Variable Refrigerant Flow: An Emerging Air Conditioner and Heat Pump Technology
|
|
|
- Estella Ferguson
- 10 years ago
- Views:
Transcription
1 Variable Refrigerant Flow: An Emerging Air Conditioner and Heat Pump Technology Ammi Amarnath, Electric Power Research Institute Morton Blatt, Energy Utilization Consultant ABSTRACT This paper reviews the attributes of an emerging space conditioning technology; variable refrigerant flow (VRF) systems. Material presented in this paper was synthesized from the open literature, private interviews with industry experts and data (sometimes proprietary data) obtained from manufacturers. VRF systems are enhanced versions of ductless multi-split systems, permitting more indoor units to be connected to each outdoor unit and providing additional features such as simultaneous heating and cooling and heat recovery. VRF technology uses smart integrated controls, variable speed drives, refrigerant piping, and heat recovery to provide products with attributes that include high energy efficiency, flexible operation, ease of installation, low noise, zone control, and comfort using all-electric technology. VRF systems are very popular in Asia and Europe and, with an increasing support available from major U.S. and Asian manufacturers are worth considering for multi-zone commercial building applications in the U.S. This paper provides an overview of variable refrigerant flow system technology, including the market situation, advantages and disadvantages for the customer, possible impact on the electric utility, applications recommendations, and technology attributes. Also addressed are what is holding back the technology, including lack of verified third party field data; codes and standards issues; technology improvements needed; and market actions needed to increase penetration of these systems. Evolution of the Technology Ductless space conditioning products, the forerunner of multi-split and VRF systems, were first introduced in Japan and elsewhere in the 1950s as split systems with single indoor units and outdoor units. These ductless products were designed as quieter, more efficient alternatives to window units (Smith, 2007). Products have evolved from a few indoor units operating off each outdoor unit, to multisplit products with 4 units to 8 units in the late 1980s, to 16 units in the early 1990s, to 32 units by Today s advanced systems permit as many as 60 or more indoor units to operate off one outdoor unit, enabling application in large commercial buildings. Electronically commutated motors, inverter-driven/capacity modulated scroll compressors, multiple compressors, versatile configurations and complex refrigerant and oil circuitry, returns, and controls have enabled this addition of up to 60 indoor units. Refrigerants have also changed. The early mini-split systems used R-22 refrigerant, then R-407C, and today s systems rely on R-410A. Figure 1 shows the piping and refrigerant flow for conventional split systems (one indoor and one outdoor unit) multi-split systems, and variable refrigerant flow systems (Dyer, 2006). Multi-splits offer some of the major advantages of VRF systems, such as zoning, capacity control, ease of retrofit, low installation costs, and minimizing ducting and use of secondary 3-1
2 fluids and associated costs and losses. On the other hand, their simpler piping results in longer total length of piping compared to VRF systems. Similarly, multi-split heat pumps do not have the opportunity for heat recovery between units that are cooling and units that are heating. As such, multi-split systems should be considered for smaller, simpler buildings where heat recovery is not a possibility and fewer numbers of zones need to be conditioned. How Does VRF Work? Multi-splits include multiple indoor units connected to a single outdoor unit. Ductless products are fundamentally different from ducted systems in that heat is transferred to or from the space directly by circulating refrigerant to indoor units (evaporators or condensers) located near or within the conditioned space. (When the indoor units are in the cooling mode they act as evaporators and when they are in the heating mode they act as condensers.) In contrast, conventional ducted systems transfer heat from the space to the refrigerant by circulating air (in ducted systems) or water (in chillers) throughout the building. VRF systems are enhanced versions of ductless multi-split systems, permitting more indoor units to be connected to each outdoor unit and providing additional features such as simultaneous heating and cooling and heat recovery. VRF heat pump systems permit heating in all of the indoor units, or cooling of the all the units, not simultaneous heating and cooling. Heat recovery systems provide simultaneous heating and cooling as well as heat recovery to reduce energy use during the heating season. Over the past 15 years the technology has advanced in a number of areas: Standard compressors to variable speed and capacity modulated scroll compressors Direct driven outdoor fans to variable frequency drive, inverter-driven fans Direct driven indoor coil motors to direct current or ECM-type motors Variable capacity indoor units Better heat exchanger surfaces with multi-segmented coils Improved controls and diagnostics R-22 to R-410A Better refrigerant charge and oil management Other features include the addition of concealed ducted units and ceiling cassette configurations to the traditional wall-mounted units. Refrigerant piping runs of more than 200 feet are possible and outdoor units are available in sizes up to 240,000 Btu/ hr. 3-2
