer? 14.2 Is the position of the gas shut-off valve(s) is indicated with a suitable notice? No Surveyor Christopher Bell Page No.: 15 of 46 TBC

16 14.3 Confirmation required that gas pipework and appliances have been tested by GAS SAFE registered Engineer. Locate gas shut off valve and provide suitable notice. 15. FUEL OIL STORAGE 15.1 Are any oil fired boilers and ancillary facilities serviced annually? 15.2 Is the oil stored in a suitable, bunded tank? 15.3 None 16. OTHER POTENTIAL FUEL HAZARDS THAT WARRANT CONSIDERATION Are any flammable liquids, gases or dusts kept in or on the premises stored and used safely? Are any plastics, rubber and/or foam plastics kept in or on the premises stored and used safely? Are paper, cardboard, textiles and wooden or upholstered furniture kept sufficiently far away from ignition sources? Does any upholstered furniture comply with the Furniture and Furnishing Regulations 1988? Are any oxygen cylinders or oxidising chemicals kept in or on the premises stored and used safely? Are any materials covered by COSHH properly stored where they cannot easily become involved in fire? 16.7 Are any other significant sources of fuel properly controlled? 16.8 Given the above, are reasonable measures taken to prevent fires as a result of other potential fuel hazards? Yes 16.9 None Surveyor Christopher Bell Page No.: 16 of 46

17 17. HOUSEKEEPING & REMOVAL OF WASTE 17.1 Do combustible materials appear to be adequately separated from ignition sources? Yes 17.2 Is the accumulation of combustible materials and/or waste avoided? Yes 17.3 Are there appropriate storage arrangements for combustible materials? No 17.4 Are waste and materials stored outside separated from ignition sources? Yes 17.5 Are there procedures to ensure that waste stored outside is kept in an ordered manner and those quantities are controlled by regular waste collections? 17.6 The refuse chute is located within the single stairway and discharges directly into a bin store at ground level. Both chute and store are not separated by fire resisting construction. See item 12.8 above. Yes 18. HAZARDS INTRODUCED BY OUTSIDE CONTRACTORS 18.1 Are written fire safety conditions imposed on outside contractors? TBC 18.2 Is a satisfactory hot work permit system used to control works carried out in the building by outside contractors? 18.3 Is a suitable hot work permit system used to control works carried out by in-house maintenance personnel? 18.4 Given the above, is the risk of outside contractors introducing hazards properly guarded against? TBC TBC TBC 18.5 Recommend maintenance team/contractors undertake risk assessments and are issued appropriate policy procedures and permits to work as necessary. 19. OTHER SIGNIFICANT FIRE HAZARDS Is there any process or other hazard that requires the general fire precautions to be reviewed? Is proper control exercised over any process that results in the formation of very fine particles? 19.3 Is proper control exercised over any process involving cutting, grinding or welding? 19.4 Is proper control exercised over any process involving the use of hot surfaces, melting of flammable solids or heat producing machinery? No Surveyor Christopher Bell Page No.: 17 of 46

18 19.5 None 20. DANGEROUS SUBSTANCES 20.1 List dangerous substances: None 20.2 Are storage arrangements for hazardous materials satisfactory? Has the risk from dangerous substances been eliminated, reduced or properly 20.3 controlled? Is information on emergency arrangements for dealing with dangerous substances 20.4 available to relevant persons in appropriate circumstances? Where dangerous substances are, or could be, used, has a risk assessment been 20.5 carried out, as required by the Dangerous Substances and Explosive Atmospheres Regulations 2002? 20.6 None Surveyor Christopher Bell Page No.: 18 of 46

19 PREVENTATIVE AND PROTECTIVE MEASURES 21. MEANS OF ESCAPE FROM FIRE Stair Cores 21.1 Are there sufficient staircases? Yes Are the staircases wide enough to cater for the full occupancy during simultaneous evacuation? Are the staircases adequately protected at each level by two self-closing fire doors, forming a fire lobby, where appropriate? 21.4 Are fire-fighting stairs provided where necessary? 21.5 Are any external staircases and walkways provided with protection against inclement weather? 21.6 Is there a procedure in place to ensure that external staircases and walkways which are not weather protected are kept clear of snow and ice etc.? Final Exits 21.7 Are there an adequate number of final fire exits? Yes 21.8 Is the use of sliding or revolving doors as fire exits avoided where necessary? Yes 21.9 Do fire exits open in the direction of escape where necessary? Are fire exit doors easily and immediately openable from the inside without a key where necessary? Are the fastenings on fire exit doors of a satisfactory type, e.g. panic bars? Yes Are fire exits routinely checked on a daily basis? TBC Travel Distances Where there is a single direction of escape, is the travel distance acceptable? Yes Where there are alternative directions of escape are the travel distances acceptable? Internal Fire Doors Are all fire doors fitted with a self-closing device which fully closes the leaf into the frame from any angle, overriding the resistance of any latch and/or seals but not including rising butts? (BS 9999: 2008) Are all fire doors not provided with a self-closing device kept locked? Yes Are all fire doors fitted with a latch which engages when located in the frame? Yes Yes See comments Not necessary Yes No Surveyor Christopher Bell Page No.: 19 of 46

