Geotechnical Investigation Reports and Foundation Recommendations - Scope for Improvement - Examples
|
|
|
- Dale Garey Hawkins
- 9 years ago
- Views:
Transcription
1 Geotechnical Investigation Reports and Foundation Recommendations - Scope for Improvement - Examples Prof. V.S.Raju (Formerly: Director, IIT Delhi & Professor and Dean, IIT Madras) [email protected] Prof. V.S. Raju 1 CHOICE OF APPROPRIATE FOUNDATION AND EXECUTION Optimum foundation design should ensure: technical adequacy, cost effectiveness and ease of execution. This is not easy, because of many variables including insufficient and inaccurate information at the time of design. Variation in strata and changes in project requirement during execution 2 1
2 TOPICS COVERED Inadequacy of the Investigations and Inappropriate Foundation Recommendations with Illustrative Examples 1. Fertilizer Plant on the East Coast 2. Fertilizer Plant in Gangetic Belt 3. Office cum Residential Complex at Jodhpur 4. University Campus at Adilabad District 5. L&T Serene County (Residential Campus) 3 FERTILIZER PLANT ON THE EAST COAST The average soil strata consists of : top layer of dense fine sand 4 to 8 m thick. followed by soft marine clay up to a depth of 14 to 18 m below ground level. very stiff clay up to 30 to 40 m below ground level. 4 2
3 5 PROBLEMS DUE TO THE PRESENCE OF SOFT CLAY LAYER For site grading, 1-2 m fill is required - results in a settlement of 12 cm of soft clay. - Along with clay, sand layer also moves down. In case of pile foundation, large negative drag on piles from soft clay and sand layer. Considerable reduction in pile capacity (upto 50%), and hence increase in the number of piles. For structures like bulk storage with large area loads, the stability of soft clay layer and lateral flow to be checked. Large settlements of floors and lateral forces on neighbouring pile foundations. 6 3
4 FOUNDATIONS ADOPTED Precast driven piles were chosen, with bitumen coat in the top layers to reduce the negative drag. All light structures, not sensitive to settlements, are supported on shallow foundations. For structures having distributed loads over large areas (silos, water storages), surcharge provided on the periphery to achieve reduced shear stresses on soft clay. 7 CHOICE OF THE PILE The original recommendation was to go for bored piles, 45 cm in diameter. Two alternative pile types have been tested. a) Precast driven piles 40 cm x 40 cm, 22 m long (to be able to drive). b) Bored cast in situ piles, 45cm dia, 22 m long Full scale tests for a final decision on the choice of the pile type. 6 test piles, 3 each of the 2 types, installed in locations in close proximity. 3 different Bored cast in-situ piles were installed by bailer boring method. 8 4
5 RESULTS OF PILE LOAD TESTS 9 Table 1: WORKING LOAD IN TONS AS PER IS 2911 Pile No. (1) 2 / 3 of Load at 12 mm settlement (2) Failure Load (3) Half of Failure Load (4) Working Load (smaller of 2 and 4) (5) P (100) * B P B P B The pile length is 19.5 m, and failure load extrapolated for 22 m length is 100 tons. 10 5
6 CONCLUSIONS Precast driven piles with design load of 70 to 100 tonnes adopted for the following reasons : For comparable dimensions, the precast pile has 50 to 80% higher capacity than a bored pile. Precast pile offers better protection to reinforcement. This is particularly important under the present saline ground water conditions. The jetting of precast pile up to 12 m will reduce the friction over this depth, and consequently the effects of negative drag. In case of precast piles, the negative drag can be reduced by applying a slip layer of bitumen. 11 Conclusions (Contd.) Bored piles not preferred for the following reasons: Lower Capacity Boring operations through stiff fissured clay will result in softening of this layer, thereby limiting the load carrying capacity of piles. There is no possibility of applying any slip layer and to reduce the negative drag. 12 6
7 ANTICIPATED NEGATIVE DRAG 40 tonnes based on theoretical consideration. Field load tests on i) Short piles resting on soft clay, ii) Instrumented piles, where the load distribution with depth has been measured. Model tests for the proper choice of bitumen coating to reduce negative drag. i) Precast concrete 10 cm dia and 50 cm long piles were used. ii) Bitumen coatings using different grades of bitumen were applied, and results showed 80 to 90% reduction in friction. iii) Finally SAE 80 grade bitumen was adopted. 13 FERTILIZER PLANT IN GANGETIC BELT The Soil Strata: Silty sand with low N values (<10) upto 10 m depth, N > 20 beyond 20 m depth. N-values ranging between 10 to 20 for the layer between 10 to 20 m depth. High water table with possibility of liquefaction during earthquake. 14 7