3 Figure 1. Split, Multi-Split and VRF Operation in a 4 Zone Building (Cooling Mode) 3-3
4 Figure 2 shows a single outdoor unit and a general schematic of multiple indoor units in a VRF heat pump system. The indoor units include wall mounted, floor mounted, ceiling cassette and concealed ducted configurations. The term variable refrigerant flow refers to the ability of the system to control the amount of refrigerant flowing to each of the evaporators, enabling the use of many evaporators of differing capacities and configurations, individualized comfort control, simultaneous heating and cooling in different zones, and heat recovery from one zone to another. Most VRF condensers use variable frequency drives to control the flow of refrigerant to the evaporators. Refrigerant flow control lies at the heart of VRF systems and is the major technical challenge as well as the source of many of the system s advantages (Goetzler, 2007). In most cases, two-pipe systems can be used effectively (in VRF heat pump systems) when all the zones in the facility require cooling or all require heating during the same operating period. Three-pipe (a heating pipe, a cooling pipe and a return pipe) systems work best when there is a need for some of the spaces to be cooled and some of them to be heated during the same period. (This often occurs in the winter in medium-sized to large-sized buildings with a substantial core.) One manufacturer has a two-pipe system than can be used to provide simultaneous heating and cooling as well as heat recovery operations. Figure 2. Major Components Of A VRF System Including The Range Of Possible Indoor Unit Configurations And A Typical Outdoor Unit. (Courtesy of Daikin) Heat recovery can be accomplished by transferring heat between the pipes providing refrigerant to the cooling and heating units. One way is to use heat exchangers to extract the superheat from the units in the cooling mode and route it into refrigerant entering a heated zone. One manufacturer sends the refrigerant first to the units that require heating, allows the refrigerant to condense, collects it at a central point and then sends it to the indoor evaporators to do cooling. Most manufacturers have a proprietary design for the heat recovery plumbing and operation with special valving arrangements, heat exchangers, controls, receivers and distribution boxes. 3-4
5 Ventilation can be integrated with the VRF system in several ways. A dedicated VRF indoor unit could be used in a ducted configuration to condition the ventilation air. A separate ventilation system and conditioning unit could be installed using conventional technology and the VRF system function would be restricted to the recirculation air. Some VRF units have the ability to handle some outside air and could be used accordingly. Bringing the outside air into the room and then conditioning it with the VRF is not recommended (because of humidity issues) except in dry climates where condensation will not create moisture problems. Heat recovery ventilators can be to reduce cooling loads on the VRF units. Both water-cooled and air cooled systems are available as well as systems integrated with ice storage units. Market Adoption of VRF Systems Ductless and multi-split products are often considered factory-built systems, competing with traditional unitary products, whereas some manufacturers position their VRF systems as engineered systems that are alternatives to traditional field-applied systems such as chillers. U.S. sales of all ductless, multi-split and VRF products will be around 250,000 units in Less than 10,000 of these are VRF units (Goetzler, 2007). Sales in Japan, where the VRF concept was developed, and other parts of Asia, have been strong. In Japan VRF systems are used in approximately 50% of medium sized commercial buildings (up to 70,000 ft 2 ) and close to 33% of large commercial buildings (greater than 70,000 ft 2 ). In Europe, where many existing buildings did not have air-conditioning, retrofit opportunities have also created strong demand (Goetzler, 2007). Ductless products entered the United States market in the early 1980 s but market penetration was minimal. Lack of Japanese manufacturer support infrastructure, and market unfamiliarity with the technology held back sales. Moreover, ozone depletion issues became a concern at that time, and the issue of a high refrigerant charge of multi-split systems was likely a strong negative for the system. Since that time, refrigerant developments, advances in charge management, controls and inverter technology have transformed the technology. Asian manufacturers have recently re-entered the U.S. market individually or in partnership with U.S.