White Paper. Scope of Practice. Plumber, Underground Utility and Fire Sprinkler Contractors VP NFSA

Size: px
Start display at page:

Download "White Paper. Scope of Practice. Plumber, Underground Utility and Fire Sprinkler Contractors VP NFSA"

Transcription

1 White Paper Scope of Practice Plumber, Underground Utility and Fire Sprinkler Contractors by Buddy Dewar, VP NFSA February 7,

2 Executive Summary The Florida Legislature has clearly established contractor licensure for multiple trades including plumbing, underground utility and fire sprinkler contracting. In its empowerment, the Florida legislature clearly established a scope of practice for each trade. The Legislature has enumerated with specificity contractor tasks that, because of life and property safety concerns, require a greater level of training, and experience to perform. This paper is written to educate the unqualified contractor, the oversight Boards, the Courts, and others why the life and property saving fire protection systems require specific licensure criteria and why the point of service and more stringent fire line installation, listing, testing and bend restraints are needed. The location and type of fire sprinkler is critical for successful operation. Sprinkler systems are designed based on the occupancy being protected. Obstructions preventing proper sprinkler activation, the gluing of plastic pie, the type and strength of metal pipe, the hydraulic calculation to ensure the system works are some of the many factors unique to fire protection systems all warranting specific education and experience to install and maintain. Water flow demand for fire protection systems, thousands of gallons per minute, causes demand on water distribution systems but becomes significant when these large volumes of flow are through smaller diameter pipe. Large volume flows through smaller pipes pushes the limit on pipe pressure capabilities and also places thousands of pounds of thrust on 90 degree and 45 degree bends. This significantly increased thrust has led to stronger piping restraints to prevent system catastrophic failure developed in the national model fire protection system design codes and standards adopted in all 50 states. Thus, the design and installation criterion for fire protection systems is different, more stringent requirements, than the water distribution system design codes and standards. Florida has clearly identified the point of service; has specifically created a classification of fire protection contractors in an attempt to ensure those installing the underground fire line and even residential sprinkler systems are properly trained and insured to protect the public. Plumbers and underground utility contractors are specifically prohibited by law from installing underground fire lines and backflows connected to water based fire protection systems unless they also certified as a fire protection contractor; these provisions have been in place for decades. 2

3 Table of Contents i Executive Summary Page 2 ii Table of Contents Page 3 1. Intent Overview. Page 4 2. Plumbing Contractors. Page 4 3. Fire Protection Contractors. Page 5 4. Underground Utility Contractors. Page 7 5. Point of Service. Page 8 6. Fire Protection Contractor V. Page Combination Plumbing/Fire Protection Systems. Page Inspection, Testing, and Maintenance of Page 12 Fire Protection Systems and Backflow Preventors. 9. Fire Line Backflow Preventor Installation Page Q&A Page 15 3

4 Scope of Practice Plumber, Underground Utility and Fire Sprinkler Contractors 1. Intent Overview. This paper is intended to provide clarity to the scope of practice of plumbers, underground utility and fire sprinkler contractors. The separate and distinct professions are regulated by two different Florida Statutes; Chapter 489 for Plumbers and Underground Utility Contractors and Chapter 633 for Fire Protection Contractors. The Fire Protection Contractor is licensed by the State Fire Marshal for many reasons with the most prominent being consistency in enforcement which is done by fire inspectors also trained and licensed by the State Fire Marshal. The two professions have different insurance and workers compensation costs as a result of different liability exposure. Litigation following a fire death or injury and/or large property loss in sprinkler protected buildings is 100 times more significant than water leak damage from plumbing installation defects. In fact many insurance companies providing plumbers with General Liability insurance coverage are advising plumbers they are not covered for fire sprinkler work unless they pay a significantly higher premium rate. Failure to carry the appropriate level of insurance is not in the best interest of the public. And then the fire sprinkler contractor, in their efforts to minimize insurance costs and liability exposure, train their employees to a high level improving quality control. For example, language in Chapter 633 requires inspectors of fire sprinkler systems to be certified by the National Institute for Certification in Engineering Technologies, a very demanding training program, before they can inspect fire sprinkler systems. This paper also addresses Point of Service, inspection of fire protection systems including backflow preventors, and combination plumbing/fire sprinkler systems. 2. Plumbing Contractors: Plumbing contractors are defined in s (2)(m), F.S., which reads: (m) Plumbing contractor means a contractor whose contracting business consists of the execution of contracts requiring the experience, financial means, knowledge, and skill to install, maintain, repair, alter, extend, or, if not prohibited by law, design plumbing. A plumbing contractor may install, maintain, repair, alter, extend, or, if not prohibited by law, design the following without obtaining an additional local regulatory license, certificate, or registration: sanitary drainage or storm drainage facilities; venting systems; public or private water supply systems; septic tanks; drainage and supply wells; swimming pool piping; irrigation systems; or solar heating water systems and all appurtenances, apparatus, or equipment used in connection therewith, including boilers and pressure process piping and including the installation of water, natural gas, liquefied petroleum gas and related venting, and storm and sanitary sewer lines; and water and sewer plants and substations. The scope of work of the plumbing contractor also includes the design, if not prohibited by law, and installation, maintenance, repair, alteration, or extension of airpiping, vacuum line piping, oxygen line piping, nitrous oxide piping, and all related medical gas systems; fire line standpipes and fire sprinklers if authorized by law; ink and chemical lines; fuel oil and gasoline piping and tank and pump installation, except bulk storage plants; and pneumatic control piping systems, all in a manner that complies with all plans, specifications, codes, laws, and regulations applicable. The scope of work of the 4

5 plumbing contractor applies to private property and public property, including any excavation work incidental thereto, and includes the work of the specialty plumbing contractor. Such contractor shall subcontract, with a qualified contractor in the field concerned, all other work incidental to the work but which is specified as being the work of a trade other than that of a plumbing contractor. This definition does not limit the scope of work of any specialty contractor certified pursuant to s (6), and does not require certification or registration under this part of any authorized employee of a public natural gas utility or of a private natural gas utility regulated by the Public Service Commission when disconnecting and reconnecting water lines in the servicing or replacement of an existing water heater. (Emphasis Added) The fire line standpipes and fire sprinklers if authorized by law language means there are other laws in the Florida Statutes that empower plumbers to do this work. Said another way, the scope of work with respect to standpipes and sprinklers can only be done if and to the extent authorized by law. The authorizing law is in Chapter 633, the Florida statute that regulates fire protection system contractors Exemptions; farm outbuildings; standpipe systems installed by plumbing contractors. (1) This act does not apply to owners of property who are building or improving farm outbuildings. (2) A licensed plumbing contractor is not required to be certified under this act to install standpipe systems and the following items connected thereto: overhead and underground water mains, fire hydrants and hydrant mains, hose connections, tanks and pumps; including sprinkler heads in trash chutes and in trash rooms, having no connection to an automatic sprinkler. (Emphasis added). Thus, Florida Statute, s (3)(m), says a plumber can install sprinklers only if authorized by law and the authorizing law, s , says a plumber may install sprinklers in trash rooms and/or trash chutes that are not connected to a fire sprinkler system. This is the extent of sprinkler installation authority allowed by law for plumbers absent Fire Protection Contractor licensure required in Chapter 633, F.S. More than 6 fire sprinklers in one building is considered a fire sprinkler system. 3. Fire Protection Contractor. In Chapter 633, the Florida legislature made it clear that an organization or individual must obtain a Fire Protection System Contractor certificate before it can engage in the activities regulated under the Act. This conclusion is evident from section (1), which expressly prohibits and penalizes certain unlawful conduct: (1). It is unlawful for any organization or individual to engage in the business of layout, fabrication, installation, inspection, alteration, repair, or service of a fire protection system, other than a preengineered system, act in the capacity of a fire protection contractor, or advertise itself as being a fire protection contractor without having been duly certified and holding a valid and existing certificate, except as hereinafter provided. 5