20 21.18 Are all fire doors of the correct fire rating to comply with the fire strategy and means of escape arrangements for the building? (Generally FD30 doors are 44mm thick and FD60 doors are 54mm thick.) No Are all fire doors provided with intumescent strips? No Are all fire doors provided with cold smoke seals? No Are the gaps around all door edges and door frames 4mm or less? Are the gaps between the bottom of all fire doors and the sill 8mm or less? TBC Are vision panels installed where required? Yes Were all doors found to be free of wedges or other obstructions? Yes Are all fire doors free from damage which could affect their fire rating? TBC General Is the protection of internal horizontal escape routes adequate? No Are inner rooms provided with adequate means of warning and escape? No Were corridors, staircases and escape routes found to be free from obstruction? Yes Are all occupants able to reach or be assisted to a place of ultimate or comparative safety within an acceptable period of time? Evacuation of Occupants with a Disability Is the building provided with acceptable means of escape arrangements for disabled people? Are satisfactory safe refuges provided for people with disabilities (BS 9999: 2008)? Are refuges provided with communications facilities complying with BS 5588: Part 8? Are evacuation lifts provided for use in an emergency by people with disabilities? Are lifts indicated with notices describing their status, e.g. Fire Lift, or Evacuation Lift? Are lifts indicated with notices prohibiting their use in the event of fire? Are evacuation chairs or other means provided to assist with the movement of disabled people onto the ground or exit floor? Are members of staff trained in the use of evacuation chairs? See comments Typical original flat entrance door was noted as 44mm thick with 25mm stops, rising butt hinges, and non fire resisting letterbox ((Fig 7). In the guide Fire safety in purpose built blocks of flats (July 2011), in certain circumstances these doors subject to being in good condition, good fit in frame, fire resisting letter box, & self closing device fitted can be accepted. It is advised that all Yes Surveyor Christopher Bell Page No.: 20 of 46

21 these doors be examined and checked to ensure they meet this standard, with rising butt hinges being replaced with self closing devices, and fitting fire resisting letter boxes as a minimum. Where not meeting all the above criteria these doors should be upgraded/replaced to an FD30s standard. Under a planned & phased programme it is recommended that all these doors be replaced to an FD30s standard. Adjacent to the flat entrance door is located a store & electric/gas meter cupboard. It was noted that this cupboard is accessible from both within the flat and outside in the stairwell, and does not have fire resisting access doors fitted. (Fig 8) This cupboard should be permanently separated from the stairwell by fire resisting construction, or alternatively separated from the flat in the same way. Access door(s) from the stairwell side should be upgraded or replaced to meet an FD30 standard, be locked, and signed fire door keep locked. It was noted that Internal flat hallways are not enclosed in fire resisting doors providing a protected lobby to the stairwell. See item 27.3 In respect of the internal flat layout it was noted that the two bedrooms (inner rooms) were located remote from the flat entrance door and access only obtained through the living room (outer room). The location of the kitchen adjacent to the flat entrance door compounds this very poor arrangement in respect of means of escape. This layout is not considered adequate as a suitable means of escape from the flat. An immediate practicable solution could be to extend the mains operated smoke detection system to cover all habitable rooms within the flat, and a heat detector in the kitchen. The system should accord with BS 5839 Part 6. An FD 20 fire door should also be provided to the kitchen to isolate the high risk. Alternatively, and recommended is a fire sprinkler system installed in accordance with BS 9251, or mist system in accordance with DD 8458 & DD8489. As the building has good compartmentation it is recommended that a Stay Put Policy be adopted, providing all flat entrance doors meet an FD30s Standard, and recommendations made in the Action Report in respect items 8, 9, 10, & 13 are implemented. Residents should be made aware of this fire safety strategy, along with general fire safety information. 22. EMERGENCY ESCAPE LIGHTING Commissioning and Testing 22.1 Is there a commissioning certificate to validate the system? TBC 22.2 Has the system been checked to ensure connection to relevant electrical sub-circuits? TBC 22.3 Are the neon indicators in emergency lighting units visually inspected by staff on a regular basis between monthly tests? Surveyor Christopher Bell Page No.: 21 of 46 TBC

22 Is the emergency lighting system tested at least once per month by a member of staff? Is the emergency lighting system subject to a full annual discharge test by a competent engineer? System Design and Features Does the emergency lighting system have a duration period appropriate to the type of premises? Was confirmation obtained on-site that there is sufficient illumination provided by the emergency lighting system for occupants to see to leave the building safely? Are external routes, (including outside final exits and assembly points) adequately illuminated by both primary and emergency lighting? Are toilets larger than 8m 2 and those provided for people with disabilities fitted with emergency lighting? Are areas larger than 60m 2 provided with anti-panic lighting? Are there suitable emergency lighting systems for higher task work areas? There appears to be an emergency lighting system installed to common stairwell, and external exit routes, although no neon indicators are visible. N.B. Common areas have good natural day lighting, and borrowed artificial lighting from street lighting. TBC TBC TBC No Yes 23. FIRE SAFETY SIGNS AND NOTICES 23.1 Are all fire doors provided with Fire Door Keep Shut or Fire Door Keep Locked notices? 23.2 Are all routes and changes of direction clearly and adequately indicated? Are sufficient and suitable fire action notices conspicuously displayed around the premises, (e.g. near fire alarm points and storey exits)? Are fire alarm operating points indicated with appropriate signs where they might be obscured or otherwise unobserved or unrecognised? 23.5 Is the fire assembly point and the route to it adequately signposted and indicated? No No 23.6 Display of Fire Action notices not considered necessary. Surveyor Christopher Bell Page No.: 22 of 46

23 24. MEANS OF GIVING WARNING IN CASE OF FIRE Type of Fire Alarm System 24.1 Grade of fire alarm system: None in communal areas. Category LD3 System in circulation areas (the two hallways) of individual flats 24.2 Is an adequate manually operated electrical fire alarm system provided? Is the type of sounder/alerter appropriate for the use of the premises and all occupants including those with hearing difficulties and lone workers? Where people sleep on the premises does the fire warning system take account of people with hearing difficulties, (e.g. vibrating pads or pillows)? 24.5 Is automatic fire detection provided throughout the building? No 24.6 Is the extent of automatic fire detection generally appropriate for the occupancy and fire risk? 24.7 Where required, are emergency refuge communication points provided? Fire Warning and Fire Alarm Transmission Protocols 24.8 If the fire warning system has two stages of operation, is that arrangement appropriate? 24.9 Is there a pre-investigation period built into the fire warning system? If yes, specify the pre-investigation period Not Necessary Yes Is the pre-investigation period appropriate considering the fire safety management arrangements in operation at the premises Are fire alarm signals transmitted automatically to a remote alarm receiving centre? No Testing and Maintenance Is the fire alarm tested weekly using a different break glass call-point, ensuring that all call points are tested in rotation over a period of time? Is the control and indicating equipment checked daily to ensure there are no fault conditions showing? Is the fire warning system tested and serviced at least twice per year by a competent engineer? Regular testing of smoke detectors to be part of fire safety advice given to tenants/occupiers Surveyor Christopher Bell Page No.: 23 of 46