8 PHASE I : INITIAL FOUNDATION DESIGN RCC Piles, Driven Cast-in situ, 400 mm dia Sand Compaction Piles, 2-3 Rows Around RCC Piles, Pile capacities Vertical downward : 50 t, Tension : 5t, Lateral : 2.5t, Result Total Requirement 16,000 RCC Piles 32,000 Compaction Piles Problem of execution on time 15 REVIEW AND FURTHER INVESTIGATION (Pile Load Tests) Revised Pile Capacities Vertical : 65t Tension : 25t Lateral : 3.5t Reduction in RCC Piles : 40% Increase in spacing of compaction piles from 3d to 4 d ; reduction in Compaction Piles : 50% Saving in construction time : 6 months Substantial cost savings as well. 16 8
9 SETTLEMENT (mm) PHASE II OF THE PLANT No RCC Piles. 900 mm dia Vibro-Stone Columns with varied spacing (2d,2.25d and 2.5d) to suit the foundation requirement. Full scale field trials. Several Footing tests for confirmation. Substantial savings in time and cost. 17 LOAD kg / m 2 x LOAD SETTLEMENT CURVES FOR SINGLE COLUMN LOAD TEST 18 9
10 SETTLEMENT (mm) LOAD kg / m 2 x Aonla (Compressor House) Single column Test Aonla (Benefield) Aonla (Prill Tower) Three Column Test LOAD SETTLEMENT CURVES FOR SINGLE AND THREE COLUMN TEST 19 Office cum Residential Complex at Jodhpur 2-3 Storeyed Buildings Investigations Done 8 Bore holes drilled to 6 m depth each. As per bore logs Rocky strata. Strata starts at Ground level (GL) in all bore holes except in Bore hole 5, where it starts at 1.5 m. BH 5 is at the extreme corner of the plot where nothing is planned to be built. Bore logs do not give the core recovery, which is a must to be given
11 Recommendations by Investigation Agency 1. Open foundations (footings) 2. Unconfined compressive strength of rock range given 650 to 850 t/m 2 3. Calculated safe bearing capacity (SBC) 80 to 100 t/m 2 21 FOUNDATION RECOMMENDATIONS (Contd ) 4. Recommended SBC is 40 t/m 2 at 1m below GL, except in BH 5; where SBC is 10 t/m 2 at 1.2 m depth and 40 t/m 2 from 2 m depth onwards. 5. The SBC adopted in Design is not known. It should have been written on the drawings
12 WHAT HAPPENED AT SITE 1. Foundation Depth adopted: 1.5m. 2. Foundation sizes 1.5m x 1.5m to 2.3m x 2.3m 3. For excavation Rock Blasting has been done 4. Instead of excavating / blasting individual pits for each footing, the entire foot print of all the buildings has been blasted and excavated. 23 What Happened at Site (Contd ) 5. This resulted in excavated rock material ranging from huge boulders to rubble of volume of about 25,000 m 3 (Actually needed 10% of this). 6. Additional issues: (a) How to dispose of the excavated material. (b) Huge quantity of soil material for plinth filling needed
13 Prof. V.S. Raju s Investigation of the Situation and Foundation Recommendations Basis : Site visit Inspection of the strata in the excavated pits Study of the soil report 1. The investigation is not as per the relevant Indian Standards. 25 Prof. V.S. Raju s Recommendations (Contd ) 2. The recommendations in the report are wrong and are less by a Factor 3 to The correct SBC values are 150 t/m 2 (on a conservative side) with a minimum size of footing as 0.8m x 0.8m. Depth of footing 0.5m to 1m
14 Prof. V.S. Raju s Recommendations (Contd ) 4. There is absolutely no justification to stipulate a foundation depth of 1.5m for the entire site. 5. There was no need at all to make the footing sizes so big as given (1.5m x 1.5m to 2.3m x 2.3m) 6. There is no need to blast the strata over the entire foot print of the building. 27 Prof. V.S. Raju s Recommendations (Contd ) 7. No need to blast for the individual footings also as the required likely sizes are 0.8m x 0.8m to 1.2m x 1.2m, depth 0.5 m to 1.0m only. Pavement breakers (jack hammers) will do the job
15 Photographs of Blasted Rocks 29 rap Photographs of Blasted Rocks 30 15
16 5.8 m to 25m soft rock University Campus at Adilabad District Total area ~ 300 acres For Phase I development, Only 7 boreholes Bore logs improper and inadequate. First SPT at 10 m below GL. Pile Foundations recommended and executed, which are not at all required. Pile safe capacity for 600 mm dia, 12 m length : 83 tons (Very low) - Settlement of pile up to 10 % of pile diameter could not be attained by 3 times the design load. Prof. V.S. Raju to 1.80 m Brown clay 1.80 mto 5.80 m yellow clay & Murrum First SPT at 10m below G.L, Required every 1m to 1.5m Typical Bore Profile Prof. V.S. Raju 32 16
17 Pile Load Tests: Five Initial Load Tests At 3 times the design load, settlements are only 2 mm to 27 mm as against permitted 45 mm to 60 mm. Pile capacities are not revised. Piles, which are not required in the first place are grossly over designed. Prof. V.S. Raju Acres site L&T Serene County Strata Rocks and Boulders with local depressions, highly uneven. 10 towers between 11 and 14 floors Recommended SBC by the soil Investigation Agency 30 t/m 2 - One value for the entire site? 34 17
18 30 m L&T Serene County Prof. V.S. Raju 35 Extreme Issue was with one of the 10 towers built Tower Dimension : 75 m x 30 m Highly variable strata at Founding Level. 75 m Hard Rock SBC 400 t/m 2 Hard Murrum Soft Clay 80 t/m 2 4 m thick 0 t/m 2 Prof. V.S. Raju Tower Foot Print 36 18