6 This same conclusion is supported by section , which states in clear terms who can install fire protection systems in Florida: (1) The requirements for installation of fire protection systems are as follows: (a) Contractors of fire protection systems shall be certified under s Thus, absent State Fire Marshal Fire Protection Contractor licensure, a plumbing or underground utility contractor cannot touch or hold themselves out to be authorized to touch a fire protection system. A fire protection system is defined in s F.S. as follows: (10) A fire protection system is a system individually designed to protect the interior or exterior of a specific building, structure, or other special hazard from fire. Such systems include, but are not limited to, water sprinkler systems, water spray systems, foam-water sprinkler systems, foam-water spray systems, CO2 systems, foam extinguishing systems, dry chemical systems, and Halon and other chemical systems used for fire protection use. Such systems also include any overhead and underground fire mains, fire hydrants and hydrant mains, standpipes and hoses connected to sprinkler systems, sprinkler tank heaters, air lines, thermal systems used in connection with fire sprinkler systems, and tanks and pumps connected to fire sprinkler systems. (emphasis added) And s , F.S., defines the Classifications of Fire Protection Contractor as: (5) Definitions. (a) Contractor I means a contractor whose business includes the execution of contracts requiring the ability to lay out, fabricate, install, inspect, alter, repair, and service all types of fire protection systems, excluding preengineered systems. (b) Contractor II means a contractor whose business is limited to the execution of contracts requiring the ability to lay out, fabricate, install, inspect, alter, repair, and service water sprinkler systems, water spray systems, foam-water sprinkler systems, foam-water spray systems, standpipes, combination standpipes and sprinkler risers, all piping that is an integral part of the system beginning at the point of service as defined in this section, sprinkler tank heaters, air lines, thermal systems used in connection with sprinklers, and tanks and pumps connected thereto, excluding preengineered systems. (c) Contractor III means a contractor whose business is limited to the execution of contracts requiring the ability to fabricate, install, inspect, alter, repair, and service CO2 systems, foam extinguishing systems, dry chemical systems, and Halon and other chemical systems, excluding preengineered systems. (d) Contractor IV means a contractor whose business is limited to the execution of contracts requiring the ability to lay out, fabricate, install, inspect, alter, repair, and service automatic fire sprinkler systems for detached one-family dwellings, detached two-family dwellings, and mobile homes, excluding preengineered systems and excluding single-family homes in cluster units, such as apartments, condominiums, and assisted living facilities or any building that is connected to other dwellings. 6

7 (e) Contractor V means a contractor whose business is limited to the execution of contracts requiring the ability to fabricate, install, inspect, alter, repair, and service the underground piping for a fire protection system using water as the extinguishing agent beginning at the point of service as defined in this act and ending no more than 1 foot above the finished floor. Simply stated, only one certified by the State Fire Marshal as Contractor I, Contractor II, Contractor IV or Contractor V as defined in s , F.S., may install fire mains or fire lines connected to water based fire protection systems. There are restrictions for each classification. For example, the Contractor IV is restricted to NFPA 13D systems, one and two family homes not commercial systems. The Contractor I may also install piping for CO 2 and other dry chemical fire protection systems. It is significant to note that the Contractor V classification was specifically created to accommodate the underground utility contracting industry. The intent of the Contractor V classification was to ensure that those installing underground fire lines were properly trained on the more stringent standards and products making fire lines or mains distinctly different than domestic water mains. The number of licensed contractors qualified to install commercial underground fire lines as of this writing are: Contractor I 152 Contractor II 355 Contractor V 342 Significant is the large number of underground utility contractors, 342, who have become licensed as Contractor V so they can install underground fire mains. And again, these certification requirements have been in place for decades. 4. Underground Utility Contractors. Florida Statute (3)(n) addresses Underground Utility Contractors and this law reads: (n) Underground utility and excavation contractor means a contractor whose services are limited to the construction, installation, and repair, on public or private property, whether accomplished through open excavations or through other means, including, but not limited to, directional drilling, auger boring, jacking and boring, trenchless technologies, wet and dry taps, grouting, and slip lining, of main sanitary sewer collection systems, main water distribution systems, storm sewer collection systems, and the continuation of utility lines from the main systems to a point of termination up to and including the meter location for the individual occupancy, sewer collection systems at property line on residential or singleoccupancy commercial properties, or on multioccupancy properties at manhole or wye lateral extended to an invert elevation as engineered to accommodate future building sewers, water distribution systems, or storm sewer collection systems at storm sewer structures. However, an underground utility and excavation contractor may install empty underground conduits in rights-of-way, easements, platted rights-of-way in new site development, and sleeves for parking lot crossings no smaller than 2 inches in diameter if each conduit system installed is designed by a licensed professional engineer or an authorized employee of a municipality, county, or public utility and the installation of such conduit does not include installation of any conductor wiring or connection to an energized 7

8 electrical system. An underground utility and excavation contractor may not install piping that is an integral part of a fire protection system as defined in s beginning at the point where the piping is used exclusively for such system. (emphasis added) Thus an Underground Utility contractor cannot install piping that is an integral part of a fire protection system. But discussed herein, an Underground Utility contractor and a Plumber may install underground piping that is an integral part of a water based fire protection system if and only if they are also licensed by the State Fire Marshal as a Fire Protection Contractor V. 5. Point of Service. The question then comes where does the piping become an integral of a fire protection system? Florida law s (20), F.S., which reads: (20) Point-of-service means the point at which the underground piping for a fire protection system as defined in this section using water as the extinguishing agent becomes used exclusively for the fire protection system. (Emphasis added) The Point of Service definition is considered specific statutory direction and in the case of any possible interpretation of some general statement in Florida statutes that may be considered in conflict, the specific overrules the general. This Point of Service definition says a couple of things. First, the definition of a Fire Protection System cited above includes water based but also includes dry chemical and other types of fire protection systems. This definition is intended only for those fire protection systems using water as an extinguishing agent. Secondly, the point of service is where the piping is used exclusively for the fire protection system. The Point of Service is typically at the roadway valve installed by the water utility which is a straight piece of pipe tapped off the water main with a valve used to shut off service. The roadway tap is typically a smaller diameter pipe than the supplying fire service main and the roadway is a concealed shut off valve using ending at the public property line. Some parties argue that the point of service begins at the system side of the backflow preventor. The Legislature uncontrovertibly enumerated with specificity that only State Fire Marshal licensed contractors can install and test fire line backflow preventors. There is a significant safety issue ignored by the proponents advocating that the point of service starts at the system side of the backflow. The substantive concern is the piping leading to the backflow would not meet NFPA or fire line standards. Those who install domestic underground follow American Water Works Association (AWWA) design standards while those who install fire lines follow NFPA standards. NFPA fire line design standards require different products and installation standards and practices and the State Fire Marshal contractor licensure standards are in place to ensure that those installing fire lines follow the state adopted national fire line design standards and practices. So advocates promoting the false point of service being at arrow A in the following example are suggesting that the underground utility contractor install piping following AWWA standards up to point B and that that beyond Point B piping compliant with NFPA be installed by the fire 8

9 protection contractor. The substantive problem is water flowing through the backflow reaching Point B at 800 gpm at 100 psi is placing approximately 5,288 pounds of thrust at Point B. However, with water flowing at this capacity at Point B there is actually greater demands created at Point C (friction loss through backflow). But the backflow point of service advocates suggest this piping be installed to a lower standard by people not properly trained up to Point B on all fire line installation and practices. Again, this pressure problem on both the supply and Double Check Backflow Preventor C A B Flow Direction system side of a backflow preventor has been discussed decades ago prompting the Florida Legislature to clearly indicate the point of service begins at the point where the piping is used for the fire protection system begins. Some advocates argue that only underground utility contractors can install piping that contains potable water or the supply side of a backflow preventor. They even go so far as to suggest the water sitting in the pipe leading up to the backflow is not specifically designated for fire protection because it can backflow to the water main. First and foremost, water in the system side of the backflow can also flow back into the water main. That is the reason for annual backflow testing that has in fact found backflows inoperable. Secondly, the piping from the point of service through the backflow preventor to the fire protection system is engineered or designed for a specific flow of water. The design of fire lines does not include water backflow or allocations of portions of the water to backflow to the water main this piping is specifically designed to feed the fire protection system, there is no source of water from the fire sprinkler system that can provide water pressure or flow to the water main for use downstream. And 9

