1 SECTION 7: page 1 Section 7.1: Voice Alarm Design Guide
2 SECTION 7: page 3 7.1: V O I C E A L A R M D E S I G N G U I D E The following is a guide for designers on VA / PA systems, and their use in conjunction with advanced fire detection systems, incorporating the requirements of BS :1998 It will highlight some of the main difficulties in system design paying particular attention to intelligibility, which is the key differentiator between good and poor design. Contents 1 Background research: why Voice Alarm is the future for Fire Alarm systems 2 The difference between Public Address (PA) and Voice Alarm (VA) 3 BS :1998 Fire detection and alarm systems for buildings 3.1 Section 1 General 3.2 Section 2 Design considerations 3.3 Section 3 Workmanship, installation & commissioning 3.4 Section 4 User responsibilities 3.5 Annexes 4 Current solutions 4.1 Voice sounders 4.2 Central Rack systems 4.3 Distributed amplifiers 4.4 Loop powered micro amplifiers 5 Guideline for future designs 1 Background research: why Voice Alarm is the future for Fire Alarm systems It has often been observed that occupants in the initial moments of a fire, upon smelling smoke or hearing the fire alarm do not react; they deny there is danger or they ignore the situation. This seems especially true in public buildings where occupants do not want to be seen to overreact to a false alarm or to a situation that is already under control. Such avoidance behaviour in a dangerous situation often results in a delayed start to evacuating a building or taking protective action. This statement by Dr Guylène Proulx 1 was further illustrated by research carried out by Brian Piggott of the Fire Research Centre and published by David Canter of Surrey University 2 which showed that in the event of a fire: 13% of people reacted to bells 45% of people reacted to text 75% of people reacted to voice! It was also made clear that in the event of an alarm people generally exit by the entrance they first used and need to be directed to the nearest escape route. A Voice Alarm system can be used to to give people clear information about when to evacuate and what route to take and hence alleviate some the of the problems highlighted above. 2 The difference between Public Address (PA) and Voice Alarm (VA) Many people believe they can simply use their PA system to provide a voice message in the event of an emergency like a fire. Unfortunately PA systems, whilst very good for providing music and messages, are not guaranteed to work when there is an emergency. This is where the British Standard BS :1998 on Voice Alarm comes into use, as it clearly defines the requirements of a true VA system. A true VA system is a HIGHLY SECURE PUBLIC ADDRESS system which has the following features; All internal and external circuits are monitored for faults A minimum battery back up of 24 hours standby and 30 minutes alarm. A monitored secure link to a fire alarm panel A number of pre-recorded emergency messages Incorporates an emergency firemans microphone The use of speech sounders is not considered as a true VA system and the recommendations detailed within annexe E of the standard should be consulted. References 1: Guylène Proulx, Ph.D, Misconceptions about human behaviour in fire emergencies published in Canadian Consulting Engineer, March 1997, pp36, 38. 2: David Cantor, Studies of Human Behaviour in Fire: Emprical results and their implications for education and design. Published by BRE, July 1985
3 SECTION 7: page 4 7.1: V O I C E A L A R M D E S I G N G U I D E 3 BS :1998 Fire detection and alarm systems for buildings There is no substitute for reading the standard, this section only deals with the most obvious or possibly contentious issues facing the designer. Copies of this standard can be obtained from: British Standards Institute (BSI) at We also suggest reference is made to BS :2002. The standard is split into various sections, the following looks at the key points for designers in each section. 3.1 Section 1 General The key part of this section for a new design is the need to exchange information with interested parties, as it is likely that the information gathered here will form the basis of the design. An understanding needs to be gained of what messages are to be played in the event of a fire or other emergencies as well as what the system may be asked to do in addition, ie music and/or paging. This section also provides a full planning schedule as a check list which is well worth following, especially for anyone who is embarking on a design for the first time. The designers check list is as follows : Survey of the site and/or a detailed examination of site drawings including an acoustic assessment Assessment of usage of the building including; Periods of non occupation Areas with high noise levels Personnel including those hard of hearing Actions that take place in the event of a fire Liaison with all manufacturers to ensure compatibility between the fire and voice alarm systems A system specification and requirements for estimation purposes Tendering and quotation Consideration of proposals Consideration of servicing requirements Agreement on proposals and confirmation of Fire plan Agreement on the controls ie microphones etc Detailed system design Ordering Agreement on final specification including any variations Production, pre-delivery acceptance certificate and delivery Installation and testing phase Commissioning System documentation and user training Acceptance by client Handover of system Service agreement
4 SECTION 7: page 5 7.1: V O I C E A L A R M D E S I G N G U I D E It goes on to suggest that for large sites considerations be included for: Understanding the stages of a critical path chart Siting and accommodation of the control equipment On site work not conflicting with other services Temporary physical protection to avoid deterioration of equipment due to damp, dust etc Ensuring final commissioning of the VA system is carried out when all parties can witness the results under various occupation levels it may be necessary to consider partial occupation and soak testing to ensure all parties are ultimately satisfied with the final result 3.2 Section 2 Design consideration Like all the Fire application standards this section is by far the largest and additional training on this section is advised for anyone heavily involved in VA design. Some of the KEY issues the designer should consider are: The Distribution of the speaker circuits Consideration should be given to the degree of monitoring required, particularly for the speaker circuits. In certain circumstances it is recommended that they are interleaved to ensure the voice message is delivered throughout a zone, irrespective of whether one of the two circuits have failed. The Choice and siting of the speakers Loudspeakers should be positioned to achieve the correct sound pressure (db) level and good intelligibility, with an STI (speech transmission index) of 0.5 considered to be acceptable. Speaker selection should not be a simple matter of aesthetics and it is often advisable to carry out an acoustic survey to establish the best solution for a particular application. The Link between the Fire and VA control panels The link between the fire control panel and the Voice alarm control unit needs to be secure, that is monitored for open and short circuits and wired in recognised fire resistant cables to avoid failure, as the VA may be the only means of warning people there is a fire. In complex buildings where activation of the Evacuate and Alert signal can be manually overridden it should be clearly indicated on the control panel which area is receiving which message. Combined use of Fire Sounders with VA system In certain circumstances a site may require VA in public areas whereas sounders can be used in staff only areas. In such cases the operation of the sounders should not affect the intelligibility of the VA system The sounder tone should be the same as the attention drawing tone used by the VA system The procedures for operating such systems should be simple to avoid confusion in the event of an emergency If it is necessary to silence the alarm sounders to enable a voice message to be broadcast then restarting of the sounders should be automatic. There should not be a silent period exceeding 10 seconds between broadcast and sounders
5 SECTION 7: page 6 7.1: V O I C E A L A R M D E S I G N G U I D E 3.3 Section 3 Workmanship, installation & commissioning The installation requirements follow closely the recommendations within BS5839-1:2002. However the crucial issue here is the commissioning stage especially checking of the sound pressure levels (db s) and intelligibility. Specialist equipment may be required to check the audibility and intelligibility. However the standard suggests that to check the sound pressure level, a standard sound level meter set to A weighting and slow response will give an approximate reading, as long as the speech is slow in delivery with virtually no gaps. Intelligibility is a little more difficult and whilst a minimum STI of 0.5 is quoted it may be difficult or near impossible to measure under all circumstances. The standard suggests that a subjective assessment of intelligibility may be sufficient as long as all interested parties agree. In the case of dispute it is recommended that an appropriate method of measurement detailed within BS EN may be called into play. 3.4 Section 4 User responsibilities The major issue for the user, besides ensuring the equipment is not showing any faults and is healthy at all times, is training of the operators. This may be an ongoing requirement as personnel change and complex procedures for phased evacuation, which require manual intervention, may be in place. 3.5 Annexes The annexes A to E provide a designer with some useful data in respect of loudspeaker capabilities, typical noise levels in different buildings, a battery standby calculator, a model certificate and a guideline or recommendations for the use of voice sounders 4 Current solutions There are three main methods of providing voice messages, these consist of; Stand alone voice sounders Central Rack amplifier systems Distributed amplifier systems All these types have possible use dependent on the type and size of building where they are being installed. 4.1 Voice enhanced sounders Although these devices can not be considered a true VA they do offer voice messages, with each device containing a memory chip that has a number of pre-recorded standard messages, operated directly from the fire alarm control panel. It is important that the control panel does have a synchronisation capability so all the independent recorded messages are delivered at the same time. This is particularly important when you have two or more alarm zones where different messages are required, i.e. an Evacuate and Alert message, as synchronisation and intelligibility may be affected. Furthermore additional cables may be required to switch from one message to another. It is therefore, suggested that these devices are generally used for the smaller properties where there is a one out - all out evacuation required and no messaging or background music facility is needed.