24 25. FIRE COMPARTMENTATION Where required, are walls for the protection of escape corridors, lobbies and stairs, of an acceptable fire resisting standard? Where required, are floors separating one level from another to prevent fire spread, of an acceptable fire resisting standard? Where required, are walls and floors for fire protection and separation free from holes and other breaches? Are areas of wall and ceiling linings that might promote fire spread limited to acceptable proportions? Are structural features that could allow the rapid spread of fire and the passage of smoke, such as lifts, service shafts and staircases etc. properly protected? Are fire dampers provided as necessary to protect critical means of escape against the passage of fire, smoke and combustion products in the early stages of a fire? Yes Yes See comments No common area breaches of compartmentation evident. Recommend that intrusive investigation be carried out to a sample of individual flats to check for any breaches of fire resisting enclosures/fire stopping to any service risers, including soil pipe (SVP). Yes Yes 25.7 As the building has good compartmentation it is recommended that a Stay Put Policy be adopted, providing all flat entrance doors meet an FD30s Standard, and recommendations made in the Action Report in respect items 8, 9, 10, & 13 are implemented. Residents should be made aware of this fire safety strategy, along with general fire safety information. 26. AUTOMATIC FIRE EXTINGUISHING SYSTEMS 26.1 Specify type(s) of system: 26.2 Location(s) of systems(s): 26.3 None 27. SMOKE CONTROL SYSTEMS 27.1 Specify type(s) of system: Manual 27.2 Location(s) of systems(s): Surveyor Christopher Bell Page No.: 24 of 46

25 27.3 Smoke venting to the common stairway possible through existing roof light at head of stairway. (N.B. In consultation with Herts Fire & Rescue Service this has been accepted as being adequate for purpose) N.B. Omission of protected lobbies to flats can be accepted subject adequate ventilation to the stairway. (Guide Fire safety in purpose built blocks of flats (July 2011)) 28. MANUAL FIRE EXTINGUISHING APPLIANCES 28.1 Is there adequate provision of portable fire extinguishers? None 28.2 Are fire hose reels provided where necessary? 28.3 Are members of staff trained to use fire hose reels? 28.4 Are fire extinguishing appliances readily accessible? 28.5 Are fire extinguishers mounted on wall brackets or floor stands? 28.6 Are fire extinguishing appliances tested annually by a competent engineer? (Specify date of last test) 28.7 None 29. FIRE FIGHTER SWITCHES 29.1 Is there suitable provision of fire-fighter s switches for high voltage luminous tube signs, etc.? 29.2 Are fire-fighter s switches tested periodically to ensure safe and proper operation? 29.3 Location of switches: 29.4 None Surveyor Christopher Bell Page No.: 25 of 46

26 MANAGEMENT OF FIRE SAFETY 30. PROCEDURES AND ARRANGEMENTS 30.1 Fire safety is managed by: Name Andrew llott Position: Estates Services Officer Competent person(s) appointed to assist in undertaking the preventive Name and protective measures (i.e. relevant general fire precautions)? Position Where there are two or more responsible persons in the building or premises are arrangements in place to ensure their co-operation and co-ordination of their safety measures Is there a suitable record of the fire safety arrangements? No 30.5 It appears that an adequate fire risk assessment of the building has not been carried out in the past. Absence of fire safety records & log book 31. EMERGENCY PROCEDURES 31.1 Are procedures to be followed in the event of fire properly documented? TBC 31.2 Is there a suitable procedure for summoning the Fire and Rescue Service? TBC Are there suitable procedures for liaising with the Fire and Rescue Service upon their 31.3 arrival including the provision of relevant information (especially in relation to hazards to fire fighters)? Are there suitable procedures for ensuring that the premises have been fully 31.4 evacuated? Are there adequate arrangements to cater for the evacuation of disabled people who 31.5 may be present? 31.6 Recommend that the above emergency procedures are reviewed, and where relevant put in place. General fire safety information including what to do in an emergency be confirmed to all residents. TBC TBC Surveyor Christopher Bell Page No.: 26 of 46

27 32. PROCEDURES FOR SERIOUS AND IMMINENT DANGER Are members of staff are given adequate fire safety instruction and training on induction? Are members of staff given adequate periodic refresher training at suitable intervals? Are members of staff given adequate instruction and training on the use of fire extinguishers? Are members of staff with special responsibilities (e.g. fire wardens) given additional training? Are fire drills carried out at appropriate intervals and is there a procedure for assessing their success and where appropriate for reviewing procedures in the light of problems identified? Does staff training include the provision of information, instruction and training on the following? Fire risk in the premises Fire safety measures in the building Action in the event of fire Action on hearing the fire alarm Roll call procedures Method of operation of manual call points Location of fire extinguishers Means of summoning the Fire and Rescue Service Identity of persons nominated to assist with evacuation Identity of persons nominated to use fire extinguishing appliances 32.7 See Item PROVISION OF INFORMATION TO EMPLOYEES AND OTHER RELEVANT PERSONS 33.1 Are employees provided with information in accordance with Article 19 of the Regulatory Reform (Fire Safety) Order 2005? Surveyor Christopher Bell Page No.: 27 of 46