10 thirdly, should a tap be added to a fire line between the point of service and the backflow preventor or after the backflow preventor before the fire protection system, the entire system design back to the point of service must be re engineered to ensure adequate water volume and pressure is available for the fire protection system. But more substantive, plumbers and underground utility contractors argue only they can touch potable water piping, that only they are trained to protect the drinking water. The reality is the plumber and underground utility contractor does not have the training or empowerment to determine safe water drinking mitigation actions this is done by the water utility. For example, if a 50 foot piece of 4 inch underground piping is installed to feed a domestic or fire protection the water utility directs the installing what action to take to protect the water. Some water utilities will want added chlorine or other chemicals added to the water supply in the new piping others may simply want verification that the water flow test was conducted thereby flushing out contaminates. Typically, water utilities only require action when the piping is of substantial length. Thus, notwithstanding plumber, underground utility or fire protection contractor licensure, it is the water utility that establishes safe drinking water criteria, not the contractor. 6. Fire Protection Contractor V. An Underground Utility or Plumbing contractor licensed under Chapter 489 may install underground fire lines from the Point of Service to one foot above the finished floor if and only if they are also licensed by the State Fire Marshal as a Contractor V. This Contractor V classification was established in the mid 1980s allowing underground and plumbing contractors to do this work, work that had been done for decades and is still being done by the fire sprinkler contractor. From s , F.S., (e) Contractor V means a contractor whose business is limited to the execution of contracts requiring the ability to fabricate, install, inspect, alter, repair, and service the underground piping for a fire protection system using water as the extinguishing agent beginning at the point of service as defined in this act and ending no more than 1 foot above the finished floor. Adding even more clarity is s , F.S which states: (3) For contracts written after June 30, 2005, the [Fire Protection System] contractor who installs the underground piping from the point of service is responsible for completing the installation to the aboveground connection flange, which by definition in this chapter is no more than 1 foot above the finished floor, before completing the Contractor s Material and Test Certificate for Underground Piping document. Aboveground contractors may not complete the Contractor s Material and Test Certificate for Underground Piping document for underground piping or portions thereof which have been installed by others. (Emphasis added) Flushing has been significantly problematic. AWWA standards require system flushing at 3 feet per second. Part of the Contractor V training and testing educates the Contractor V that flushing requirement for fire lines is 10 ft/sec for NFPA 13 designed systems. In fact, if a fire pump is to be installed, the flushing rate is even higher, can be as high as 15 ft/sec depending on the type of fire pump used. This higher flush rate is beyond the scope of training provided 10

11 those installing AWWA underground compliant water supplies but is precisely one of the topics presented to fire line underground Contractor V during certification training. This higher flush rate is intended to remove debris such as pee rocks that can plug the fire sprinkler system or disable the fire pump but also places more stress on the system; the reason for higher standards for fire lines. Thus part of the Contractor V training includes the required Underground Test Certificate that is required to be submitted to the code authority for final system approval. What the legislature is saying by requiring the Underground Materials and Test Certificate is if an underground utility contractors who is dual licensed as a Contractor V chooses to install a fire line underground they must do it correctly, not leave parts to be done by others or leave parts they installed to become a liability for others. This language also is intended to stop the shift of liability from an unqualified underground installation to the aboveground installing fire protection system contractor. In respect to an individual who seeks to become certified as a Contractor V, section (3)(f) establishes the following eligibility criteria: (f). As a prerequisite to taking the examination for certification as a Contractor V, the applicant must be at least 18 years old, be of good moral character, and have been licensed as a certified underground utility and excavation contractor or certified plumbing contractor pursuant to chapter 489, have verification by an individual who is licensed as a certified utility contractor or certified plumbing contractor pursuant to chapter 489 that the applicant has 4 years proven experience in the employ of a certified underground utility and excavation contractor or certified plumbing contractor, or have a combination of education and experience equivalent to 4 years proven experience in the employ of a certified underground utility and excavation contractor or certified plumbing contractor. Thus, the Florida legislature recognizes s. 489 licensure requirements imposed on those who wish to do plumbing or Underground Utility work. But the legislature also clearly acknowledges the need for a higher level of care and the Contractor V license is needed to work on fire protection system underground. These requirements have been in place for decades. 7. Combination Plumbing/Fire Protection Systems. NFPA 13D, the national fire sprinkler design standard, provides design criteria allowing a combined plumbing/fire sprinkler system to be installed in one and two family homes. Piping installed in a home can provide water flow to both plumbing fixtures and fire sprinklers. Some product manufacturers promoting combination system products also provide design assistance. Working together, the trade associations supporting plumbers and fire sprinkler contractors lobbied to allow plumbers licensed pursuant to Chapter 489 to meet much of the Contractor IV licensing criteria. Contractor I and II may install NFPA 13D systems as their licensure requirements impose training and experience far above that expected for the Contractor IV. The fire sprinkler portion of a combination system provides a challenge far and beyond the scope of training typical for plumbers the basis for Contractor IV licensing. The gluing practice 11

12 for plastic pipe is different on fire sprinkler plastic pipe than plumbing pipe, obstructions to fire sprinkler flow must be noticed and corrected, proper flow pressure and volume must be calculated, freeze protection for sprinkler piping provides a unique training challenge. The Contractor IV classification is intended to provide the training to ensure those installing fire sprinkler systems in one and two family homes are properly trained and the training objects and curriculum is designed on the assumption the applicant is a qualified plumber licensed in accordance with Chapter 489, F.S. Some counties offer county licensure for some trades and a county issued plumbers license not consistent with Chapter 489 does not qualifiy one to take the Contractor IV training and examination. A stand alone fire protection system can also be installed by the Contractor I, II, and IV in oneand two family homes. To minimize the need for backflow prevention some stand alone systems have a drop installed which is connected to a commonly used toilet. The fire protection system is installed by the Fire Protection Contractor who installs and caps a drop at a remote point. The point at which the drop is capped is the interface between the sprinkler and the plumber trades. The plumber extends piping from the drop cap location to the toilet. 8. Inspection, Testing, and Maintenance of Fire Protection Systems and Backflow Preventors. The Legislature has clearly adopted two fire protection system maintenance standards, NFPA 24 for the underground piping and NFPA 25 for the above ground water based fire protection systems Inspection of fire control systems, fire hydrants, and fire protection systems.-- (2) Fire hydrants and fire protection systems installed in public and private properties, except one-family or two-family dwellings, in this state shall be inspected following procedures established in the nationally recognized inspection, testing, and maintenance standards NFPA-24 and NFPA-25 as set forth in the edition adopted by the State Fire Marshal. Quarterly, annual, 3-year, and 5-year inspections consistent with the contractual provisions with the owner shall be conducted by the certificateholder or permittees employed by the certificateholder pursuant to s Those certificate holders and their permittees must pass a significant training program and testing of the National Institute of Certification in Engineering Technologies (NICET) before they are allowed to test and maintain a fire protection system. The permittees testing backflow preventors for backflow are dual licensed by DEP as backflow testers just like plumbers and other trades who are dual licensed. The permittee requirement is in (8) below: Certificate application and issuance; permit issuance; examination and investigation of applicant.-- (8) An individual employed by a Contractor I or Contractor II certificateholder, as established in this section, who will be inspecting water-based fire protection systems as required under s , must be issued a permit by the State Fire Marshal to conduct such work. The permit is valid solely for use by the holder thereof in his or her employment by the certificateholder named in the permit. A permittee must have a valid and subsisting 12