6 SECTION 7: page 7 7.1: V O I C E A L A R M D E S I G N G U I D E 4.2 Central Rack systems Central Rack systems consist of a rack or racks of amplifiers that control all the speaker circuits, which are radially wired as shown. This rack may also contain facilities for zone selection, music input, emergency and general paging announcements. The issues with this type of set up are:- To ensure the link between the fire control panel and the rack is fully protected and monitored The correct cables sizes, to allow for volt drop, are provided for the speaker circuits particularly if they extend across many floors The battery standby capacity has been properly calculated and there is some contingency to extend in the future 4.3 Distributed amplifiers Distributed amplifiers (DAU) are the latest innovation allowing the speakers to be connected to local amplifiers, often on the fire system loop communication cables, as shown. The benefits of this approach are:- There is a lot less cable needed for the speaker circuits The cables will often be smaller in size and therefore cost less The system can easily be extended at minimal cost as extra DAU s can be connected on the fire communication loops The central control unit (ACU) for the voice system is much smaller as it contains no amplifiers DAU s are easier to accommodate than central racks Distributed Amplifiers The issues or options with this approach are:- There is a requirement to provide additional audio circuits between all the DAU s, shown on the diagram in a dashed line. These will be needed for synchronised voice messages and to provide an emergency firemans speech facility. A choice is available whereby on some medium size buildings the DAU s can obtain their power direct from the fire communication loop cable Gent s Compact Voice system combines the fire panel and ACU in a single enclosure. 5 Guideline for future designs Finally, for anyone setting out to provide a VA system we would suggest the following guideline:- Obtain and read a copy of BS :1998 Consult all interested parties and agree the Fire Plan and other uses for the system Agree Evacuation/Paging zones and the messages you require Involve someone who can assess the acoustics and calculate the loudspeaker types and requirements Decide which system to use Check the intelligibility after completion and obtain a certificate Ensure the End User is trained on its use and is aware of their responsibilities
7 SECTION 7: page 8 7.1: V O I C E A L A R M D E S I G N G U I D E Notes
8 SECTION 7: page 9 Section 7.2: Vigilon Compact Voice Alarm System
9 SECTION 7: page : V I G I LO N C O M PA C T V O I C E A L A R M 10 reasons to specify Vigilon Compact Voice 1 An industry first Combined FDA and VA/PA providing the highest levels of system integrity, with proven Vigilon technology including built-in isolators in all devices Safe evacuation for everyone in the building High quality intelligible voice messages reduce confusion and panic 3 Savings on installation costs compared with conventional voice alarm systems Loop powered DAUs do not require secondary mains or battery supplies and reduce length of speaker circuits. Reliable system compatibility Proven Vigilon system technology with speakers individually monitored and designed to meet the requirements of BS Highly flexible software allows on-site configuration Additional DAUs can be easily accommodated with flexible message changes selected from the standard Audio Pack. Reduction in on-going costs Innovative 'off the shelf' technology requiring only one person testing the system, which can also be maintained at standard competitive rates. 7 Free extras A fire alarm system offering VA/PA benefits or vice versa. True analogue time comparison sensors for false alarm reduction The very latest S-Quad sensors are fully compatible with Vigilon Compact Voice for the ultimate system specification. 9 The reassurance of GENT support Designed and manufactured by the UK s life safety specialists with unrivalled expertise and technical support capabilities. Fully compliant with relevant industry standards GENT are LPCB approved for both systems and products and Vigilon Compact Voice is designed to comply with BS/EN standards.
10 SECTION 7: page : V I G I LO N C O M PA C T V O I C E A L A R M S Y S T E M System Architecture MCP SENSOR ZONE 2 INTERFACE UNIT S-QUAD S-CUBED SOUNDER STROBE DAU ZONE 3 ZONE 1 DAU DAU SOUNDERS Should be separated acoustically from speaker zones LIVE AUDIO CHANNEL SINGLE ZONE LOOP POWERED DAU MCP ZONE 4 DAU MCP PAGING MUSIC SOURCE CONTROL PANEL OPTICAL HEAT SENSOR MCP
11 SECTION 7: page : V I G I LO N C O M PA C T V O I C E A L A R M S Y S T E M Vigilon Compact Voice System An industry first Vigilon Compact Voice is the new integrated fire detection, voice alarm and public address system from Gent an innovation that combines the analogue addressable fire detection and alarm functionality of Gent s proven Vigilon Compact system with the very latest voice alarm and public address (VA/PA) technology. The Vigilon Compact fire and voice alarm control panel drives one or two loops of fire detection and alarm devices and a number of loop powered distributed amplifier units (DAUs). A separate fault tolerant audio loop carries the live announcements for emergency situations and public address. The control panel has a built in emergency microphone and is able to accept inputs from a PA paging microphone and a background music source, e.g. CD player. Life Safety First The Vigilon Compact Voice system delivers clear, intelligible voice alarm meassages. Vigilon Compact Analogue Addressable fire detection and alarm technology ensures reliable and constant life safety protection for both people and property. Research* shows only 13% of people react to bells, whilst 70% react to a voice message. Orderly phased evacuation in the event of a fire or other hazards through loudspeaker messages in relevant zones and live emergency messages relayed via the panel s built in microphone. Increased operational efficiency Routine paging functionality provides an effective public address system. An on board emergency microphone is fitted into the control panel. Improved building comfort Enhances environments with CD quality background music around the building as required. System integrity Control and indicating equipment designed to EN54-2 & 4 and BS All devices powered directly from the same two wires, including the DAUs. Only one panel required to control both fire and voice. Smallest DAU available in the marketplace. Delivers highest levels of system integrity and clear, high quality sound. Fire and VA/PA System...at no extra cost! Paging capability. Plays music in selected areas. Provides emergency and non-emergency messages. Operates during mains failure. Live message facility, routine paging announcements and advertising background music enhances all environments. * Sources: Brian Piggot (The Fire Research Station) and David Canter (Surrey University).
