S2A6620 Technical Service Bulletin. Cache Protect Battery Replacement

Size: px
Start display at page:

Download "S2A6620 Technical Service Bulletin. Cache Protect Battery Replacement"

Transcription

1 S2A6620 Technical Service Bulletin Cache Protect Battery Replacement

2 Table of Contents 1 OVERVIEW EXPLANATION Background Increased Functionality Applicability UPGRADE PROCEDURE Online Replacement Controller Replacement Steps SUPPORT ACCESSING A CONTROLLER WITHOUT A SERIAL CABLE SFA OS APP SHOW SUB SUM COMMAND EQUIVALENTS FOR EARLIER VERSIONS...7 DataDirect Networks S2A6620 Technical Service Bulletin, Cache Protect Battery Replacement 2

3 1 Overview DDN recommends all S2A6620 battery packs be replaced with a new and improved Li-Ion battery. Because S2A6620 battery packs are not CRUs (Customer Replaceable Units) the entire controller canister must be replaced. 2 Explanation 2.1 Background The S2A6620 battery pack is used to protect volatile cache on power loss while cache contents are flushed to internal non-volatile memory. If a battery is incapable of this task, upon reboot, the controller will enter a critical condition. This condition is usually recoverable as the SFA OS mirrors the contents of cache across both controllers in a S2A6620 system. If the batteries on both controllers in a system are incapable of performing a successful cache flush, the system runs the risk of losing cached writes for storage pools that have write-back cache enabled during a powerloss event. DDN has encountered some batteries that are not operating at an acceptable level. After further investigation, DDN has decided to replace all existing S2A6620 canisters using nickel-metal hydride batteries with a new design that incorporates newer Li-Ion batteries as well as improved battery monitoring and conditioning features. 2.2 Increased Functionality The new controller canister with improved battery provides an interface for SFA OS firmware to communicate with an onboard fuel gauge on the battery pack. SFA OS FW has been enhanced to provide monitoring information provided by the fuel gauge via the CLUI and GUI displays and also now captures new events related to the new packs. 2.3 Applicability An upgrade to the (or later) release of SFA OS, coupled with controller hardware replacement, is a mandatory upgrade for the entire S2A6620 customer base. DataDirect Networks S2A6620 Technical Service Bulletin, Cache Protect Battery Replacement 3

4 3 Upgrade Procedure DDN recommends that the controller replacement procedure, described in this document, only be performed as an online replacement procedure. In this scenario, the S2A6620 system is up and running (with or without host I/O), while the operator replaces each controller canister individually. 3.1 Online Replacement Two things must be accounted for when performing online controller replacements. The first has to do with the installed host side failover mechanisms (also commonly referred to as multi-pathing I/O or MPIO). If host I/O will be serviced by the SFA6620 during this operation, it is imperative that host side multi-pathing software be configured and operating correctly. Because this online upgrade procedure will involve a controller failover/failback operation, functioning multi-pathing mechanisms must be in place to ensure data availability is maintained throughout the online replacement procedure. NOTE: Multi-pathing software is implemented on the host system and not the S2A6620 and is only critical if host I/Os or mounted file systems are expected during this controller replacement procedure. Any questions or concerns in this area should be directed to DDN Support before proceeding. The second consideration is related to the power supply units currently installed in the controller enclosure of the S2A6620 system. There are currently two types of power supplies deployed with S2A6620 systems. Note that older generation power supplies are not compatible with this online controller replacement. To verify the installed power supply type, issue the command show power_supply all and examine the Serial Number field. If the main chassis power supply serial numbers begin with THDEL then you are okay to proceed with the online replacement. If your main chassis power supply serial numbers start with CATEC then you will not be able to perform the online replacement and you will need to contact DDN support for further instructions. 3.2 Controller Replacement Steps NOTE: An S2A6620 serial cable is required for the following procedure. If you do not have one available, contact DDN support (see contact details at the end of this document) before proceeding. If you need to perform the following steps without a serial cable, see Section 5 for a procedure to set up the network to access a controller when a serial cable isn t available and then return to this procedure. 1. Disable Controller Write-Back Cache (WBC): SSH into one of the S2A6620 controller canister CLUI sessions (with USERNAME: user and PASSWORD: user). Disable writeback cache on all storage pools. To do this, type the following command for each configured storage pool on the system: set pool ID write_ back_caching=false 2. Capture Controller Logs: From an SSH CLUI session on each S2A6620 controller canister, issue the command show sub sum, app show sub sum, and ui show network and save all the output as plain text. NOTE: app show sub sum may not be supported on earlier SFA OS versions. A list of equivalent commands is included at the end of this document. DataDirect Networks S2A6620 Technical Service Bulletin, Cache Protect Battery Replacement 4