13 permit upon his or her person at all times while engaging in inspecting fire protection systems, and a permitholder must be able to produce such a permit upon demand. In addition, a permittee shall, at all times while performing inspections, carry an identification card containing his or her photograph and other identifying information as prescribed by the State Fire Marshal, and the permittee must produce the identification card and information upon demand. The permit and the identification may be one and the same. A permittee is limited as to the specific type of work performed, depending upon the class of certificate held by the certificateholder under whom the permittee is working. The permit class shall be known as a Water-Based Fire Protection Inspector whose permit allows the holder to inspect water sprinkler systems, water spray systems, foam-water sprinkler systems, foam-water spray systems, standpipes, combination standpipes and sprinkler systems, all piping that is an integral part of the system beginning at the point where the piping is used exclusively for fire protection, sprinkler tank heaters, air lines, thermal systems used in connection with sprinklers, and tanks and pumps connected thereto, excluding preengineered systems. And to eliminate any conflicting thoughts, the legislature clearly intended post indicating valves, backflow preventors and other exposed appurtenances of the underground water supply be inspected, tested, and maintained by the Contractor I or II permittee as shown in (9) below. Plumbing contractors are expressly prohibited from testing fire line backflow preventors even if they hold DEP backflow tester certification. (9) It is the intent of the Legislature that the inspections and testing of automatic fire sprinkler systems for detached one-family dwellings, detached two-family dwellings, and mobile homes be accomplished by the owner, who is responsible for requesting service from a contractor when necessary. It is further intended that the NFPA-25 inspection of exposed underground piping and any attached appurtenances supplying a fire protection system be conducted by a Contractor I or Contractor II. (Emphasis added) One key element of testing fire protection systems is to ensure they will work. This therefore requires what is known as a forward flow test to ensure that a backflow malfunction is not restricting the needed fire flow for the fire protection systems. And while this is not a common occurrence; it does occur with such frequency that the national standard requires a forward flow test annually. Also part of the annual test is to ensure the isolation valves on the backflow preventor are operational and lubricated. Flowing large volumes of water through the backflow activates the check flap. Thus, the NFPA standard also requires checking for backflow. Again, Florida requires the testing permittee to be certified by DEP to test backflow devices. One solid reason others were restricted from testing backflow preventors came from a State Senator who stated, Why should I pay a plumber to test the same backflow I am paying the fire sprinkler contractor to test? The fire sprinkler industry has liability concerns with exercising a backflow device and not being allowed to test for backflow as required by NFPA 25. Should a rock or piece of debris block the backflow from closing after the forward flow test failure to test to ensure the backflow prevents backflow is a liability concern of major proportion. Also of concern is the practice of backflow testers not qualified as a fire line contractor. The policy is if the backflow fails and water is allowed to enter the potable water 13

14 supply, the isolation valves are to be shut until the backflow is repaired. The problem is the plumber testing the fire line backflow shuts off the fire protection system in an occupied building, a nursing home for example, while they negotiate repair costs. The fire protection contractor carries repair parts and immediately fixes the valve after notifying the fire department that the fire protection system will be shut down for a limited period of time. This allows the fire department an opportunity to assess the risk in the property and they may respond with fire suppression forces to stand by on site while the repair is being conducted. There have been numerous cases where plumbers have shut down fire protection systems but failed to notify local fire safety authorities (10). Effective July 1, 2008, the State Fire Marshal shall require the National Institute of Certification in Engineering Technologies (NICET), Sub-field of Inspection and Testing of Fire Protection Systems Level II or equivalent training and education as determined by the division as proof that the permitholders are knowledgeable about nationally accepted standards for the inspection of fire protection systems. It is the intent of this act, from July 1, 2005, until July 1, 2008, to accept continuing education of all certificateholders' employees who perform inspection functions which specifically prepares the permitholder to qualify for NICET II certification. And in (10) above is the NICET requirement, a bar raised high to gain assurance fire protection systems are properly maintained and serviced. Some argue that only the plumber and the underground utility contractor can touch piping using potable water. Surely they are not suggesting backflows do not backflow. The truth is the plumbers and underground utility contractors are not certified as a environmental engineers. The truth is whoever installs the underground water or fire main must follow local environmental and water quality guidelines which typically includes taking a water sample to the appropriate tester who, according to local policy, advises if and if so now much chlorine or other additive must be placed in the pipe. And while the takeover advocates suggest so, they really are not environmental engineers and follow the same direction and procedures for water quality control as the fire protection contractor. 9. Fire Line Backflow Preventor Installation. Who installs backflow preventors? The Legislature is very clear. A fire protection system from the point of service to the most remote fire sprinkler can only be installed by a State Fire Marshal certified fire protection contractor. The Legislature does allow new backflow preventors to be installed by a Contractor V on the assumption the design engineer will have specified the size and type of backflow to be used, which is coordinated with the fire protection system design calculations Requirements for installation, inspection, and maintenance of fire protection systems.-- 14

15 (4) The Contractor V may install the cross-connection backflow prevention device as defined in this chapter on new installations. The retrofitting of a backflow device on an existing fire protection system will cause a reduction in available water pressure and probable system malfunction. The development of aboveground fire protection system hydraulic calculations is a task of the Contractor I and II, as defined in this chapter. Accordingly, a Contractor V is expressly prohibited from retrofitting cross-connection backflow prevention devices on an existing fire protection system, and only a Contractor I or Contractor II who is tasked to recalculate the system and take corrective actions to ensure that the system will function with the available water supply may retroactively install these backflow devices on existing fire protection systems. While a Contractor V can install a backflow preventor on a fire protection system, they are expressly prohibited from retrofitting a backflow on an existing system. The issue here is retrofitting a backflow on an existing system, in most cases, will lower the available water flow and pressure to the extent that the fire sprinkler system will no longer operate as designed. There are safety margins built into the fire sprinkler design standards but most systems are designed to operate on the existing water flow. For example, a fire sprinkler system is designed to flow 450 gpm at 40 psi residual (water flowing) pressure. The water supply provided is capable of 800 gpm at 45 psi. The system as designed is connected. But then a Reduced Pressure Zone (RPZ) backflow preventor is installed and this device creates a 14 psi friction loss. So now the supply is 800 gpm but only at 31 psi at the system side of the backflow when the fire protection system was designed to work at 45 psi or higher we now have created system failure. Allowing backflow preventors to be retrofitted on existing fire protection systems is incredibly problematic; thus the reason for the specificity in Florida law requiring a Contractor I, or Contractor II to recalculated and possibly redesign the existing system. There are many options afforded the design professional, fire pumps or upsizing the piping and sprinkler orifices in the remote design area are two most common options. But installing a backflow on an existing fire protection system without recalculating the impact of the backflow preventor friction loss is not an option and, quite frankly, a huge liability exposure for the retrofitting contractor. 10. Q&A: a. Does a Fire protection Contractor have to also be licensed as a plumbing contractor to install and connect to a water distribution system? No, provisions in Florida law clearly allow an exemption: Exemptions. This part does not apply to: (22) A person licensed pursuant to s (1)(d) or (3)(b) performing work authorized by such license. Fire protection systems are complex and include electrical and plumbing features. For example, a double interlock preaction system has two separate detection devices that are integral parts of the fire sprinkler systems activation. The fire protection contractor has ultimate responsibility and liability for the proper installation of the system and is properly trained on the electrical and water distribution system connections necessary for proper system functions 15

16 and future system testing. This exemption does not allow the fire protection contractor to do plumbing work outside the scope of a fire protection system as defined by law. b. Can a domestic tap on a fire line be installed to change the point of service? No. A fire sprinkler system is designed from the most remote fire sprinkler back to the Point of service. Thus the sizing of the pipe and the tap on the water supply main is designed to meet the fire sprinkler demand. Should water be diverted from the fire sprinkler demanded water flow then the system may not properly function. Water flow demands for fire sprinkler systems place significantly more stress on underground piping. For example, a 6 inch pipe flowing at 100 psi and 800 gpm, a flow rate not uncommon in sprinkler testing particularly if a fire pump is connected, the thrust or force on a 90 degree bend would be over 5,000lbs. The fire protection system guidelines require piping listed by UL or other nationally recognized testing agencies that meet higher pressure ratings, connections and restraints on bends and curves in this piping to withstand much greater thrust and pressures than that expected of domestic water lines of the same diameter. In fact, those inspecting fire line underground inspect to ensure the piping used is properly listed and properly restrained in accordance with NFPA guidelines, not AWWA guidelines. Thus, if there were flow demands as used in this example and pipe bends prior to the added domestic tap there would be no change in piping leading up to the domestic tap thus no change in the point of service or that point where higher standards are needed. Any domestic tap must be approved by a qualified engineer who will assume responsibility that the water flow diverted to the domestic water flow demand will not diminish the effective operation for the fire protection systems. c. What if the engineer of record designates the point of service being five feet from the building? There is a problem. It is unlikely that the public property line is just five feet from the building. This means the actual point of service as intended in statute has been misstated. If identifying the point of service different that that intended by Florida law, the engineer of record now assumes liability and professional licensure exposure. The provisions of Florida law prohibits the above ground fire protection contractor from connecting to the underground absent an underground materials and test certificate which is required to end one foot above the finished floor. d. I have a Cross Connection Tester Certificate from TREEO, can I inspect a fire line backflow preventor? No, unless you are under the employ of a licensed fire sprinkler contractor. Backflow testers under the employ of a fire protection contractor must have a DEP approved backflow testing certificate. A plumber who has DEP approved backflow certification cannot test a backflow that is part of a fire protection system. e. Can a governmental entity require backflows to be installed on fire sprinkler systems only by plumbers? No. Florida law clearly designates the fire sprinkler contractor as the contractor in charge of cross connection protection on fire protection systems. The substantive problem is system 16