19 Important: These type of variations do occur in rocky and bouldry strata The soft clay is due to a old pond, which normally gets covered up during site grading. 37 All these examples reaffirm the requirement of high quality Geotechnical Investigation, Interpretation by a qualified Foundation Engineer in close collaboration with the Structural Designer
20 THANK YOU JAI HIND 20
Geotechnical Measurements and Explorations Prof. Nihar Ranjan Patra Department of Civil Engineering Indian Institute of Technology, Kanpur
Geotechnical Measurements and Explorations Prof. Nihar Ranjan Patra Department of Civil Engineering Indian Institute of Technology, Kanpur Lecture No. # 13 (Refer Slide Time: 00:18) So last class, it was
Anirudhan I.V. Geotechnical Solutions, Chennai
Anirudhan I.V. Geotechnical Solutions, Chennai Often inadequate In some cases, excess In some cases, disoriented Bad investigation Once in a while good ones Depends on one type of investigation, often
Local Authority Building Control Technical Information Note 3 Driven and In-situ Piled Foundations
Local Authority Building Control Technical Information Note 3 Driven and In-situ Piled Foundations Cambridge City Council - East Cambridgeshire District Council - Fenland District Council, Huntingdonshire
FINAL REPORT ON SOIL INVESTIGATION
FINAL REPORT ON SOIL INVESTIGATION FOR PROPOSED CONSTRUCTION AT SS-6B AREA AT HPCL VISAKH REFINERY VISAKHAPATNAM ANDHRA PRADESH J.J. ASSOCIATES(VISAKHAPATNAM) AETP(P) LIMITED #11-6-3, RockDale Layout,
PILE FOUNDATIONS FM 5-134
C H A P T E R 6 PILE FOUNDATIONS Section I. GROUP BEHAVIOR 6-1. Group action. Piles are most effective when combined in groups or clusters. Combining piles in a group complicates analysis since the characteristics
USE OF MICROPILES IN TEXAS BRIDGES. by John G. Delphia, P.E. TxDOT Bridge Division Geotechnical Branch
USE OF MICROPILES IN TEXAS BRIDGES by John G. Delphia, P.E. TxDOT Bridge Division Geotechnical Branch DEFINITION OF A MICROPILE A micropile is a small diameter (typically less than 12 in.), drilled and
An Automatic Kunzelstab Penetration Test
An Automatic Kunzelstab Penetration Test Yongyuth Sirisriphet 1, Kitidech Santichaianant 2 1 Graduated student: Faculty of Industrial Education in and Technology. King Mongkut's University of Technology
A study on the Effect of Distorted Sampler Shoe on Standard Penetration Test Result in Cohesionless soil
ISSN: 319-53 (An ISO 39: 00 Certified Organization) A study on the Effect of Distorted Sampler Shoe on Standard Penetration Test Result in Cohesionless soil Utpal Kumar Das Associate Professor, Department
ENCE 4610 Foundation Analysis and Design
This image cannot currently be displayed. ENCE 4610 Foundation Analysis and Design Shallow Foundations Total and Differential Settlement Schmertmann s Method This image cannot currently be displayed. Strength
Site Investigation. Some unsung heroes of Civil Engineering. buried right under your feet. 4. Need good knowledge of the soil conditions
This is an attempt to create a stand alone self learning module on site investigation. Fasten your seat belts. Sit back, relax and enjoy. 1 2 Site Investigation Some unsung heroes of Civil Engineering
Geotechnical Investigation Test Report
Geotechnical Investigation Test Report Report No. htsc/rcd/ 3457 Dated: - 20/03/2010 Asphalt Standard Penetration Test as per IS 2131 ------------- IS 6403 Soil Job Card No - 1649 Cement Client/Department
1.0 INTRODUCTION 1 2.0 SCOPE OF WORK 2 3.0 EXECUTION OF FIELD WORK 2 4.0 LABORATORY TESTS 8 5.0 FINDINGS OF THE GEOTECHNICAL INVESTIGATION 9
REPORT ON GEOTECHNICAL INVESTIGATION FOR LPG MOUNDED STORAGE AT VISAKHA REFINERY, MALKAPURAM, VISAKHAPATNAM (A.P) FOR HINDUSTAN PETROLEUM CORPORATION LIMITED CONTENTS SR.NO. DESCRIPTION PAGE NO. 1.0 INTRODUCTION
How To Design A Foundation
The Islamic university - Gaza Faculty of Engineering Civil Engineering Department CHAPTER (2) SITE INVESTIGATION Instructor : Dr. Jehad Hamad Definition The process of determining the layers of natural
HOUSE BUILDING DIGEST
HOUSE BUILDING DIGEST (Construction Specifications-Foundations) Creating Enabling Environment for Affordable Housing for All This is an attempt by BMTPC to provide useful but often ignored information
COSMOS 2012: Earthquakes in Action COSMOS 2012
COSMOS 2012 What is SFSI and why is it important? Soil issues in Earthquakes Structures where SFSI important Retaining structures (lateral earth pressure) Foundations (spread and pile footings, bearing
Design, Testing and Automated Monitoring of ACIP Piles in Residual Soils
Design, Testing and Automated Monitoring of ACIP Piles in Residual Soils Stephen W. Lacz 1, M. ASCE, P.E. and Richard C. Wells 2, F. ASCE, P.E. 1 Senior Professional, Trigon Kleinfelder, Inc., 313 Gallimore
Method Statement FOR. Soil Investigation
Method Statement FOR Soil Investigation PREPARED BY JUNE 2010 Infratech ASTM CO., LTD. TABLE OF CONTENTS Chapter Title Page Table of Contents..1 List of Appendix... 2 List of Table... 2 List of Figures...
