1 Building Envelope Overview The design of the building envelope involves many considerations Both indoor and outdoor materials must be durable, resistant to vandalism, easy to maintain, and affordable They must be strong enough to meet structural and seismic codes, yet appear aesthetically pleasing The building enclosure affects acoustic comfort as it can attenuate site and traffic noise The selection of materials for the construction of the building enclosure affects resource efficiency, including transport energy, the volume and type of raw materials that must be extracted from the earth, as well as the energy required for manufacturing and packaging The building enclosure needs to provide a water barrier to keep out the rain, a thermal barrier to reduce heat losses and gains, an air barrier to reduce infiltration, and a vapor barrier to prevent moisture migration and possible condensation within the structure Because of the considerations above, the building envelope is a key aspect of energy-efficient highperformance buildings Solar gains, air leaks, moisture control and thermal (conduction) losses and gains are all affected by the design and construction of the building envelope The building envelope affects the size and types of mechanical systems needed to provide heating and cooling With well designed and constructed building envelopes, perimeter heating systems can usually be eliminated in all but the coldest climates The building envelope and the configuration of spaces within the building also affect the potential to bring daylight into the building and to reduce lighting energy used Of all the building envelope components, the most important is the fenestration (windows and skylights) Fenestration design, including the size and placement of windows and skylights, affects daylighting opportunities, solar gains, cooling loads, and glare Thermal losses and gains through windows are usually the largest building envelope component, typically greater than losses and gains through walls and roofs combined Apart from energy efficiency, the design and construction of the building envelope has a significant effect on occupant comfort Even when heating and cooling systems are large enough to make up for poorly insulated or leaky building envelope, interior surface temperatures may be cold or hot (depending on season), and this affects the radiant temperature of the space Even when the air temperature and humidity within the space are within acceptable bounds, comfort cannot be achieved if an occupant is surrounded by hot or cold surfaces Heat Transfer through the Building Enclosure Heat transfer through envelope components is complex and dynamic The direction and magnitude of heat flow are affected by solar gains from the sun, outdoor temperature, indoor temperature, and exposed surface area Building envelope components have three important characteristics that affect their thermal performance: their U-factor or thermal resistance; their thermal mass or ability to store heat, measured as heat capacity (HC); and their exterior surface condition/finish (for example, are they light in color to reflect the sun or dark to absorb solar heat?) These concepts are explained in greater detail below Also discussed below is the use of radiant barriers to reduce heat transfer in certain situations U-factor The U-factor is the rate of steady-state heat flow It is the amount of heat in British thermal units (Btu) that flows each hour through 1 ft 2 of surface area when there is a 1 F temperature difference between the inside and outside air Heat flow can be in either direction, as heat will flow from the warmer side to the cooler side Insulation and most other building materials affect heat flow equally in both directions, but some construction elements such as radiant barriers may reduce heat flow entering the building, and have little impact on heat leaving the building
2 Steady-state heat flow assumes that temperatures on both sides of the building envelope element (while different) are held constant for a sufficient period so that heat leaving one side of the assembly is equal to heat entering the opposite side The concept of steady-state heat flow is a simplification because, in the real world, temperatures change constantly However, U-factor can predict average heat flow rates over time and is commonly used to explain the thermal performance of construction assemblies Because they are easy to understand and use, the terms for steady-state heat flow (R-values and U-factors) are part of the basic vocabulary of building energy performance Most walls are not homogeneous: often there are wood, metal or concrete framing members that may penetrate the insulation and create thermal bridges Thermal bridges, especially if they are metal, have a significant impact on the performance of the overall assembly, sometimes reducing the insulation effectiveness by more than half The U-factor accounts for thermal bridges and the conductance of every element of the construction assembly, including the air film conductance on the interior and exterior surfaces For light construction frame walls, U-factors provide an adequate description of heat transfer For heavy concrete and masonry walls, however, U-factors are only meaningful for constant temperature conditions The dynamic heat storage properties of concrete and masonry alter the thermal behavior of the wall, and the U-factor becomes less accurate as a predictor of heat flow (see later discussion of Thermal Mass) Thermal performance and U-factors are also affected by the quality of construction It is especially important for the insulation to be in direct contact with the air barrier If there is a gap between the air barrier and the insulation, then air currents can render the insulation virtually useless This is especially a problem in attic knee walls and other similar situations Another common insulation quality issue are voids or gaps in the insulation which are common around electrical equipment and other wall or roof penetrations Yet another problem is insulation compression; if the insulation thickness is reduced through compression, its rated R-value is not achieved Insulation quality problems are widespread the California Energy Commission assumes faulty construction and degrades the U-factor of framed wall, roof, and floor constructions unless they are inspected by an expert R-values R-values are also used to describe steady-state heat flow but in a slightly different way Where U-factor takes account of the overall construction assembly, the R-value is a material property, like density, specific heat, and conductance A larger R-value has greater thermal resistance, or more insulating potential, than a smaller R-value (Of course, the opposite is true with U-factors the lower the better) R-values are widely recognized in the building industry and are used to describe insulation effectiveness The insulation R-value does not describe the overall performance of the complete assembly, however It only describes the thermal resistance of the insulation material Keep in mind that U-factor, not R-value, is what matters and the