5 It s important to capture the current network settings on the existing controllers. The network settings are required as they will be needed to configure network interfaces on the new controller canisters. The default IP addresses of the new controllers are Shutdown First Controller: SSH into the first controller to be replaced. Issue the command shutdown controller local. This command will initiate a shutdown of this controller only. This is a safe operation to do on a production system as all Pools and VDs as well as HOST I/O will be automatically transferred to the remaining active controller. 4. Remove and Install First New Controller: Verify the controller has shut down by confirming there is no LED activity on the shut down controller. Properly label all cables connected to the shutdown down controller and remove them. Disengage the controller and replace with the new controller. Make sure the new controller is fully seated and latched into place. Plug the FC cables in at this time but do not plug in the Ethernet cable. Note: If you are not using a serial cable interface but instead are going to configure the controller using an Ethernet/ssh connection and have verified there are no IP address conflicts as described in section 5, proceed with plugging in the Ethernet cable). 5. Verify Installed Controller Powers Up: The new controller should power up automatically. If this doesn t occur automatically, power up the new controller by pressing the power button located on the back of the controller: 6. Connect To Newly Installed Controller Using An RS-232/Serial Connection: Allow the controller to power up, this will take approximately two minutes. Once fully powered up, log into the newly installed controller CLUI using a serial cable connection. The newly installed controller should be in a Manual Intervention Required (MIR) Firmware Mismatch state (the firmware on the newly installed controller will likely be at a different level than the existing controller). If any other MIR state is seen, contact DDN Support for guidance. The controller will remain in the MIR Mismatched Firmware state until the other controller is replaced (later in this procedure). 7. Change the network settings to match that of the removed controller: Using the output of the ui show network data previously captured, run the following command on this controller canister: ui set network local 0 ip_address=x ip_mask=x ip_gateway=x DataDirect Networks S2A6620 Technical Service Bulletin, Cache Protect Battery Replacement 5

6 Where x, y, and z are the ip address, netmask, and gateway address of the original controller. If it s not already connected, plug the Ethernet cable into the new controller. Ping the newly installed controller to ensure network communication is set up correctly on the new controller. 8. Repeat For Second Controller Replacement. To replace the other controller repeat steps 2-7 referencing the second controller. Once the other controller has been shutdown (in step 3), the Firmware Mismatch MIR state will be cleared from the first controller and host I/O failover (if applicable) will occur. Note that when you execute step 6 for the second controller, that it should not come up in any MIR state, including MIR Mismatched Firmware. 9. Validate Functional Controllers: Both controllers should be fully functional at this point and serving I/O. You can run the command app show channel to look at the S2A 6620 host port status. You can also run show vd counter rate several times to see host I/O going through the S2A6620 controller FC ports (assuming host I/O is running). 10. Enable Controller Write-Back Cache (WBC): From an SSH session on either one of the S2A6620 controller canister CLUI sessions, enable write-back cache on all storage pools. To do this, type the following command for each configured storage pool on the system: set pool ID write_ back_caching=true 4 Support Please contact DataDirect Networks Support at any time for assistance. Support can be reached by the following methods: Web: [email protected] North America: International: Accessing a Controller without a Serial Cable Note: This procedure will only work if there are no other devices on the local subnet with an IP address of and If a 6620 serial cable is not available, this procedure can be used to access a controller using the network. 1. Ping the local network to see if any devices on the network have the IP address and If possible, remove these devices from the network until the controller replacement is complete. If it s not possible to remove the devices with these IP addresses, the remaining steps below cannot be used because doing so will create conflicting IP addresses. 2. DDN uses two IP addresses with replacement controllers. Your replacement controller s address will be either or with a netmask of Once the controller is installed and powered on, plug in the Ethernet cable. 4. SSH into one of the addresses given in Step 1. (One of the two addresses will work.) DataDirect Networks S2A6620 Technical Service Bulletin, Cache Protect Battery Replacement 6

7 5. Now that communication is established, change the IP address, netmask, and gateway to participate in your network. Use the following command to make the changes: ui set network local 0 ip_address=x ip_mask=y ip_gateway= z 6. Once the network settings have been applied, exit out of the CLI and SSH back into the controller using the new IP address. The steps described in this section can be used in lieu of the RS-232/Serial Connection steps described throughout Section SFA OS app show sub sum Command Equivalents for Earlier Versions If the customer is running 1.3.x.x or newer, they can use the app show sub sum command. If the system is running a version of SFA OS prior to 1.3.x.x, the following commands will need to be run to capture the required data. show controller * all show slot * app show proc * show subsystem all show pool * app show channel * show enclosure * show virtual disk * app show stack * show expander * show physical_disk * ui show show fan * show job * all ui show network loc * show temperature * app show discovered * ui show snmp show power_supply * app show host * show controller local log num=max show power_supply * all app show initiator * show ups * app show pres * DataDirect Networks S2A6620 Technical Service Bulletin, Cache Protect Battery Replacement 7

Step-by-Step Guide. to configure Open-E DSS V7 Active-Active iscsi Failover on Intel Server Systems R2224GZ4GC4. Software Version: DSS ver. 7.

Step-by-Step Guide. to configure Open-E DSS V7 Active-Active iscsi Failover on Intel Server Systems R2224GZ4GC4. Software Version: DSS ver. 7. Step-by-Step Guide to configure on Intel Server Systems R2224GZ4GC4 Software Version: DSS ver. 7.00 up01 Presentation updated: April 2013 www.open-e.com 1 www.open-e.com 2 TECHNICAL SPECIFICATIONS OF THE

More information

Quick Installation Guide Network Management Card

Quick Installation Guide Network Management Card Rev.1.1 www.cyberpowersystems.com Quick Installation Guide Network Management Card Intelligent Network Management Card allows UPS to be managed, monitored, and configured via SNMP Card Configuration Tool

More information

Reboot the ExtraHop System and Test Hardware with the Rescue USB Flash Drive

Reboot the ExtraHop System and Test Hardware with the Rescue USB Flash Drive Reboot the ExtraHop System and Test Hardware with the Rescue USB Flash Drive This guide explains how to create and use a Rescue USB flash drive to reinstall and recover the ExtraHop system. When booting

More information

HighPoint RAID Management User s Guide

HighPoint RAID Management User s Guide HighPoint RAID Management User s Guide Revision: 1.0 Date: August 2009 HighPoint Technologies, Inc. HighPoint RAID Management User s Guide 1 - HighPoint RAID Management Utilities (HRM) Installation The