product manual HS-4210 HS-4210_MAN_09.08 Digital Static Cone Penetrometer
HS-4210_MAN_09.08 product manual HS-4210 Digital Static Cone Penetrometer Introduction This Manual covers the measurement of bearing capacity using the Humboldt Digital Static Cone Penetrometer (DSCP).
KWANG SING ENGINEERING PTE LTD
KWANG SING ENGINEERING PTE LTD 1. INTRODUCTION This report represents the soil investigation works at Aljunied Road / Geylang East Central. The objective of the soil investigation is to obtain soil parameters
Engineered, Time-Tested Foundation Repairs for Settlement in Residential and Light Commercial Structures. The Leading Edge.
TM TM Engineered, Time-Tested Foundation Repairs for Settlement in Residential and Light Commercial Structures. SM The Leading Edge. 10 One Major Causes of foundation settlement or more conditions may
COMPENDIUM OF INDIAN STANDARDS ON SOIL ENGINEERING PART 2
(PREVIEW) SP 36 (Part 2) : 1988 COMPENDIUM OF INDIAN STANDARDS ON SOIL ENGINEERING PART 2 IS 1893 : 1979 (Reaffirmed 1987) CODE OF PRACTICE FOR SUBSURFACE INVESTIGATION FOR FOUNDATIONS 1.1 This code deals
Module 1 : Site Exploration and Geotechnical Investigation. Lecture 4 : In-situ tests [ Section 4.1: Penetrometer Tests ] Objectives
Lecture 4 : In-situ tests [ Section 4.1: Penetrometer Tests ] Objectives In this section you will learn the following Penetrometer Tests Standard penetration test Static cone penetration test Dynamic cone
STRUCTURES. 1.1. Excavation and backfill for structures should conform to the topic EXCAVATION AND BACKFILL.
STRUCTURES 1. General. Critical structures may impact the integrity of a flood control project in several manners such as the excavation for construction of the structure, the type of foundation, backfill
CIVL451. Soil Exploration and Characterization
CIVL451 Soil Exploration and Characterization 1 Definition The process of determining the layers of natural soil deposits that will underlie a proposed structure and their physical properties is generally
SPECIFICATION FOR DYNAMIC CONSOLIDATION / DYNAMIC REPLACEMENT
SPECIFICATION FOR DYNAMIC CONSOLIDATION / DYNAMIC REPLACEMENT 1.0 SOIL IMPROVEMENT 1.1 General Soil Investigation Information are provided in Part B1 annex as a guide to the Contractor for his consideration
ASSESSMENT OF SHEAR WAVE VELOCITY FROM INDIRECT INSITU TESTS
Proceedings of Indian Geotechnical Conference IGC-2014 December 18-20, 2014, Kakinada, India ASSESSMENT OF SHEAR WAVE VELOCITY FROM INDIRECT INSITU TESTS Kant, L., M. Tech Student, Department of Earthquake
METHOD OF STATEMENT FOR STATIC LOADING TEST
Compression Test, METHOD OF STATEMENT FOR STATIC LOADING TEST Tension Test and Lateral Test According to the American Standards ASTM D1143 07, ASTM D3689 07, ASTM D3966 07 and Euro Codes EC7 Table of Contents
FOUNDATION DESIGN. Instructional Materials Complementing FEMA 451, Design Examples
FOUNDATION DESIGN Proportioning elements for: Transfer of seismic forces Strength and stiffness Shallow and deep foundations Elastic and plastic analysis Foundation Design 14-1 Load Path and Transfer to
INDIRECT METHODS SOUNDING OR PENETRATION TESTS. Dr. K. M. Kouzer, Associate Professor in Civil Engineering, GEC Kozhikode
INDIRECT METHODS SOUNDING OR PENETRATION TESTS STANDARD PENETRATION TEST (SPT) Reference can be made to IS 2131 1981 for details on SPT. It is a field edtest to estimate e the penetration e resistance
BRIDGE RESTORATION AND LANDSLIDE CORRECTION USING STRUCTURAL PIER AND GRADE BEAM
BRIDGE RESTORATION AND LANDSLIDE CORRECTION USING STRUCTURAL PIER AND GRADE BEAM Swaminathan Srinivasan, P.E., M.ASCE H.C. Nutting/Terracon David Tomley, P.E., M.ASCE KZF Design Delivering Success for
Geotechnical Testing Methods II
Geotechnical Testing Methods II Ajanta Sachan Assistant Professor Civil Engineering IIT Gandhinagar FIELD TESTING 2 1 Field Test (In-situ Test) When it is difficult to obtain undisturbed samples. In case
GUJARAT NARMADA VALLEY FERTILIZER CO. LTD. (GNFC Ltd) TECHNICAL REPORT GEOTECHNICAL INVESTIGATION FOR PROPOSED TDI PLANT AT VILLAGE RAHIYAD, DAHEJ
GUJARAT NARMADA VALLEY FERTILIZER CO. LTD. (GNFC Ltd) TECHNICAL REPORT OF GEOTECHNICAL INVESTIGATION FOR PROPOSED TDI PLANT AT VILLAGE RAHIYAD, DAHEJ BY: DR.K.C.THAKER B.E.(CIVIL) ; M.TECH (S.M.); (I.I.T,
2009 Japan-Russia Energy and Environment Dialogue in Niigata S2-6 TANAKA ERINA