U-factor is affected by many factors other than the thermal resistance of the insulation material (see previous discussion) The R-value of insulating materials is also dependent on its temperature All insulation is rated at 75ºF (intended to be close to room air) The rated R- value of insulation increases at lower temperatures and lessens at higher temperatures The primary reason for the temperature dependency is that most insulation products consist of trapped air, and while air is a good insulator, its thermal properties change with temperature For example, light density fiberglass batts provide R-32 per in at 75ºF and R-27 per in at 115ºF, which may be the temperature in an attic on a hot day a 16% reduction in the R-value The impact of temperature may be greater with loose fill insulation if the density is not adequate, because convection air currents may occur within the insulation The following table compares and contrasts common insulation types Several criteria should be used when selecting insulation: total installed cost, ease of installation, health and safety issues, sound control, fire resistance, water permeability, and settling Figure E-1: Concept of U-Factor
3 Table E-1: Insulation Comparison Table LOOSE-FILL ( BLOWN-IN ) For use in finished walls or cathedral ceilings, unfinished attic floors, hard to reach places Also can be used for retrofits of existing uninsulated walls Insulation Type R-value/in Cost/ft 2 Advantages Disadvantages Cellulose Low $038 (R-13) $112 (R-38) Fiberglass (34 42) dense-pack Mineral Wool (Rock wool or slag wool) Low $049 (R-11) $122 (R-26) Low $ Forms better air barrier - Continuous insulation barrier for maintaining rated R-value - High use of recycled content - Provides better air barrier - Continuous insulation allows for installation to achieve rating - Non-combustible - Good sound attenuation relative to fiberglass - Weight may cause settling and reduction in R-value over time - High installation costs for wall-cavity - Requires fire-retardant chemicals, which may be impacted by water vapor sorption -May settle over time, though less settling occurs than with cellulose - Higher installation costs - Potential creation of airborne respirable particles BATTS Insulation fitted between frame studs joists and beams Allows for easy installation, but gaps and compression may result in a lower effective R-value Insulation Type R-value/in Cost/ft 2 Advantages Disadvantages Fiberglass Batts Low $048 (R-11) 120 (R-38) unfaced; $ kraft-faced Cotton Batts Medium $050 (R-11) $070 material cost only Plastic fiber (PET) Batts - Low cost and very low installation cost - Good fire protection - High recycled content (~75%) - Recyclable material - Easier handling for installer - Good sound absorption - Causes fewer respiratory problems than fiberglass during installation N/A - Recycled content - Less skin irritation - Known carcinogen - Unfaced only: vapor retarder must be added separately - Water leakage can affect fire retardant - not readily available in some areas - Melts at a lower temperature - More difficult to handle
4 SPRAY-IN FOAMS For use in unfinished walls, attics, and floors and steel framing EPS can be used in basement masonry walls and floors This type costs more than batt insulation, but provides coverage near obstructions and provides a good air barrier Insulation Type R-value/in Cost/ft 2 Advantages Disadvantages Polyurethane foam $175 - High R-value/inch - Provides a vapor barrier Low-density urethane foam 36 $130 - Use water or CO 2 as blowing agent Icynene foam N/A - Suitable for different construction types - Water-blowing agent causes no VOC emission - Good sound attenuation Wet-spray cellulose Low* - High recycled content - Suitable for unfinished spaces with exposed studs Spray-in fiberglass Low* - Popular choice for hard to reach areas Cementitious 39 $150 - Best for coverage near obstructions - Works well at low temperatures - Non-toxic - Non-flammable - No dust - More expensive than batt or loose-fill installations - Use fluorocarbons during production and installation - More expensive than batt or loose-fill installations - May take a couple months to fully dry after installation; excess water may lead to rot or mildew - Overfluffing may allow insulation to reach the desired depth, but with less material, reducing the R-value - Costly to retrofit RIGID FOAMS For use in basement masonry walls and floors, exterior walls, structural panels Rigid panels also provide a continuous thermal insulation barrier Rigid foams are also used as an outer layer of insulation Insulation Type R-value/in Cost/ft 2 Advantages Disadvantages Expanded Polystyrene 39 (1 lb/ft 3 ) 42 (2 lb/ft 3 ) Low Medium $062 $108 Extruded Polystyrene 50 Medium $084 (R-5) $157 (R-15) Polyisocyanurate Medium $079 (R-39)- $202 (R-288) - Good moisture resistance - Maintains its rated R-value - Excellent moisture resistance - R-value increases with low temperatures - Suitable for use in belowgrade applications - High R-value/in - Good compressive strength Polyurethane N/A - High R-value/in Phenolic 82 (closed) 44 (open cell) N/A - Good fire resistance - Uses air as a blowing agent - R-value degrades over time - Shrinkage occurs over time Costs are total installed costs / ft 2 from RS Means 2002 Construction Data, including O&P, unless otherwise specified * Relative cost to other insulation materials of the same insulation type Thermal Mass Mass is another important characteristic that affects the thermal performance of construction assemblies Heavy walls, roofs, and floors have more thermal mass than light ones Thermal mass both delays and dampens heat transfer (see Figure E-2) The time lag between peak outdoor temperature and interior heat transfer is between four and twelve hours depending on the heat capacity of the construction and other characteristics The impact of thermal mass is greater in climates where there is a large temperature difference between night and day (such as mountain and desert climates) Thermal mass has far less impact when outdoor conditions are steadily hot or cold
5 Figure E-2: Time Lag and Damping Effects of Thermal Mass The benefits of thermal mass in stabilizing indoor temperature are greater when the insulation is placed on the exterior side of the construction assembly If the mass is allowed to cool at night, it will absorb heat during the day and reduce the cooling load If the interior thermal mass is exposed to sunlight, it will warm during the day, release the heat at night, and reduce the heating load Thermal mass used in this way is a basic principal of passive solar design and may be appropriate in cold climates Figure E-3 shows examples of common mass wall constructions Figure E-3: Mass Wall Constructions HC is the metric used to quantify thermal mass HC is the amount of heat in Btu that must be added to 1 ft 2 of surface area to uniformly elevate the temperature of the construction by 1 F The units are Btu/ft 2 F HC is the sum of the heat capacity of each individual layer in the wall The heat capacity of each layer is the density of the material times its thickness times its specific heat (all in consistent units) HC can be approximated by multiplying the weight of a square foot of wall, roof, or floor by 02 For example, a wall with a weight of 100 lb/p ft² has an HC of approximately 20 Btu/ft 2 - F Many energy standards (including ASHRAE Standard 901) consider HC as a factor in the overall performance of walls Concrete, which has high thermal mass, does not have a high R-value However, some varieties are better than others Aerated concrete has entrained air bubbles, which makes the concrete lighter and also improve its