More information

SGI InfiniteStorage NAS 50/100 Quick Start Guide 007-5621-001

SGI InfiniteStorage NAS 50/100 Quick Start Guide 007-5621-001 SGI InfiniteStorage NAS 50/100 Quick Start Guide 007-5621-001 COPYRIGHT 2010 SGI. All rights reserved; provided portions may be copyright in third parties, as indicated elsewhere herein. No permission

More information

Microsoft Windows Server 2008* (x86 & x64) Dual SCM (ALUA) Installation BKM. Intel Order Number: E37652-004

Microsoft Windows Server 2008* (x86 & x64) Dual SCM (ALUA) Installation BKM. Intel Order Number: E37652-004 Microsoft Windows Server 2008* (x86 & x64) Dual SCM (ALUA) Installation BKM Intel Order Number: E37652-004 Microsoft Windows Server 2008* Dual SCM Installation Table of Contents Slides 3-5: Upgrading from

More information

VTrak 15200 SATA RAID Storage System

VTrak 15200 SATA RAID Storage System Page 1 15-Drive Supports over 5 TB of reliable, low-cost, high performance storage 15200 Product Highlights First to deliver a full HW iscsi solution with SATA drives - Lower CPU utilization - Higher data

More information

UBIQUITI BRIDGE CONFIGURATION PROCEDURE (PowerStation & NanoStation Units ONLY)

UBIQUITI BRIDGE CONFIGURATION PROCEDURE (PowerStation & NanoStation Units ONLY) UBIQUITI BRIDGE CONFIGURATION PROCEDURE (PowerStation & NanoStation Units ONLY) Hardware Installation 1. Initial placement for programming and configuration purposes should be performed in an indoor environment.

More information

HP StoreVirtual 4630 Storage Maintenance Guide

HP StoreVirtual 4630 Storage Maintenance Guide HP StoreVirtual 4630 Storage Maintenance Guide Abstract This guide explains how to back up, restore, upgrade, and otherwise maintain the HP StoreVirtual 4630 storage system and solution components. The

More information

Step-by-Step Guide to Open-E DSS V7 Active-Active iscsi Failover

Step-by-Step Guide to Open-E DSS V7 Active-Active iscsi Failover www.open-e.com 1 Step-by-Step Guide to Software Version: DSS ver. 7.00 up10 Presentation updated: June 2013 www.open-e.com 2 TO SET UP ACTIVE-ACTIVE ISCSI FAILOVER, PERFORM THE FOLLOWING STEPS: 1. Hardware

More information

Step-by-Step Guide to Open-E DSS V7 Active-Active Load Balanced iscsi HA Cluster

Step-by-Step Guide to Open-E DSS V7 Active-Active Load Balanced iscsi HA Cluster www.open-e.com 1 Step-by-Step Guide to Open-E DSS V7 Active-Active Load Balanced iscsi HA Cluster (without bonding) Software Version: DSS ver. 7.00 up10 Presentation updated: May 2013 www.open-e.com 2

More information

SSD Firmware Update Utility Guide

SSD Firmware Update Utility Guide SSD Firmware Update Utility Guide Crucial m4 2.5 SSD Firmware Revision 070H Firmware Update Guide for Windows 8 (Update from Rev 0001, 0002, 0009, 0309, 000F, 010G, 040H to Rev 070H) Introduction This

More information

This chapter explains a preparation for the use of RemoteControlService.

This chapter explains a preparation for the use of RemoteControlService. ServerView User's Guide (For RemoteControlService) Areas Covered Before Reading This Manual This section explains the notes for your safety and conventions used in this manual. Chapter 1 Overview of RemoteControlService

More information

: HP HP0-771. Version : R6.1

: HP HP0-771. Version : R6.1 Exam : HP HP0-771 Title : Designing & Implementing HP Enterprise Backup Solutions Version : R6.1 Prepking - King of Computer Certification Important Information, Please Read Carefully Other Prepking products

More information

Note: This case study utilizes Packet Tracer. Please see the Chapter 5 Packet Tracer file located in Supplemental Materials.

Note: This case study utilizes Packet Tracer. Please see the Chapter 5 Packet Tracer file located in Supplemental Materials. Note: This case study utilizes Packet Tracer. Please see the Chapter 5 Packet Tracer file located in Supplemental Materials. CHAPTER 5 OBJECTIVES Configure a router with an initial configuration. Use the

More information

System Compatibility. Enhancements. Email Security. SonicWALL Email Security 7.3.2 Appliance Release Notes

System Compatibility. Enhancements. Email Security. SonicWALL Email Security 7.3.2 Appliance Release Notes Email Security SonicWALL Email Security 7.3.2 Appliance Release Notes System Compatibility SonicWALL Email Security 7.3.2 is supported on the following SonicWALL Email Security appliances: SonicWALL Email

More information

McAfee Data Loss Prevention

McAfee Data Loss Prevention Hardware Guide Revision B McAfee Data Loss Prevention 1650, 3650, 4400, 5500 This guide describes the features and capabilities of McAfee Data Loss Prevention (McAfee DLP) appliances to help you to manage

More information

Cisco Active Network Abstraction Gateway High Availability Solution

Cisco Active Network Abstraction Gateway High Availability Solution . Cisco Active Network Abstraction Gateway High Availability Solution White Paper This white paper describes the Cisco Active Network Abstraction (ANA) Gateway High Availability solution developed and

More information

Chapter 1 Installing the Gateway

Chapter 1 Installing the Gateway Chapter 1 Installing the Gateway This chapter describes how to set up the wireless voice gateway on your Local Area Network (LAN), connect to the Internet, and perform basic configuration. For information

More information

SNMP Web Management. User s Manual For SNMP Web Card/Box

SNMP Web Management. User s Manual For SNMP Web Card/Box SNMP Web Management User s Manual For SNMP Web Card/Box Management Software for Off-Grid Inverter Version: 1.2 Table of Contents 1. Overview... 1 1.1 Introduction... 1 1.2 Features... 1 1.3 Overlook...