- based manufacturers to help promote the technology. Evidence of the applicability of this technology in the U.S. is the inclusion of a multisplit variable refrigerant flow system with zoned inverter-driven heat pump and heat recovery in the renovation of the headquarters building of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) in Atlanta, Georgia (Johnson, 2007). Customer Issues Customers desire products that enhance comfort and productivity at a reasonable capital cost and energy cost. The low noise, individual controllability and effective temperature control of multi-split system air conditioners and heat pumps have the potential to enhance workplace productivity. The energy saving features of the product, such as capacity modulation, zone control, heat recovery and low duct losses contribute to ownership cost savings. However, the cost effectiveness of the technology is highly application dependent. Cost and energy use data should be obtained from detailed analysis and corresponding rigorous laboratory and field testing 3-5
6 of multi-split systems. The need for this information currently exists for applications in the United States. Manufacturer and case study information from outside the U.S. indicate that VRF systems are cost effective, but results, again, depend on specific application features. Typically, energy savings are achieved, ranging from 10% to 60%, depending on climate and the type of system displaced, among other factors. Initial costs are also typically higher, with payback periods dependent on energy savings. Examples of application and operation costs outside the U.S. include the following: Anecdotal information exists that shows savings of 38% in a side-by-side comparison with a rooftop variable air volume (VAV) installation, but this study compared a new VRF system to the existing rooftop VAV system (Roth 2002). Simulation results for a Brazilian climate showed savings of over 30% in summer and over 60% in winter. Savings of 5% to 15% were suggested to be more likely in the United States. A modeling study conducted with a version of EnergyPlus that was modified to simulate VRF systems showed that, in a ten story office building in Shanghai, a VRF system saved more than 20% of the energy compared to a VAV system and more than 10% compared to a fan coil plus fresh air system (Zhou 2006). Information obtained in discussions with one manufacturer suggests that the company s VRF systems could save up to 30% to 40% of the energy used by a chiller-based system for a 200-ton cooling system for a generic commercial building. The same data set indicates that the installed cost of a VRF system will be about 8% more than a watercooled chiller and 16% more than an air-cooled chiller. Combining these energy use and installed cost projections provides an estimated payback period of about 1.5 years for the VRF compare to an air-cooled chiller and 2/3rds of a year compared to a water-cooled chiller. Data from another VRF manufacturer compared installation and operating costs for a set of 14 branch buildings in Central/Northern Italy, where a chiller/boiler system was installed in 7 of the buildings and a VRF system was installed in the other 7 buildings (designed to handle heating down to -20 C [-4 F]) in The VRF systems used 35% less energy and had 40% lower maintenance costs for the period studied. As suggested by other manufacturers, the equipment costs for the VRF systems were higher than the equipment costs for the chiller-based systems but this was offset by lower installation costs for the VRF systems. Advantages of VRF and Multi-Split Systems Some of the features of multi-split systems should provide energy savings. These include: Good part load performance due to multiple compressor and variable speed compressor systems permitting capacity modulation to serve 7% to 100% of the cooling or heating load. Many hours of HVAC system operation are spent between 30% and 70% of maximum capacity where the VRF system efficiency is high (Roth 2002). Good zone control, saving by not conditioning unoccupied zones and by providing capability to condition single zones off hours at a reasonable cost. Figure 3 shows how VRF systems can provide zone control, including simultaneous heating and cooling. 3-6
7 Heat recovery is readily accomplished with the refrigerant when some of the indoor units are heating and some of the units are cooling. According to one manufacturer s published data, if a 50% demand for full cooling and a 50% demand for full heating exist, in the heat recovery mode the compressor would only be 48% loaded (Inman, 2007). Duct losses are confined to the ventilation air which is normally about 1/5th of the air flow of a ducted system circulating and conditioning both the ventilation air and the recirculated air. (Since ducts are often in unconditioned spaces, duct losses may not contribute to building space conditioning). Refrigerant is used directly as both the working fluid and the heat transfer fluid tending to make the VRF system more efficient than systems that use air or water as a secondary heat transfer fluid for delivering heating or cooling. The use of R-410Aand other features such a variable speed compressors, multiple speed