6 insulating ability Low-density aggregates such as perlite or vermiculite can also be used to produce lightweight concrete Cool Roofs Heat transfer is also affected by the reflectance and emittance of the exterior surface This is especially important for roofs In fact, the term cool roof is used to describe those with favorable surface characteristics Cool roofs have two key features First, they have a high solar reflectance, which means that they are light in color The high reflectance means that solar radiation is reflected rather than absorbed by the roof surface, keeping the surface temperature lower and reducing heat gain Second, cool roofs have a high (or normal) emittance Emittance is the percentage of energy that is radiated from a surface Galvanized metal and other metallic finishes have a low emittance, which means that when they warm up, they can not easily release their heat by radiating it back to the sky Radiant Barriers One last feature of construction assemblies that deserves some discussion is radiant barriers Many construction assemblies have a large cavity An attic, for instance, is a cavity separating the roof from the ceiling In construction assemblies that have a cavity, much of the heat transfer is radiation from the warmer surface to the colder surface A radiant barrier can significantly reduce this component of heat transfer A radiant barrier is a shiny metallic surface on one or more sides of the cavity that has a low emittance While radiant barriers are most commonly used in attics, they can also be used effectively in exterior walls that are not shaded by overhangs or neighboring buildings Other Building Envelope Performance Factors The thermal performance of the building envelope is only one consideration The building envelope must serve other functions as well It needs to provide a moisture barrier so the rain cannot get in, an air barrier to reduce leakage, and a vapor barrier to control humidity and condensation Moisture (Rain) Barrier Keeping the rain out is perhaps the most basic and fundamental function of the building envelope Providing moisture protection is achieved through selecting water shedding exterior materials; through careful flashing and weeping at building envelope openings such as windows, doors, and junctions between exterior wall materials Caulking is needed for many types of construction Mold can grow in wet or damp construction cavities, attics, and plenums and can contribute significantly to indoor air quality (IAQ) problems In addition, moisture can damage the structure and degrade the performance of insulation, increasing energy and operating costs Air Barriers & Air Retarders Another important function of the building envelope is to keep outside air from entering the building This is the function of the air barrier Typical air barrier materials can include gypsum board or plywood, but the challenge with these materials is to seal the joints between panels Another, perhaps more difficult, challenge is to seal the joints between different construction assemblies such as the joint at windows or floors, etc Because of the difficulty involved in sealing the joints between panels and construction assemblies, modern air barrier designs often include a special layer designed to reduce and control infiltration or air leaks Special air barrier layers or housewraps are thin plastic membranes that are sandwiched between the sheathing and the exterior finish Positioning the air barrier between rigid panels enables the pressure between the inside and the outside of the building to be safely transferred to the building structure without the membrane bellowing Other air barrier systems consist of peel-and-stick membranes that are applied to exterior gypsum board or plywood These are more air impermeable and also provide a vapor barrier Both the terms air barriers and air retarders are commonly used in the design and construction professions, but they mean slightly different things An air barrier is a layer within the construction assembly (eg, exterior plywood sheathing) where half of the total pressure drop between the inside of the building and the outdoors occurs An air retarder, on the other hand reduces airflow, but accounts for less than 50% of the total pressure drop Achieving a continuous airtight barrier is a challenge to both the design and construction teams
7 Vapor Retarders & Vapor Barriers Water vapor can enter the building or construction cavities through the process of water vapor migration Water vapor migrates from the warm and humid side of the construction assembly to the cold dry side of the construction assembly As the water vapor moves through the construction assembly and cools, it may condense into water molecules that can accumulate, cause damage, and support mold growth Building Science Inc has identified three classes of vapor barriers and retarders based on the permeability of the material (see sidebar and Table E-2) Class I materials have a permeability of 01 or less Class II materials have a permeability of 10 or less Both are considered impermeable and are considered vapor barriers Class III materials have a permeability of 100 or less and are considered vapor retarders, rather than vapor barriers To prevent or reduce water vapor migration, a vapor barrier or retarder should be installed within the construction assembly in most climate zones For colder climates, a vapor barrier should be on the interior side and in hot humid climates a vapor barrier should be on the exterior side of the wall Table E-3 has recommendations for all the climate zones In addition to correctly installing a vapor retarder, it is also important to adequately ventilate spaces where moisture can build up Most building codes require that attics and crawl spaces be ventilated, and some require a minimum 1- in clear airspace above the insulation for ventilation of vaulted ceilings Even the wall cavity may need to be ventilated in extreme climates A vapor barrier should be installed under slabs with ventilated gravel in areas with soil gas contaminants like radon or methane Vapor barriers should also be installed under slabs to mitigate ground moisture Table E-2:Types and Classifications of Vapor Barriers Type Description Class Perms Examples I 01 or less Rubber membranes, polyethylene film, glass, aluminum foil, sheet metal, oilbased paints, vinyl wall coverings, and foil-faced insulating sheathings Vapor Barrier Impermeable II 10 or less Vapor Retarder Semi- Permeable III 100 or less Breathable Permeable more than 100 Plywood, oriented strand board, unfaced expanded polystyrene, fiberfaced