17 design which is based upon available water flow at the water main. If the fire sprinkler system is designed expecting a 5 psi friction loss through a double check valve assembly, the contractor installs the system as designed and then finds a RPZ 15 psi friction loss backflow, the entire system may have to be replaced. f. The code official in my community mandates that only a plumber can install a backflow on a fire line and only a plumber can retrofit a backflow on existing fire lines. Is he correct? No. Only contractors licensed by the State Fire Marshal can install a backflow device connected to a water based fire protection system. g. The General Contractor is requiring me to sign off on the underground which was done by an contractor unknown and probably not licensed by the State Fire Marshal? Will I get into trouble? Yes, and you are being exposed to greater liability. The provisions of Florida law requires the person installing the underground to finish the underground up to one foot above the finished floor and prepare an Underground Materials & Test Certificate which is provided the code authority and the above ground contractor. Florida law specifically prohibits and above ground contractor from signing off on underground work done by others so in addition to assuming greater liability should the system fail because of faulty underground, the above ground contractor s license is in peril as the law specifically prohibits signing off on work done by others. 17

87-21. Definitions; contractors licensed by Board; examination; posting license, etc.

87-21. Definitions; contractors licensed by Board; examination; posting license, etc. 87-21. Definitions; contractors licensed by Board; examination; posting license, etc. (a) Definitions. For the purpose of this Article: (1) The word "plumbing" is hereby defined to be the system of pipes,

More information

CHAPTER 69A-46 FIRE PROTECTION SYSTEM CONTRACTORS AND SYSTEMS

CHAPTER 69A-46 FIRE PROTECTION SYSTEM CONTRACTORS AND SYSTEMS CHAPTER 69A-46 FIRE PROTECTION SYSTEM CONTRACTORS AND SYSTEMS 69A-46.001 69A-46.010 69A-46.015 69A-46.016 69A-46.0165 69A-46.017 69A-46.025 69A-46.030 69A-46.035 69A-46.040 69A-46.041 Scope Submission

More information

Scope of Work Class I Contractor s Licenses. Putnam County Ordinance 2004-13. Section 17. Types of Authorized Contractor Licenses.

Scope of Work Class I Contractor s Licenses. Putnam County Ordinance 2004-13. Section 17. Types of Authorized Contractor Licenses. Scope of Work Class I Contractor s Licenses Putnam County Ordinance 2004-13 Section 17. Types of Authorized Contractor Licenses. A. Class I Contractors: The Class I Contractors are listed in this subsection

More information

WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS

WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS a. New Plumbing and Gas Piping Systems. This code in conjunction with the Plumbing and Fuel Gas Codes of the State of New York shall apply to plumbing

More information

DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIRECTOR'S OFFICE

DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIRECTOR'S OFFICE DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIRECTOR'S OFFICE CERTIFICATION OF FIRMS FOR FIRE ALARM SYSTEMS AND FIRE SUPPRESSION SYSTEMS IN STATE-REGULATED FACILITIES (By authority conferred on the state

More information

CITY OF SURREY BY-LAW NO. 6569

CITY OF SURREY BY-LAW NO. 6569 CITY OF SURREY BY-LAW NO. 6569 As amended by By-laws No. 7026, 02/01/82; 9960, 03/13/90; 10368, 01/22/90; 10797, 01/28/91; 12268, 04/25/94; 12384, 07/02/94; 12828, 05/13/96; 13171, 07/29/97; 13220, 09/22/97;

More information

AMERICAN SOCIETY OF CERTIFIED ENGINEERING TECHNICIANS

AMERICAN SOCIETY OF CERTIFIED ENGINEERING TECHNICIANS GREEN TAG/RED TAG AMERICAN SOCIETY OF CERTIFIED ENGINEERING TECHNICIANS ORLANDO CHAPTER ORLANDO, FL February 7, 2013 2012 FLORIDA STATUTES 633.082 Inspection of fire control systems, fire hydrants, and

More information

Oregon Administrative Rules, Chapter 918-2016 Compilation- Building Codes Division DIVISION 695

Oregon Administrative Rules, Chapter 918-2016 Compilation- Building Codes Division DIVISION 695 DIVISION 695 Hist.: DC 2-1983, f. & ef. 1-3-83; Renumbered from 814-020- PLUMBING LICENSING AND CERTIFICATION 0040; BCD 6-1998, f. 3-2-98, cert. ef. 4-1-98, Renumbered from 918-690-0055; BCD 21-1998, f.

More information

SECTION 105 PERMITS. Gas:

SECTION 105 PERMITS. Gas: SECTION 105 PERMITS SECTION 105 PERMITS 105.1 Required. Any owner or authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure,

More information

WESTFIELD WATER RESOURCES DEPARTMENT

WESTFIELD WATER RESOURCES DEPARTMENT WESTFIELD WATER RESOURCES DEPARTMENT DRINKING WATER DIVISION CROSS CONNECTION CONTROL RULES AND REGULATIONS POLICY NO. CS-009 Effective January 1, 1999 Revised March 14, 2007 I. Purpose: A. To protect

More information

CHAPTER 2011-222. Committee Substitute for Committee Substitute for Committee Substitute for House Bill No. 849

CHAPTER 2011-222. Committee Substitute for Committee Substitute for Committee Substitute for House Bill No. 849 CHAPTER 2011-222 Committee Substitute for Committee Substitute for Committee Substitute for House Bill No. 849 An act relating to building construction and inspection; amending s. 120.541, F.S.; exempting

More information

TORONTO MUNICIPAL CODE CHAPTER 851, WATER SUPPLY. Chapter 851 WATER SUPPLY

TORONTO MUNICIPAL CODE CHAPTER 851, WATER SUPPLY. Chapter 851 WATER SUPPLY Chapter 851 WATER SUPPLY 851-1. Definitions. 851-2. Administration. 851-3. Use and receipt of water. 851-4. Water service connections. 851-5. Metering of water. 851-6. Water meter inspection. 851-7. Maintenance.

More information

Reference Guide for Obtaining Permits and Utility Services For New Construction

Reference Guide for Obtaining Permits and Utility Services For New Construction Reference Guide for Obtaining Permits and Utility Services For New Construction (Revised 04-2012) Table of Contents City Offices Telephone Numbers...1 Application for Utilities...2 Building Permits New

More information

CHAPTER XIX PLUMBING

CHAPTER XIX PLUMBING CHAPTER XIX PLUMBING Section 1. Section 2. Section 3. Section 4. Sec tion 5. Section 6. Section 7. Section 8. Section 9. Sec tion 10. Section 11. Section 12. Section 13. Section 14. Short Title Administration

More information

Chapter 16.130 PLUMBING CODE

Chapter 16.130 PLUMBING CODE DISSCUSSION ITEM 3 ATTACHMENT E Chapter 16.130 PLUMBING CODE 16.130.100 Plumbing Code - Incorporation. There is incorporated by reference, for purpose of adopting regulations, provisions, conditions, terms,

More information

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth

More information

GENERAL ASSEMBLY OF NORTH CAROLINA SESSION

GENERAL ASSEMBLY OF NORTH CAROLINA SESSION GENERAL ASSEMBLY OF NORTH CAROLINA SESSION 00 S SENATE BILL Finance Committee Substitute Adopted //0 House Committee Substitute Favorable //0 Short Title: Plumbing and Heating Contractors. Sponsors: Referred