Importance of the Site Investigation for Development of Methane Hydrate Hokkaido University Hiroyuki Tanaka Civil Engineer My Background Site Investigation Soil Parameters for Design Very Soft Clay and
ALLOWABLE LOADS ON A SINGLE PILE
C H A P T E R 5 ALLOWABLE LOADS ON A SINGLE PILE Section I. BASICS 5-1. Considerations. For safe, economical pile foundations in military construction, it is necessary to determine the allowable load capacity
BUTE Department of Construction Management and Technology
BUTE Department of Construction Management and Technology 02.10.2012 Definition 1: Foundation: The structure, that transmits the load of the building to the soil Definition 2: Load bearing soil (strata):
INSITU TESTS! Shear Vanes! Shear Vanes! Shear Vane Test! Sensitive Soils! Insitu testing is used for two reasons:!
In-situ Testing! Insitu Testing! Insitu testing is used for two reasons:! To allow the determination of shear strength or penetration resistance or permeability of soils that would be difficult or impossible
Chittagong Hill Tract Development Facilities (CHTDF) United Nations Development Programme
Chittagong Hill Tract Development Facilities (CHTDF) United Nations Development Programme Main Report Deliverable 02 Sub-Surface Properties of Soil Development in Rangamati, Bandarban and Khagrachari Municipality
load on the soil. For this article s examples, load bearing values given by the following table will be assumed.
How Many Piers? By Gary Collins, P.E. A clear-cut guide to helical pier spacing Introduction Helical pier spacing is not an exact science. How many does it take to support a structure adequately or repair
Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. The design of any foundation consists of following two parts.
8.7. Design procedure for foundation The design of any foundation consists of following two parts. 8.7.1 Stability analysis Stability analysis aims at removing the possibility of failure of foundation
INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 3, No 3, 2013
INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 3, No 3, 2013 Copyright by the authors - Licensee IPA- Under Creative Commons license 3.0 Research article ISSN 0976 4399 Reliability of
GUIDELINES FOR GEOTECHNICAL INVESTIGATION OF BRIDGE STRUCTURES. Materials Engineering Report No. 2009-8M (Supersedes Report No.
GUIDELINES FOR GEOTECHNICAL INVESTIGATION OF BRIDGE STRUCTURES Materials Engineering Report No. 2009-8M (Supersedes Report No. 21) F CHOWDHURY GEOMECHANICS AND STRUCTURAL MATERIALS ENGINEER S REHMAN GEOTECHNICAL
High Strain Dynamic Load Testing of Drilled Shafts
Supplemental Technical Specification for High Strain Dynamic Load Testing of Drilled Shafts SCDOT Designation: SC-M-712 (9/15) September 3, 2015 1.0 GENERAL This work shall consist of performing high-strain
King Saud University College of Engineering Civil Engineering Department DEFORMATION OF PARTIALLY SATURATED SAND. Sultan Musaed Al-Ghamdi
King Saud University College of Engineering Civil Engineering Department DEFORMATION OF PARTIALLY SATURATED SAND By Sultan Musaed Al-Ghamdi Submitted in Partial Fulfillment of The Required For the Degree
Geotechnical Investigation using Standard Penetration Test (SPT) in Rangamati, Bandarban and Khagrachari Towns
1. Introduction 1.1 Scope of Work The Asian Disaster Preparedness Centre (ADPC) is implementing the project Seismic Hazard and Vulnerability Mapping for Rangamati, Bandarban and Khagrachari Municipality.
Pile test at the Shard London Bridge
technical paper Pile test at the Shard London Bridge David Beadman, Byrne Looby Partners, Mark Pennington, Balfour Beatty Ground Engineering, Matthew Sharratt, WSP Group Introduction The Shard London Bridge,
Quality control: Annex-A.
Quality control: Quality of the constructed work has been checked by our staff as per frequency and provision mentioned section 900 in MoRT&H and as per provision mentioned in Concession Agreement. The
SERVICES 2015 ISO 18001
SERVICES 2015 A family business with a solid foundation of experience, we handle all aspects of site investigation.... Phase 1 Environmental Studies Phase 2 Intrusive Investigations Phase 3 Remediation
Pavements should be well drained both during and upon completion of construction. Water should not be allowed to pond on or near pavement surfaces.