isocyanurate, heavy asphalt impregnated building papers, the paper and bitumen facing on most fiberglass batt insulation and most latex based paints Unpainted gypsum board and plaster, unfaced fiberglass insulation, cellulose insulation, unpainted stucco, lightweight asphalt impregnated building papers, asphalt impregnated fiberboard, exterior gypsum sheathings, cement sheathings, and housewraps Source: Joseph Lstiburek Understanding the Terms Barrier and Retarder for Vapor and Air, February 2002 Terminology Moisture Barrier A set of building envelope components designed to prevent rain from entering the building Vapor Barrier An impermeable membrane (perm rating 10 or less) that blocks moisture migration through construction assemblies Examples include vinyl wall coverings, oil based paints, and aluminum foil Vapor Retarder A semi-permeable material (perm rating of 100 or less) that retards but does not block moisture migration Examples include asphalt impregnated building papers Smart Vapor Barrier A material that has a low permeability when exposed to dry conditions (relative humidity in the range of 30% to 35%) and becomes semi permeable when exposed to more humid conditions (relative humidity above 50%) Air Barrier Systems of materials that completely enclose the air within a building To qualify as an air barrier, 50% of the pressure drop across the entire construction assembly must occur at the air barrier layer Air Retarder A system of materials that reduce airflow or control airflow across the assembly, but account for less than 50% of the pressure drop across the entire assembly Source: Joseph Lstiburek Understanding the Terms Barrier and Retarder for Vapor and Air, February 2002
8 Table E-3:Vapor Barrier Design Recommendations* Climate Region Climate Zone Vapor Barrier Type and Location Hot-Humid Hot-Dry Mixed-Humid Marine Mixed-Dry Climate Zones 1A + 2A + 2B + 3A below the white Warm-Humid line ( A represents the moist portion of the DOE temperature zones) Climate Zones 2B + 3B ( B represents the dry portion of the DOE temperature zones) Climate Zone 4A + 3A above the white Warm-Humid line Climate Zones 3C + 4C Climate Zone 4B Cold Climate Zones Very Cold Climate Zone 7 Subarctic/Arctic Climate Zone 8 Class II vapor barriers (or vapor retarders) are required on the warm summer side of assemblies that are not ventilated and are not required on the warm winter side of any assemblies Vapor barriers are not required *See Figure 1-2, Advanced Buildings Climate Zones, for map Source: Joseph Lstiburek Understanding the Terms Barrier and Retarder for Vapor and Air, February 2002 Class III vapor barriers (or vapor retarders) are required on the warm winter side of all assemblies Class II vapor barriers are required on the warm winter side of all assemblies Class I vapor barriers are required on the warm winter side of all assemblies Integrated Solutions The air barrier, the vapor barrier, and the thermal barrier (insulation) should work together For the insulation to be effective, it must be in direct contact with the air barrier so that live air currents cannot occur, which would shortcut the effectiveness of the insulation Obviously, the benefit of insulation is negated if the wall or roof assembly has holes through which air can freely pass Another challenge in air barrier design is to provide a means for the pressure difference between the inside and the outside of the building to be safely transferred to the building structure Depending on the climate and the position of the insulation, the vapor barrier and the air barrier may be the same thing For instance, a common wall construction technique that works in most climates is to place a peel and stick combination air barrier and vapor barrier on the exterior side of the building sheathing A rigid insulation is them placed over this and then the exterior finish material, eg, brick, stucco, siding, etc This system works in most climates Fenestration Products High-performance fenestration features include double glazing, low-emittance coatings, blue/green tints, and advanced frame construction These have become a very important means of energy conservation in modern construction to reduce both thermal losses and solar gains Fenestration has three principal energy performance characteristics, which have been identified by the National Fenestration Rating Council (NFRC) to be tested and labeled on manufactured windows: Visible light transmittance (VLT), solar heat gain coefficient (SHGC), and U-factor NFRC ratings may not be available for some fenestration products (in particular site-built windows and skylights) VLT is the fraction of light that is transmitted through the glazing Light is that portion of solar radiation that is visible, meaning it has a wavelength between about 380 and 780 nanometers Single clear glass has a VLT of about 090, while highly reflective glass can have a VLT as low as 005 The quantity of daylight that enters a window or skylight is directly proportional to the VLT In general, VLT should be as high as possible, provided it does not create glare or other visibility problems SHGC measures the solar heat gain through a window A window that has no solar gain would have a SHGC value of zero, while a perfectly transmissive glazing would have a SHGC of 10 These extremes are both theoretical concepts that are not possible in the real world Except in passive solar applications where solar heat gain is desired, everything else being equal, glazing materials should be selected with the lowest possible SHGC However, glazing materials with a low SHGC (like dark gray and bronze tints)
9 may also have a low VLT, so the challenge is to identify specialized selective low-e products and blue/green tints that combine the lowest SHGC with the highest VLT Shading coefficient (SC) is the ratio of heat gain through the glazing compared to 1/8 in clear, double strength glass As a measurement, SC is being replaced by SHGC, which is the preferred measurement to quantify heat gain U-factor measures the heat flow through a window assembly due to the temperature difference between the inside and outside The lower the U-factor, the lower the rate of heat loss and of heating energy consumption Everything else being equal, the U-factor should be as low as possible The fenestration frame and glazing edge spacers degrade the U-factor of an insulated glass assembly So two U-factors are frequently specified: the center of glass (COG) value, which is the U-factor measured at the center of the assembly, and the whole-window value, which is the overall U-factor of the glazing plus the spacer and frame system (The whole-unit value will usually be higher than the COG value) Single pane windows typically have a U-factor in the range of 10 to 12 COG; double pane windows range from 065 to 045 COG With low-e coatings, inert gas fills, and multiple glazings, the U-factor can be as low as 01 COG Other glazing considerations include diffusion, transparency, and durability: Diffusion and Transparency Transparent glazing materials provide views, but diffuse materials can spread daylight better in the space Diffusion is