More information

Configuring the Switch with the CLI-Based Setup Program

Configuring the Switch with the CLI-Based Setup Program APPENDIX D Configuring the Switch with the CLI-Based Setup Program This appendix provides a command-line interface (CLI)-based setup procedure for a standalone switch. For product overview information,

More information

Router Lab Reference Guide

Router Lab Reference Guide Router Lab Reference Guide 1 PURPOSE AND GOALS The routing lab allows testing different IP-related protocols and solutions in a close to live environment. You can learn how to configure Cisco routers and

More information

Ambient Temperature In Range Probe X

Ambient Temperature In Range Probe X List of Events This section lists all events that are written to the Event Log. Some of these events can be configured through the Configuring Events to Take Actions page, and these are listed in the first

More information

StorSimple Appliance Quick Start Guide

StorSimple Appliance Quick Start Guide StorSimple Appliance Quick Start Guide 5000 and 7000 Series Appliance Software Version 2.1.1 (2.1.1-267) Exported from Online Help on September 15, 2012 Contents Getting Started... 3 Power and Cabling...

More information

HP PolyServe Software 4.1.0 upgrade guide

HP PolyServe Software 4.1.0 upgrade guide HP StorageWorks HP PolyServe Software 4.1.0 upgrade guide This document describes how to upgrade to HP PolyServe Matrix Server 4.1.0, HP PolyServe Software for Microsoft SQL Server 4.1.0, and HP PolyServe

More information

Building Microsoft Windows Server 2012 Clusters on the Dell PowerEdge VRTX

Building Microsoft Windows Server 2012 Clusters on the Dell PowerEdge VRTX Building Microsoft Windows Server 2012 Clusters on the Dell PowerEdge VRTX Startup Guide Paul Marquardt Contents Introduction... 4 Requirements... 4 Chassis setup... 6 Chassis placement and CMC cabling...

More information

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade Installation Instructions SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade Catalog Numbers 1747-DU501 Topic Page System Requirements 3 Install ControlFLASH 3 Prior to Running ControlFLASH

More information

AP6511 First Time Configuration Procedure

AP6511 First Time Configuration Procedure AP6511 First Time Configuration Procedure Recommended Minimum Configuration Steps From the factory, all of the 6511 AP s should be configured with a shadow IP that starts with 169.254.xxx.xxx with the

More information

How to Set Up Your NSM4000 Appliance

How to Set Up Your NSM4000 Appliance How to Set Up Your NSM4000 Appliance Juniper Networks NSM4000 is an appliance version of Network and Security Manager (NSM), a software application that centralizes control and management of your Juniper

More information

Drobo How-To Guide. Topics. What You Will Need. Prerequisites. Deploy Drobo B1200i with Microsoft Hyper-V Clustering

Drobo How-To Guide. Topics. What You Will Need. Prerequisites. Deploy Drobo B1200i with Microsoft Hyper-V Clustering Multipathing I/O (MPIO) enables the use of multiple iscsi ports on a Drobo SAN to provide fault tolerance. MPIO can also boost performance of an application by load balancing traffic across multiple ports.

More information

Configuring a Trimble Sps 461 using the Ethernet Connection GETTING THE GPS ON THE NETWORK HTTP PORT. By Bob Glover

Configuring a Trimble Sps 461 using the Ethernet Connection GETTING THE GPS ON THE NETWORK HTTP PORT. By Bob Glover Configuring a Trimble Sps 461 using the Ethernet Connection By Bob Glover With most computers today, finding a serial port on board is a thing of the past. Increasingly, fewer and fewer computers even

More information

1 DVR 670 Series firmware version 2.1.2 (date 2014-06-17)

1 DVR 670 Series firmware version 2.1.2 (date 2014-06-17) Video Recorder 670 Series 1 DVR 670 Series firmware version 2.1.2 (date 2014-06-17) File name: 600rtseries_2.1.2_140617.bin - When a unit detects a HDD error, the DVR will automatically reboot so that

More information

SNMP Manager User s Manual

SNMP Manager User s Manual SNMP Manager User s Manual Table of Contents 1. Introduction...2 2. SNMP Manager Install, Quick Start and Uninstall...2 2.1. Software Installation...2 2.2. Software Quick Start...2 2.3. Software Uninstall...2

More information

Dell PowerVault MD3400 and MD3420 Series Storage Arrays Deployment Guide

Dell PowerVault MD3400 and MD3420 Series Storage Arrays Deployment Guide Dell PowerVault MD3400 and MD3420 Series Storage Arrays Deployment Guide Notes, Cautions, and Warnings NOTE: A NOTE indicates important information that helps you make better use of your computer. CAUTION:

More information

Set Up Panorama. Palo Alto Networks. Panorama Administrator s Guide Version 6.0. Copyright 2007-2015 Palo Alto Networks

Set Up Panorama. Palo Alto Networks. Panorama Administrator s Guide Version 6.0. Copyright 2007-2015 Palo Alto Networks Set Up Panorama Palo Alto Networks Panorama Administrator s Guide Version 6.0 Contact Information Corporate Headquarters: Palo Alto Networks 4401 Great America Parkway Santa Clara, CA 95054 www.paloaltonetworks.com/company/contact-us

More information

SNMP-1 Configuration Guide

SNMP-1 Configuration Guide SNMP-1 Configuration Guide You must configure the Net Logic Card before it can operate properly. You have two methods to configure the Net Logic Card: Using telnet or terminal. Using Telnet 1. Make sure

More information

AX4 5 Series Software Overview

AX4 5 Series Software Overview AX4 5 Series Software Overview March 6, 2008 This document presents an overview of all software you need to configure and monitor any AX4 5 series storage system running the Navisphere Express management

More information

If you are unable to set up your Linksys Router by using one of the above options, use the steps below to manually configure your router.