12 SECTION 7: page : V I G I LO N C O M PA C T V O I C E A L A R M S Y S T E M Vigilon Compact Voice System Features DISPLAY KEYBOARD WITH LED/LCD INDICATORS 8 LINE / 40 CHARACTER LCD DISPLAY LED ZONAL DISPLAY secret until lit FUNCTION KEYS PRE-RECORDED MESSAGES SELECTABLE FROM THE AUDIO PACK BUILT IN VU METER 7 AUDIO CONTROL PANEL INTEGRAL EMERGENCY MICROPHONE WITH EMERGENCY AND AUXILIARY CONTROLS Each loop powered DAU can drive up to ten loudspeakers wired as A + B circuits 5 per circuit Two detection loops with up to 10 DAUs driving a maximum of 100 speakers DAUs can be zoned in software and isolators in every DAU protect against short circuits Speakers are individually monitored, including the wiring Volume level can be set via commissioning tool or by infra-red remote control key fob Integral power supply and battery backup Comprehensive fault management Built-in history log stores the last 200 events, which can be accessed via the integral keyboard and printed via an external printer External audio input facilities for PA and background music Configurable relay output at the DAU
13 SECTION 7: page : V I G I LO N C O M PA C T V O I C E A L A R M S Y S T E M Vigilon Compact Voice Panel A one to two loop panel accommodating up to 200 devices per loop (see Vigilon section for device details). Each loop can drive up to 5 DAUs and 5 voice evacuation zones. There is a built in emergency microphone for live emergency speech, which can be directed to any or multiple voice evacuation zones. Vigilon Compact Voice Panel TECHNICAL SPECIFICATION Max No of Loops 2 Loop Capacity 200 Ingress Protection IP31 Approx Weight 28 Kg including batteries Operating Temperature 0 o C to +45 o C Relevant Standards EN54: 2&4 BS Batteries 2 x 12Ah Battery Standby 24 hrs + 30 mins alarm Supply Voltage 216V 253V 50-Hz Power Consumption 75W Cable Entry Top and rear knock outs Auxiliary Contacts Programmable to activate on fire, fault or disablement (1 x SPCO 1 x DPCO) Common Fire Contacts Voltage free 1 x SPCO Sounder Circuits 2 each Monitored Input 1 input which is programmable to perform a logical action via a command build Colour Egg shell white (Dupont 7EPZ1172S) Back box Graphite grey (RAL 7024) Communication Ports 2 x RS485 1 x RS232 selectable functions The panel has an 8-line by 40 character LCD display showing detailed fire and fault information, and 32 fire detection zonal LEDs. Dimensions (mm) 547 ORDER CODES Compact Voice Panel COMPACT-VA
14 SECTION 7: page : V I G I LO N C O M PA C T V O I C E A L A R M S Y S T E M Loop Powered DAU Each DAU can drive up to Ohm high efficiency speakers on two circuits (5 speakers per circuit). The DAUs are wired in a fault tolerant ring configuration, and each DAU has an isolator to protect against short circuits on the analogue audio loop. Local volume of voice alarm, PA and background music can be adjusted via an IR remote control. Loop Powered DAU TECHNICAL SPECIFICATION Weight Mounting 2Kg Wall Amplifier Load 2 x 12.8 Ohm 10V RMS Output (class D) Microphone Input Sensitivity Aux Input Sensitivity Signal to Noise Ratio Frequency Response Total Harmonic Distortion Power Supply Auxiliary Relay LED Indication 5mV-22mV/10k Ohm (includes AGC) 775mV/600 Ohm (Balanced) >80dB 100Hz to 18kHz ± 3dB 1KHz Loop powered Two configurable voltage free contacts reated 24Vdc Audio status Audio I/P present/power Circuit A Fault wiring or AMP fault Circuit B fault wiring or AMP fault Dimensions (mm) ORDER CODES Loop Powered DAU COMPACT-DAU
15 SECTION 7: page : V I G I LO N C O M PA C T V O I C E A L A R M S Y S T E M Loudspeakers Bi-directional Wall Speaker The system can support up to Ohm low impedance loudspeakers Wall Loudspeaker Public Address Paging Microphone Ceiling Loudspeaker TECHNICAL SPECIFICATION LOUDSPEAKERS Description Wall Loudspeakers Ceiling Loudspeakers Bi-directional Wall Speakers Impedance 64 Ohms 64 Ohms 64 Ohms Material Steel Steel including Fire Dome Steel Sensitivity Effective Frequency Response 1m (1kHz Tone) (1kHz Tone) (1kHz Tone) 85Hz 18.5 khz 85Hz 18.5kHz 125Hz 12kHz Directivity Q factor, 1k Hz Colour White White White Mounting Surface Flush Surface Dimensions (WxHxD) mm 190 x 190 x x 110 dia 210 x 130 x 98 TECHNICAL SPECIFICATION PUBLIC ADDRESS PAGING MICROPHONE Console Stainless Steel Mounting Surface Desk Mount Microphone Style Gooseneck Polar Response Cardioid Frequency Response 150Hz to 12kHz Power Supply Powered from control panel Zone Control Software programmable ORDER CODES Wall Loudspeakers Ceiling Loudspeakers COMPACT CAB COMPACT RCS Bi-directional Wall Speakers COMPACT BDCAB Public Address Paging Microphone DPM-102
16 SECTION 7: page : V I G I LO N C O M PA C T V O I C E A L A R M Audio Pack Audio Pack messages and pre-tones. The message card fitted in all factory supplied Vigilon Compact Voice alarm panels and DAUs contains an Audio Pack of messages and tones. During commissioning it is possible to re-configure this by selecting alternative centralised and distributed messages and pre tones for Alert, Evacuate, Bomb and Auxiliary 1, 2 and 3 controls. NUMBER TYPE OF MESSAGE VOICE MESSAGE 1 DAU Test Male The voice alarm volumes are being adjusted there is no need to take any action Alert (default Emergency 1) Evacuate (default Emergency 2) Bomb (default Emergency 3) Alert (alternative) Evacuate (alternative) Female Male Female Female Male 7 Gas Carbon Monoxide Male Gas Fixed Extinguishant Fire alarm test end (default Auxiliary 1) Fire alarm test end (default Auxiliary 2) Male Female Your attention please, the fire alarm has been activated in another area, please remain where you are and await further instructions. Attention please, attention please, this is an emergency. Please leave the building by the nearest available exit. Do not use the lifts or escalators. May I have your attention please, an incident has been reported in the area. As a precaution, please move away from the windows. I repeat, please move away from all windows, further information will follow shortly. May I have your attention please, may I have your attention please, an incident has been reported in the building. While this report is being investigated, please remain at your workplace. Ladies and gentlemen, due to unforeseen circumstances we are required to evacuate the building. Please leave the building immediately by the nearest available exit. May I have your attention please, may I have your attention please, excessive carbon monoxide levels have been detected, please leave the area immediately by the nearest available exit. May I have your attention please, may I have your attention please, extinguishant gas release imminent, please evacuate the area immediately by the nearest available exit. Attention please, attention please, this is a test of the fire and voice alarm system, there is no need to take any action. Female The test of the fire and voice alarm system has now been completed (default Auxiliary 2) 11 Coded message Female Would Mr. Sands please report to reception. 12 Class change Female Class change Gent Limited (advertisement) Stand down (default Auxiliary 3) Female Female 15 Special tone 1 Beep beep beep (950Hz 80ms beep every 420ms) 16 Special tone 2 Beep beep beep (950Hz 50ms beep every 80ms) 17 Factory test Frequency sweep (300Hz to 10KHz in 3s) 18 Nursery rhyme 1 Tune Boys and Girls Come Out to Play 19 Nursery rhyme 2 Tune Twinkle Twinkle Little Star Ladies and gentlemen this speech message is produced by Gent Limited s Vigilon Compact Voice alarm system. This product integrates voice alarm functions into an analogue fire alarm system ideal for small to medium sized buildings. May I have your attention please, the cause of the alarm has been investigated and the system reset. There is no cause for concern. Thank you. ATTENTION TONE Number Description of tone Number Description of tone 1 Nee Naw x 8 6 Pulse 2 Two tone (ding dong) 7 Continuous 3 Four tones ascending 8 Dong 4 Four tones descending 9 Chopin 5 Bell 10 Sleigh Bells
17 SECTION 7: page 19 Section 7.3: Vigilon Voice Alarm System
18 SECTION 7: page : V I G I LO N V O I C E A L A R M S Y S T E M 10 Reasons to specify Vigilon Voice 1 Safe evacuation confusion and panic. High quality intelligible voice messages reduce State of the art technology High quality audio with full digital signal processing, continuous audio path surveillance and DVA message monitoring Save on space Fully featured wall mounted control panel, easier to accommodate than conventional rack systems. Simple configuration and upgrades All functions software configurable with no hardware links etc to set. Configuration can be readily archived and restored. Functionality upgrades involve only software not hardware. Full compliance with relevant standards Complies fully with BS , which is widely called for in project specifications. Ideal for large Multi-storey premises System can be networked, with a central Audio Control Unit (ACU) controlling up to 30 Distributed Amplifier Units (DAU). System reliability The network is tolerant to open or short circuit faults between any two units on data or audio busses, automatically recovering and pinpointing the location of the fault. Even if all the processors in the system fail, an All-Call announcement is still possible from the ACU Emergency Microphone. Site wide audio synchronisation 3 audio channels plus data, allows simultaneous distribution of Alert and Evacuation messages to allow site wide audio synchronisation in addition to Emergency Microphone audio. When no emergency audio is present these channels may support routine paging or background music functions. 9 No data degradation Data is re-clocked at each DAU to ensure there is no data degradation as the size of the system increases. Easy to maintain Detailed full system fault status can be viewed at the central ACU, meaning that remote units do not need to be inspected to diagnose the exact fault.