28 33.2 Are employees of another employer working in the premises given appropriate information on fire risks and procedures in accordance with Article 20 of the Regulatory Reform (Fire Safety) Order? 33.3 See Item 3.16 & 18.5 MAINTENANCE 34. MAINTENANCE AND TESTING Is the fire alarm system tested weekly and periodically inspected by a competent contractor in accordance with the guidance contained BS : 2002? Is the emergency lighting system tested monthly to confirm operability of the system and is the system inspected and tested annually by a competent contractor? 34.3 Are manual fire extinguishing appliances inspected and tested annually? Are external stairs and external escape routes periodically inspected to ensure they are free form obstruction and in a safe condition? Are rising and falling mains inspected and tested annually or 6-monthly where necessary? (Specify date of last inspection) 34.6 Are fire-fighting lifts checked monthly for correct operation? 34.7 Are fire-fighting lifts inspected annually by a competent person? 34.8 (Specify date of last inspection) Is the sprinkler system tested weekly and inspected twice yearly by a contractor approved by a third party accreditation scheme? 34.9 Is the lightning protection system inspected and tested annually? TBC See comments Are final exit doors and security fastenings checked daily to ensure all final exit doors are easily openable? Evidence of inspecting and testing the emergency lighting & and smoke detection system to be provided It has been assumed that stairwells are periodically inspected to ensure that they are free from obstruction and in a safe condition. Surveyor Christopher Bell Page No.: 28 of 46

29 35. RECORDS Are appropriate records kept of: 35.1 Fire drills 35.2 Fire training 35.3 Fire alarm tests 35.4 Refuge communication tests 35.5 Emergency escape lighting tests 35.6 Maintenance and testing of other fire protection systems 35.7 Staff training 35.8 Fire safety log book to be established & include all relevant fire safety information records Surveyor Christopher Bell Page No.: 29 of 46

30 EVALUATION OF FIRE SAFETY The following simple risk level estimator is based on a more general health and safety risk level estimator contained in BS 8800: Potential consequences of fire Fire hazard Slight harm Moderate harm Extreme harm Low Insignificant risk Tolerable risk Moderate risk Medium Tolerable risk Moderate risk Substantial risk High Moderate risk Substantial risk Intolerable risk Taking into account the fire prevention measures observed the hazard from fire (probability of ignition) at this building is: Taking into account the nature of the building and its occupants, as well as the observed fire protection and procedural arrangements, the direct consequences for life safety in the event of fire would be: LOW * MEDIUM HIGH SLIGHT HARM MODERATE HARM * EXTREME HARM In this context, a definition of the above terms is as follows: LOW MEDIUM HIGH Unusually low likelihood of fire as a result of negligible potential sources of ignition. Normal fire hazards (e.g. potential ignition sources) for this type of occupancy, with fire hazards generally subject to appropriate controls (other than minor shortcomings). Lack of adequate controls applied to one or more significant fire hazards, such as to result in significant increase in likelihood of fire. Accordingly, the risk to life from fire at this building is: INSIGNIFICANT TOLERABLE MODERATE * SUBSTANTIAL INTOLERABLE Surveyor Christopher Bell Page No.: 30 of 46

31 A suitable risk-based control plan should involve effort and urgency that is proportional to risk. The following risk-based control plan is based on one advocated by BS 8800 for general health and safety risks: RISK LEVEL Insignificant Tolerable Moderate Substantial Intolerable ACTION AND TIMESCALE No action is required and no detailed records need be kept. No major additional controls required. However, there might be the need the need to consider for improvements that involve limited cost or resources. It is essential that efforts be made to reduce the risk. Risk reduction measures should be implemented within a defined time period. Where moderate risk is associated with consequences that constitute extreme harm, further assessment may be required to establish more precisely the likelihood of harm as a basis for determining the priority for improved control measures. Considerable resources may have to be allocated to reduce the risk. If the building is unoccupied, it should not be occupied until the risk has been reduced. If the building is occupied, urgent action should be taken. Building (or relevant area) should not be occupied until the risk is reduced. Note that, although the purpose of this section is to place the fire risk in context, the above approach to fire risk assessment is subjective and for guidance only. All hazards and deficiencies identified in this report should be addressed by implementing all recommendations contained in the following section. The risk assessment should be reviewed periodically. Surveyor Christopher Bell Page No.: 31 of 46

32 ACTION PLAN AND GUIDANCE NOTES Article 5 requires the responsible person to ensure that any duty imposed by articles 8 to 22 is complied with in respect of these premises. Article 8 requires the responsible person to take such general fire precautions as will ensure, so far as is reasonably practicable, the safety of employees, and to take such general fire precautions as may reasonably be required in the circumstances of the case for other relevant persons. Article 10 requires that preventative and protective measures must be implemented on the basis of the principles specified in Schedule 1: Part 3, viz. risks must be avoided if possible and if not they must be evaluated and combated at source. The actions listed below are considered necessary to comply with those statutory duties. Guidance Whilst all of the items listed below are considered necessary to meet the statutory duty imposed on the responsible person, it must be recognised that everything cannot be done at once. It should be borne in mind that, although they appear less important than other higher priority items that might take longer to complete, easily achieved improvements should not be unnecessarily delayed and dealt with in strict rotation. It is considered that the following recommendations should be implemented in order to reduce fire risk to, or maintain it at insignificant or tolerable level: Definition of Priorities Immediate action required for legislative compliance. High priority Medium priority Contravention of statutory requirements that could lead to a fire resulting in fatalities and/or serious injury, and the issue of a prohibition notice and/or legal proceedings instituted by the enforcing authority. Action required to be completed within 3 to 6 months for legislative compliance. Contravention of statutory requirements that could lead to a fire resulting in injury and/or the issue of an enforcement notice. These matters should be part of a planned programme of work to address deficiencies in the fire precaution arrangements and/or control the risk(s) and implementation should not be unduly delayed. Action necessary as part of a planned programme of work to meet the principles of good fire safety practice. Low priority These are matters where the principles of good fire safety practice and/or established company procedures are not being followed. Enforcement action is unlikely, but fire, accidents and/or property damage could result. The suggestions made are recommended to improve fire precautions and/or health and safety practices. Surveyor Christopher Bell Page No.: 32 of 46