If you are unable to set up your Linksys Router by using one of the above options, use the steps below to manually configure your router. This article describes how to manually configure a Linksys Router for broadband DSL that uses PPPoE (Point-to-Point Protocol over Ethernet) for authentication. For automatic configuration options, please

More information

Chapter 2 Array Configuration [SATA Setup Utility] This chapter explains array configurations using this array controller.

Chapter 2 Array Configuration [SATA Setup Utility] This chapter explains array configurations using this array controller. Embedded MegaRAID SATA User's Guide Areas Covered Before Reading This Manual This section explains the notes for your safety and conventions used in this manual. Chapter 1 Overview This chapter introduces

More information

HP StoreVirtual DSM for Microsoft MPIO Deployment Guide

HP StoreVirtual DSM for Microsoft MPIO Deployment Guide HP StoreVirtual DSM for Microsoft MPIO Deployment Guide HP Part Number: AX696-96254 Published: March 2013 Edition: 3 Copyright 2011, 2013 Hewlett-Packard Development Company, L.P. 1 Using MPIO Description

More information

HP BladeSystem c-class Virtual Connect Support Utility User Guide

HP BladeSystem c-class Virtual Connect Support Utility User Guide HP BladeSystem c-class Virtual Connect Support Utility User Guide Version 1.2.0 Part Number 482172-001 February 2008 (First Edition) Copyright 2008 Hewlett-Packard Development Company, L.P. The information

More information

PS6500 Storage Arrays Hardware Maintenance

PS6500 Storage Arrays Hardware Maintenance PS6500 Storage Arrays Hardware Maintenance 110-0118-EN-R2 Copyright 2010 Dell, Inc. All rights reserved. Dell is a trademark of Dell, Inc. EqualLogic is a registered trademark. All trademarks and registered

More information

ATTO ExpressSAS Troubleshooting Guide for Windows

ATTO ExpressSAS Troubleshooting Guide for Windows ATTO ExpressSAS Troubleshooting Guide for Windows This document describes troubleshooting techniques that can be used to identify and resolve issues associated with the ATTO ExpressSAS Raid Controller.

More information

Avocent Universal Management Gateway Appliance Plug-in for DSView 4 Management Software Release Notes Version 2.9.0.

Avocent Universal Management Gateway Appliance Plug-in for DSView 4 Management Software Release Notes Version 2.9.0. Avocent Universal Management Gateway Appliance Plug-in for DSView 4 Management Software Release Notes Version 2.9.0.13 March 11, 2015 This document outlines: 1. System Requirements 2. Language Support

More information

Drobo How-To Guide. Topics. What You Will Need. Configure Windows iscsi Multipath I/O (MPIO) with Drobo iscsi SAN

Drobo How-To Guide. Topics. What You Will Need. Configure Windows iscsi Multipath I/O (MPIO) with Drobo iscsi SAN Multipath I/O (MPIO) enables the use of multiple iscsi ports on a Drobo SAN to provide fault tolerance. MPIO can also boost performance of an application by load balancing traffic across multiple ports.

More information

GSC/VRC IP Converter. Installation and Operation Manual

GSC/VRC IP Converter. Installation and Operation Manual GSC/VRC IP Converter Installation and Operation Manual Table of Contents Introduction... 2 Compatibility... 2 Remote Control Hardware... 2 PC Software... 2 Unpacking... 2 Front Panel Indicators... 3 Hardware

More information

Manual. IP Sensor and Watchdog IPSW2210. I P S W 2 2 1 0 M a n u a l P a g e 1. Relay Output. Power input. 12VDC adapter LED Indicators. 2 Dry.

Manual. IP Sensor and Watchdog IPSW2210. I P S W 2 2 1 0 M a n u a l P a g e 1. Relay Output. Power input. 12VDC adapter LED Indicators. 2 Dry. IP Sensor and Watchdog IPSW2210 Manual Relay Output Power input 12VDC adapter LED Indicators 1 wire 2 Dry Output Green : Power Yellow: Link temperature & humidity contact inputs LED indicator sensor input

More information

SNMP Web card. User s Manual. Management Software for Uninterruptible Power Supply Systems

SNMP Web card. User s Manual. Management Software for Uninterruptible Power Supply Systems SNMP Web card User s Manual Management Software for Uninterruptible Power Supply Systems Table of Contents 1. Overview... 3 1.1 Introduction... 3 1.2 Features... 3 1.3 Overlook... 3 1.4 Installation and

More information

Deploying SAP on Microsoft SQL Server 2008 Environments Using the Hitachi Virtual Storage Platform

Deploying SAP on Microsoft SQL Server 2008 Environments Using the Hitachi Virtual Storage Platform 1 Deploying SAP on Microsoft SQL Server 2008 Environments Using the Hitachi Virtual Storage Platform Implementation Guide By Sean Siegmund June 2011 Feedback Hitachi Data Systems welcomes your feedback.