one of the most important characteristics in selecting a skylight Good diffusing glazings maximize the spread of light in the space and minimize hot spots and glare Diffusion may be accomplished by using a white pigment, a prismatic surface, or embedded fibers Unfortunately, specifications on diffusion properties are rarely available for fenestration products Thus, samples of diffusing glazing materials should be visually evaluated to see how well they diffuse direct sunlight A simple test is to place the product in the sun and see if it allows your hand to cast a shadow A fully diffusing material will blur the shadow beyond recognition and will not concentrate the sunlight into local hot spots Note that diffusing glazing placed in direct sunlight can be glaringly bright if it is within the field of view It should be placed above the direct line of sight or be obscured by baffles Durability Characteristics such as ultraviolet (UV) degradation (yellowing and other aging effects), structural strength, scratch resistance, breaking and fire resistance, along with replacement cost and availability, should be considered in selecting a glazing material The frame holds the glazing material in place and forms the structural link with the building envelope The frame and the spacer between the glazing panes in multiple glazed units form a thermal short circuit in the insulating value of the fenestration This degradation of the U-factor at the fenestration perimeter can be minimized with high-performance frame and spacer technologies now available This is important both for energy conservation and the potential for condensation on the frame Frames are available in metal, wood, vinyl, composite, and fiberglass Metal frames conduct the most heat and must have a thermal break for good performance Insulated vinyl and fiberglass frames have the lowest U- factor The NFRC has established a rating system to evaluate the whole window performance including the frame, spacer, and glazing More information can be found at wwwnfrcorg See also Basic Criteria 16: Window, Door & Skylight Certification The whole-window U-factor, VLT, and SHGC is shown on a label attached to all rated windows Design Tools The thermal performance of construction assemblies can be calculated in many ways The appropriate method depends on the type and complexity of the construction assembly The basic calculation methods include: Series Calculation Method is the easiest way of calculating U-factor, but its use is limited to constructions that have no framing and are made of homogenous materials Parallel Path Calculation Method, a simple extension of the series calculation method, can be used for wood-framed assemblies You separately calculate the U-factor through the solid wood and the insulated cavity and take the weighted average
10 Effective R-Value (Isothermal Planes) Method uses principles similar to the series and parallel path calculation methods and is appropriate for construction assemblies such as concrete masonry and metalframed walls/roofs where highly conductive materials are used in conjunction with insulated or hollow cavities Two-Dimensional Calculation Method may be used to accurately predict the U-factor of a complex construction assembly Calculating two-dimensional heat flow involves advanced mathematics and is best performed with a computer Testing is the most accurate way to determine the U-factor for all types of construction, except slabs-ongrade But it is costly and time consuming, and because a large variety of possible construction assemblies exist, it is impractical to test them all Often, testing is used for generic construction assemblies and calculations are used to adjust these results for other situations More details on these calculation methods can be found in the American Society of Heating, Refrigeration, and Air-Conditioning Engineers (ASHRAE) Handbook Fundamentals Table E-4 provides guidance on which method can be used with different types of construction assemblies Table E-4: Acceptable Procedures for Determining U-Factors for Opaque Assemblies Series Calculation Method Parallel Path Calculation Method Effective R-value (Isothermal Planes) Two-Dimensional Calculation Method Testing Roofs Insulation above Deck Attic (wood joists) Attic (steel joists) Other Walls Mass Wood Framed Steel Framed Other Below-Grade Walls Mass Other Floors Mass Steel Joist Wood Framed Other Computer Programs The calculation methods described above are implemented in a number of design tools and computer programs General-purpose energy simulation programs such EnergyPlus can be used to calculate the energy savings of various construction assemblies With these programs, the dynamics of heat transfer are modeled In fact, EnergyPlus models the temperature gradient in constructions DOE-2, on the other hand, uses a more simple response factor method The Therm program available from Lawrence Berkeley National Laboratory is designed primarily to analyze window frames, but can be used for any type of two-dimensional heat transfer analysis This program can be downloaded from
11 The EZFrame program, available from the California Energy Commission (CEC), can be used to calculate the U-factor of metal framed wall and roof constructions and accounts for many features such as the gauge of the steel used for framing members, the percent of knockouts in the web, and insulating tape between the framing members and the sheathing Web site: wwwenergycagov/efficiency/computer_prog_listhtml Pre-Calculated Data The U-factor of common constructions has been pre-calculated, and values are published in a number of sources Appendix A of ASHRAE Standard has published values in both inch-pound and metric (SI) units Constructions include walls, roofs, floors, slabs, and below-grade walls These values are also contained in the EnvStd 40 computer program, which can be downloaded from wwwarchenergycom
Presented by: Jennifer Doyle, P.E., RRC, LEED AP
Presented by: Jennifer Doyle, P.E., RRC, LEED AP Moisture Gas: Molecules are spread out "Vapor" suspended in air forms a mixture, present everywhere Liquid: Molecules are closer Rain Condensation Pipes
Article. Protecting the Building Envelope from Water Damage. MemBrain Smart Vapor Retarder & Air Barrier Film
Article Protecting the Building Envelope from Water Damage Vapor Retarders Play a Crucial Role in Moisture Management Whether we like it or not, moisture in the form of water vapor diffusion and humid
Renovating Your Basement
building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:
1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
1/9/13 By Brett T. Fagan, P.E. Presented by Marie Horan, P.E. Building Diagnostics, Inc. Building Diagnostics Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
Housing Fact Sheets. Insulation Check-Up
Insulation Check-Up Housing Fact Sheets Introduction Heating and cooling account for the majority of energy costs in homes throughout the United States. Although current energy prices are relatively low,
*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.
Dow Chemical is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members.