fans and blowers, refrigerant circuitry, electronic expansion valves and advanced controls contributes to enhanced low temperature performance that can avoid or minimize the need for supplementary heat in many U.S. climates. Figure 3. Cooling and Heating Provided By VRF System Using One Outdoor Unit Other non-energy advantages include: Better comfort. Since the system can be modulated to follow the load, units can remain running to maintain temperature within narrow limits, assuring a comfortable temperature envelope. Low noise levels. Levels are 24 dba for the indoor unit and 56 dba for the outdoor unit (Siddens, 2007). Flexible and quick installation. Only a small (3 or so) opening is needed for the refrigerant piping. Low-profile, low space requirements and light weight make units easier to fit into tight spaces and to avoid obtrusive terminal units that could spoil the esthetics of a space. Claimed low maintenance and high reliability. Although the large amount of refrigerant piping and numbers of connections is a concern to U.S. specifiers and installers, 3-7
8 manufacturers claim low maintenance costs and a record of reliability. Maintenance consists of changing filters and cleaning coils. Modularity allows easy apportioning of energy costs among tenants or operations. Increased useful building space is enabled by reducing floor to floor height (12 ceiling void vs. 20 ) and eliminating the need for a machine room. Avoids the need for an on-site, trained operator as might be desirable with a large chillerbased system. Disadvantages of VRF and Multi-Split Systems Some of the features of the VRF and multi-split systems may result in increased energy costs relative to some competitive systems, and thus offset savings: Less economizer cycle benefit may occur with the smaller ventilation system since the ducting is sized just for ventilation. Use of supplementary heat may be required for quick recovery from night setback. This can be avoided to a great extent by providing sufficient time to allow the heat pump cycle to be used with the compressors running at maximum capacity to provide morning warm up. Use of backup strip heat for space heating in cold weather would be a detriment to the efficiency of the system. However, as indicated above in the list of advantages, speed variation and other features help increase the heat pump capacity to offset some of the vapor compression cycle degradation with lower temperatures. This can avoid or minimize the need for backup heat. Integrated gas heating systems are not available as yet as a dual fuel option. It may be less economical to provide high efficiency components (such as fans, or filter systems) for many decentralized indoor units compared to the efficiency of these systems when installed in a single larger centralized system. Other disadvantages include: The need for a separate ventilation system to satisfy code requirements for delivery of outside air offsets some of the retrofit advantages of the VRF system. Each VRF indoor unit should be supplied with a condensate drain that needs to have access to a water collection system. Long refrigerant runs and large numbers of connections could result in refrigerant leakage that could be significant, causing safety issues and repair difficulties. One VRF manufacturer cautions not to install an air conditioner in a room where the limit density will be exceeded if refrigerant leaks. They assert that the refrigerant (R410A) used by this system is itself a safe refrigerant; however, if for some reason the refrigerant leaks and the limit density is exceeded, there is a risk of injury to persons due to a lack of oxygen. Oil return (and refrigerant positioning) could be an issue but many systems employ special oil retrieving modes that are periodically, automatically activated to flush oil (or refrigerant liquid) out of any locations where it has accumulated 3-8
9 Costs Installed costs are highly dependent on the application, construction and layout of the building and whether the installation is new or retrofit. Lack of familiarity with the technology in the U.S. will add to VRF costs. Total costs for VRF systems are likely to be about 5% to 20% higher than chilled water systems of similar capacity (Roth 2002). One manufacturer provided verbal information that VRF systems cost about 30% to 50% more than equivalent capacity single package ducted systems with a SEER of 13 to 14. And that VRF systems cost more than twice as much as packaged terminal units. This information is interesting but not as important as the comparisons of VRF and chiller systems if VRF manufacturers position their product as a chiller alternative. In some retrofit situations where the distribution system needs to be replaced or lack of access to the chiller makes chiller replacement untenable the VRF system could have a lower cost. Utility Issues From a utility standpoint, one of the positive features of the VRF system heat pump is the ability of the customer to use an all-electric system. Since no integrated gas heating options currently exist for this technology, this provides the electric utility an opportunity to serve the heating load on buildings that