More information

Proposed New City of Toronto Water Supply By-law CONTENTS. Water Supply By-law. Index of Fee Schedules A, B, C. Orders Fines Tickets (reference list)

Proposed New City of Toronto Water Supply By-law CONTENTS. Water Supply By-law. Index of Fee Schedules A, B, C. Orders Fines Tickets (reference list) Proposed New City of Toronto Water Supply By-law CONTENTS Water Supply By-law Index of Fee Schedules A, B, C Schedule of Fines Summary General plus D, E, F Orders Fines Tickets (reference list) Backflow

More information

ALBUQUERQUE BERNALILLO COUNTY WATER UTILITY AUTHORITY CROSS CONNECTION PREVENTION AND CONTROL ORDINANCE

ALBUQUERQUE BERNALILLO COUNTY WATER UTILITY AUTHORITY CROSS CONNECTION PREVENTION AND CONTROL ORDINANCE ALBUQUERQUE BERNALILLO COUNTY WATER UTILITY AUTHORITY CROSS CONNECTION PREVENTION AND CONTROL ORDINANCE 8-1-2. SHORT TITLE. This Ordinance shall be known and may be cited as The Cross Connection Prevention

More information

LICENSE CATEGORIES. (2) A demolition contractor class II may demolish any building not more than three stories in height.

LICENSE CATEGORIES. (2) A demolition contractor class II may demolish any building not more than three stories in height. CONTRACTOR LICENSING & CERTIFICATION REQUIREMENTS INFORMATION BULLETIN NO. 118 -- June 2, 1997 (Revised May 1, 2012) City of Kansas City, Missouri http://www.kcmo.org/codes/ CONTRACTOR LICENSING & CERTIFICATION

More information

COLORADO FIRE SUPPRESSION RULES 2006 2015 REVISION TABLE OF CONTENTS

COLORADO FIRE SUPPRESSION RULES 2006 2015 REVISION TABLE OF CONTENTS COLORADO FIRE SUPPRESSION RULES 2006 2015 REVISION TABLE OF CONTENTS SECTION 1 Introduction And Background Information 1 SECTION 2 Definitions 2 SECTION 3 Fire Suppression Contractor Registration 4 SECTION

More information

ARLINGTON COUNTY CODE. Chapter 18 PLUMBING AND GAS CODES

ARLINGTON COUNTY CODE. Chapter 18 PLUMBING AND GAS CODES Chapter 18 18-1. Title and Scope. 18-2. Definitions. 18-3. Availability of Codes. 18-4. Administration and Enforcement. 18-5. Registration of Contractors and Certification Requirements. 18-6. Permits and

More information

Hancock County Combined General Health District Plumbing Regulations

Hancock County Combined General Health District Plumbing Regulations Hancock County Combined General Health District Plumbing Regulations Adopted Pursuit To Ohio Revised Code 3709.21 By Hancock County Combined General Health District Board of Health on DATE 1 HANCOCK COUNTY

More information

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations

More information

MISCELLANEOUS STATUTES RELATED TO THE MINNESOTA PLUMBING CODE

MISCELLANEOUS STATUTES RELATED TO THE MINNESOTA PLUMBING CODE MISCELLANEOUS STATUTES RELATED TO THE MINNESOTA PLUMBING CODE 144.3855 LIMITATION. To meet cross-connection control requirements, as defined in Minnesota Rules, parts 4715.1920 and 4720.0025, the use of

More information

Appendix B Forms for Inspection, Testing, and Maintenance

Appendix B Forms for Inspection, Testing, and Maintenance Appendix B Forms for Inspection, Testing, and Maintenance This appendix is not a part of the requirements of this NFPA document but is included for informational purposes only. Forms need to be complete

More information

Chapter 693 1999 EDITION. Plumbers. 693.025 Insurance required of certain providers of low-flow showerheads or faucet aerators

Chapter 693 1999 EDITION. Plumbers. 693.025 Insurance required of certain providers of low-flow showerheads or faucet aerators Chapter 693 1999 EDITION Plumbers GENERAL PROVISIONS 693.010 Definitions 693.020 Application 693.025 Insurance required of certain providers of low-flow showerheads or faucet aerators LICENSING 693.030

More information

SECTION 5 - COMMERCIAL CONSTRUCTION MECHANICAL, ELECTRICAL, PLUMBING AND SOLAR OTHER TECHNICAL CODES

SECTION 5 - COMMERCIAL CONSTRUCTION MECHANICAL, ELECTRICAL, PLUMBING AND SOLAR OTHER TECHNICAL CODES SECTION 5 - COMMERCIAL CONSTRUCTION MECHANICAL, ELECTRICAL, PLUMBING AND SOLAR OTHER TECHNICAL CODES 5.1.0 GENERAL Section five reviews consolidates the various local amendments technical code information

More information

Fraternity and Sorority House Fire Safety

Fraternity and Sorority House Fire Safety Fraternity and Sorority House Fire Safety Buddy Dewar Director of Regional Operations National Fire Sprinkler Association 850-222-2070 How To Manage Greek Housing Fire Sprinkler Retrofit Brief Overview.

More information

SECTION THREE CONSTRUCTION CODES

SECTION THREE CONSTRUCTION CODES SECTION THREE CONSTRUCTION CODES CHAPTER 36: Construction Codes in Michigan Purpose and Applicability of Regulations Manufacturing facilities and other businesses must be designed according to code in

More information

Close-Out Documents... 9

Close-Out Documents... 9 Water and Sanitary Sewer Service Connection Requirements Service Connection Requirements... 1 Application for Services... 2 Water Meter Application... 2 Wet Tap/Tie-in Connection Requirements... 3 Meter

More information

2-1 TITLE 7 CONSTRUCTION REGULATIONS 2-4

2-1 TITLE 7 CONSTRUCTION REGULATIONS 2-4 2-1 TITLE 7 CONSTRUCTION REGULATIONS 2-4 Sec. 2-1: Sec. 2-2: Sec. 2-3: Sec. 2-4: Sec. 2-5: Sec. 2-6: Sec. 2-7: Sec. 2-8: Sec. 2-9: Sec. 2-10: Sec. 2-11: Sec. 2-12: Sec. 2-13: Sec. 2-14: Sec. 2-15: Sec.

More information

FOR CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS

FOR CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS EXAMINATION REQUIREMENTS FOR FIRE SUPPRESSION SYSTEM CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS REGULATION

More information

H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S

H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S HomeFireSprinkler.org F I R E T H E L A R G E ST S I N G L E C AU S E O F

More information

SERVICE RULES AND REGULATIONS LOUISVILLE WATER COMPANY

SERVICE RULES AND REGULATIONS LOUISVILLE WATER COMPANY 2015 SERVICE RULES AND REGULATIONS LOUISVILLE WATER COMPANY TABLE OF CONTENTS 1.0 Water Service and Meters 1.01 General Policies 1.01.1 Application of Rules... page 1 1.01.2 Violation of Rules... page

More information

SERVICE RULES AND REGULATIONS LOUISVILLE WATER COMPANY

SERVICE RULES AND REGULATIONS LOUISVILLE WATER COMPANY 2014 SERVICE RULES AND REGULATIONS LOUISVILLE WATER COMPANY TABLE OF CONTENTS 1.0 Water Service and Meters 1.01 General Policies 1.01.1 Application of Rules... page 1 1.01.2 Violation of Rules... page

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined Standpipes and Hose Systems CHAPTER 3 This chapter, which opens with an overview of standpipe and hose systems, is intended to assist the registered design professional (RDP), commissioning agent, authority

More information

SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes)

SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes) SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes) Maintenance Office Administrative Office Billing Office 530-426-7802 530-426-7800 916-332-4872

More information

Chapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS

Chapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS Title 153 - NEBRASKA STATE FIRE MARSHAL Chapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS Scope. Chapter 19 of Title 153 of the Nebraska Administrative Code is concerned with the certification of contractors

More information

City of La Vernia 102 E. Chihuahua Street, La Vernia, Texas 78121 Phone: (830)779-4541 Fax: (830) 253-1198 cityoflavernia@lavernia-tx.