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
Molds and mildew are fungi that grow
Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate
Residential Windows, 3 rd edition Corrected index 1
Residential Windows, 3 rd edition Corrected index 1 A absorptance definition, 78 determinants of, 78 79 energy performance and, 78 tinted glass, 84 acoustical properties of windows, 60 61 acrylic glazing
Signs of insulation problems In the winter. In the summer. conditioning system
about your house CE 19 While previous generations may have been content to live in drafty houses, most people now want comfortable warm houses. A healthy house today is well sealed, well insulated and
) and air spaces (R a
5.3.3 Thermal Resistance (R-value) Common thermal properties of materials and air spaces are based on steady state tests, which measure the heat that passes from the warm side to the cool side of the test
Selecting Energy Efficient New Windows in Georgia
Selecting Energy Efficient New Windows in Georgia www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.
Selecting Energy Efficient New Windows in Arizona
Selecting Energy Efficient New Windows in Arizona www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.
In the Fall 2002 issue of HHE News I examined
Choosing Replacement Windows 1 For Your Home Mark Pierce In the Fall 2002 issue of HHE News I examined reasons for, and against, replacing older windows with new, energy efficient windows. That article
Basements are Changing. Basements Part of the Enclosure. Basements. Energy Efficient, Durable, Healthy. Below grade enclosure
Basements are Changing John Straube, Ph.D., P.Eng Basements: New & Retrofit Energy Efficient, Durable, Healthy Increasingly used as living space Not a root /coal cellar anymore! High quality space expected
Selecting Energy Efficient Replacement Windows in Nevada
Selecting Energy Efficient Replacement Windows in Nevada www.efficientwindows.org January 06 STAR Zones. Meet the Energy Code & Look for the STAR Windows must comply with your local energy code. Windows
Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction
T e c h n i c a l n o t e Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction Number J450 February 2009 Controlling against moisture damage in structures depends upon proper system
Introduction. 1. Heat Transfer. In Townsville s climate it is essential to choose building materials that perform well in our local conditions.
In Townsville s climate it is essential to choose building materials that perform well in our local conditions. Choosing the correct materials and insulation will improve the overall thermal performance
solutions & tips six Wise Energy Guide Building envelope solutions and simple tips AIR SEALING
Wise Energy Guide solutions & tips 32 AIR SEALING Is your house leaking money? six Building envelope solutions and simple tips If your home is like most, the greatest amount of heat loss is from air leakage;
Insulation R-Value Comparisons
Insulation R-Value Comparisons American Ingenuity s component panels for the 22 48 domes contains seven inch thick rigid Expanded Polystyrene (E.P.S.) insulation which has an R value of 28. American Ingenuity
Foundation. Foundation
Moisture Aside from structural concerns, the most important consideration for foundation design is moisture. No client wants a wet basement. No client wants a damp basement. No client wants mold in their
2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
Basement Insulation Systems
Basement Insulation Systems The Problem Meeting Energy Star levels of performance is one of the criteria for constructing homes to Building America levels of performance levels defined by the Building
Comment Form on Proposed Gut Rehabilitation Alternatives
Comment Form on Gut Rehabilitation Alternatives Name: Organization: Email: Instructions Submission: Please submit this form to [email protected] by October 10 th, 2012 with the subject line
research highlight Highly Energy Efficient Building Envelope Retrofits for Houses
research highlight June 2012 Technical Series 12-103 Highly Energy Efficient Building Envelope Retrofits for Houses introduction In Canada approximately 30% of all energy is consumed in buildings, with
Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION
Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION The Condensation Process Condensation occurs when warmer moist air comes in contact with cold surfaces such as framing members, windows
Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit
R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed
03/05/14 REVISOR RSI/JC RD3945
1.1 Department of Commerce 1.2 Proposed Permanent Rules Relating to Commerce; Thermal Insulation Standards; 1.3 Materials and Installation 1.4 7640.0100 AUTHORITY; PURPOSE; INCORPORATIONS BY REFERENCE.
Heating Load Calculation
Heating Load Calculation ME 425 Air Conditioning System Design Keith E. Elder, P.E. Heating Load Calculation The heating load calculation begins with the determination of heat loss through a variety of
EcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
ROOFS, SNOW AND ICE DAMS
ROOFS, SNOW AND ICE DAMS The Problem Ice dams are a common roof performance problem in cold climate buildings. Simply put, they are ridges of ice and icicles caused by melt water from further up the roof
Field Performance of Different Interior Basement Insulation Systems
Field Performance of Different Interior Basement Insulation Systems Marc Zuluaga Robb Aldrich Dianne Griffiths, P.E. Associate Member ASHRAE ABSTRACT With the support of the Department of Energy s Building
2009 IECC Update. Scope. Content. International Energy Conservation Code
2009 IECC Update International Energy Conservation Code Scope The code applies to both residential and commercial buildings. In the code, the United States is divided into eight climate zones which are
Performance of 8 Passive House Envelopes in Cold Climates
7 th Annual North American Passive House Conference September 27-30, 2012 Denver CO Performance of 8 Passive House Envelopes in Cold Climates Rolf Jacobson, LEED AP CSBR, University of Minnesota ZEB, Norwegian
DEFAULT HEAT LOSS COEFFICIENTS
DEFAULT HEAT LOSS COEFFICIENTS SECTION A101 GENERAL REQUIREMENTS A101.1 Scope. The following defaults shall apply to Chapter 4 of both the (RE) and (CE) sections of the IECC. This chapter includes tables
R-Value and Densities Chart
R-Value and Densities Chart Material R-Value Per Inch R-Value Per Unit Inside Air Film 0.68 Air Space between Studs 0.95 Building Pa 0.06 ½ in. Fiberboard Sheathing 1.52 Gypsum Wallboard or Drywall 0.90
Insulating Basements: Part 3 Basement Wall Systems
The Pennsylvania Housing Research Center Insulating Basements: Part 3 Basement Wall Systems Builder Brief: BB0710 Brian Wolfgang, PHRC Fellow INTRODUCTION The perception of a basement has changed significantly
R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2B Energy & IAQ (2009) Related TEK: 6-1B, 6-11, 6-12C INTRODUCTION
An information series from the national authority on concrete masonry technology R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS TEK 6-2B Energy & IAQ (2009) INTRODUCTION Single wythe concrete
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM
CITY PLAN REVIEW AND INSPECTION Lisa Fleming Brown, CPM Houston Commercial Energy Conservation Code (2011) A choice of 2009 IECC or ASHRAE 90.1-2007 with amendments. Effective September 2, 2011. Complete
Selecting Energy Efficient New Windows in Texas
Selecting Energy Efficient New Windows in Texas www.efficientwindows.org January 06 Zones. Meet the Energy Code & Look for the Windows must comply with your local energy code. Windows that are certified
R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2C Energy & IAQ (2013) Related TEK: 2-5B, 6-1C, 6-4B, 6-11A, 6-12C, 6-12D, 6-12E
An information series from the national authority on concrete masonry technology R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS TEK 6-2C Energy & IAQ (201) INTRODUCTION Single wythe concrete
Insulation Products For Residential Thermal Applications ROXUL. Better Best ROXUL. Solutions For Residential Thermal Applications.