More information

AssuredSAN Event Descriptions Reference Guide

AssuredSAN Event Descriptions Reference Guide AssuredSAN Event Descriptions Reference Guide Abstract This guide is for reference by storage administrators to help troubleshoot storage-system issues. It describes event messages that may be reported

More information

Configuring an A Series LED Sign Controller for your Network

Configuring an A Series LED Sign Controller for your Network Configuring an A Series LED Sign Controller for your Network A Series LED displays from Optec support both serial and 10BaseT Ethernet communication. Serial communication via RS232 or RS485 is independent

More information

HP Insight Management Agents architecture for Windows servers

HP Insight Management Agents architecture for Windows servers HP Insight Management Agents architecture for Windows servers Technology brief, 2 nd edition Introduction... 3 A first look at the Insight Management Agents architecture... 3 HP Insight Management agents...

More information

Hyper-V Installation Guide for Snare Server

Hyper-V Installation Guide for Snare Server Hyper-V Installation Guide for Snare Server Intersect Alliance International Pty Ltd. All rights reserved worldwide. Intersect Alliance Pty Ltd shall not be liable for errors contained herein or for direct,

More information

PRILINK PRI Management System

PRILINK PRI Management System www.prilink.com PRILINK PRI MANAGEMENT SSTEM INSTALLATION GUIDE PRI Management PRILINK PRI Management System Installation Guide Version 3.0, Rev. 12-01-24 Page 1 Table of Contents 1 HARDWARE INSTALLATION...

More information

IEI emerge and Dedicated Micros Digital Video Recorder. Install, Setup, and Integration Guide. Version 3.0 and above

IEI emerge and Dedicated Micros Digital Video Recorder. Install, Setup, and Integration Guide. Version 3.0 and above IEI emerge and Dedicated Micros Digital Video Recorder Install, Setup, and Integration Guide Version 3.0 and above CONTENTS DVR Features Requirements List...3 Hardware...3 Software and Licenses...3 Upgrading

More information

Network Management Card. User Manual

Network Management Card. User Manual User Manual 1 Contents Contents 2 Chapter 1 Overview 3 1.1 NMC package contents 4 1.2 NMC CD Resources 4 1.3 Features 4 1.4 NMC Applications 5 Chapter 2 NMC parameters setting via serial COM port 6 2.1

More information

RS16 FS Manual v.6.1a. RS16FS User s Guide. Version 6.1A - 1 -

RS16 FS Manual v.6.1a. RS16FS User s Guide. Version 6.1A - 1 - RS16FS User s Guide Version 6.1A - 1 - Preface About this manual This manual is the introduction of RS16FScontroller and it aims to help users know the operations of the disk array system easily. Information

More information

Dell EqualLogic Red Hat Enterprise Linux 6.2 Boot from SAN

Dell EqualLogic Red Hat Enterprise Linux 6.2 Boot from SAN Dell EqualLogic Red Hat Enterprise Linux 6.2 Boot from SAN A Dell EqualLogic best practices technical white paper Storage Infrastructure and Solutions Engineering Dell Product Group November 2012 2012

More information

1 MAXDATA Modular System Firmware Update

1 MAXDATA Modular System Firmware Update 1 MAXDATA Modular System Firmware Update This document will help you to update the firmware from a MAXDATA Modular System. Modular Systems which was purchased before 1 st April 2009 with Microsoft Windows

More information

Quick Note 038. Upgrade Software options and/or VPN Licenses on a Digi Transport router.

Quick Note 038. Upgrade Software options and/or VPN Licenses on a Digi Transport router. Quick Note 038 Upgrade Software options and/or VPN Licenses on a Digi Transport router. Digi Support August 2013 1 Contents 1 Introduction... 2 1.1 Assumptions... 2 2 Version... 2 3 Configuration... 2

More information

Configuring PROFINET

Configuring PROFINET CHAPTER 9 This chapter describes how to configure the PROFINET feature on the Cisco IE 3000 switch. Understanding PROFINET, page 9-1, page 9-4 Displaying the PROFINET Configuration, page 9-5 Troubleshooting

More information

Servers and two Client with failover

Servers and two Client with failover How to create two VIO Servers and two Client with failover Author : Siddhartha S Sinha Rev : 1.0 Check my website www.sinhass.com for more technical stuffs. Test Scenario: Two VIO servers will have these

More information

Procedure: You can find the problem sheet on Drive D: of the lab PCs. Part 1: Router & Switch

Procedure: You can find the problem sheet on Drive D: of the lab PCs. Part 1: Router & Switch University of Jordan Faculty of Engineering & Technology Computer Engineering Department Computer Networks Laboratory 907528 Lab. 2 Network Devices & Packet Tracer Objectives 1. To become familiar with

More information

Amcrest 960H DVR Quick Start Guide

Amcrest 960H DVR Quick Start Guide Amcrest 960H DVR Quick Start Guide Welcome Thank you for purchasing our Amcrest 960H DVR! This quick start guide will help you become familiar with our DVR in a very short time. Before installation and

More information

Acellus Lab Cart. User s Manual. Version 4B. Acellus Corporation www.acellus.com. Copyright 2010 Acellus Corporation. All Rights Reserved.