City of La Vernia 102 E. Chihuahua Street, La Vernia, Texas 78121 Phone: (830)779-4541 Fax: (830) 253-1198 cityoflavernia@lavernia-tx. cityoflavernia@lavernia-tx.gov Commercial New/Remodel Building Requirements This document is not meant to modify any Federal or State laws or City Ordinances. It is intended to be informative and to be

More information

THE JERSEY CITY MUNICIPAL UTILITIES AUTHORITY REQUIREMENTS FOR FIRE AND DOMESTIC WATER LINE AND METER INSTALLATIONS

THE JERSEY CITY MUNICIPAL UTILITIES AUTHORITY REQUIREMENTS FOR FIRE AND DOMESTIC WATER LINE AND METER INSTALLATIONS THE JERSEY CITY MUNICIPAL UTILITIES AUTHORITY REQUIREMENTS FOR FIRE AND DOMESTIC WATER LINE AND METER INSTALLATIONS 1) All fire service applications and all domestic service applications two (2) inches

More information

STATE OF OKLAHOMA. 2nd Session of the 44th Legislature (1994) AS INTRODUCED An Act relating to professions and occupations;

STATE OF OKLAHOMA. 2nd Session of the 44th Legislature (1994) AS INTRODUCED An Act relating to professions and occupations; STATE OF OKLAHOMA 2nd Session of the 44th Legislature (1994) HOUSE BILL NO. 1984 By: Phillips AS INTRODUCED An Act relating to professions and occupations; amending 59 O.S. 1991, Sections 1002, as amended

More information

SECTION 1 PURPOSE AND POLICIES

SECTION 1 PURPOSE AND POLICIES SECTION 1 PURPOSE AND POLICIES These Rules and Regulations have been enacted to serve the public in securing the health, safety, and general welfare of the inhabitants of the Southwest Suburban Denver

More information

WHAT EACH LICENSE TYPE CAN DO (Abbreviated)

WHAT EACH LICENSE TYPE CAN DO (Abbreviated) WHAT EACH LICENSE TYPE CAN DO (Abbreviated) DIVISION - I - General, Building, and Residential Contractors: F.S. 489.105(3)(a, b, & c) and Sarasota County Ordinance 2002-079, Section 22-112(D)(1, 2, & 3)

More information

One of the fundamental design elements that every

One of the fundamental design elements that every Preliminary Design Information Before starting the water system design, you must assemble a collection of information. This includes information from the owner, the local utility, and the architect. Things

More information

Inspection and Testing of Water-Based Systems

Inspection and Testing of Water-Based Systems Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based

More information

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling October 2014 contents General Information

More information

Building Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County

Building Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County Building Permit Application Packet The purpose of Building Codes is to establish the minimum requirements to safe guard the public health, safety and general welfare through structural strength, means

More information

Arkansas Plumbers Law

Arkansas Plumbers Law Arkansas Plumbers Law Act 200, 1951 as amended Source: Arkansas Code 1951, Annotated Title 17 Chapter 38 1 17-38-101. Definitions. As used in this chapter: (1) Apprentice plumber means any person other

More information

FIRE SUPPRESSION INSTALLATION CITY OF HARRISONBURG, VIRGINIA

FIRE SUPPRESSION INSTALLATION CITY OF HARRISONBURG, VIRGINIA FIRE SUPPRESSION INSTALLATION CITY OF HARRISONBURG, VIRGINIA I. PURPOSE The purpose of this document is to provide planners and designers with information necessary in the design and construction of sprinkler

More information

ARTICLE II (2) ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH 020001 Purpose and Application.

ARTICLE II (2) ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH 020001 Purpose and Application. ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH 020001 Purpose and Application. Article II provides rules governing the allowable connection to the City POTW and the construction and inspection of

More information

ALBEMARLE COUNTY CODE CHAPTER 5 BUILDING REGULATIONS ARTICLE I. ADMINISTRATION

ALBEMARLE COUNTY CODE CHAPTER 5 BUILDING REGULATIONS ARTICLE I. ADMINISTRATION CHAPTER 5 BUILDING REGULATIONS Sections: ARTICLE I. ADMINISTRATION 5-100 Purpose and intent. 5-101 Building inspection office established; powers and duties. 5-102 Board of appeals established; powers

More information

NFPA 25 FAQs. 1. When inspecting an old system (60 years or older), when/where does NFPA 25 require a system to be upgraded to present standards?

NFPA 25 FAQs. 1. When inspecting an old system (60 years or older), when/where does NFPA 25 require a system to be upgraded to present standards? NFPA 25 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued

More information

NOTE: Unless otherwise specified, unit prices for the demolition of structures shall be for wet demolitions.

NOTE: Unless otherwise specified, unit prices for the demolition of structures shall be for wet demolitions. ATTACHMENT AA DETAILED SCOPE OF WORK Demolition & Removal Services for SR-7/US-441 from North of Fillmore Street to South of Stirling Road Hollywood, Broward County, Florida 1.0 Structures Structures are

More information

IAC 6/17/09 Public Safety[661] Ch 275, p.1 CHAPTER 275 CERTIFICATION OF AUTOMATIC FIRE EXTINGUISHING SYSTEM CONTRACTORS

IAC 6/17/09 Public Safety[661] Ch 275, p.1 CHAPTER 275 CERTIFICATION OF AUTOMATIC FIRE EXTINGUISHING SYSTEM CONTRACTORS IAC 6/17/09 Public Safety[661] Ch 275, p.1 CHAPTER 275 CERTIFICATION OF AUTOMATIC FIRE EXTINGUISHING SYSTEM CONTRACTORS 661 275.1(100C) Establishment of program. There is established within the fire marshal

More information

Cross Connection Control and Backflow Prevention Program Guidelines

Cross Connection Control and Backflow Prevention Program Guidelines Cross Connection Control and Backflow Prevention Program Guidelines February 2010 EPB #422 Note: As of October 1, 2012 The Water Security Agency and Saskatchewan Ministry of Environment share responsibility

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND

More information

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations. PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to June 1, 2014. It is intended for information and reference purposes only.

More information

Design & Construction Standards, Revised January 2013 5.21.30-1

Design & Construction Standards, Revised January 2013 5.21.30-1 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.

More information

Plumbing Code in Commercial Kitchens

Plumbing Code in Commercial Kitchens Plumbing Code in Commercial Kitchens City of Concord Code Administration 225-8580 Dan Clark Plumbing Inspector Tedd Evans, Chief Building Inspector Code References from the 2009 edition of the International

More information

Licensing & Certification

Licensing & Certification Licensing & Certification In this section we will be discussing various license and certification requirements and scopes. It is important that the plumber understand what his license may and may not cover.

More information

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below)

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE CHAPTER 17 - NONPOTABLE RAINWATER CATCHMENT SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state

More information

CITY OF RUTLAND DEPARTMENT OF PUBLIC WORKS. WATER DISTRIBUTION SYSTEM REGULATIONS August 1996 Last Revision: January 2015

CITY OF RUTLAND DEPARTMENT OF PUBLIC WORKS. WATER DISTRIBUTION SYSTEM REGULATIONS August 1996 Last Revision: January 2015 Table on Contents CITY OF RUTLAND DEPARTMENT OF PUBLIC WORKS WATER DISTRIBUTION SYSTEM REGULATIONS August 1996 Last Revision: January 2015 1. Authority 2. Definitions 3. Application 4. Commissioner as

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

ATTACHMENT AA DETAILED SCOPE OF WORK

ATTACHMENT AA DETAILED SCOPE OF WORK 1.0 Structures ATTACHMENT AA DETAILED SCOPE OF WORK Districtwide Right of Way Demolition and Removal Services ITB-DOT-14/15-4022TB Structures are buildings, including attached improvements, which could

More information

OREGON ELECTRICAL LAWS OREGON REVISED STATUTE 479

OREGON ELECTRICAL LAWS OREGON REVISED STATUTE 479 This PDF contains the Oregon Electrical Law (ORS 479) and the Oregon Administrative Code (Division 918-251 thru 311). This document was created using the codes and statutes in effect as of 15 April 2008.