ROXUL Insulation Products For Residential Thermal Applications Better Best ROXUL Solutions For Residential Thermal Applications. Better Best Better. Best. This thermal guide to ROXUL Insulation s Better
The Optimum Basement Wall
The Optimum Basement Wall Solutions to the Wet Blanket Basement Problem February 27 th, 2014 1 Adapting to Change! We ve made significant advances in water management. Customers no longer accept that musty
Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls
PCA R&D Serial No. 415 Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls by John Gajda and Martha VanGeem 000 Portland Cement Association KEYWORDS Concrete,
Uncovering Myths and Opportunities of Advanced Building Envelope Technologies: BIPV, Roofing and Windows
Uncovering Myths and Opportunities of Advanced Building Envelope Technologies: BIPV, Roofing and Windows Marc LaFrance Technology Development Manager US Department of Energy Building Technology Program
Underwriters Laboratories Testing Information
Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
Spandrel Glass Types and Recommendations
Spandrel Glass Types and Recommendations Introduction PPG has long offered recommendations regarding alternatives for glass spandrel applications. Over the years these recommendations were included in
BEST 2 WB 3 4 SIX WAYS FOR CONDENSATION IN BUILDINGS. Wagdy Anis, FAIA, LEED ap*
BEST 2 WB 3 4 SIX WAYS FOR CONDENSATION IN BUILDINGS Wagdy Anis, FAIA, LEED ap* Abstract: Six of the ways condensation can occur on cold surfaces in buildings are discussed here. They are: 1. Air Leakage,
CHAPTER 6: WINDOWS AND DOORS
Chapter 6: Windows and Doors 89 CHAPTER 6: WINDOWS AND DOORS Windows and doors connect the interior of a house to the outdoors, provide ventilation and daylight, and are important aesthetic elements. Windows
Windows are one of the most important components of a
design concepts Arjun Kamal MAKING BETTER INDOOR ENVIRONMENTS WITH ENERGY-EFFICIENT WINDOW DESIGN An insight into the various technologies used for constructing windows, and an attempt at understanding
Selecting Energy Efficient New Windows in Florida
Selecting Energy Efficient New Windows in Florida www.efficientwindows.org January 06 Zones. Meet the Energy Code & Look for the Windows must comply with your local energy code. Windows that are certified
Energy Code Compliance With SIPs. Frank Baker, PFB Corporation Don Ferrier, Ferrier Custom Homes
Energy Code Compliance With SIPs Frank Baker, PFB Corporation Don Ferrier, Ferrier Custom Homes Outline Overview of 2009 and 2012 energy codes Code compliance with SIPs Reducing air infiltration with SIP
IECC Compliance Guide for Homes in Virginia
IECC Compliance Guide for Homes in Virginia Amended Version of 2012 International Energy Conservation Code July 14, 2014 Climate Zone Since the entire state of Virginia falls in the IECC Climate Zone 4,
OUTSTANDING CHARACTERISTICS OF TEKFOIL HI-PERFORMANCE REFLECTIVE INSULATION
OUTSTANDING CHARACTERISTICS OF TEKFOIL HI-PERFORMANCE REFLECTIVE INSULATION Unaffected by ultraviolet rays Environmentally safe Nontoxic Nonallergenic Anti-static Stops air infiltration Better ventilation
Answers to Your Questions from the Webinar
2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in
State of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
Adaptive strategies for office spaces in the UK climate
International Conference Passive and Low Energy Cooling 631 Adaptive strategies for office spaces in the UK climate I. Gallou Environment & Energy Studies Programme, Architectural Association Graduate
Best Practices for Crawl Space Insulation
Best Practices for Crawl Space Insulation Copyright 2011 Basement Systems Inc. All Rights Reserved Table of Contents I - Introduction II - Step By Step Guide 1 - Providing Adequate Drainage 2 - Controling
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
Residential Weatherization Plus Program
Since 1982, Cowlitz PUD has been helping its customers reduce their monthly electric bills and make their homes more comfortable through our weatherization programs. Under the current program Residential
The Case for Cross Laminated Timber: Part 2
Learning Objectives The Case for Cross Laminated Timber: Part 2 Opportunities and Challenges for a New Class of Timber Product 1. Review answers to common questions regarding the design and construction
Selecting Energy-Efficient Windows
Selecting Energy-Efficient Windows E N E R I N F O A D V I S O R S E R I E S Key Points Improving the energy performance of windows is important, since windows are the least insulated surface of most homes.