install multi-split system heat pumps. Summer peaking utilities can benefit from installations of VRF heat pumps, since the systems additional heating loads will provide off-peak winter load that could improve capital utilization and return on investment. For most of the cooling season, VRF systems will use less energy than many other cooling means that do not have comparable zoning or capacity modulation. (Much of the energy savings in the cooling mode will occur off peak due to capacity modulation and zone control that turns off units when the space in unoccupied.) On peak, when cooling systems are operating at or near 100% capacity, the VRF system could have lower demand than a rooftop direct expansion variable air volume system but will likely have higher demand than a high efficiency chillerbased fan coil system. Whether a summer peaking utility wants to encourage VRF systems or some other electric or gas system will depend on the local rates, reserve margins, regulatory environment and other factors. For a winter-peaking utility the use of electric heat may make the VRF system less attractive than it might be for a summer peaking utility. Demand Response Issues To use VRF systems as a demand response tool, it is possible to turn off the indoor units in one or more spaces, letting the space temperature and humidity drift (with some spillover of conditioned air from the adjacent conditioned spaces). The on-off sequencing between zones could be alternated to minimize temperature changes to minimize occupant discomfort. Alternately, units could be operated at a fraction of normal capacity to maintain minimally effective environmental conditions in the occupied space. Sequentially starting of the outdoor units serving a building is possible to spread out demand spikes caused by starting power transients. 3-9
10 With regard to interoperability, VRF system air conditioners and heat pumps have sophisticated controls and components that will enable the units to adjust their performance in response to internal or external signals. Best Applications for VRF Systems Initial applications of VRF in commercial buildings in the U.S. have included building add-ons such as a new data center and situations where spot cooling is needed. Historical buildings have benefited from the minimum alterations needed for the addition of a VRF system. Retrofit situations where air conditioning may be an addition/upgrade to the space can be good applications of ductless systems since additional duct work and conditioning needed for ventilation can be minimized with VRF systems compared to ducted systems. Other applications well suited to VRF systems include any case in which there is an advantage to delivering personalized, compartmentalized comfort conditioning, such as: office buildings, strip malls, hotels and motels, hospitals and nursing homes, banks and schools. Offices and strip malls have occupants with different space conditioning requirements, making the zoning opportunities of VRF attractive for these applications. Hospitals and nursing homes can be good candidates since the VRF system makes it easy to avoid zone to zone air mixing. Banks have favored the system for security because the egress paths into the bank are minimized due to the minimal smaller diameter ductwork. Even in schools, which because of high occupancy often have a 100% outside air requirement, VRF units can be used (often with heat recovery ventilators) to meet the load. What s Holding Back VRF in the United States The traditional barriers to new technology have hampered market acceptance of VRF systems. These barriers include the natural resistance to change and unwillingness of specifiers and users to be subjected to the uncertainty of using a new, unproven technology. Other barriers common to this and most new technologies include: performance uncertainties; lack of knowledge of design, operation, servicing and maintenance; and ownership costs. Concerns also exist about manufacturer support and spare parts availability, especially since most of the manufacturers are not based in the U.S. These barriers tend to translate into higher first costs. Those specifiers and installers who are willing to take the risk of recommending the technology will expect to get paid extra for taking on the added risk. As specifiers become more familiar with VRF these markups will diminish. Barriers specific to VRF systems include: Concerns about potential for leaks. Having a system with long refrigerant piping runs and many connections exposes the systems to leakage. Brazed joints are used instead of flared or flanged connections in the refrigerant circuit to minimize/avoid leakage (Dyer June 2006). Leaks may be difficult to detect and repair in the field and a perception exists among engineers and building owners that these could cause safety issues since large quantities of refrigerant could be released. Safety problems caused by refrigerant leakage must be addressed in accordance with ASHRAE Standard that specifies the safe design, construction, installation and operation of refrigeration systems. The refrigerant charge, circuiting and occupied space served by the VRF circuits must be designed so as 3-10