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT This template has been provided to assist the Responsible Person with the preparation of a Fire Risk Assessment and is not intended for commercial

More information

Fire Safety Risk Assessment Checklist for Residential Care Premises

Fire Safety Risk Assessment Checklist for Residential Care Premises Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005. Fire Risk Assessment. 145 Drury Lane Covent Garden London WC2B 5TA

REGULATORY REFORM (FIRE SAFETY) ORDER 2005. Fire Risk Assessment. 145 Drury Lane Covent Garden London WC2B 5TA REGULATORY REFORM (FIRE SAFETY) ORDER 2005 Fire Risk Assessment 145 Drury Lane Covent Garden London WC2B 5TA Annex A (informative) Model pro-forma for documentation of the fire risk assessment for premises

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT The Regulatory Reform (Fire Safety) Order 2005 FIRE RISK ASSESSMENT Employer or other responsible person Name of Premises Address Post Code Telephone N o Name of Assessor(s) Date of Assessment Date of

More information

Fire Risk Assessment Safety Checklist

Fire Risk Assessment Safety Checklist Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory

More information

For use by landlords of small premises Premises Address

For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern

More information

Fire Safety Risk Assessment

Fire Safety Risk Assessment 1 Sources of ignition The main sources of ignition in Cass building are: PAF arrange for the fixed electrical installation to be tested in accordance with the British Standards. Test certificates are kept

More information

Fire Risk Assessment For Simple Premises

Fire Risk Assessment For Simple Premises Fire Risk Assessment For Simple Premises Responsible Person (Employer or other person having control of the relevant premises) Company / Premises Name Address of Premises Postcode Primary Use of Premises

More information

Fire risk assessment a guide for businesses

Fire risk assessment a guide for businesses Fire risk assessment a guide for businesses Disclaimer Cornwall Fire and Rescue Service provide this guide to assist businesses to improve fire safety in their premises, but stress the person completing

More information

FIRE SAFETY RISK ASSESSMENT

FIRE SAFETY RISK ASSESSMENT FIRE SAFETY RISK ASSESSMENT For small single occupancy premises Premises Hertco Ltd ACME House, Old London Road, Hertford SG17 7LD Fire Safety Risk Assessment for Small Premises Introduction Regulatory

More information

Grasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment

Grasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment Grasshoppers Rugby Football Sports and Social Club The Fire Risk Assessment Revision 1 Dated: 15th February 2013 CONTENTS 1. PREMISES DETAILS 2. PREMISES PLAN 3. HAZARDS 4. HISTORY 5. MITIGATING THE EFFECTS

More information

1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS

1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS Fire Risk assessment 1.0 APPOINTMENTS 1.1 Responsible Person. In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO) the School s Head, Mrs J M Miles is appointed as the Responsible Person

More information

Action required (Please tick) If you answered YES, record Action Points at STEP 4

Action required (Please tick) If you answered YES, record Action Points at STEP 4 RECORD OF FIRE SAFETY RISK ASSESSMENT Building Name & Use: Address: Postcode: Name of person(s) with fire safety duties: Name and contact details of assessor: Date of Assessment: 6 th February 2011 Laurel

More information

Lee Baron FIRE RISK ASSESSMENT

Lee Baron FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT, 13/21 Cantelupe Road, East Grinstead Prepared for: Lee Baron 7 Swallow Place Oxford Circus London W1B 2AG Prepared by: Violet McIntyre CMIOSH William Martin Compliance Solutions Limited

More information

FIRE RISK ASSESSMENT. The Workplace Fire Precautions Legislation

FIRE RISK ASSESSMENT. The Workplace Fire Precautions Legislation FIRE RISK ASSESSMENT The Workplace Fire Precautions Legislation The Fire Precautions (Workplace) Regulations 1997 The Fire Precautions (Workplace)(Amendment) Regulations 1999 The Management of Health and

More information

For use by landlords of small premises Premises Address

For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

Fire Safety Log Book

Fire Safety Log Book Fire Safety Log Book Company... Address........ Responsible Person. Competent Person. Date Started For Additional Information: Safety Management (UK) Ltd Holme Suite, Clawthorpe Hall Business Centre, Burton

More information

1.1. EMERGENCY PROCEDURE On discovering a fire or being informed of an emergency;

1.1. EMERGENCY PROCEDURE On discovering a fire or being informed of an emergency; Fire Action Plan FIRE ACTION PLAN SEStran aims to provide and maintain safe & healthy working conditions, equipment and systems of work for all our employees, and to provide such information, training

More information

UPP Residential Services Fire Risk Assessment

UPP Residential Services Fire Risk Assessment UPP Residential Services Fire Risk Assessment TS11151-R02-DRAFT1 15 August 2011 for: Keynes College University Road Canterbury Kent Recommended latest review date 14 August 2011 Executive summary This

More information

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone

More information

Fire precautions in dwellings. Private sector housing Providing homes building communities

Fire precautions in dwellings. Private sector housing Providing homes building communities Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared

More information

1.1.4 The findings from Fire Risk Assessment must be incorporated into the FRAMS Action Plan to manage fire safety at each premise.