ENERGY SMARTS: ENERGY EFFICIENT WINDOWS
Practical solutions for a complex world. ENERGY SMARTS: ENERGY EFFICIENT WINDOWS Leona K. Hawks, Professor Extension Specialist Housing & Environment College of Natural Resources Utah State University
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
United States. Why You Should Insulate Foundations. There is a science to adding value.
United States R E S I D E N T I A L Why You Should Insulate Foundations. There is a science to adding value. Built On Science. STYROFOAM* extruded polystyrene and polyisocyanurate insulations from Dow
National Building Code of Canada 2010
National Building Code of Canada 2010 Emergency Change Issued by the Canadian Commission on Building and Fire Codes The table that follows lists two emergency changes that apply to the National Building
windows energy-efficient choices
windows energy-efficient choices taking responsibility As an individual, your efficient use of energy brings benefits such as lower bills, improved comfort levels in your home and a reduced personal impact
2015 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY
MINNESOTA ENERGY CODE COMPLIANCE COLLABORATIVE 2015 Minnesota Residential Energy Code (MR 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY (July 15, 2015 Update) Note: The following information contains
Energy Savings with Window Retrofits
Center for Energy and Environment Energy Savings with Window Retrofits Presentation to Energy Design Conference & Expo Duluth, MN February 25, 2014 Agenda v Background v Introduction: What are window retrofits?
Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature
Thermal Values Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature relative to changing exterior temperatures. By reducing interior temperature
A Kingspan Summary of a Building Science Corporation Report
Insulated Panels REVIEW & ANALYSIS OF EXTERIOR WALL ASSEMBLY PERFORMANCE A Kingspan Summary of a Building Science Corporation Report REVIEW & ANALYSIS OF EXTERIOR WALL ASSEMBLY PERFORMANCE Exterior Wall
Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance
Building Energy Codes 101 October 23, 2013 Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance OVERVIEW 1. Introduction 2. Energy Code Development 3. Adoption Process 4. Elements
Post-insulation of cellar ceiling and cellar walls
WP5 Education and Economic Promotion Post-insulation of cellar ceiling and cellar walls Educational product: New lecture material for training modules dealing with knowledge and skills how to apply suitable
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
Basic B.S. (building science) insights for. Spray Foam, HVAC and Moisture
Basic B.S. (building science) insights for Spray Foam, HVAC and Moisture Claudette Hanks Reichel, Ed.D. Professor and Extension Housing Specialist Director, LaHouse Resource Center When the blind leads
HEAT FLOW BASICS. J. F. Straube
HEAT FLOW BASICS Heat flows from hot to cold. Always. Within air conditioners and heat pumps this process is manipulated to make it appear that the opposite occurs. Temperature a measure of thermal energy,
Mold Preventing I nterior System
interior insulation and renovation boards A system of components that have been designed to work perfectly together to repair damage caused by mold. The system consists of boards, insulation wedges, reveal
Fiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
Roof Insulation Building. Energy. Environment friendly e-library
Roof Insulation Building Codes & Energy Efficiency Environment friendly e-library Building Code Driver Buildings consumer almost 50% of all energy. Experts believe that a 30% increase in building efficiency
AIRCONDITIONING Cooling Loads Calculations
Calculations -1- AIRCONDITIONING Cooling s Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example (p. 18.37)
The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A
TechSpecs A builder s blueprint for construction technologies January 2013 The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A C B A E D H G F A. Wood Floor Framing - p. 2 B. Foundation
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
Preventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
Open-cell spray foam & what every contractor
Open-cell spray foam & what every contractor should know Overview Open-cell or Closed-cell? The age old question that many stumped - from industry bloggers to homeowners - is whether to choose opencell
ECHO System for Basements
ECHO System for Basements Homeowners looking for more space are all too familiar with the cold, damp and dingy basement. Now, the Enclosure Conditioned Housing (ECHO) System TM, winner of the Ottawa-Carleton
HOW AN ENERGY EFFICIENT HOME CAN HELP THE ENVIRONMENT
HOW AN ENERGY EFFICIENT HOME CAN HELP THE ENVIRONMENT During the last century, concern about the environment increased, as issues such as global warming and the Greenhouse Effect convinced us that the
Continuous Insulation Using Polyiso Wall Sheathing
PIMA Technical Bulletin #403 Continuous Insulation Using Polyiso Wall Sheathing What it is, what it does, and why you need it About Polyiso Insulation Polyiso is a rigid foam insulation used in over 70%
Housing Fact Sheets. Energy Saving Window Treatments
Housing Fact Sheets Energy Saving Window Treatments Windows are a major source of heat loss but they are necessary for light, ventilation, and view. In a typical single family home, about 20% of the heat
Common Problems with Walls
Common Problems with Walls Common Problems with Walls There are problems and concerns that are shared by all walls and siding installations. In this article, we will learn about the following commonly
In accordance with the Department of Labor and Industry s statute 326.0981, Subd. 11,
In accordance with the Department of Labor and Industry s statute 326.0981, Subd. 11, This educational offering is recognized by the Minnesota Department of Labor and Industry as satisfying 1.5 hours of
Mississippi. Energy and Cost Savings. for New Single and Multifamily Homes: 2009 and 2012 IECC as Compared to the 2006 IECC
BUILDING TECHNOLOGIES PROGRAM Mississippi Energy and Cost Savings for New Single and Multifamily Homes: 2009 and 2012 IECC as Compared to the 2006 IECC 1 2009 AND 2012 IECC AS COMPARED TO THE 2006 IECC
Energy efficiency - Always compare whole window performance and not just the individual components.
EnErgy E fficiency See back for Tax Credit information. Energy efficiency - Always compare whole window performance and not just the individual components. Windows have played an important role in home
Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi
Climate and Energy Responsive Housing in Continental Climates The Suitability of Passive Houses for Iran's Dry and Cold Climate Farshad Nasrollahi Table of Contents Abstract German Abstract Introduction