Acellus Lab Cart. User s Manual. Version 4B. Acellus Corporation www.acellus.com. Copyright 2010 Acellus Corporation. All Rights Reserved. Acellus Lab Cart User s Manual Version 4B Acellus Corporation www.acellus.com 1 Table of Contents Using Acellus... 3 Acellus Lab Cart and Server... 3 Acellus Laptops... 3 Acellus Updates... 4 Accessing

More information

Upgrading Software Using the Online Installer

Upgrading Software Using the Online Installer Upgrading Software Using the Online Installer Last Updated: December 8, 2009 This chapter provides the procedures for upgrading from a previous software version of the Cisco Integrated Storage System module

More information

Netwatch Installation For Windows

Netwatch Installation For Windows Netwatch Installation For Windows Netwatch is a program designed to monitor a Powerware UPS unit using the ConnectUPS-Web or Bestlink-Web interfaces and MGE UPS unit using the Network Management Card over

More information

Changing the MAC address on a Guardium Appliance

Changing the MAC address on a Guardium Appliance Changing the MAC address on a Guardium Appliance When the InfoSphere Guardium appliance is installed as a physical appliance, the Ethernet adapters are configured and saved on the appliance. An Ethernet

More information

SonicWALL SRA Virtual Appliance Getting Started Guide

SonicWALL SRA Virtual Appliance Getting Started Guide COMPREHENSIVE INTERNET SECURITY SonicWALL Secure Remote Access Appliances SonicWALL SRA Virtual Appliance Getting Started Guide SonicWALL SRA Virtual Appliance5.0 Getting Started Guide This Getting Started

More information

Troubleshooting, Recovery, and Maintenance Guide

Troubleshooting, Recovery, and Maintenance Guide IBM Storwize V7000 Troubleshooting, Recovery, and Maintenance Guide Version 6.1.0 GC27-2291-00 IBM Storwize V7000 Troubleshooting, Recovery, and Maintenance Guide Version 6.1.0 GC27-2291-00 Note Before

More information

RSA Security Analytics. S4 Broker Setup Guide

RSA Security Analytics. S4 Broker Setup Guide RSA Security Analytics S4 Broker Setup Guide Copyright 2010-2013 RSA, the Security Division of EMC. All rights reserved. Trademarks RSA, the RSA Logo and EMC are either registered trademarks or trademarks

More information

HP Virtual Connect Ethernet Cookbook: Single and Multi Enclosure Domain (Stacked) Scenarios

HP Virtual Connect Ethernet Cookbook: Single and Multi Enclosure Domain (Stacked) Scenarios HP Virtual Connect Ethernet Cookbook: Single and Multi Enclosure Domain (Stacked) Scenarios Part number 603028-003 Third edition August 2010 Copyright 2009,2010 Hewlett-Packard Development Company, L.P.

More information

1-Port Wireless USB 2.0 Print Server Model # APSUSB201W. Quick Installation Guide. Ver. 2A

1-Port Wireless USB 2.0 Print Server Model # APSUSB201W. Quick Installation Guide. Ver. 2A 1-Port Wireless USB 2.0 Print Server Model # APSUSB201W Quick Installation Guide Ver. 2A Section 1 Step 1Connect one end of the Ethernet cable to the RJ-45 port of the Print Server and attach the other

More information

QOS 8 High-Speed RAID System Guide

QOS 8 High-Speed RAID System Guide QOS 8 High-Speed RAID System Guide Not for Redistribution 1 Introduction The QOS is a standalone storage array, part of a file- based workflow involving numerous users sharing the same files in real time.

More information

MegaRAID SAS User Guide for Linux

MegaRAID SAS User Guide for Linux Table of Contents RAID Configuration... 1 Storage Manager Installation... 11 Running MegaRAID Storage Manager (MSM)... 11 Running MegaCLI... 11 Special Notes... 15 Technical Support... 15 This guide is

More information

Unified Access Point Administrator's Guide

Unified Access Point Administrator's Guide Unified Access Point Administrator's Guide Product Model: DWL-3600AP DWL-6600AP DWL-8600AP Unified Wired & Wireless Access System Release 2.0 November 2011 Copyright 2011. All rights reserved. November

More information

Type Message Description Probable Cause Suggested Action. Fan in the system is not functioning or room temperature

Type Message Description Probable Cause Suggested Action. Fan in the system is not functioning or room temperature Table of Content Error Messages List... 2 Troubleshooting the Storage System... 3 I can t access the Manager... 3 I forgot the password for logging in to the Manager... 3 The users can t access the shared

More information

File Transfers. Contents

File Transfers. Contents A File Transfers Contents Overview..................................................... A-2................................... A-2 General Switch Software Download Rules..................... A-3 Using

More information

HP StorageWorks 8Gb Simple SAN Connection Kit quick start instructions

HP StorageWorks 8Gb Simple SAN Connection Kit quick start instructions HP StorageWorks 8Gb Simple SAN Connection Kit quick start instructions Congratulations on your purchase of the 8Gb Simple SAN Connection Kit. This guide provides procedures for installing the kit components,

More information

Instructions for Adding a MacOS 10.4.x Server to ASURITE for File Sharing. Installation Section

Instructions for Adding a MacOS 10.4.x Server to ASURITE for File Sharing. Installation Section Instructions for Adding a MacOS 10.4.x Server to ASURITE for File Sharing Installation Section Purpose: We are setting up a server in ASU s specific environment. Power on the Server Insert the CD Hold

More information

1 Download & Installation... 4. 1 Usernames and... Passwords

1 Download & Installation... 4. 1 Usernames and... Passwords Contents I Table of Contents Part I Document Overview 2 Part II Document Details 3 Part III EventSentry Setup 4 1 Download & Installation... 4 Part IV Configuration 4 1 Usernames and... Passwords 5 2 Network...