19 SECTION 7: page : V I G I LO N V O I C E A L A R M S Y S T E M System Architecture Slave ACU A B MIC Audio Highway 3 x 2 x 1mm 2 A/B A/B A/B 4x A/B Speaker zones Additional Emergency Microphone 16A 230vac supply Data Highway 1 x 2 x 1mm 2 EVAC ALERT MIC DATA DAU Local Inputs Paging Microphones MIC Master ACU EVAC ALERT MIC DATA 16A 230vac supply A B A/B A/B A/B 4x A/B Speaker zones Music Source 16A 230vac supply EVAC ALERT MIC DATA DAU Local Inputs 16A 230vac supply Fire Detecton Loop Vigilon Fire Panel S-Quad MCP
20 SECTION 7: page : V I G I LO N V O I C E A L A R M S Y S T E M System Overview Vigilon Voice is a voice alarm system, which supports the needs of large buildings and complex sites. The system enables a number of Distributed Amplifier Units (DAU s), to be controlled by Audio Control Units (ACU s). A Master ACU allows additional Slave ACU s or microphone units to be supported. This Slave acts as a second VA control panel and mimics the controls of the Master. No keypad or LCD for programming is provided at the Slave The Master ACU can be supplied as either a blank version or complete with a user interface and integral emergency microphone. A Master ACU is always required when more than one DAU is to be used on the same system. The ACU enables paging announcements to be made to the distributed systems. An interface is provided to allow inputs from the Vigilon control panel(s) to control Digital Voice Announcements (DVA s) from the distributed systems. Control Network Operation The control network acts as a transparent transmission medium for the control protocol to be transmitted from the ACU to the DAU s. The network is configured as a loop and is tolerant to open or short circuit cable faults between nodes of the loop. This is achieved by the network normally operating in a preferred transmission direction, should a fault be detected, the originating node shall effectively transmit in both directions around the ring. Receiving DAU s are able to detect the new data direction. Audio Distribution Baseband Audio will require one copper pair per channel. Three audio channels are supported as a minimum to enable simultaneous Alert, Evacuate and emergency microphone audio to be broadcast. In non-emergency conditions the audio channels may be used for background music and routine paging functions. The audio loops are fault-tolerant. As well as distributing the audio, it is required that a master microphone, Press-to-talk, signal is also conveyed over the audio link. This is to fulfill the BS requirement that an All-Call Fireman s Microphone operation is supported even if control processors fail. It is possible for multiple ACU microphones to contend for a single audio channel for emergency microphone announcements. A simple global priority is implemented between microphones for granting access.
21 SECTION 7: page : V I G I LO N V O I C E A L A R M S Y S T E M Master Audio Control Unit The Master ACU takes the form of a wall-mounted box fulfilling the primary function of a Voice Alarm Control Panel. The ACU features a keypad and LCD display for configuration and fault reporting, and can be supplied either blank, with no further control functions, or with an integral emergency microphone and a number of configurable front panel buttons for zone selection, and 8 push button selectors for DVA broadcasts. The ACU is able to interface with the Vigilon fire alarm system to facilitate centralised control. It is possible to connect a PC via an RS232 interface for programming of the ACU itself, or any of the attached satellite DAU s. The ACU will automatically display the status of all connected DAU s by means of the standard Fault LED/ Sounder arrangement and with a cycling display on a local (2x40) LCD. If the blank version of the Master ACU is supplied, in order to provide the same functionality, an additional Desk Console or wall mounted Emergency microphone can be provided in place of the on-board Keypad. ORDER CODES ACU blank with network VA-1311 ACU with 20 way keyboard and network VA-1312 ACU Slave with 20 way keyboard VA Way Expansion Keyboard VA Way Desk Console and Emergency Microphone VA-1315 Master Audio Control Unit TECHNICAL SPECIFICATION Capacity 30 DAUs Messages 2 66 second and 2 50 second digital messages Approx Weight (Inc batteries) 35Kg Operating Temperature -5 o C to 50 o C Relevant Standard BS Batteries 18 Ah Valve Regulated SLA Battery Standby 24h + 0.5h alarm Supply Voltage 230V +10%, -6% rms 50Hz AC Power Consumption 2A at 230V ac 600VA Dimension (mm) 700h x 510w x 156d Microphone Inputs and Control panels The ACU allows up to 4 microphone consoles to be supported with configurable buttons for paging or DVA messages. The microphone consoles buttons may be implemented in a number of ways: 1 Modular Microphone panels on the front panel of the ACU. 2 Custom Mic Boards to enable customer specific fire Microphone panels to be constructed. 3 Standard DMS Microphones for simple paging functions. Additional Audio inputs In addition to the four microphone-capable audio inputs, an additional 4 balanced audio inputs are provided. These may be used for background music and similar input sources. The ACU supports 2 x 66 second emergency messages and 2 x 50 second auxiliary messages. Audio Outputs The ACU provides 4 analogue outputs that feed busses on the analogue network. Three channels will be used for the network audio, #1 Emergency Microphone; #2 Evacuate Message; #3 Alert Message.
22 SECTION 7: page : V I G I LO N V O I C E A L A R M S Y S T E M Distributed Amplifier Unit The Vigilon Voice distributed amplifier unit (DAU) is a selfcontained, wall mounted voice alarm system. The unit contains all audio processing, amplification and battery back up elements needed to provide a fully BS compliant system. The DAU comprises: TECHNICAL SPECIFICATION Audio Amplification Emergency microphone interfaces Serial Communications Messages 200W DAU 4 50W amplifiers which may be paralleled to achieve 2x100W 400W DAU 400W DAU 4 100W amplifiers which may be paralleled to achieve 2x200W 2 sets of monitored PTT and Speak Now interfaces to support emergency microphone operation on inputs 1 and 2 are provided 1 x RS232 and 1 x RS485 2 x 66s and 2 x 50s messages Approx Weight (Inc batteries) 51Kg 70Kg Operating Temperature -5 o C to 50 o C -5 o C to 50 o C Relevant Standard BS Batteries 24 Ah valve regulated SLA 38 Ah valve regulated SLA Battery Standby Supply Voltage 24h +0.5h alarm 230V +10, -6% rms 50Hz AC Power Consumption 600VA 800VA Dimensions (mm) 700h x 510w x 156d 790h x 580w x 204d Zonal Power Amplification Surveillance Routing Power Supply and Battery Charger Control Interfaces Fault Display User Interface Network Interface Vigilon Loop Interface Audio Inputs General purpose inputs four inputs are provided. The first two inputs maybe used as Fire Microphone inputs. The general-purpose inputs feature a serial interface for connection of Zoned Paging and Fire microphones. Two background music inputs are provided. Digital Messages Two 66 second emergency messages and two 50 second Auxiliary Messages are provided. Audio Monitor Input A connection is provided for an audio monitor bus from the amplifier system. This allows for audio monitoring of selected amplifier outputs under the control of the front panel. ORDER CODES 200W DAU 400W DAU VA-1321 VA-1322
23 SECTION 7: page : V I G I LO N V O I C E A L A R M S Y S T E M Ceiling Loudspeakers This family of ceiling loudspeakers has been carefully designed to satisfy the most critical eye. The units are stylish yet unobtrusive and are supplied with a firedome. The units are made from a pressed steel epoxy coated chassis incorporating a twin cone driver, which has a wider frequency range than the standard single cone alternative, making this range more suitable for use in applications where background music is a primary requirement. Ease of installation is a key feature of these units, incorporating a user-friendly spring release action providing quick and easy access to transformer tappings once installed ORDER CODES 5 6W Round Metal DC Ceiling Loudspeaker 6 6W Round Metal DC Ceiling Loudspeaker 20W Coaxial Round Metal DC Ceiling Loudspeaker 5 10W Coaxial Round Metal DC Ceiling Loudspeaker 6 10W Coaxial Round Metal DC Ceiling Loudspeaker Ceiling Loudspeakers TECHNICAL SPECIFICATION 5 6W Round Loudspeaker 6 6W Round Loudspeaker 20W Coaxial Loudspeaker Rated power, watts Transformer tappings 100 volt line, Watts Transformer Impedance, Ohms 6/ 3/ 1.5/ 0.75/ / 3/ 1.5/ 0.75/ / 10/ 5/ k/ 3.33k/ 6.66k/ 13.3k/ 39.9k 1.67k/ 3.33k/ 6.66k/ 13.3k/ 39.9k 0.5K/ 1k/ 2k/ 4k 70.7 volt line, Watts 3/ 1.5/ 0.75/ 0.375/ / 1.5/ 0.75/ 0.375/ / 5/ 2.5/ 1.25 Driver impedance, Ohms Effective frequency range, Hz 1m, 1 watt, db, Test Signal Bandwidth 100Hz-10 khz Full power Octave bandwidth, db Acoustic Power (db- PWL@1 watt) 1KHz/2KHz, db , /93 88/90 88/89 Dispersion at 1KHz/2KHz, 180/ / /90 Directivity Q factor, 1KHz/2KHz 1.9/ / /8.6 Dimensions Diameter, mm Net weight, Kg Colour / Finish White RAL9016 White RAL9016 White RAL9016 Material Steel Steel Steel Mounting Torsion Springs Torsion Spring Torsion Springs Coaxial Range The Coaxial range of ceiling loudspeakers employs a two-way speaker system comprising a bass mid-range driver and separate tweeter. The bass response has been extended to give depth and warmth to both music and vocals. This range of Coaxial ceiling loudspeakers has all the aesthetic and installation advantages of our standard ceiling loudspeakers, with the addition of extended bass and top end performance. These units are ideally suited for applications that require a superior high quality performance such as shops, restaurants, hotels, pubs etc.