11 not to exceed limits for the maximum permissible quantity of refrigerant that can enter the occupied space as specified in the standard (ANSI/ASHRAE 2007). Manufacturer presence and support in the United States has been limited but Japanese manufacturers have aggressively entered the market, with Daikin acquiring McQuay, and Carrier and Toshiba forming an alliance (and currently selling products in Europe and Latin America. Some Japanese and Korean manufacturers are using manufacturer s representatives to represent them in the U.S. Lack of availability of an integrated gas heating option may affect the cost effectiveness of the heat pump systems. The need for a separate ventilation system to provide fresh air to the occupied space to comply with ASHRAE Standard 62 requirements offsets a part of the advantage of using a refrigerant distribution system rather than an air distribution system for the bulk of the space conditioning. The lack of suitable test rating procedures and code compliance procedures certified by the Air-Conditioning and Refrigeration Institute (ARI) and approved by the U.S. Department of Energy (DOE) are also impediments to selection of VRF systems. European and Japanese testing procedures are well established. Work is needed to better simulate the performance of VRF systems to provide certified tools that predict energy use for compliance calculations to satisfy energy code requirements - or to capture energy credits for programs such as LEED (Leadership in Energy and Environmental Design Green Building Rating System ) - or to qualify for rebates for programs such as Savings by Design. Available programs include: Trace700, a program developed by the Trane Company (TRACE 2007) but widely used in the industry that has had the ability to model VRF systems since EnergyPlus subroutines have been developed to model VRF systems. Privately sponsored work is underway to develop a version of equest, and work is being done by EnergySoft to develop a version of EnergyPro that incorporate VRF technology. Both equest and EnergyPro programs have been accepted by the California Energy Commission and when completed as anticipated by mid-year 2008 should greatly facilitate the use of VRF systems in California. Both programs are well connected with California utility rebate programs and will make needed calculations and fill out corresponding utility rebate forms. What Else is Needed? Based on what we know about VRF applications outside the U.S., and applications that are occurring in the U.S., this space conditioning technology has the potential to reduce energy use, and could be well positioned for retrofitting multiple types of large commercial buildings, ranging from office buildings to retail establishments to nursing homes. To help end users and specifiers understand and take advantage of improved low temperature heat pump performance and the flexibility of the VRF systems requires testing, documentation, and market development for existing products as well as development of advanced features for future products. To take advantage of the energy savings potential of VRF systems, considerable market barriers must be overcome, including lack of performance and cost data from unbiased third party organizations. Risk-averse specifiers and purchasers of space conditioning systems must 3-11
12 have reliable data on the efficacy of the VRF approach for U.S. applications. Ventilation system design refinements could also hasten applications acceptance. To overcome reluctance by those who design, specify, and purchase systems, the following tools, resources, and technology are needed: Energy analysis tools should be enhanced to incorporate algorithms that can accurately model VRF systems. The development of rating and testing methods needs to be encouraged to provide a reasonable means of comparing the VRF systems to ducted and hydronic systems. Well designed field tests and design and construction evaluations by independent third parties to derive reliable energy use data and true installed costs of VRF systems. A U.S.-focused design guide based on field studies and including information that provides the type of trusted data that specifiers, users and other important market participants need to for selecting systems. Such a guide and other training materials could help overcome specifier resistance to change and lack of information. Technical references and articles in journal and industry trade publications are needed in addition to the design guide to enhance knowledge of the applicability of VRF systems. Better, more economical means are needed to integrate fresh air delivery with VRF systems to provide ventilation while maintaining ease of retrofit. Develop advanced VRF systems with improved low temperature heat pump performance using cycle and configuration improvements such as multi-stage, supercharged cycles and flash-injection circuits. Guidance on use of ice storage systems in conjunction with VRF systems. If ice storage systems are charged by VRF systems then the ice storage system could, in turn, be integrated into the ventilation system and VRF systems to provide cold water for dehumidification. References ANSI/ASHRAE Standard , Safety Standard for Refrigeration Systems, ISSN , 2007 Dyer, Mark June Approaching 20 years of VRF in the UK, Modern Building Services, html Goetzler, William April Variable Refrigerant Flow Systems, ASHRAE Journal, Inman, Jon A., September Going With The Variable Flow, Engineered Systems, Johnson, S. June 26, ASHRAE Headquarters Building Renovation, Mechanical Systems Narrative 3-12