More information

Sample Configuration Using the ip nat outside source list C

Sample Configuration Using the ip nat outside source list C Sample Configuration Using the ip nat outside source list C Table of Contents Sample Configuration Using the ip nat outside source list Command...1 Introduction...1 Before You Begin...1 Conventions...1

More information

USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6

USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6 KRAMER ELECTRONICS LTD. USER GUIDE Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6 Contents 1 Connecting to the Kramer Device via the Ethernet Port 1 1.1 Connecting the Ethernet Port Directly

More information

High Availability and MetroCluster Configuration Guide For 7-Mode

High Availability and MetroCluster Configuration Guide For 7-Mode Data ONTAP 8.2 High Availability and MetroCluster Configuration Guide For 7-Mode NetApp, Inc. 495 East Java Drive Sunnyvale, CA 94089 U.S. Telephone: +1(408) 822-6000 Fax: +1(408) 822-4501 Support telephone:

More information

AssuredSAN 3000 Series Event Descriptions Reference Guide

AssuredSAN 3000 Series Event Descriptions Reference Guide AssuredSAN 3000 Series Event Descriptions Reference Guide P/N 83-00005973-13-01 Revision A May 2011 Copyright 2011 Dot Hill Systems Corp. All rights reserved. Dot Hill Systems Corp., Dot Hill, the Dot

More information

2. RAID Management. 2-5. RAID migration N5200 allows below RAID migration cases.

2. RAID Management. 2-5. RAID migration N5200 allows below RAID migration cases. Thecus N5200 FAQ Thecus N5200 FAQ...1 1. NAS Management...2 1-1. Map a network drive in Windows XP...2 1-2. Could not map a network drive in Windows XP...2 1-3. Map a network drive in Mac OS X...2 1-4.

More information

CCT vs. CCENT Skill Set Comparison

CCT vs. CCENT Skill Set Comparison Operation of IP Data Networks Recognize the purpose and functions of various network devices such as Routers, Switches, Bridges and Hubs Select the components required to meet a given network specification

More information

Technical Support Bulletin 1

Technical Support Bulletin 1 Technical Support Bulletin 1 Windows 2000 and Windows XP Computer Systems SUBJECT: Troubleshooting Computer Systems Scope February 22, 2006 Troubleshooting Computer System problems on Windows 2000 and

More information

DD160 and DD620 Hardware Overview

DD160 and DD620 Hardware Overview DD160 and DD620 Hardware Overview Data Domain, Inc. 2421 Mission College Boulevard, Santa Clara, CA 95054 866-WE-DDUPE; 408-980-4800 775-0206-0001 Revision A March 21, 2011 Copyright 2011 EMC Corporation.

More information

Deploying Windows Streaming Media Servers NLB Cluster and metasan

Deploying Windows Streaming Media Servers NLB Cluster and metasan Deploying Windows Streaming Media Servers NLB Cluster and metasan Introduction...................................................... 2 Objectives.......................................................

More information

Intel Management Engine BIOS Extension (Intel MEBX) User s Guide

Intel Management Engine BIOS Extension (Intel MEBX) User s Guide Intel Management Engine BIOS Extension (Intel MEBX) User s Guide User s Guide For systems based on Intel B75 Chipset August 2012 Revision 1.0 INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH

More information

istorage Server: High Availability iscsi SAN for Windows Server 2012 Cluster

istorage Server: High Availability iscsi SAN for Windows Server 2012 Cluster istorage Server: High Availability iscsi SAN for Windows Server 2012 Cluster Tuesday, December 26, 2013 KernSafe Technologies, Inc www.kernsafe.com Copyright KernSafe Technologies 2006-2013.All right reserved.

More information

Administering the Network Analysis Module. Cisco IOS Software. Logging In to the NAM with Cisco IOS Software CHAPTER

Administering the Network Analysis Module. Cisco IOS Software. Logging In to the NAM with Cisco IOS Software CHAPTER CHAPTER 4 How you administer the NAM on your Catalyst 6500 series switch or Cisco 7600 series router depends on whether you are using the Cisco IOS software or the Catalyst operating system software. Several

More information

Dell OpenManage Mobile Version 1.4 User s Guide (Android)

Dell OpenManage Mobile Version 1.4 User s Guide (Android) Dell OpenManage Mobile Version 1.4 User s Guide (Android) Notes, cautions, and warnings NOTE: A NOTE indicates important information that helps you make better use of your computer. CAUTION: A CAUTION

More information

PCI-to-SATA RAID Adapter AEC-6890M. User s Manual Version:1.0

PCI-to-SATA RAID Adapter AEC-6890M. User s Manual Version:1.0 PCI-to-SATA RAID Adapter AEC-6890M User s Manual Version:1.0 Copyright 2003 ACARD Technology Corp. Release: August 2003 Copyright and Trademarks The information of the product in this manual is subject

More information

Configure Cisco Unified Customer Voice Portal

Configure Cisco Unified Customer Voice Portal Cisco Unified Customer Voice Portal Configuration, page 1 Configure Gateways, page 1 Transfer Unified CVP Scripts and Media Files, page 2 Unified Customer Voice Portal Licenses, page 2 Configure SNMP,

More information

PRORAE REMOTE HOST CONTROLLER: COMMUNICATION TROUBLESHOOTING GUIDE

PRORAE REMOTE HOST CONTROLLER: COMMUNICATION TROUBLESHOOTING GUIDE PRORAE REMOTE HOST CONTROLLER: COMMUNICATION TROUBLESHOOTING GUIDE INTRODUCTION This technical note provides simple procedures that can be performed in the field to help identify and correct the cause

More information

Modicon M340 Firmware

Modicon M340 Firmware Modicon M340 Firmware Update procedure 04/2009 eng Edition V2.0 www.schneider-electric.com EIO0000000057.01 Purpose Subject of this Document This document explains how to update Modicon M340 PLC firmware

More information

EXAScaler. Product Release Notes. Version 2.0.1. Revision A0

EXAScaler. Product Release Notes. Version 2.0.1. Revision A0 EXAScaler Version 2.0.1 Product Release Notes Revision A0 December 2013 Important Information Information in this document is subject to change without notice and does not represent a commitment on the

More information