More information

ARTICLE 1141 Cross Connection Control Program

ARTICLE 1141 Cross Connection Control Program 43 ARTICLE 1141 Cross Connection Control Program 1141.01 Purpose. 1141.07 Degree of hazard. 1141.02 Authority. 1147.08 Existing in-use backflow 1141.03 Responsibility. prevention devices. 1141.04 Definitions.

More information

CHAPTER 26 PLUMBING CODE

CHAPTER 26 PLUMBING CODE CHAPTER 26 PLUMBING CODE 26.01 PLUMBING CODE The Illinois Plumbing Code as promulgated by the Illinois Department of Public Health at 77 Illinois Administrative Code, Part 890, is hereby adopted as the

More information

PLUMBING ROUGH IN INSPECTION

PLUMBING ROUGH IN INSPECTION This Program is made Possible through the Code Officials Education & Training Fund. Revenue for the Fund comes from Assessments on Building Permits. Please turn down cell phones and put pagers on vibrate.

More information

Revised April (May) 2015

Revised April (May) 2015 Section 19.0 Cross Connection Control Policy 19.1 Responsibility 19.1.1 The Elkhart Water Utility has the responsibility to supply safe, potable water from the source to the point of delivery defined as

More information

PLEASE READ. The official text of New Jersey Statutes can be found through the home page of the New Jersey Legislature http://www.njleg.state.nj.

PLEASE READ. The official text of New Jersey Statutes can be found through the home page of the New Jersey Legislature http://www.njleg.state.nj. PLEASE READ The official text of New Jersey Statutes can be found through the home page of the New Jersey Legislature http://www.njleg.state.nj.us/ New Jersey Statutes Annotated (N.J.S.A.), published by

More information

OREGON FIRE CODE Interpretations and Technical Advisories

OREGON FIRE CODE Interpretations and Technical Advisories OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

UPPER MOHAWK VALLEY REGIONAL WATER BOARD SERVICE AREA. City of Utica

UPPER MOHAWK VALLEY REGIONAL WATER BOARD SERVICE AREA. City of Utica UPPER MOHAWK VALLEY REGIONAL WATER BOARD The following Rules and Regulations and the fees rates and charges incorporated herein are to be considered as a part of the contract between the Upper Mohawk Valley

More information

505.3.6 For a building with a crawl space, see Figure 10. 505-1

505.3.6 For a building with a crawl space, see Figure 10. 505-1 505 WATER SERVICE INSTALLATION 505.1 DEFINITION A service line is comprised of the piping and related appurtenances including the connection installed from the Des Moines Water Works water main to the

More information

ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING

ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING 1.0 General 1.1 The work covered by this section consists of providing all labor, equipment, material and supplies, insurance, accessories, tools, transportation,

More information

When Should Examination Preparation Begin?

When Should Examination Preparation Begin? Texas State Board of Plumbing Examiners Tradesman Plumber-Limited Licensee Examination Review Course The following Examination Review Course is designed to assist a registered Plumber s Apprentice in preparing

More information

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting

More information

OKLAHOMA STATUTES TITLE 59. PROFESSIONS AND OCCUPATIONS PLUMBERS AND PLUMBING CONTRACTORS

OKLAHOMA STATUTES TITLE 59. PROFESSIONS AND OCCUPATIONS PLUMBERS AND PLUMBING CONTRACTORS OKLAHOMA STATUTES TITLE 59. PROFESSIONS AND OCCUPATIONS PLUMBERS AND PLUMBING CONTRACTORS Section 1001. Citation Sections 1001 through 1023.1 of this title shall be known and may be cited as "The Plumbing

More information

SECTION IV - TESTS AND INSPECTIONS PART 1 - GENERAL. 1.01 Testing - General

SECTION IV - TESTS AND INSPECTIONS PART 1 - GENERAL. 1.01 Testing - General SECTION IV - TESTS AND INSPECTIONS PART 1 - GENERAL 1.01 Testing - General Testing shall be of the type and frequency described in each section and summarized in Item 1 of this section. In addition to

More information

www.garyklinka.com Page 1 of 51 Exterior Plumbing Quiz Part 1

www.garyklinka.com Page 1 of 51 Exterior Plumbing Quiz Part 1 www.garyklinka.com Page 1 of 51 Exterior Plumbing Quiz Part 1 Instructions: $60 1. Print these pages..all reference materials are included. 2. Review and answer the simple questions in each mini section.

More information

NC General Statutes - Chapter 87 Article 2 1

NC General Statutes - Chapter 87 Article 2 1 Article 2. Plumbing and Heating Contractors. 87-16. Board of Examiners; appointment; term of office. There is created the State Board of Examiners of Plumbing, Heating, and Fire Sprinkler Contractors consisting

More information

How To Get A Building Permit In Florida

How To Get A Building Permit In Florida MIAMI-DADE COUNTY BUILDING DEPARTMENT PERMIT EXEMPTIONS Please note that the exemptions listed in this section are from Florida Building Code requirements only. Other State and County regulatory departments

More information

Metropolitan Domestic Water Improvement District. Backflow Prevention Control Ordinance. Ordinance No. 1993-01

Metropolitan Domestic Water Improvement District. Backflow Prevention Control Ordinance. Ordinance No. 1993-01 Metropolitan Domestic Water Improvement District Backflow Prevention Control Ordinance Ordinance No. 1993-01 September 23, 1993 Metropolitan Domestic Water Improvement District Backflow Prevention Control

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.

3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees. The following shall serve as the minimum requirements for contractors performing work in relation to the Authority s potable water and sanitary sewer system(s), appurtenances and service connections. General:

More information

Project Building Permit No. One complete set of Record or as-built drawings (electronic) One complete set of Record or as-built drawings (hard copy)

Project Building Permit No. One complete set of Record or as-built drawings (electronic) One complete set of Record or as-built drawings (hard copy) University at Albany, State University of New York Office of Facilities Management Code Administration Certificate of Occupancy/Compliance Records Checklist On-site Inspection Items Not Included Project

More information

LOCKOUT/TAGOUT (LOTO) SAFETY PROGRAM

LOCKOUT/TAGOUT (LOTO) SAFETY PROGRAM 1 UNIVERSITY OF WEST FLORIDA LOCKOUT/TAGOUT (LOTO) SAFETY PROGRAM (EQUIPMENT HAZARD DE-ENERGIZING AND ISOLATION) DEPARTMENT OF ENVIRONMENTAL HEALTH AND SAFETY 11000University Parkway Pensacola, FL 32514

More information

2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS

2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS 2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS Water system improvements proposed for inclusion into Western s service area shall be designed in accordance with all appropriate AWWA standards, include

More information

Table of Contents. 07.02.05 - Rules Governing Plumbing Safety Licensing

Table of Contents. 07.02.05 - Rules Governing Plumbing Safety Licensing Table of Contents 07.02.05-000. Legal Authority.... 2 001. Title And Scope.... 2 002. Written Interpretations.... 2 003. Administrative Appeals.... 2 004. -- 009. (Reserved)... 2 010. Licensure History....

More information

Oregon Plumbing Rule and Law RV 3.3.16

Oregon Plumbing Rule and Law RV 3.3.16 PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

KS 60, 66067 (785) 229-3620 (785) 229-3625 E-

KS 60, 66067 (785) 229-3620 (785) 229-3625 E- Requirements for Obtaining a Contractor Occupational License: 1. Completed Application Form. 2. Proof of General Liability and Workers Compensation Insurance. a. Every contractor except a contractor who

More information

Plumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection

Plumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection Plumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection Jobs are Alaska s Future MECHANICAL INSPECTION CUSTOMER COUNTER LOCATIONS Main Office MI Anchorage

More information

City of West Chicago Community Development Department 475 Main Street, West Chicago, IL 60185 Phone: (630) 293-2200 x 131 / Fax: (630) 293-1257

City of West Chicago Community Development Department 475 Main Street, West Chicago, IL 60185 Phone: (630) 293-2200 x 131 / Fax: (630) 293-1257 City of West Chicago Community Development Department 475 Main Street, West Chicago, IL 60185 Phone: (630) 293-2200 x 131 / Fax: (630) 293-1257 APPLICATION FOR DEMOLITION PERMIT Permit Number: Date Received:

More information