13 Roth, Kurt et al Energy Consumption Characteristics of Commercial Building HVAC Systems Volume III: Energy Savings Potential, TIAX LLC for DOE or Siddens, Scott January Variable Refrigerant Systems Make for Zoned HVAC Control, Consulting-Specifying Engineer Smith, Lee April 30, History Lesson: Ductless Has Come a Long Way, ACHR News TRACE700 Version 6.1.2, October 31, and Zhou, Y. et al Module Development And Simulation of The Variable Refrigerant Flow Air Conditioning System Under Cooling Conditions In EnergyPlus, Texas A&M University, Energy Systems Laboratory 3-13
Variable Refrigerant Flow Systems
The following article was published in ASHRAE Journal, April 2007. Copyright 2007 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
Ductless Heat Pumps. Gary Nordeen January 2009. www.nwbuildings.org/dhp.aspx [email protected]
Ductless Heat Pumps Gary Nordeen January 2009 www.nwbuildings.org/dhp.aspx [email protected] Outline Heat Pump Basics Ductless Heat Pumps Efficiency Advantages Commercial installations Planning (applications,
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Air-Conditioning Buying Guide
Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence
HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget
A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable
EnergyPro Building Energy Analysis. Assisted Living Building
EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can
HVAC Variable Refrigerant Flow Systems
HVAC Variable Refrigerant Flow Systems Course No: M03-014 Credit: 3 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems Author:
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
HEATING, VENTILATION & AIR CONDITIONING
HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating
Introduction To VRF: System Overview, Applications, & Savings Opportunities
Introduction To VRF: System Overview, Applications, & Savings Opportunities System Overview What is VRF? Zoning System Two-Pipe / Three Pipe System Packaged DDC Control Operates as a Heat Pump Simultaneous
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems
APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage
The ABC s of VRF: A Green HVAC Technology An Ideal Green School Solution. Presented by: Fujitsu General America, Inc.
The ABC s of VRF: A Green HVAC Technology An Ideal Green School Solution Presented by: Fujitsu General America, Inc. What to look for in a Green HVAC solution? What if your HVAC system could provide Individual
Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
HVAC Basic Science - System Capacity
HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
air conditioners how to choose a cooling system
air conditioners how to choose a cooling system taking responsibility As an individual, your efficient use of energy brings benefits such as lower bills, improved comfort levels in your home and a reduced
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,
HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.
Reducing Building HVAC Costs of site rec By Stephen J. Pargeter Building owners are caught between two powerful forces the need to lower energy costs and the need to meet or exceed outdoor air ventilation
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
Energy Efficiency in Industrial HVAC Systems
Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards
Variable Refrigerant Flow Systems vs. Geothermal Water Source Heat Pump Systems
Variable Refrigerant Flow Systems vs. Geothermal Water Source Heat Pump Systems Presented by: Matt Green Agenda Section I: Case Study Northern Illinois Food Bank NIFB challenge/goal System choices considered
ASTACEA4 Inspect complex/central air conditioning systems
Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air
Why Daikin? 2015 Houston, Texas USA www.daikincomfort.com
Why Daikin? Daikin: The Premium Brand industry leader Daikin is recognized as the world s number one leader in the manufacture of HVAC equipment and refrigerants. For over 90 years, Daikin has grown consistently
Chilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
How Ground/Water Source Heat Pumps Work
How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
Using Time-of-Day Scheduling To Save Energy
The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction What is DNSS EcoSave? The Daikin Network Service System (DNSS EcoSave) is a Daikin developed internet based remote
newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer
engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems
ECO-AIR AIR CONDITIONING www.northamericanhvac.com
INDEX ACCESSORIES INSTALLATION... 3-7 LINE SETS... 3-7 GEOTHERMAL... 3-8 WIRING CABLE... 3-8 CIRCULATOR PUMPS (PRO-TECH MODEL)... 3-9 DC INVERTER SINGLE ZONE HEAT PUMP... 3-6 DC INVERTER TECHNOLOGY...