24 SECTION 7: page : V I G I LO N V O I C E A L A R M S Y S T E M Cabinet Loudspeakers Our range of plastic moulded cabinet loudspeakers is both stylish and elegant, and offers a cost effective alternative to metal cabinets. TECHNICAL SPECIFICATION Cabinet Speaker Vandal-proof Cabinet Speaker Rated power, watts 6 6 Transformer tappings 100 volt line, Watts 6/ 3/ 1.5/ 0.75/ /3 /1.5 /0.75 Transformer Impedance, Ohms 1.67k/ 3.33k/ 6.66k/ 13.3k/ 39.9k 1.67K /3.33K /6.66K /13.3K 70.7 volt line, Watts 3/ 1.5/ 0.75/ 0.375/ /1.5 /0.75 /0.375 Driver impedance, Ohms 8 8 Effective frequency range, Hz ,000 1m, 1 watt, db, Test Signal Bandwidth 100Hz-10 khz Full power Octave bandwidth, db Acoustic Power (db-pwl@1 watt) 1KHz/2KHz, db /95 Dispersion at 1KHz/2KHz, 160/ Directivity Q factor, 1KHz/2KHz 3.6/ Dimensions Diameter, mm 330 x 240 x x 190 x 75 Net weight, Kg Colour / Finish White White, RAL9010 Material Steel mesh ABS moulding with UV inhibitors Mounting Keyhole and/or screws Screw Steel Moulded Cabinet Speaker This 6 watt unit contains dual cone loudspeakers offering a wide frequency range suitable for both high quality speech and music application. This model is also available as a 10 watt co-axial unit and both versions incorporate ceramic terminal blocks and thermal fuses for compliance with BS 5839 Pt 8. Our range of vandal-proof metal cabinet loudspeakers is constructed of high-grade steel, epoxy coated and can be installed on solid ceilings or walls. Although our standard finish is White, RAL9016, alternative finishes are available dependent upon your requirement. ORDER CODES 6W Moulded Cabinet Speaker Vandal-proof 6W Metal Cabinet Speaker Flush Mounted Vandal-proof 6W Metal Cabinet Speaker Bi-directional Vandal-proof 6W Metal Cabinet Speaker DC DC DC DC
25 SECTION 7: page : V I G I LO N V O I C E A L A R M S Y S T E M Weatherproof Speakers Weatherproof Plastic Horns This range of lightweight plastic weatherproof re-entrant horns has been designed for high quality sound re-enforcement. Offering clarity of speech and high efficiency these horns are suitable for communications or signal warnings. Resistant to salt-laden air and non-corrosive, they are suitable for use indoors and out. They are ideal for marine and industrial applications as they are unaffected by most chemicals. Weatherproof Sound Projectors This range of weatherproof Sound Projectors offers a combination of style and performance. Manufactured from an ABS moulded compound with in-built UVL (ultra violet light) protection. The drive unit is a high quality, dual polypropylene cone. Both units are supplied in the same stylish and compact enclosure, ideally suited for both speech and music reproduction. These units have the added advantage of being fully weatherproof and are ideal for use on railways, in car parks, shopping centres, sports grounds. Weatherproof Plastic Horns TECHNICAL SPECIFICATIONS 10W Weatherproof Horn 20W Weatherproof Horn 10W Weatherproof Projector 20W Weatherproof Projector Rated power, Watts Transformer tappings 100 volt line, Watts Transformer Impedance, Ohms 10 /5 /2.5 / / 10 /5 /2.5 10/ 5/ 2.5/ / 10/ 5/ 2.5 1K /2K /4K /8K 500/ 1K /2K /4K 1k/ 2k/ 4k/ 8k 0.5k/ 1k/ 2k/ 4k c 70.7 volt line, Watts 5 /2.5 /1.25 / / 5 /2.5 /1.25 5/ 2.5/ 1.25/ / 5/ 2.5/ 1.25 Driver impedance, Ohms Effective frequency range, Hz S.P.L.,@ 1m, 1watt, db S.P.L.,@Full power/ 1m, db Dispersion at 1,000 Hz, Degrees Directivity Q factor, 1k Hz Dimensions front and depth, mm 20 or 8 20 or , , , , f139 x 200 F203 x 254 f138 x 200 f138 x 200 Net weight, Kg Colour / Finish Cold grey Cold grey White White Material ABS plastic housing ABS plastic housing Mounting Stainless Steel U bracket & hardware Stainless Steel U bracket & hardware Plastic & Stainless steel hardware Aluminium U bracket Plastic & Stainless steel hardware Aluminium U bracket ORDER CODES 10W Weatherproof Plastic Horn DC 20W Weatherproof Plastic Horn DC 10W Weatherproof Plastic Projector 20W Weatherproof Plastic Projector DC DC
26 SECTION 7: page : V I G I LO N V O I C E A L A R M S Y S T E M Loudspeakers TECHNICAL SPECIFICATION Spherical Pendant Loudspeaker 20W Column Loudspeaker 40W Column Loudspeaker 80W Column Loudspeaker Rated power, Watts Transformer tappings 100 volt line, Watts Transformer Impedance, Ohms 20/ 10/ 5/ /10/5/2.5 40/ 20/ 10/ 5 80/40/20/10 500/ 1k/ 2k/ 4k 500/1k/2k/4k 250/ 500/ 1k/ 2k 125/250/500/1k 70.7 volt line, Watts 10/ 5/ 2.5/ / 5/ 2.5/ /10/5/2.5 40/20/10/5 Driver impedance, Ohms Effective frequency range, Hz 1m, 1 watt, db, Test Signal Bandwidth 100Hz- 10KHz Full power, Octave Bandwidth, db Acoustic Power (db PWL@1 watt) 1 k/2khz, db Dispersion at 1KHz/ 2KHz, Degrees Directivity Q factor, 1KHz/2KHz Dimensions, Diameter, mm , /90 85/89 97/99 92/94 140/160(Vertical); 360/360(Horizontal) 180/140(Horizontal); 70/120(Vertical) 170/140(Horizontal); 60/55(Vertical) 180/140(Horizontal); 70/45(Verticall) 4.3/ / / / x 98 x x 98 x x 98 x 90 Approx. Weight, Kg Colour / Finish White White RAL 9016 White RAL 9016 White RAL 9016 Material ABS moulding with UV inhibitors Spherical Pendant Loudspeaker & Column Loudspeakers Aluminium Aluminum Aluminium Mounting Pendant hung L Type Steel Bracket L type Steel bracket L type steel bracket Ingress Protection IP 55 Spherical Pendant Loudspeaker This modern styled spherical loudspeaker is a true omnidirectional device. It provides coverage angles of 360 degrees horizontally and 140~160 degrees vertically giving an even dispersion over the audio spectrum. The smooth frequency response, excellent dispersion and carefully controlled performance means that they are ideally suited for covering large open spaces such as warehouses, open plan retail complexes, concourses and factories, as well as being suitable for both speech and background music. The DC is supplied with a metal braided cable strong enough to carry ten times its own weight. Metal Column Loudspeaker The weather resistant metal column loudspeaker offers a combination of elegant styling, robust construction and high performance. The enclosure is tuned to give a wide frequency range not normally associated with column loudspeakers and as such produces high quality music and speech reproduction. Ideally suited for use in airports, churches, factories, sports and conference centres. ORDER CODES Spherical Pendant Loudspeaker DC 20W Metal Column Loudspeaker DC 40W Metal Column Loudspeaker DC 80W Metal Column Loudspeaker DC 7
27 SECTION 7: page : V I G I LO N V O I C E A L A R M S Y S T E M Specialist loudspeakers Intellivox 4C Loudspeaker Array The Intellivox-4c is a fully integrated digitally controlled loudspeaker array and has been serving a wide variety of applications since its introduction in It has proven to be a versatile and effective solution for vocal reinforcement within reverberant venues, offering excellent speech intelligibility even in demanding acoustical conditions. A single Intellivox-4c is capable of covering an area of up to 65m whilst maintaining an even sound pressure level. The seventeen, custom designed, 4 loudspeakers are driven by a sixteen channel class-d amplifier. The loudspeakers themselves are arranged in accordance with our patented algorithm. The increased lower frequency control offered by the array makes the Intellivox-4c suitable for easy and unobtrusive implementation in highly reverberant and architecturally sensitive environments. The Intellivox units can be controlled using our proprietary WinControl software that offers user friendly control of the beam steering parameters, audio processing and surveillance features. TECHNICAL SPECIFICATION Intellivox 1c Intellivox 4c Frequency Range k Hz (+/- 3dB) k Hz (+/- 3dB) Max SPL Continuous Peak Coverage 92 db A-weighted pink noise at 10m 96 db at 10m 91 db A-weighted pink noise at 30m Horizontal (Fixed) 150deg 150 deg Vertical (adjustable) 15 to 40 deg 6 to 14 deg Aiming Angle -16 to 14 deg -16 to 14 deg Focus Distance 2 to 40m 5 to 100m Typical Throw (may be increased with marginal losses) Input Intellivox 1B Loudspeaker Array The Intellivox-1b is the smallest member of the Intellivox DDC range. Despite its modest dimensions, the Intellivox-1b still offers remarkably tight directivity control and is capable of covering an area of up to 15m whilst maintaining an even sound pressure over the audience area. The six, custom designed, 4 loudspeakers and two dome tweeters are driven by an eight channel class-d amplifier. Its compact array length makes the Intellivox-1b suitable for easy and unobtrusive implementation in even the most architecturally sensitive environment. Nominal level Type Impedance (balance) 15m 0 dbu (line input) Transformer Balanced 6k8 (line input) 50m 0 dbu (line input) Transformer Balanced 6k8 (line input) Power Amps 8 x 40 Wrms (4_), PWM (class D) 16 x 40 Wrms (4_), PWM (class D) Mains Voltage 230 or 115V (+5/-10%) 230 or 115V (+5/-10%) Power Consumption 28 VA (idle) / 150 VA (full load) 84 VA (idle) / 750 VA (full load) Operating Temperature 0 to +40 C 0 to +40 C Transducers 6 x 4 full range, 2 x 10mm dome tweeter 17 x 4 full range Dimensions (mm) 670h x 134w x 186d 4350h x 134w x 92d Colour / Finish RAL 9010 (white) RAL 9010 (white) Approx. Weight 16 Kg 46 Kg ORDER CODES Contact Gent for details
Public Address and Voice Alarm
Training Presentation Public Address and Voice Alarm Slide 1 Contents Introduction What is Voice Alarm? What are the benefits? What standards apply? Intelligibility requirements Issues when designing VA
(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently
(68.52) X June 2000 Supercedes February 2000 xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM.... we look @ business differently XENEX SYSTEM ARCHITECTURE Note: This schematic is for guidance only please
EN54-16 Voice Alarm System PRODUCT DATASHEETS
EN54-16 Voice Alarm System PRODUCT DATASHEETS WayGuard This page is intentionally left blank Pagina 2 di 16 WayGuard Revision history Rel. Data Autore Modifiche 1.00 25/02/15 First emission Pagina 3 di
500r+ Installation and User Guide
500r+ Installation and User Guide Compatible Equipment 502rUK-50 Watch/Pendant PA. 509rUK-50 Smoke Detector 515rUK-00 10 metre passive infra red movement detector. 525rUK-00 Remote Set/Unset (Full and
Voice alarm system E100 the new standard for safe evacuation
Voice alarm system E100 the new standard for safe evacuation Clear announcements and future-proof protection in case of fire Answers for infrastructure. E100 from Siemens so everyone knows what to do when
I Notification. Loudspeaker HONEYWELL COMMERCIAL VOICE ALARM AUDIO
I Notification Loudspeaker HONEYWELL COMMERCIAL VOICE ALARM AUDIO Honeywell is a Fortune 100 company that invents and manufactures technologies to address tough challenges linked to global macro trends
CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access
CSP Combined Series Telephone Door Entry with Proximity Keyfob Access PD-094 Issue 3 General Description The CSP series systems are combined Door Entry Telephone and Proximity Access Systems. The entrance
PS 29M DUAL CHANNEL BELTPACK IN METAL CASE
PS 29M DUAL CHANNEL BELTPACK IN METAL CASE USER MANUAL October 2013 This product is designed and manufactured by: ASL Intercom BV Zonnebaan 42 3542 EG Utrecht The Netherlands Phone: +31 (0)30 2411901 Fax:
Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling
Electronics Ltd Presenting Power, Intelligence... with a sense of feeling By Appointment to Her Majesty The Queen Supplier of Fire Detection Equipment Kentec Electronics Ltd. Dartford Plug in slots K772
Fire Alarm system Installation Guide
Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this
VM-3000 Series. With new features! Integrated Voice Evacuation System. sound without compromise. www.toa.eu
VM-3000 Series Integrated Voice Evacuation System With new features! sound without compromise www.toa.eu SECURITY WITH CONVICTION Continuously TOA brings the knowledge gained from years of experience in
Fire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
LOXONE 12 Channel Amplifier
LOXONE 12 Channel Amplifier Item no.: 200110 Thank you for purchasing the Loxone Twelve Channel Amplifier. The versatility of the Amplifier makes it the perfect choice for almost every type of custom multi-room
Zone Mixer. 6 channels configurable from 24 inputs. 3 zone outputs. Expandable via Sys-Link TM Built-in comp/limiter, ducking and alarm functions
GR 1 Zone Mixer W H E N Y O U R E M I X I N G W I T H P R O F E S S I O N A L S 6 channels configurable from 24 inputs. 3 zone outputs. Expandable via Sys-Link TM Built-in comp/limiter, ducking and alarm
SECTION 13850 DETECTION AND ALARM
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring
TELIKOU Intercom System. MS-500(4+1 channel) Main Station Instruction Manual
TELIKOU Intercom System MS-500(4+1 channel) Main Station Instruction Manual TELIKOU Systems All Rights Reserved While TELIKOU makes every attempt to maintain the accuracy of the information contained in
FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
1 All safety instructions, warnings and operating instructions must be read first.
ONYX USER MANUAL 2 Dateq ONYX Manual Safety instructions EN Safety instructions 1 All safety instructions, warnings and operating instructions must be read first. 2 All warnings on the equipment must be
Emergency Voice Communication Systems EVCS Network 8 Data Sheet
Emergency Voice Communication Systems EVCS Network 8 Data Sheet The Emergency Voice Communications System (EVCS) Network 8 is for use as a Fire Telephone system, Disabled Refuge Call system or as a combined
BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell
Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault
JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410
The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a
Emergency voice communications Product Name
Product Name 76 EATON FIRE AND VOICE ALARM SYSTEMS CFCC2556 January 2015 Contents Contents Emergency voice communications Panels Network exchange units 78 Non network exchange units 80 Devices Outstations
Notifier by Honeywell: Voice Alarm Solutions
Notifier by Honeywell: Voice Alarm Solutions Notifier by Honeywell: Voice Alarm The role of Voice Alarm As modern buildings become more complex, it is vital to manage people safely in an emergency. Voice
HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS
ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS USER MANUAL USER MANUAL ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS INTRODUCTION The (HA-841K) is a complete
B. Equipment shall be furnished and installed as specified. No substitutions will be allowed.
CLASSROOM SOUNDFIELD DISTRIBUTION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification
Sound Engineering for 60 Years EmerCall Disabled Refuge and Fire Telephone System
EmerCall Disabled Refuge and Fire Telephone System Slide 1 Audix EmerCall Fully Compliant to BS5839 Part 9 Slide 2 Audix EmerCall One System for Fire phones and Disabled persons See BS5839 Part 9 Forward,
2 Ohm Nominal Coaxial Speaker OWNER S MANUAL
2 Ohm Nominal Coaxial Speaker OWNER S MANUAL 1 page 1 SPL 65 Coaxial Speaker Congratulations on your purchase of the Soundstream SPL 65 Coaxial Speaker. When used with a high quality 2 ohm rated power
Repeaters and Mimics Data Sheet
Repeaters and Mimics Data Sheet IDR series repeaters and mimics allow vital information from a Notifier fire system to be communicated to points around a building remote from the fire alarm control panel.
AC-115 Compact Networked Single Door Controller. Installation and User Manual
AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.