1.1.4 The findings from Fire Risk Assessment must be incorporated into the FRAMS Action Plan to manage fire safety at each premise. Fire Safety Policy 1.1 Policy Statement of Intent 1.1.1 Under the current UK Legislation (In England and Wales, the Regulatory Reform (Fire Safety) Order 2005, Fire (Scotland) Act 2005, Fire and Rescue

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600 OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK MARIE CURIE SCEAUX GARDENS ESTATE LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

The terms hazard and risk are often used, which we define as the following:

The terms hazard and risk are often used, which we define as the following: Fire Safety Last updated in October 2010 This information sheet aims to give safety reps a basic understanding of fire safety and fire risk assessments under the current law. More detailed information

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK CASTLEMEAD CAMBERWELL ROAD LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

Fire Evacuation Procedures Network Building, 97 Tottenham Court Road, London, W1

Fire Evacuation Procedures Network Building, 97 Tottenham Court Road, London, W1 Network Building Fire Safety Management Plan & Fire Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means for Fighting

More information

LANCASTER UNIVERSITY. MANUAL OF SAFETY Section 29 POLICY ON FIRE RISK ASSESSMENTS

LANCASTER UNIVERSITY. MANUAL OF SAFETY Section 29 POLICY ON FIRE RISK ASSESSMENTS LANCASTER UNIVERSITY MANUAL OF SAFETY Section 29 POLICY ON FIRE RISK ASSESSMENTS 1 Introduction 1.1 The Fire Precautions (Workplace) Regulations, require the University to carry out fire risk assessments

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK PERRONET HOUSE PRINCESS STREET LONDON SE1 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

Additional Guidance. for application to. HM Government Guide to Fire Safety Risk Assessment Residential Care Premises

Additional Guidance. for application to. HM Government Guide to Fire Safety Risk Assessment Residential Care Premises Additional Guidance for application to HM Government Guide to Fire Safety Risk Assessment Residential Care Premises Good Practice Guidance 2016 Additional Guidance agreed between the National Association

More information

FIRE RISK ASSESSMENT SW13 0HA

FIRE RISK ASSESSMENT SW13 0HA FIRE RISK ASSESSMENT at Carmichael Court Grove Road London SW13 0HA ON BEHALF OF Farrar Property Management Date of assessment: 14/01/2013 Recommended review date: January 2015 CONTENTS 1.0 INTRODUCTION

More information

Guidance on loft conversions in two-storey houses

Guidance on loft conversions in two-storey houses Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for

More information

How To Write A Fire Risk Assessment

How To Write A Fire Risk Assessment Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes

More information

Fire Risk Assessment for Simple Premises Guidance Notes

Fire Risk Assessment for Simple Premises Guidance Notes Fire Risk Assessment for Simple Premises Guidance Notes The UK s national fire safety organisation Protecting people, property, business and the environment Introduction This guide and the accompanying

More information

Fire Safety Management Strategy 2015-2018

Fire Safety Management Strategy 2015-2018 Fire Safety Management Strategy 2015-2018 Introduction This strategy is a plan and method of approach to how Medway Council Housing Services (the council) will both continue to meet our statutory obligations

More information

1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety.

1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety. Management Checklist 1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety. 2. Fire Hazard and Risk Assessment. Use

More information

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the

More information

CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY

CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY This policy was written in July 2014 and will be agreed by the Board of Governors in October 2014. To be reviewed by June

More information

Fire Safety Challenges and Solutions. Claire Guise Health and Safety Manager

Fire Safety Challenges and Solutions. Claire Guise Health and Safety Manager Fire Safety Challenges and Solutions Claire Guise Health and Safety Manager Marie Curie Cancer Care (UK Wide) 9 Palliative Care Hospices (owned) Facilities Manager in place (NEBOSH General Certificate

More information

Fire Risk Assessment for

Fire Risk Assessment for Regulatory Reform (Fire Safety) Order 2005 The Management of Health and Safety at Work Regulations 1999 Fire Risk Assessment for Tokyo Diner Restaurant 2 Newport Place London WC2H 7JJ Prepared by Robert

More information

An inventory of hazardous materials used in your workplace will prove useful.

An inventory of hazardous materials used in your workplace will prove useful. Introduction Fire Protection is an organized approach designed to prevent fires. In the event of a fire, a fire protection program will help prevent or minimize personal injuries, losses, and harm to the

More information

Fire Policy and Procedures. Cañada Blanch Spanish School

Fire Policy and Procedures. Cañada Blanch Spanish School Fire Policy and Procedures Cañada Blanch Spanish School SUMMARY 1. Introduction (p. 3) 2. Roles and responsibilities (p. 3) -- Headteacher -- Fire Team -- All staff -- Contractors 3. Fire procedures (p.

More information

FIRE SAFETY GUIDANCE NOTE Regulatory Reform (Fire Safety) Order 2005

FIRE SAFETY GUIDANCE NOTE Regulatory Reform (Fire Safety) Order 2005 FIRE SAFETY GUIDANCE NOTE Regulatory Reform (Fire Safety) Order 2005 Number: GN66 This Guidance Note provides advice on the requirements of the Regulatory Reform (Fire Safety) Order 2005 and how to complete

More information

Fire Risk Assessment Report

Fire Risk Assessment Report Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Site Contact Date of Assessment Date of Report St Augustines Priory Main School Building Hillcrest Rd, London

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

FLA S FIRE SAFETY INITIATIVE

FLA S FIRE SAFETY INITIATIVE Improving Workers Lives Worldwide FLA S FIRE SAFETY INITIATIVE Preventing fires and saving lives by empowering workers and factory managers SCENARIO 1 OCCURS AT FACTORY ABC, WHICH HAS NOT IMPLEMENTED NECESSARY

More information

NOTTINGHAMSHIRE FIRE & RESCUE SERVICE. Fire Risk Assessment Information / Guidance

NOTTINGHAMSHIRE FIRE & RESCUE SERVICE. Fire Risk Assessment Information / Guidance NOTTINGHAMSHIRE FIRE & RESCUE SERVICE Fire Risk Assessment Information / Guidance Version 2 - dated March 2014 Nottinghamshire Fire & Rescue Service www.notts-fire.gov.uk CONTENTS Introduction Fire Risk

More information

Fire Risk Assessment Tool

Fire Risk Assessment Tool Fire Risk Assessment Tool DATE OF ASSESSMENT PLANNED REVIEW DATE www.twfire.gov.uk Introduction The Regulatory Reform (Fire Safety) Order 2005 (FSO) replaced previous fire safety legislation. Where the

More information

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use. Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent

More information

London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords

London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords London Borough of Barnet Fire Safety in Houses in Multiple Occupation A Guide to Landlords March 2016 Contents Introduction p.3 Summary of main requirements p.3 Fire Safety Precautions p.4 Protecting the

More information

EAST LINDSEY DISTRICT COUNCIL ~ RESIDENTIAL CARAVAN SITES CONDITIONS OF SITE LICENCE

EAST LINDSEY DISTRICT COUNCIL ~ RESIDENTIAL CARAVAN SITES CONDITIONS OF SITE LICENCE Residential Site Licence Conditions of Licence February 2014 EAST LINDSEY DISTRICT COUNCIL ~ RESIDENTIAL CARAVAN SITES Index of conditions CONDITIONS OF SITE LICENCE 1. Period of use 2. Bases 3. Siting

More information

Fire Safety Policy. Fire Safety Policy: May 2011 Page 1 of 6. Version 1. Scope:

Fire Safety Policy. Fire Safety Policy: May 2011 Page 1 of 6. Version 1. Scope: Version 1 Fire Safety Policy Scope: Effective Date: Review Date: Signed Off by: Author: Policy Owned by: This policy applies to Hackney Homes Ltd working on behalf of the London Borough of Hackney July

More information

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.

More information

PRACTICAL FIRE SAFETY GUIDANCE FOR OFFICES, SHOPS AND SIMILAR PREMISES

PRACTICAL FIRE SAFETY GUIDANCE FOR OFFICES, SHOPS AND SIMILAR PREMISES PRACTICAL FIRE SAFETY GUIDANCE FOR OFFICES, SHOPS AND SIMILAR PREMISES Revised February 2008 The guidance in this document has been jointly produced by the Scottish Government s Police and Community Safety

More information

PRACTICAL FIRE SAFETY GUIDANCE FOR EDUCATIONAL AND DAY CARE FOR CHILDREN PREMISES

PRACTICAL FIRE SAFETY GUIDANCE FOR EDUCATIONAL AND DAY CARE FOR CHILDREN PREMISES PRACTICAL FIRE SAFETY GUIDANCE FOR EDUCATIONAL AND DAY CARE FOR CHILDREN PREMISES Revised February 2008 The guidance in this document has been jointly produced by the Scottish Government s Police and Community

More information

Fire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book:

Fire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book: Fire Safety Log Book Premises Name: Premises Address: Date From: Date To: Location of Log Book: CONTENTS PART 1 FIRE SAFETY ADVICE 1 PART 2 FIRE PRECAUTIONS 2 Section 1 Guidance on Fire Risks and Preventative

More information

Fire safety advice for landlords

Fire safety advice for landlords YOU CAN PREVENT IT Fire safety advice for landlords Introduction Each year there are over 50,000 fires in dwellings in the UK. These result in around 300 hundred fatalities and several thousand serious

More information

SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS

SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses

More information

FIRE RISK ASSESSMENT WORKED EXAMPLE

FIRE RISK ASSESSMENT WORKED EXAMPLE FIRE RISK ASSESSMENT WORKED EXAMPLE 1 PREMISES PARTICULARS BE-INT05 Premises Name S M Enterprises Address Small Place Medium Road Anywhere Tel no: 01234 567890 Date of Risk Assessment 1 st July 2011 Use

More information

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this

More information

FIRE SAFETY RECORD OF TESTS LOGBOOK

FIRE SAFETY RECORD OF TESTS LOGBOOK FIRE SAFETY RECORD OF TESTS LOGBOOK PREMISES ADDRESS: Responsible person AN INTRODUCTION TO YOUR LOG BOOK The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person for a premises to

More information

FIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie

FIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie FIRE SAFETY REGISTER Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie 1 CONTENTS Section Title Page 1.0 Introduction 3 2.0 Guidance for the completion

More information

FIRE SAFETY PRECAUTIONS

FIRE SAFETY PRECAUTIONS FIRE SAFETY PRECAUTIONS LOG BOOK PLEASE KEEP AVAILABLE 1 Business Name Premises Information Building / Unit Number Property Name Road: (Address Line 1) (Address Line 2) Locality: Town: Post Code: Name

More information

Caravan Sites and Control of Development Act 1960. Permanent Residential Mobile Home Sites Licence Conditions

Caravan Sites and Control of Development Act 1960. Permanent Residential Mobile Home Sites Licence Conditions Caravan Sites and Control of Development Act 1960 Permanent Residential Mobile Home Sites Licence Conditions 1 Permanent Residential Mobile Home Site Licence Conditions Caravan Sites and Control of Development

More information

No. Name of Legislation Applicable Issues and Requirements Demonstration of Compliance 1. Health and Safety at Work Act 1974

No. Name of Legislation Applicable Issues and Requirements Demonstration of Compliance 1. Health and Safety at Work Act 1974 The Police Treatment Centres Health and Safety Legal Compliance Register No. Name of Legislation Applicable Issues and Requirements Demonstration of Compliance 1. Health and Safety at Work Act 1974 2.

More information

Housing Act 2004 Regulatory Reform (Fire Safety) Order 2005 Fire Safety in Purpose-Built Flats Have you taken sufficient action?