Project No. 208-8719 January, 2009 Ref: 2-8719BR Anthony Hudson - Broadscale Geotechnical Investigation - Proposed Commercial Development - 52 Old Pacific Highway, Pimpama Page 32 iii) Pavements should
DESIGNING STRUCTURES IN EXPANSIVE CLAY
DESIGNING STRUCTURES IN EXPANSIVE CLAY A GUIDE FOR A RCHITECTS AND E NGINEERS Table of Contents 1. Introduction Page 1 2. Common Foundation Systems Page 2 3. Drilled Piers Page 3 a. Skin Friction Piers
Civil. 2. City of Seattle Supplement to the Specification for Road, Bridge and Municipal Construction, most current addition.
Design Guide Basis of Design This section applies to the design and installation of earthwork and backfill. Design Criteria No stockpiling of excavation materials is allowed unless the Geotechnical Engineer
ENGINEERED FOUNDATIONS. Department of Public Works Jeff Hill, PE
ENGINEERED FOUNDATIONS Department of Public Works Jeff Hill, PE What is an engineered foundation. A Foundation Design Developed by a Trained Professional (Engineer) Types of Foundations (All of which can
State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS
State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS While its use is not required, this checklist has been prepared to provide the field inspector a summary
c. Borehole Shear Test (BST): BST is performed according to the instructions published by Handy Geotechnical Instruments, Inc.
Design Manual Chapter 6 - Geotechnical 6B - Subsurface Exploration Program 6B-2 Testing A. General Information Several testing methods can be used to measure soil engineering properties. The advantages,
Eurocode 7 - Geotechnical design - Part 2 Ground investigation and testing
Brussels, 18-20 February 2008 Dissemination of information workshop 1 Eurocode 7 - Geotechnical design - Part 2 Ground investigation and testing Dr.-Ing. Bernd Schuppener, Federal Waterways Engineering
SETTLEMENT MONITORING OF DISCRETE REINFORCED SOIL LAYER BENEATH MAT FOUNDATIONS, CALIFORNIA, USA
SETTLEMENT MONITORING OF DISCRETE REINFORCED SOIL LAYER BENEATH MAT FOUNDATIONS, CALIFORNIA, USA Ken Hoevelkamp, PE Geopier Foundation Company West, Inc., Irvine, CA, USA Brendan FitzPatrick, PE Geopier
Estimation of Adjacent Building Settlement During Drilling of Urban Tunnels
Estimation of Adjacent Building During Drilling of Urban Tunnels Shahram Pourakbar 1, Mohammad Azadi 2, Bujang B. K. Huat 1, Afshin Asadi 1 1 Department of Civil Engineering, University Putra Malaysia
EVALUATING THE IMPROVEMENT FROM IMPACT ROLLING ON SAND
EVALUATING THE IMPROVEMENT FROM IMPACT ROLLING ON SAND D.L. Avalle, Broons Hire (SA) Pty Ltd, Australia J.P. Carter, The University of Sydney, Australia Abstract Impact rolling, utilising a non-circular
GEOTECHNICAL ENGINEERING FORMULAS. A handy reference for use in geotechnical analysis and design
GEOTECHNICAL ENGINEERING FORMULAS A handy reference for use in geotechnical analysis and design TABLE OF CONTENTS Page 1. SOIL CLASSIFICATION...3 1.1 USCS: Unified Soil Classification System...3 1.1.1
Use of a Reinforced Jet Grout Excavation Support System for a Major Sewer Line Repair
Use of a Reinforced Jet Grout Excavation Support System for a Major Sewer Line Repair Eric M. Klein, P. E., Rummel, Klepper & Kahl, LLP, Baltimore, Maryland Kenneth B. Andromalos, P. E., Brayman Environmental,
Strength Determination of "Tooth-Paste" Like Sand and Gravel Washing Fines Using DMT
Strength Determination of "Tooth-Paste" Like Sand and Gravel Washing Fines Using DMT David L. Knott, P.E. and James M. Sheahan, P.E. HDR Engineering, Inc. 3 Gateway Center Pittsburgh, PA 15222-1074 Phone:
GLOSSARY OF TERMINOLOGY
GLOSSARY OF TERMINOLOGY AUTHORIZED PILE LENGTHS - (a.k.a. Authorized Pile Lengths letter) Official letter stating Engineer's recommended length of concrete piles to be cast for construction of foundation.
Load Testing of Drilled Shaft Foundations in Limestone, Nashville, TN Dan Brown, P.E., Ph.D.