THE MOST POWERFUL EON EVER
E O N 5 1 0 E O N 5 1 5 E O N 5 1 8 S THE NEXT GENERATION E N THE MOST POWERFUL EON EVER For the past 14 years JBL has led the portable PA market with EON, the best selling powered speaker in professional
D200+ Auto-Dialler Installation/Operators Manual
D200+ Auto-Dialler Installation/Operators Manual Bell System (Telephones) Ltd. Presley Way, Crownhill, Milton Keynes, MK8 0ET D200+ Software Version 1.0 Contents General Description...3 Central Station
ACTIVE 5 ENGINEERING MANUAL
ACTIVE 5 ENGINEERING MANUAL C & K Systems Ltd C031-066 Issue 3 THE ACTIVE 5 INSTALLATION MANUAL. Date: Feb 1997 INTRODUCTION. The Active 5 is a microprocessor controlled intruder alarm panel. It features
TOTALLY SOLID STATE NON-DIRECTIONAL RADIO BEACONS 190-535 khz
TOTALLY SOLID STATE NON-DIRECTIONAL RADIO S 190-535 khz This family of radio transmitters has been developed as extremely efficient, highly reliable Non Directional Beacons. ND2000A/4000A» MODULAR CONSTRUCTION»
Premier M Plus & Infinity 8
25 Years of Manufacturing Excellence Premier M Plus & Infinity 8 Conventional Fire Alarm Systems 007 Assessed to ISO 9001: 2008 Certificate number 330 Premier M Plus 8-24 Zone Conventional Fire Alarm Panel
Mitel DECT Base Stations
Mitel DECT Base Stations On-site Mobility for Professionals The Mitel BS300 range of base stations offers a variety of coverage patterns to suit different situations. By choosing the right mix of base
Control/Communicator Installation Manual
DAS NETWORX NX-8 Control/Communicator Installation Manual Page General Description... 2 Ordering Information... 2 Option Definitions... 2 Programming the LED Code Pads... 4 Programming the NX-8... 8 Types
IMPORTANT SAFETY INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS When using this electronic device, basic precautions should always be taken, including the following: 1. Read all instructions before using the product. 2. Do not use this
Plena Voice Alarm System. Software Manual Configuration Software
Plena Voice Alarm System en Software Manual Configuration Software Plena Voice Alarm System Software Manual Table of Contents en 3 Table of Contents Table of Contents...3 1. Introduction...7 1.1 Purpose...7
Standard the the Raising
Raising the Standard Introduction to BS 5839-1:2013 An Overview of the BS 5839 1:2013 for professionals who are responsible for the provision of fire detection and alarm systems for buildings Agenda Introduction
Owners Manual. Three-Way Architectural Speaker. www. artcoustic.com
Owners Manual Three-Way Architectural Speaker www. artcoustic.com Architect SL Three-Way Architectural Speaker Features: - X2 bass system, extended low frequency - Extremely small and compact design -
Active Speaker System LX523 AUDAC PROFESSIONAL AUDIO EQUIPMENT. Active Speaker System with remote input LX523. User Manual & Installation Guide
Active Speaker System LX523 AUDAC PROFESSIONAL AUDIO EQUIPMENT Active Speaker System with remote input LX523 User Manual & Installation Guide AUDAC PROFESSIONAL AUDIO EQUIPMENT User Manual & Installation
INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description
INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's
Data sheet AS-40 / ASP-40. Arc- Series. Architectural Sound Design.
Data sheet AS-40 / ASP-40 Arc- Series Architectural Sound Design. AS- 40 / ASP-40 subwoofer system Fohhn AS-40 / ASP-40 Compact high-power bass system, 800W, 118, back-leaded resonator. Description Fohhn
FIREDEX 2200. Conventional Fire Panels
68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class
Praesideo - Digital Public Address and Emergency Sound System
Praesideo - Digital Public Address and Emergency Sound System Praesideo - Digital Public Address and Emergency Sound System 2 Praesideo - Digital Public Address and Emergency Sound System Praesideo - Digital
welcome to our world fire alarm systems - series 600 www.staticsystems.co.uk
Static Systems Group PLC Heath Mill Road, Wombourne Staffordshire WV5 8AN. United Kingdom. Tel: +44 (0) 1902 895551 Fax: +44 (0) 1902 324969 www.staticsystems.co.uk welcome to our world In line with our
Conventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
Always on the Lookout Perfect Protection against Burglary
Always on the Lookout Perfect Protection against Burglary Terxon wired and hybrid alarm systems One system offers all possibilities Rely on experts With a qualified specialist installation contractor on
PLENA matrix Digital Sound System Surprisingly Flexible. Powerful Control.
PLENA matrix Digital Sound System Surprisingly Flexible. Powerful Control. 2 PLENA matrix Digital Sound System Your versatile choice for excellent audio performance Wireless control across multiple zones
9452/9453 Installation and User Guide
9452/9453 Installation and User Guide Compatible Equipment 9425 Remote Keypad 9040 Internal Sounder 660 Speech Communicator 8440 4-Channel Minicom 496330 Issue 1 1 of 10 9452/3 Introduction The 9452 and
Section D..General Auto Electrical Corporation
43 Section D..General Auto Electrical Corporation 1. LED Based Signal unit GAEC manufacture LED based signaling system for use in electrified and non electrified sections of Indian railways. The exceptional
ZMR 80 STEREO MODULAR ZONER USERS MANUAL
ZMR 80 STEREO MODULAR ZONER USERS MANUAL Lime Technologies http://limetechnologies.co.uk Tel: 08712 233127 ZMR80 Stereo Modular Zoner Mixer Introduction The modular construction of the ZMR80 allows it
SECTION 16760 - PLANT INTERCOMMUNICATION SYSTEM. City of San Diego, CWP Guidelines
PART 1 - GENERAL SECTION 16760-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing plant intercommunication systems with power supplies, signal amplifiers,
CB200W Water Leak Detection Panel Application Guide
Checked by: AJC Approved by: JBJ Contents CB200W Water Leak Detection Panel Application Guide 1. Cabinet Specifications... 2 2. Panel Hardware Specifications... 3 3. Panel Configuration... 4 4. Technical
AlarmSense 2-wire detection and alarm system. Product Guide
AlarmSense 2-wire detection and alarm system Product Guide Contents What is AlarmSense? 2 The purpose of AlarmSense 4 How AlarmSense works 4 Alarmsense Features 5 Detector removal monitoring 5 Priority/non-priority
TS510 & TS500. Installation & User Guide. Compatible Equipment
Installation & User Guide Compatible Equipment TS510 REM - Remote Keypad 9040 - Loudspeaker DC54/58 - Digital Communicator SD1+ - Speech Dialler 496525 Issue A 1 of 10 TS510 and TS500 Overview Introduction
FIRE DETECTION SYSTEMS ALARM STRATEGIES 2.0. New Version
FIRE DETECTION SYSTEMS STRATEGIES 2.0 New Version STRATEGIES TO FIT IN EVERY SITE A former factory now as a call center: Each alarm concept hat to meet the actual conditions of the building. A general
Operation Manual for Users
Operation Manual for Users Model No.: FLTAMFMRCD!!!!!!!!!! ATTENTION!!!!!!!!!! THE RESET BUTTON MUST BE PRESSED TO ENSURE PROPER OPERATION. SEE INSTRUCTION MANUAL Table of Contents Table of Contents ---------------------------------------------------------------------------------------------
ELEMENTS E 835/E 435 TECHNICAL DATA SHEET > > FEATURES > TECHNICAL SPECIFICATIONS. HK Audio E 435. HK Audio E 835
TECHNICAL DATA SHEET > > FEATURES Scalable mid/high units featuring line array technology Excellent directivity; uniform sound Column speakers with an inconspicuous design Rugged aluminum housing Built-in
ENGINEERING SPECIFICATIONS SENSAPHONE IMS-4000
ENGINEERING SPECIFICATIONS SENSAPHONE IMS-4000 I. General A. Summary The monitoring system shall be an expandable, self-contained microprocessor-controlled IMS-4000 Host unit (hereafter referred to as
EVID Compact Sound Speaker System
EVID Compact Sound Speaker System EVID-C44, EVID-C2.1, EVID-40C, EVID-S44, EVID-S44W, EVID-2.1, EVID-2.1W, EVID-40S, and EVID-40SW en Installation Manual en 3 Table of contents 1 Safety 4 2 Welcome 6
USER GUIDE. Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator. DM Engineering. Version 1.