2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
AIR CONDITIONING - VENTILATION - HEATING
AIR CONDITIONING - VENTILATION - HEATING Air Conditioning & Building Services COMMERCIAL - RESIDENTIAL - PUBLIC SECTOR About Airtech Airtech was formed in 1979 and during that time has built up expert
Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues
LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental
All the best brands all under one roof
All the best brands all under one roof Year round comfort and energy efficiency The air conditioner you choose today is going to be with you for a long time, so it s important to choose wisely. The best
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V Water II Heat Recovery VRF System)
Energy Efficiency Analysis for a Multi-Story Commercial Office Building (LG Multi V Water II Heat VRF System) Commercial Air-Conditioning Engineering Study VRF-ES-BL-001-US 011M05 Executive Summary Contents
Selection Tips For Air-Conditioning Cooling Systems
PDHonline Course M117 (2 PDH) Selection Tips For -Conditioning Cooling Systems Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V III Heat Recovery VRF System)
Energy Efficiency Analysis for a Multi-Story Commercial Office Building (LG Multi V III Heat Recovery VRF System) Commercial Air-Conditioning Engineering Study VRF-ES-BK-011-US 011L18 Executive Summary
LG Electronics AE Company, Commercial Air Conditioning
www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,
White Paper #10. Energy Efficiency in Computer Data Centers
s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS by Dr. Bing Chen and Prof. John Bonsell Passive Solar Research Group University of Nebraska-Lincoln Omaha campus and Richard
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
VRF Zoning: An Ideal HVAC Solution for Multifamily Applications
VRF Zoning: An Ideal HVAC Solution for Multifamily Applications White Paper June 2014 1 Variable Refrigerant Flow (VRF) zoning systems are the fastest growing segment of the U.S. HVAC market. This paper
SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS
SASO XXXX:2016 (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS PERFORMANCE REQUIREMENTS AND METHODS OF TESTING 1 LARGE CAPACITY AIR CONDITIONERS
Ductless Mini-Split Systems. Comfort... where you need it, when you need it
Ductless Mini-Split Systems Comfort... where you need it, when you need it Ductless mini-splits THE COMFORT SOLUTION Ductless mini-split systems are a great solution to a wide variety of installation challenges,
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
MEETING AGENDA. Project Administrator:
MEETING AGENDA Project Administrator: To: Ann Green M. Baker, SLCS C. Bullinger, SLCS R. Clark, SLCS Board C. Cox, SLCS S. Dotinga, Granger J. Graham, SLCS J. Gusick, SLCS, Board C. Hanshaw, SLCS Board
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design
Copyright 24, American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 79 Tullie Circle NE, Atlanta, GA. 3329. Reprinted by permission from the September 24 Issue of ASHRAE Journal
RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA.
1. There is verbiage in the hazardous material report referring to a state licensed abatement contractor. Within the recommendations part of the report (page 64 of 111 of the specification pdf) is the
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord 09-20-2012
Air Side Economizers and Energy Recovery - Improvements and New Regulations Richard Lord 09-20-2012 Introduction For commercial buildings the use of outside air for cooling and ventilation is an important
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
Drives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
Tim Sisson - Trane HVAC OVERVIEW
Tim Sisson - Trane HVAC OVERVIEW HVAC Systems System Types Acoustics Controls Modernization more than one Down to the Studs Opportunity for new System Type Renovation Possible opportunity for new System
How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners
How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners White Paper #56 Revision 2 Executive Summary Today's technology rooms require precise, stable environments in order for
FTQ. Daikin Inverter Ducted Heat Pump
FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning) Objectives Survey current HVAC system(s), operating procedures, and maintenance schedule. Analyze results of energy audit for HVAC system(s)
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.
HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET. AFFORDABLE SOLUTIONS FROM AMERISTAR. We know that heating and cooling systems can be a major investment for homeowners. Our goal is
Heating & Cooling Efficiency
Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart
Mechanical Systems Proposal revised
Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option
DIABLO VALLEY COLLEGE CATALOG 2015-2016
HEATING, VENTILATION, AIR CONDITIONING, REFRIGERATION - HVACR Tish Young, Dean Physical Sciences and Engineering Division Physical Sciences Building, Room 263 Possible career opportunities Upon successful
LG Air Conditioning Solutions COMFORT MADE EASY. COMFORT MADE BEAUTIFUL.
Residential Brochure LG Air Conditioning Solutions COMFORT MADE EASY. COMFORT MADE BEAUTIFUL. LG DUCT-FREE Split SYSTEMS BRING COMFORTING INNOVATION LG Duct-Free Split systems allow you to cool or heat