Dan A. Brown and Associates Consulting Geotechnical Engineers 300 Woodland Rd. (423)942-8681 Sequatchie, TN 37374 fax:(423)942-8687 Load Testing of Drilled Shaft Foundations in Limestone, Nashville, TN
Caltrans Geotechnical Manual
Cone Penetration Test The cone penetration test (CPT) is an in-situ sounding that pushes an electronic penetrometer into soil and records multiple measurements continuously with depth. Compared with rotary
UNDERPINNING OF NEW STUDENT HOUSING BUILDING USING MICROPILES, NORTH CAROLINA USA
UNDERPINNING OF NEW STUDENT HOUSING BUILDING USING MICROPILES, NORTH CAROLINA USA John R. Wolosick, P.E.,D.GE 1, Michael W. Terry, P.E. 2, W. David Kirschner 3 and Robert F. Scott Jr. P.E. 4 SYNOPSIS In
vulcanhammer.net This document downloaded from
This document downloaded from vulcanhammer.net since 1997, your source for engineering information for the deep foundation and marine construction industries, and the historical site for Vulcan Iron Works
Table of Contents 16.1 GENERAL... 16.1-1. 16.1.1 Overview... 16.1-1 16.1.2 Responsibilities... 16.1-1
Table of Contents Section Page 16.1 GENERAL... 16.1-1 16.1.1 Overview... 16.1-1 16.1.2 Responsibilities... 16.1-1 16.1.2.1 Geotechnical Section/Bridge Bureau Coordination... 16.1-1 16.1.2.2 Geotechnical
Comprehensive Design Example 2: Foundations for Bulk Storage Facility
Comprehensive Design Example 2: Foundations for Bulk Storage Facility Problem The project consists of building several dry product storage silos near an existing rail siding in an open field presently
LEGACY REPORT ER-5110. www.icc-es.org. ICC Evaluation Service, Inc. Reissued November 1, 2003. Legacy report on the 1997 Uniform Building Code
LEGACY REPORT Reissued November 1, 2003 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900
and the design of construction working platforms
Federation A presentation to the Australian Geomechanics Society Victoria i Branch 11 August 2010 Dr Stephen Buttling Piling rig bearing pressures and the design of construction working platforms 1 The
SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS
July 14, 2015 1.0 GENERAL BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS This work shall consist of furnishing all materials, equipment, labor, and incidentals necessary for conducting bi-directional
The Manitoba Water Services Board SECTION 022180 Standard Construction Specifications PIPE EXCAVATION, BEDDING AND BACKFILL Page 1 of 11
Page 1 of 11 Part 1 General 1.1 DESCRIPTION OF WORK.1 The work described herein shall consist of the excavation of trenches (or excavation of tunnels); the supply and placing of bedding and backfill materials;
Work Type Definition and Submittal Requirements
Work Type: Highway Materials Testing Geotechnical Laboratory Testing, Geotechnical Laboratory Testing, Standard Penetration (SPT) & Rock Coring, Cone Penetration Test, Solid Stem Auger Drilling, and Materials
Dead load (kentledge) A structure over the test pile. Ground anchorage either by tension piles or ground anchors. Bi-directional (Osterberg-cell)
Introduction Fugro LOADTEST Overview STATIC LOAD TESTING O-cell Bi-directional testing State of the art Dr Melvin England Fugro LOADTEST Static load tests Previous/existing technology Developments O-cell
FRANKIPILE. High Pile Loads Optimum Adaptation to Foundation Soil Low-noise Manufacturing Process
FRANKIPILE High Pile Loads Optimum Adaptation to Foundation Soil Low-noise Manufacturing Process The FRANKIPILE Application possibilities The FRANKIPILE can be used in a wide range of foundation soil conditions
Permafrost in Marine Deposits at Ilulissat Airport in Greenland, Revisited
NICOP IX International Conference on Permafrost University of Alaska Fairbanks 2008 Session 28: Cold Regions Infrastructures and Transportation Permafrost in Marine Deposits at Ilulissat Airport in Greenland,
Jack-in Piling Environmental Friendly Piling System
Jack-in Piling Environmental Friendly Piling System Part 1 - Chris Loh 7 Nov 12 CSC HOLDINGS LIMITED Gracious Piling Environmental Friendly Low Noise No Vibration Jack-in Piling How Many Decibels? Permissible
Electronic Soil Test Logging. Strategic Advantage or Unnecessary Headache?
1 Electronic Soil Test Logging Strategic Advantage or Unnecessary Headache? 2 The Plan 3 4 What is it? Digitally Recording Soil Test Data Why? 5 6 Traditional Work Flow Field Digital Entry Sample Review
ATLAS RESISTANCE Pier Foundation Systems
ATLAS RESISTANCE Pier Foundation Systems Foundation Repair Systems for Civil Construction Applications: Residential, Commercial, Industrial Atlas Resistance Piers have been used to restore and/or stabilize
Emergency repair of Bridge B421
Emergency repair of Bridge B421 over the Olifants River after fl ood damage INTRODUCTION AND BACKGROUND Bridge B421 is located on the R555 at km 5.03 on Section 01E between Witbank (now known as emalahleni)
NOTES TO THE PERFORMANCE BASED SPECIFICATION FOR HOTMIX ASPHALT WEARING COURSE SURFACING
TNZ P/23 NOTES: 2005 FOR HOTMIX ASPHALT WEARING COURSE SURFACING 1. BACKGROUND 1.1 Specification Use The specification is to be used where the Engineer requires a dense graded, open graded (permeable)