USER GUIDE Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator Version 1.3 DM Engineering 2174 Chandler St. Camarillo, CA 91345-4611 805-987-7881 800-249-0487
MINERVA MX MX Virtual Multi-Sensor Detectors
DATASHEET MINERVA MX MX Virtual Multi-Sensor Detectors Over 20 fire detection modes Tyco MX FASTLOGIC Expert algorithms MX HPO detection Algorithms Up to 250 detectors per loop Optional bi-directional
ENCLOSURE DESIGN I S 2008
ENCLOSURE DESIGNS 2008 Beyma introduces a new range of enclosure designs created for obtaining the best performance from our latest loudspeakers and following the current trends in the market. The new
1000iSERIES REDEFINE THE POSSIBLE
1000iSERIES REDEFINE THE POSSIBLE 18mm Low Resonance Cabinet Anti-Resonance Bracing Acoustic Damping Inverse Field Magnetic Shielding Fourth Order Linkwitz-Riley Crossover Opti-Flow Port Bespoke Ferro-Fluid
TELIKOU Intercom System. TM-200 Main Station. Instruction Manual
Intercom System TM-200 Main Station Instruction Manual TELIKOU Systems All Rights Reserved I. Introduction Thank you for choosing TELIKOU intercom product. TM-200 main station is suitable for television
Short Form Catalogue. Alarm Systems. Reliable Supervision and Control
Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.
************* OWNER'S MANUAL BAMF800/2 BAMF1250/2 BAMF1800/2 BAMF2200/2 BAMF2600/2 BAMF1200/4 BAMF1600/4 BAMF2000/1D BAMF4000/1D BAMF5500/1D
************* OWNER'S MANUAL BAMF800/2 BAMF1250/2 BAMF1800/2 BAMF2200/2 BAMF2600/2 BAMF1200/4 BAMF1600/4 BAMF2000/1D BAMF4000/1D BAMF5500/1D INTRODUCTION Power Acoustik amplifiers provide high-performance
MSL1000 Monitored Serial Link Interface Manual V1.01
Audix Systems, Station Road, Wenden, Saffron Walden, Essex, CB11 4LG. Telephone: +44(0)1799 540888 Facsimile: +44(0)1799 541618 www.tycosafetyproducts-europe.com www.audixsystems.co.uk MSL1000 Monitored
MANUAL PC1000R [email protected]
MANUAL PC1000R [email protected] Features The APart PC1000R is a professional multisource CD/USB/SD card music player, equipped with balanced and unbalanced analog outputs, coaxial and optical digital
Vari-directional Array The smart route to acoustical perfection
Vari-directional Array The smart route to acoustical perfection 2 Vari-directional Array by Bosch The ultimate sound performance for acoustically challenging environments Unmatched sound quality and speech
BIBUS VOP. large blocks of flats with switchboard and mixed mainly audio systems. Ideal for door phone systems with up to 250 users.
BIBUS VOP Advice for use: large blocks of flats with switchboard and mixed mainly audio systems Ideal for door phone systems with up to 250 users VOP technology Easy creation of mixed audio and video door
BS5839 Part 1:2002 Overview
BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire
Generic - Hearing Loop - (AFILS) U.S. System Specification
This document is a generic specification for any Hearing Loop (Audio Frequency Induction Loop System). For the remainder of the document, we will refer to using the term Hearing Loop rather than Audio
VEGA Analogue Addressable Control Panels
Analogue Addressable Control Panels Representing the future of fire alarm control technology, Vega's modular concept enables the tailoring of system design for the smallest to the largest system. Designed
The completely Ethernet-based. protocol enables several imode devices to be linked, using easily-sourced. cables and components.
WHAT IS imode? Outline imode is proprietary technology, conceived to re-think the state of the art in the world of loudspeaker system control. Devices using this technology have a single on-board DSP that
SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description
SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped
2D & 3D TelePresence
2D & 3D TelePresence delivers the ultimate experience in communication over a distance with aligned eye contact and a life-size sense of presence in a room setting. Eye Contact systems achieve eye-to-eye
User Manual. Please read this manual carefully before using the Phoenix Octopus
User Manual Please read this manual carefully before using the Phoenix Octopus For additional help and updates, refer to our website To contact Phoenix Audio for support, please send a detailed e-mail
PBXport. Rackmount PBX Digital Hybrid. User Guide. JK Audio
PBXport Rackmount PBX Digital Hybrid User Guide JK Audio Introduction PBXport will allow you to send and receive audio through your multiline PBX, ISDN or analog telephone. While this may seem like a simple
EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual
EDA-Z5008 & Z5020 Radio Fire Alarm System User Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2EG UK Tel: 01279 635668. Fax 01279 450185 Email: [email protected]
CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1
CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL user manual & log book Approved Document No. DFU7001020 Rev 1 CONTENTS Safety...3 Important information regarding the safe use of this fire alarm panel
Plena Loop Amplifier. Installation and User Instructions PLN-1LA10
Plena Amplifier en Installation and User Instructions PLN-LA Plena Amplifier Installation and User Instructions Important safeguards en 3 Important safeguards Before you install or operate the Plena Amplifier,
BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEM EURO ALARM WIRELESS BURGLAR ALARM SYSTEM OASIS
BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEM EURO ALARM WIRELESS BURGLAR ALARM SYSTEM OASIS BURGLAR ALARM SYSTEM EURO ALARM Six zones with the following connection capabilities: One
CELO5. User & Installation Manual. www.audac.eu
CELO5 User & Installation Manual www.audac.eu 2 Introduction 5 High-end Slim Ceiling Speaker The CELO5 is the 5 version of AUDAC s CELO High-end Slim ceiling speaker series with an RMS power of 50 Watt
GSM ALARM SYSTEM USER MANUAL
GSM ALARM SYSTEM USER MANUAL 1. Instruction The alarm system is based on GSM network. With a GSM SIM card, it can be used wherever you want and no need to connect any wire, which is convenient and easy
NJP-400A NJP-401A. Safely into a new day. Advanced modular FIRE ALARM CONTROL PANEL with additional functionality. I m on FIRE (Bruce Springsteen)
Safely into a new day Advanced modular FIRE ALARM CONTROL PANEL with additional functionality NJP-400A NJP-401A I m on FIRE (Bruce Springsteen) EN 54-2, EN 54-4 Cert No. 1124a DESCRIPTION OP-400A, NJP-400A,
Kit 106. 50 Watt Audio Amplifier
Kit 106 50 Watt Audio Amplifier T his kit is based on an amazing IC amplifier module from ST Electronics, the TDA7294 It is intended for use as a high quality audio class AB amplifier in hi-fi applications
RVL470. Heating Controller. Building Technologies HVAC Products. Series B
2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones
ERS-2400B. PERS-2400B Personal Emergency Reporting System
PERS-2400B Personal Emergency Reporting System ERS-2400B Durability and Versatility for Emergency Reporting Solutions Create a customized and comprehensive Personal Emergency Reporting System with the
Triple Waveband Infra-Red Flame Detection
Minerva S200PLUS Ex ia Intrinsically Safe & Ex d Flameproof Solar Blind Flame Detectors Triple Waveband Infra-Red Flame Detection Key Features Unrivalled black body rejection over a wide range of source
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
Innkeeper PBX. Desktop Digital Hybrid. User Guide. JK Audio
Innkeeper PBX Desktop Digital Hybrid User Guide JK Audio Introduction Innkeeper PBX will allow you to send and receive audio through your multi-line PBX, ISDN or analog telephone. While this may seem like
Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual
Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS
Communication A BRITISH MANUFACTURER. Features:
care2 Radial Wired Emergency Voice Communication Manufacturing EVC systems since 2001 CARE2 is a radial wired emergency voice communication system built to the high standard you expect from Baldwin Boxall.
Plena Two-zone Call Station. Installation and User Instructions PLE-2CS
Plena Two-zone Call Station en Installation and User Instructions PLE-2CS Plena Two-zone Call Station Installation and User Instructions Important safeguards en 2 Important safeguards Before installing
SAFEPATH 4 Facility Communications System & Expansion Options
Notification SAFEPATH 4 Facility Communications System & Expansion Options SPB-320 SP40S SPB-80/4 SPB-160 SPRM SP4Z-A/B SP-SVC SP4-TZC Page SP40S Facility Communications System 2-4 Expansion Options SAFEPATH
TX GSM SMS Auto-dial Alarm System. Installation and User Manual
TX GSM SMS Auto-dial Alarm System Installation and User Manual Product Features: 1. 16 wireless zones, 3 wired zones alarm system, suitable for small to medium size offices and homes. 2. The system uses
RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
Global System Technology(UK) PLC The Intelligent Solution
Global System Technology(UK) PLC The Intelligent Solution MANUFACTURED IN ACCORDANCE WITH Intelligent Photoelectric Smoke Detector Aesthetically pleasing Low profile design 8 Bit intelligent processor