Housing Act 2004 Regulatory Reform (Fire Safety) Order 2005 Fire Safety in Purpose-Built Flats Have you taken sufficient action? Housing, Culture & Enterprise Private Sector Housing Hove Town Hall (Room 217) Norton Road Hove BN3 3BQ Telephone: (01273) 293156 Fax No: (01273) 292452 Email: psh@brighton-hove.gov.uk D G Prichard QFSM,

More information

Safety and Health Office WORKPLACE SAFETY CHECKLIST

Safety and Health Office WORKPLACE SAFETY CHECKLIST Location: Date: Inspected by: Safety and Health Office WORKPLACE SAFETY CHECKLIST WORK ENVIRONMENT Ventilation Removal of fumes and dust Temperature and humidity control Noise levels Vibration Lighting

More information

PRACTICAL FIRE SAFETY GUIDANCE FOR MEDIUM AND LARGE PREMISES PROVIDING SLEEPING ACCOMMODATION

PRACTICAL FIRE SAFETY GUIDANCE FOR MEDIUM AND LARGE PREMISES PROVIDING SLEEPING ACCOMMODATION PRACTICAL FIRE SAFETY GUIDANCE FOR MEDIUM AND LARGE PREMISES PROVIDING SLEEPING ACCOMMODATION Revised February 2008 Practical Fire Safety Guidance For Medium And Large Premises Providing Sleeping The guidance

More information

Fire Safety Policy & Procedures

Fire Safety Policy & Procedures Aire Valley Homes Leeds Limited East North East Homes Leeds Limited West North West homes Limited Fire Safety Policy & Procedures ALMO Business Centre Leeds Navigation House Leeds LS10 1DJ 1 Date Issued:

More information

HOT WORK PERMIT PROGRAM TRAINING. John Braun

HOT WORK PERMIT PROGRAM TRAINING. John Braun HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program

More information

Fire Safety Policy and Procedure

Fire Safety Policy and Procedure Fire Safety Policy and Procedure Approved by Audit & Risk Committee Approved Date April 2014 Version no. 3 Review Date April 2015 Page 1 of 20 CONTENTS 1.0 Introduction 2.0 Policy Statement 3.0 Fire Safety

More information

Fire Risk Assessment. John Revington

Fire Risk Assessment. John Revington Fire Risk Assessment John Revington PRACTICAL APPLICATION Identifying Fire Hazardsand Managing Fire Precautions History of Fire Fires that have changed our lives History of Fire Theatre Royal - Exeter

More information

FIRE RISK ASSESSMENT PRINCIPLES A GUIDE FOR LICENSED PREMISES

FIRE RISK ASSESSMENT PRINCIPLES A GUIDE FOR LICENSED PREMISES NFG27 FIRE RISK ASSESSMENT PRINCIPLES A GUIDE FOR LICENSED PREMISES The Workplace Fire Precautions Legislation brings together existing Health & Safety and Fire Legislation to form a set of dedicated Fire

More information

Bastille Court 2 Paris Garden London SE1 8ND Telephone: 020 7902 5314 Fax: 020 7902 5301 E-mail: training@thefpa.co.uk Web: http://www.thefpa.co.

Bastille Court 2 Paris Garden London SE1 8ND Telephone: 020 7902 5314 Fax: 020 7902 5301 E-mail: training@thefpa.co.uk Web: http://www.thefpa.co. Bastille Court 2 Paris Garden London SE1 8ND Telephone: 020 7902 5314 Fax: 020 7902 5301 E-mail: training@thefpa.co.uk Web: http://www.thefpa.co.uk Fire Risk Assessment Course Health & Safety at Work Inspectorate,

More information

Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company

Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing

More information

Carrying Out and Recording a Fire Risk Assessment

Carrying Out and Recording a Fire Risk Assessment Carrying Out and Recording a Fire Risk Assessment This document provides information which appropriate persons (or those carrying out a fire risk assessment on their behalf) may find helpful when completing

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

Fire Safety Requirements for Child Care Centre

Fire Safety Requirements for Child Care Centre Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

PRACTICAL FIRE SAFETY GUIDANCE FOR FACTORIES AND STORAGE PREMISES

PRACTICAL FIRE SAFETY GUIDANCE FOR FACTORIES AND STORAGE PREMISES PRACTICAL FIRE SAFETY GUIDANCE FOR FACTORIES AND STORAGE PREMISES Revised February 2008 The guidance in this document has been jointly produced by the Scottish Government s Police and Community Safety

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

BS5839 Part 1:2002 Overview

BS5839 Part 1:2002 Overview BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire

More information

THE FACTORIES A D OTHER PLACES OF WORK ACT (Cap 514)

THE FACTORIES A D OTHER PLACES OF WORK ACT (Cap 514) THE FACTORIES A D OTHER PLACES OF WORK ACT (Cap 514) I EXERCISE of the powers conferred by section 41 2(k) of the Factories and other places of Work Act, the Minister for Labour and Human Resource Development

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

Overview of Hotel Fire Safety Requirements

Overview of Hotel Fire Safety Requirements Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

THE ARTS EDUCATIONAL SCHOOLS, LONDON DAY SCHOOL AND SIXTH FORM FIRE RISK MANAGEMENT POLICY

THE ARTS EDUCATIONAL SCHOOLS, LONDON DAY SCHOOL AND SIXTH FORM FIRE RISK MANAGEMENT POLICY THE ARTS EDUCATIONAL SCHOOLS, LONDON DAY SCHOOL AND SIXTH FORM FIRE RISK MANAGEMENT POLICY STATEMENT OF INTENT The Arts Educational Schools, London, will ensure, so far as is reasonably practicable, that

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

SBR FIRE RISK ASSESSMENT

SBR FIRE RISK ASSESSMENT SBR FIRE RISK ASSESSMENT Report of audit and inspection Premises Details Occupier Premises Address Premises Description Times premises are in use Use and maximum no. people present The British School of

More information

FIRE SAFETY SIGNAGE - UCL FIRE SAFETY STANDARD

FIRE SAFETY SIGNAGE - UCL FIRE SAFETY STANDARD Fire Safety Technical Guide FIRE SAFETY SIGNAGE - UCL FIRE SAFETY STANDARD Fire Safety Signage - what you need to know: Prohibited or Check First! Local purchase of fire safety signs - departmental staff,

More information

- 5 - Table1. Maximum Compartment Volumes

- 5 - Table1. Maximum Compartment Volumes - 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839 AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you

More information

Greater Manchester Fire and Rescue Service

Greater Manchester Fire and Rescue Service Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

Restaurant & café guide

Restaurant & café guide 'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers

More information

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency

More information

Contents. 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4

Contents. 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4 Contents 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4 2. Scope and Application 2.1 Scope of the Guide 5 2.2 Premises to which the

More information