STATUS REPORT FOR THE SUBMERGED REEF BALL TM ARTIFICIAL REEF SUBMERGED BREAKWATER BEACH STABILIZATION PROJECT FOR THE GRAND CAYMAN MARRIOTT HOTEL
STATUS REPORT FOR THE SUBMERGED REEF BALL TM ARTIFICIAL REEF SUBMERGED BREAKWATER BEACH STABILIZATION PROJECT FOR THE GRAND CAYMAN MARRIOTT HOTEL performed by Lee E. Harris, Ph.D., P.E. Consulting Coastal
1 Mobilisation and demobilisation 1 Deep boring sum 2 Cone penetration tests sum 3 Miscellenous tests sum
Malaysian Civil Engineering Standard Method of Measurement (MyCESMM) CLASS D: SITE INVESTIGATION WORK Measurement covered under other classes: Excavation not carried out for the purpose of soil investigation
Requirements for an Excavation and Lateral Support Plan Building (Administration) Regulation 8(1)(bc)
Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-57 Requirements for an Excavation and Lateral Support Plan Building
SITE INVESTIGATION FACILITIES
SITE INVESTIGATION FACILITIES Drilling Hydraulic rotary & calax drilling rigs100/150mm Diameter boreholes having drilling capacity up to 200m depth. Auger drilling 100/150mm diameter boreholes up to maximum
Appendix A Sub surface displacements around excavations Data presented in Xdisp sample file
Appendix A Sub surface displacements around excavations Data presented in Xdisp sample file Notation B1 = lowest level of basement slab c = cohesion E = drained Young s Modulus Eu = undrained Young s Modulus
patersongroup Geotechnical Investigation Proposed Multi-Storey Buildings 267 O Connor Street Ottawa, Ontario Prepared For Mastercraft Starwood Group
Geotechnical Engineering patersongroup Environmental Engineering Hydrogeology Geological Engineering Materials Testing Building Science Archaeological Services 267 O Connor Street Ottawa, Ontario Prepared
FREDERICK SHERRELL LTD
FREDERICK SHERRELL LTD CONSULTING ENGINEERING GEOLOGISTS AND GEOTECHNICAL ENGINEERS 66 WEST STREET TAVISTOCK DEVON PL19 8AJ Your Ref: Our Ref: 2962.NS.JR Telephone: 01822 612915 Facsimile: 01822 617394
patersongroup Geotechnical Investigation Proposed Residential Development 590 Hazeldean Road - Ottawa Prepared For 2118356 Ontario Inc.
Geotechnical Engineering patersongroup Environmental Engineering Hydrogeology Geological Engineering Materials Testing Building Science Proposed Residential Development 590 Hazeldean Road - Ottawa Archaeological
we are Presence in India
Business areas large-diameter piling bored cast-in-situ piling and hard-rock boring driven cast-in-situ, driven precast and precast spun piles diaphragm walls and cut-off walls secant pile and sheet pile
PLUMBING MAINTENANCE WORK FOR TOILETS IN HEAD OFFICE, SUPPLYCO ESTIMATE
Sl.No. PLUMBING MAINTENANCE WORK FOR TOILETS IN HEAD OFFICE, SUPPLYCO ESTIMATE Description of item Qty Unit Rate Amount 1 Demolishing tile work/cement concrete/( carefully taking out the closet and other
How to Design Helical Piles per the 2009 International Building Code
ABSTRACT How to Design Helical Piles per the 2009 International Building Code by Darin Willis, P.E. 1 Helical piles and anchors have been used in construction applications for more than 150 years. The
The Stabilizer TM. Benefits. www.griptite.com. Supplemental support system for sagging beams and floor joists within a crawl space
The Stabilizer TM Supplemental support system for sagging beams and floor joists within a crawl space Pre-drilled holes in steel plate allow for connection to beam or floor joists. Benefits Levels and
Worked Example 2 (Version 1) Design of concrete cantilever retaining walls to resist earthquake loading for residential sites
Worked Example 2 (Version 1) Design of concrete cantilever retaining walls to resist earthquake loading for residential sites Worked example to accompany MBIE Guidance on the seismic design of retaining
Rehabilitation of Existing Foundation Building to Resist Lateral and Vertical Loads
International Journal of Current Microbiology and Applied Sciences ISSN: 2319-7706 Volume 3 Number 12 (2014) pp. 950-961 http://www.ijcmas.com Original Research Article Rehabilitation of Existing Foundation
Assessment. Ian Uglow Technical Director, SLR Consulting [email protected]. 7 th October 2010
Peat Stability Risk and Hazard Assessment Ian Uglow Technical Director, SLR Consulting [email protected] 7 th October 2010 What goes into a Peat Stability Risk Assessment? You will need: An understanding
A case study of large screw pile groups behaviour
Jongerenforum Geotechniek 5 juni 2015 A case study of large screw pile groups behaviour Alice Manzotti Content of the presentation 2 Introduction General soil conditions at the site Foundation design -
The Impact of Market Demands on Residential Post-Tensioned Foundation Design: An Ethical Dilemma
The Impact of Market Demands on Residential Post-Tensioned Foundation Design: An Ethical Dilemma Bart B. Barrett, B.S., P.E.1 Kerry S. Lee, M.B.A., P.E., M. ASCE2 Erik L. Nelson, Ph.D., P.E., M. ASCE3
Micropiles Reduce Costs and Schedule for Merchant RR Bridge Rehabilitation
Micropiles Reduce Costs and Schedule for Merchant RR Bridge Rehabilitation Jeff R. Hill, P.E. Hayward Baker Inc. 111 W. Port Plaza Drive Suite 600 St. Louis, MO 63146 314-542-3040 [email protected]